Technical data sheet C2..QPT-..-..
Piping Package with PI Zone Valve,
2-way, Euro cone
• For closed cold and warm water
systems
• For modulating control of air-
handling and heating systems on the
water side
• Snap-assembly of the actuator
• with measuring ports (P/T ports)
Type overview
Type DN G V’nom PN Sv min. kvor CD
[] [“] [ l/h] [] [] [ m³/h] [ mm]
C215QPT-B-11A 15 3/4 210 25 100 0.71 40
C215QPT-B-21A 15 3/4 210 25 100 0.71 80
C215QPT-D-11B 15 3/4 420 25 100 1.34 40
C215QPT-D-21B 15 3/4 420 25 100 1.34 80
C220QPT-F-11CG 20 3/4 980 25 100 2.5 40
C220QPT-F-21C 20 3/4 980 25 100 2.5 80
C220QPT-G-21D 20 3/4 2100 25 100 4.89 80
kvor = Flow coefficient of orifice plate
CD = Connection distance
Technical data
Functional data Fluid Cold and warm water, water with glycol up to
max. 50% vol.
Fluid temperature 2...90°C
Pressure value 16...350 kPa (PIQCV)
Close-off pressure ∆ps 1400 kPa
Flow characteristic equal percentage (VDI/VDE 2178), optimised in
the opening range
Pressure stability ±5% with a pressure value of 35...350 kPa
±10% with a pressure value of 16...35 kPa
Leakage rate air-bubble tight, leakage rate A (EN 12266-1)
Flow setting See installation instruction
Angle of rotation 90°
Angle of rotation note Operating range 15...90°
Pipe connection Euro cone, further connection possibilities with
accessories
Installation position upright to horizontal (in relation to the stem)
Servicing maintenance-free (excl. strainer)
Materials Housing Brass body
Closing element Stainless steel
Stem Stainless steel
Stem seal EPDM O-ring
Seat PTFE, O-ring EPDM
Diaphragm EPDM
Terms Abbreviations V’nom = nominal flow with valve completely
opened
V’max = maximum flow, set by the angle of
rotation limitation on the actuator
Sv = Rangebility kvs/kvr
www.belimo.com C2..QPT-..-.. • en-gb • 2020-07-15 • subject to changes 1
Piping Package with PI Zone Valve, 2-way, Euro cone
C2..QPT-..-..
Safety notes
• The valve has been designed for use in stationary heating, ventilation and air-
! conditioning systems and must not be used outside the specified field of application,
especially in aircraft or in any other airborne means of transport.
• Only authorised specialists may carry out installation. All applicable legal or
institutional installation regulations must be complied during installation.
• The valve does not contain any parts that can be replaced or repaired by the user.
• The valve may not be disposed of as household refuse. All locally valid regulations
and requirements must be observed.
• When determining the flow rate characteristic of controlled devices, the recognised
directives must be observed.
Product features
Mode of operation The ball valve is adjusted by a rotary actuator. The actuator is controlled by a
commercially available modulating or 3-point control system and moves the ball of the
valve – the throttling device – to the position dictated by the positioning signal. Open
the characterised control valve counterclockwise and close it clockwise.
Flow characteristic Equal percentage flow control is ensured by the special design of the ball.
Constant flow volume With a differential pressure of 16…350 kPa, a constant flow volume is achieved thanks
to the integrated pressure regulationg valve. Independent of the differential pressure
through the valve, a valve authority of 1 is achieved. Even with pressure variatons and
in the partial load range, the flow rate remains constant with each respective opening
position (angle of rotation) and ensures a steady control.
P- P+
M
P3 P1
Pressure at valve inlet P1
Pressure at valve outlet P3
Measuring point at measuring port (Inlet - red
marking) P+
Measuring point at measuring port (Outlet - blue
marking) P-
Flow limitation Instead of the electric actuator, the PIQCV-valve can also be operated with a flow
limiter (see accessories).
The flow limiter ensures that the heat exchanger is continuously supplied with a
manually fixed amount of water.
Measurement ports (P/T ports) The valve has two measurement ports. The total drop in pressure across the valve can
be determined using the measurement points at the valve inlet (P1) and outlet (P3).
The measurement ports can be used to easily establish whether the effective
differential pressure across the valve is within the effective pressure range of 16…350
kPa. If it is, the valve operates independently of pressure and the correct flow rate is
automatically ensured by the valve according to the setting table.
The differential pressure measurement can also be used to optimise the pump
setting. This involves reducing the delivery height of the pump until only the minimum
differential pressure required (16 kPa) is still present across the valve at the point of
lowest pressure (the furthest away from the pump in hydraulic terms).
Operating modes The piping package is equipped with two manual 3-way ball valves and a shut-off
valve at the strainer. Different operating modes can be selected by positioning these
components accordingly.
2 C2..QPT-..-.. • en-gb • 2020-07-15 • subject to changes www.belimo.com
Piping Package with PI Zone Valve, 2-way, Euro cone
C2..QPT-..-..
Product features
Normal operation Consumer in operation. The heating or cooling capacity is controlled by means of flow
adjustment on the PI zone valve.
Flushing the system No flow through the consumer. This prevents dirt from entering the consumer and
settling there during system flushing at start-up.
www.belimo.com C2..QPT-..-.. • en-gb • 2020-07-15 • subject to changes 3
Piping Package with PI Zone Valve, 2-way, Euro cone
C2..QPT-..-..
Product features
Shutting off the consumer Complete disconnection of the consumer from the hydraulic network during
maintenance of the consumer.
Emptying the consumer The consumer separated from the hydraulic network can be drained. A venting valve
at the consumer is required for this purpose.
4 C2..QPT-..-.. • en-gb • 2020-07-15 • subject to changes www.belimo.com
Piping Package with PI Zone Valve, 2-way, Euro cone
C2..QPT-..-..
Product features
Filling the consumer Filling of the consumer (e.g. after replacement). A venting valve at the consumer is
required for this purpose.
www.belimo.com C2..QPT-..-.. • en-gb • 2020-07-15 • subject to changes 5
Piping Package with PI Zone Valve, 2-way, Euro cone
C2..QPT-..-..
Product features
Maintenance strainer For testing and flushing the strainer
Forward flushing of the strainer
Backward flushing of the strainer
6 C2..QPT-..-.. • en-gb • 2020-07-15 • subject to changes www.belimo.com
Piping Package with PI Zone Valve, 2-way, Euro cone
C2..QPT-..-..
Product features
Measuring orifice The piping package is designed with an orifice plate with fixed resistance. The flow can
be verified by measuring the differential pressure across the orifice plate.
Formula
∆p ∆p: kPa
= kvor x : m3/h
100 kvor: m3/h
Connections The piping package is equipped with G 3/4” Eurocone connections. With the
corresponding accessories P2P..PC-... it is possible to connect pipes with external
thread (R 1/2” and R 3/4”) as well as copper pipes with diameter 15 or 22 mm.
Accessories
Description Type
Mechanical accessories Pipe connector for steel pipe, G 3/4” euro cone x Rp 1/2” P2P15PC-11
Pipe connector for copper pipe, G 3/4” euro cone x Ø15 mm P2P15PC-1DC
Pipe connector for steel pipe, G 3/4” euro cone x Rp 3/4” P2P20PC-11
Pipe connector for copper pipe, G 3/4” euro cone x Ø20 mm P2P20PC-1DD
Spindle extension CQ ZCQ-E
Flow limiter PIQCV ZCQ-FL
Installation notes
Recommended installation positions The ball valve can be installed upright to horizontal. The ball valve may not be installed
in a hanging position, i.e. with the stem pointing downwards.
90° 90°
Mounting position in the return Installation in the return is recommended.
Water quality requirements The water quality requirements specified in VDI 2035 must be adhered to.
Belimo valves are regulating devices. For the valves to function correctly in the long
term, they must be kept free from particle debris (e.g. welding beads during installation
work). The installation of a suitable strainer is recommended.
Servicing Ball valves and rotary actuators are maintenance-free.
Before any service work on the final controlling device is carried out, it is essential to
isolate the rotary actuator from the power supply (by unplugging the electrical cable
if necessary). Any pumps in the part of the piping system concerned must also be
switched off and the appropriate slide valves closed (allow all components to cool
down first if necessary and always reduce the system pressure to ambient pressure
level).
The system must not be returned to service until the ball valve and the rotary actuator
have been correctly reassembled in accordance with the instructions and the pipeline
has been refilled by professionally trained personnel.
www.belimo.com C2..QPT-..-.. • en-gb • 2020-07-15 • subject to changes 7
Piping Package with PI Zone Valve, 2-way, Euro cone
C2..QPT-..-..
Installation notes
Flow direction The direction of flow, specified by an arrow on the housing, is to be complied with
during normal operation, since otherwise the ball valve could become damaged.
Please ensure that the ball is in the correct position (marking on the spindle).
Flow setting The angle of rotation of the CQ.. actuator can be changed by end stop clip in 2.5°
increments. This is used to set the V’max-value (maximum flow rate of the valve).
Remove end stop clip and place at desired position.
After every change of the flow setting by means of end stop clip, an adaptation must
be triggered on the modulating actuators.
3
4
2
5
1
6
N
1 2 3 3+ 4- 4 4+ 5- 5 5+ 6- 6 6+ N- N
Pos
max (l/h) 20 30 40 45 50 60 70 80 90 105 120 135 150 165 180 210
C2..QPT-B-..
max (l/s) 0.006 0.008 0.011 0.013 0.014 0.017 0.019 0.022 0.025 0.029 0.033 0.038 0.042 0.046 0.050 0.058
max (l/h) 50 70 100 110 130 150 170 190 210 240 270 300 330 360 400 420
C2..QPT-D-..
max (l/s) 0.014 0.019 0.028 0.031 0.036 0.042 0.047 0.053 0.058 0.067 0.075 0.083 0.092 0.100 0.111 0.117
max (l/h) 90 130 190 220 250 290 340 390 440 500 570 630 700 760 820 980
C2..QPT-F-..
max (l/s) 0.025 0.036 0.053 0.061 0.069 0.081 0.094 0.108 0.122 0.139 0.158 0.175 0.194 0.211 0.228 0.272
max (l/h) 260 410 600 670 750 840 920 1010 1110 1210 1310 1420 1530 1640 1750 2100
C2..QPT-G-..
max (l/s) 0.072 0.114 0.167 0.186 0.208 0.233 0.256 0.281 0.308 0.336 0.364 0.394 0.425 0.456 0.486 0.583
8 C2..QPT-..-.. • en-gb • 2020-07-15 • subject to changes www.belimo.com
Piping Package with PI Zone Valve, 2-way, Euro cone
C2..QPT-..-..
Dimensions / Weight
Dimensional drawings
min. X
H
L L4
L6
min. Y
B2
CD
euro cone
G 3/4”
B
B1
L3 L1 L2
L5
L3, L4 and L5 is for the additionaly part mounted on C220QPT-F-11CG only
Type DN G L L1 L2 L3 L4 L5 L6 B B1
[] [“] [ mm] [ mm] [ mm] [ mm] [ mm] [ mm] [ mm] [ mm] [ mm]
C215QPT-B-11A 15 3/4 174 16 158 75 195 154
C215QPT-B-21A 15 3/4 174 16 158 75 253 194
C215QPT-D-11B 15 3/4 174 16 158 75 195 154
C215QPT-D-21B 15 3/4 174 16 158 75 253 194
C220QPT-F-11CG 20 3/4 189 12 44 245 84 209 169
C220QPT-F-21C 20 3/4 189 32 158 84 239 199
C220QPT-G-21D 20 3/4 201 48 158 92 244 206
www.belimo.com C2..QPT-..-.. • en-gb • 2020-07-15 • subject to changes 9
Piping Package with PI Zone Valve, 2-way, Euro cone
C2..QPT-..-..
Dimensions / Weight
Type B2 H X Y Weight
[ mm] [ mm] [ mm] [ mm]
C215QPT-B-11A 52 69 115 90 2.1 kg
C215QPT-B-21A 52 69 115 105 2.2 kg
C215QPT-D-11B 52 69 115 90 2.1 kg
C215QPT-D-21B 52 69 115 105 2.2 kg
C220QPT-F-11CG 63 73 120 95 2.8 kg
C220QPT-F-21C 63 73 120 95 2.6 kg
C220QPT-G-21D 77 78 125 100 3.2 kg
Further documentation
• Installation instruction for Piping Package with PI zone valve
• Installation instruction for pipe fittings
• Data sheets for actuators CQ..
• General notes for project planning
10 C2..QPT-..-.. • en-gb • 2020-07-15 • subject to changes www.belimo.com