TECHNICAL SPECIFICATION

11KV 800 AMPS OUTDOOR TYPE STAND ALONE PANEL VCB KIOSK

S.No Description Ratings Qty/Panel


1 Vacuum Circuit Breaker
1.1 Horizontal Draw Out VCB fitted with Manual/Motor Operated 11kV,800A, 1 No.
spring charging mechanism with 230V AC Motor & Motor 25kA (630A) for
Control Switch, Mechanical ON / OFF indicator Operation INCOMING.
Counter, Automatic safety shutters & push button as IEC and
IS.

1.2 Shunt trip and series Coil 110V DC

1.3 Closing Coil 110V DC

1.4 Spare auxiliary contact 6 NO + 6 NC(silver plated contacts) 6 NO +6 NC

1.5 Antipumping Feature 110V DC

1.6 Decree of protection IP 55


2 Potential Transformer

2.1 Three Phase, Resin cast, Dry type, Fixed type potential (11 kVN3) / 1 No.
transformer with one set of HTFS / LTFS and one no. Neutral (11 OV/~3)
Link

Core 1: for meter TO BE


SUITABLE·
SPECIFICATION
AS PER
DESIGN
3 Current Transformer
3.1 single phase, Resin Cast, Dry Type Current Transformer 3Nos
Core 1: for meter TO BE
SUITABLE
Core 1: for protection CT range-
SPECIFICATION
(Separate cores shall be used for metering and protection). AS PER 300- 500 A
DESIGN
4 Metering

4.1 96 sq.rnm Digital Ammeter with Inbuilt Selector Switch 1No


4.2 96 sg.mm Digital Voltmeter with Inbuilt Selector Switch 1No
4.3 3$, 4 wire, 3 Element Digital Multifunction Meter 1No
Trivector Meter 3phase 3wire system 1No
5 Protections

5.1 Numerical Non-directionallDMT combined 3 O/C+1 E/F relay TO BE 1No


SUITABLE
with hiqh set
SPECIFICATION
5.2 High speed/Master trip relay AS PER 1No
5.3 Door interlock with breaker DESIGN
6 Indication Lamps

6.1 VCB OFF/ON/Auto triplTrip circuit healthy/Spring charge LED 1 Set.


indication lamps
6.2 R,Y,B Phase Indication Lamps LED 1 Set
r
c

7 Control Switches I Push Buttons


7.1 Breaker Control Switch (Close-Neutral-Trip) (T-N-C) 1 No.

7.2 Local Remote selector switch L1R 1 No.

7.3 Flush Head type Trip Circuit Healthy Push Button 1No
8 Control wiring with appropriate colors 1 Lot
9 Busbar Ratings

9.1 11kV, 8000Amps Busbar with PVC Sleeve (63.5 X 12.7mm) Aluminium 1Set
9.1 Earth bus 40 *6 mm Aluminium 1Set
10 Common For Switchgear
10.1 Heater ON / OFF switch with filament type 80Watts space - 1Set
heater & thermostat, single phase switch with socket, 40W
cubicle Lamp for panel illumination with snap type door limit
switch, Fuses / MCBs for
AC / DC control.

• 10.2

10.3
MS Sheet steel enclosure & installation with
RAL 7032.
Incoming (Excluding Cable termination kits,
Bottom side suitable for 2RX3CX 185SQMM
cable
paint shade of

lugs & glands) -


Alu Armoured
Outdoor 1 Set.

10.4 Outgoing (Excluding Cable termination kits, lugs & glands) -


Bottom / Side suitable for 2RX3CX185SQMM Alu Armoured
cable

NOTE:
1 VCB, PT, CT, METERS, CONTROL SWITCHES, HEATER & THERMOSTAT, MCB
etc ... all are reputed make only.
2 Surge Arrestor shall be provided as per IE standards.
3 11 OV DC for operation of the circuit breaker and protection
relays shall be taken from power pack (110V DC) with
suitable capacity battery and charging circuit arrangement.
This is to ensure the operation of breaker in case of power
supply fa1lure. (2 open and 2 close operations). Only 230


volts AC supply shall be provided by BH EL .

~.~