HSCD Series

Carbon Dioxide Sensor


Honeywell HSCD series carbon dioxide (CO2)
sensors include two types: indoor installation and
duct installation. They are mainly used for detecting
carbon dioxide concentration in air of indoor and
duct.
Features
➢ Use high-precision single/dual-wavelength NDIR sensors.
➢ Optional display function, LCD digital display shows clearly.
➢ CO2 sensing component module can be replaced on site.
➢ Multiple software and hardware protection design ensures
high stability.
➢ CO2 sensors can be manually calibrated on site.
➢ The air duct type adopts a screw-free clamshell snap-on
design, making wiring and commissioning easy.
➢ Integrated RS485 matching resistor to facilitate on-site
commissioning(Modbus models only).
➢ RS485 isolation design can isolate high voltage and enhance
immunity to ground loops and common-mode signal
interference (Modbus models only).
Order Information and Technical Specification
SKU Installation Sensing component Output signal or Protocol Display
HSCD-R1U Room Single wavelength NDIR 0-10V/2-10V//4-20mA NO
HSCD-R1UL Room Single wavelength NDIR 0-10V/2-10V//4-20mA YES
HSCD-R2U Room Dual wavelength NDIR 0-10V/2-10V//4-20mA NO
HSCD-R2UL Room Dual wavelength NDIR 0-10V/2-10V//4-20mA YES
HSCD-R2M Room Dual wavelength NDIR Modbus RTU NO
HSCD-R2ML Room Dual wavelength NDIR Modbus RTU YES
HSCD-D1U Duct Single wavelength NDIR 0-10V/2-10V//4-20mA NO
HSCD-D1UL Duct Single wavelength NDIR 0-10V/2-10V//4-20mA YES
HSCD-D2U Duct Dual wavelength NDIR 0-10V/2-10V//4-20mA NO
HSCD-D2UL Duct Dual wavelength NDIR 0-10V/2-10V//4-20mA YES
HSCD-D2M Duct Dual wavelength NDIR Modbus RTU NO
HSCD-D2ML Duct Dual wavelength NDIR Modbus RTU YES

HBT-FDA-SS01-SEPT-2023-V01-CN

1
Basic Parameters
Single Wavelength NDIR: Single Wavelength non-dispersive infrared
CO2 Measurement principle
Dual Wavelength NDIR: Dual Wavelength non-dispersive infrared
Sensor Accuracy* Single Wavelength NDIR ±40PPM ±3% of measuring value
@ 25℃ Dual Wavelength NDIR ±30PPM ±3% of measuring value
Repeatability ±20PPM ± 1% of measuring value
Temperature Dependence ± 2.5 PPM / K (Dual Wavelength NDIR)
Display Resolution 1 PPM
A. Sensing Module Responding Time:
Single Wavelength NDIR: ≤30S Dual Wavelength NDIR: ≤20S

B. Whole Unit Responding Time (Typically):


Responding Time T63
Room Installation Type
Single Wavelength NDIR: ≤75S Dual Wavelength NDIR: ≤45S
Duct Installation type (air flowrate=4 m/s)
Single Wavelength NDIR: ≤60S Dual Wavelength NDIR: ≤50S
Single Wavelength NDIR: ≤ 60 S
Warm-up Time
Dual Wavelength NDIR ≤ 120 S
Power Supply 19.2~35VDC SELV 24VAC ± 20% 50/60Hz Class 2
Power Consumption ≤ 3VA
0-10V / 2-10V : Min 5 KΩ
Analog Output Load
4-20mA Max 500 Ω
0-10V / 2-10V 10mV
Analog Output Resolution
4-20mA 0.02mA
Analog Output Conversion 0-10V / 2-10V : ± 20mV+2% Output Value
Accuracy 4-20mA: ± 0.3mA+2% Output Value
Measuring Range 0 to 9999 PPM
Measurement Range with
400 to 2000 PPM
Guaranteed Accuracy
Analog Output Range 0 to 2000 PPM
Number of connected
A maximum of 64 devices can be connected to a single network segment
Modbus RTU devices
Single Wavelength NDIR 0 ℃ to 50 °C , 0 to 85 %RH (Non-condensing
Operation Environment
Dual Wavelength NDIR 0℃ to 50 °C 0 to 95 %RH (Non-condensing
Single Wavelength NDIR -20 ℃ to 50 °C , 0 to 85 %RH (Non-condensing
Storage Environment
Dual Wavelength NDIR -20 ℃ to 50 °C 0 to 95 %RH (Non-condensing
Protection Standard Duct Installation type: IP65/NEMA 4; IP20 for probe
(GB4208/IEC60529 Room Installation Type: IP30
Automatic Self-Calibration
Available On by default
Function
Calibration-free Service Life 10 Years ACS function enabled
Housing Materials PC UL94-V0
CE EN IEC 61326-1:2021);
Certification
China RoHS
* 1. The carbon dioxide sensor is an optical sensor based on the infrared detection principle, so the
accuracy of the sensor will deviate under continuous vibration.
2. The carbon dioxide sensor is a precision device. After handling, transportation and installation, the
sensing accuracy may deviate. It will return to normal after being powered on for at least 7 days.
2
Function & Setting

1. User manual forced re-calibration (FRC) operation


1) Power on the Sensor product and place it in an outdoor
atmospheric environment or a 400PPM carbon dioxide
standard gas environment. The product needs to be
covered to avoid sunlight and strong winds;
2) Anti-static measures need to be taken, long press the
button (FRC) on the PCB board for 4 seconds;
3) For products without an LCD version, the LED will flash
slowly, on for 2 seconds and off for 2 seconds (indicating
that it is being calibrated); for products with an LCD
version, "CALI" will be displayed as shown on the right.
4) The stability of the ambient carbon dioxide concentration
must be maintained during the calibration process. The
calibration ends automatically after 11 minutes and the
product returns to normal operation.

2. DIP setting

A. Analog output type

DIP No. No. 1 No.2 & No.3

Automatic Self-Calibration
Function Analog output option
ASC

Set status of ASC: DIP NO.1

DIP Position

Automatic Self-Calibration ASC Enable (Default) Disable

Select analog output signal type: DIP No.2 and No.3

DIPs position

Analog output 4-20mA (Default) 0-10V 2-10V

3
B . Modbus Communication Type

DIP No. No. 1 No.2 & No.3 No.4 to No.10 No.11 No.12

Modbus Modbus RS485


Function ASC Reserved
Baud Rate Address Terminal Resistor

Set the mode of ASC: DIP NO.1

DIP Position

Automatic Self-Calibration ASC Enable (Default) Disable

Set Modbus baud rate: DIP No.2 and No.3

DIPs
Position

Baud rate 9600 (Default) 4800 19200 38400

Set Modbus address: DIP No.4 to No.10

DIPs
Position

1. DIPs No.4 to No.10 represent 1, 2, 4, 8, 16, 32 and 64 respectively.


How to set 2. DIPs up to indicate selected number
Modbus 3. The sum of the selected numbers is the Modbus address code.
address As shown in the picture above: DIP No.8 and No.9 are selected, 16+32=48,
so the address code setting value is 48.
4
Set the mode of RS485 terminal resistor: DIP No.12

DIP
Position

Mode Enable (Default) Disable

Modbus RTU Protocol


Register Address Information

Readable R Data
ID ID function Function Qty.
/Writable W Type

Gas Current gas concentration


0x01 1 R short
Concentration Unit: PPM
0x02 Reserved 1 R short

0x03 Reserved 1 R short


ASC status,
0x04 ASC Status 1 R short
0-Disable; 1-Enable
FRC Target Value Unit: PPM
400ppm)
FRC
0x05 1 R/W short
Target Value Modify FRC Value by writing to
this ID
(Rang is 400 to 1000ppm)

0x06 Reserved 1 R short

0x07 Reserved 1 R short

0x08 Reserved 1 R short

0=Normal; 1=Sensor Error;


0x09 Error Code 1 R short
2=System Error

Function Code Information

Code Function Error Code Exception Code

0x03 Read holding register 0x83 01 or 02 or 03

0x06 Write single register 0x86 01 or 02 or 03

0x10 Write Multiple Registers 0x90 01 or 02 or 03

5
Wiring diagrams and instructions

0-10V/2-10/4-20mA Analog Output Type

Modbus Communication Type

Tips:
1. The terminals support AWG15 to AWG22 line types.
2. The maximum lengths of different conductors are as follows.

Line Type AWG15 AWG16 AWG17 AWG18 AWG20 AWG22

Max length 300 Meters 300 Meters 150 Meters 150 Meters 150 Meters 50 Meters

3. RS485 wiring requires a shielded cable with a maximum allowable length of 1200 meters.

Dimension(mm)

Room Installation Type

6
Dimension(mm)

Duct Installation Type

Fixed flange and conduit mounting hole

≥ Φ27mm

400-842-8487
7