ABB MNS-MCC
Low Voltage Motor Control Center
Application Guide
Table of Contents
The MNS-MCC is designed to meet the industry requirements The MNS-MCC offers many advantages and alternative solu-
for such markets as: tions with conventional-type installations that include:
System Overview
The basic design:
−− Standard UL845, CSA, and NOM
− − Enclosure Type: NEMA 1A
− − Withdrawable unit technology
Standards
The MNS-MCC is designed, tested, and constructed in accor-
dance with the following industry standards and guidelines:
−− UL845 — Low Voltage Motor Control Centers
− − UL50 — Enclosures for Electrical Equipment
− − NOM NMXJ853 — Normas Oficiales Mexicanas
−− NFPA 70E — National Electric Code Safety Requirements
−− NFPA 70 — National Electric Code
− − NEMAICS 1B — Motor Control Centers
− − NEMA 250 — Enclosures for Electrical Equipment
− − IEEE 1584 — Arc Flash Calculations Standard
− − CSA C22.2 — Canadian Low Voltage Electrical Equipment
− − ANSI C84.1 — Voltage Tolerances for North America
− − Seismic Qualification to IBC-2006 and CBC-2007, AC156,
“Shake-Table Testing for Nonstructural Components and
Systems,” and ASCE/SEI 7-05, “Minimum Design Loads for
Buildings and Other Structures”
Ratings
Description Value
Rated operating voltage 208Vac, 240Vac, 480Vac, 600Vac
System 3 phase-3 wire, 3 phase-4 wire
Frequency 60 Hz
Voltage Tolerances +/- 10%
Frequency Tolerances +/- 2%
Short circuit current withstand at 480Vac 42kA, 65 kA, 100kA
Short circuit current withstand at 600Vac 25kA, 42kA, 65 kA, 100 kA 1
Rated continuous current 800A, 1200A, 2000A, 2500A, 3000A
Main Busbar (Horizontal) 800A, 1200A, 2000A, 2500A , 3200A, 4000A
Distribution Bus (Vertical) at 65kA 800A, 1600A
Distribution Bus (Vertical) at 100kA 1600A
Ground Bus 400A
Notes:
1. Consult with sales office for additional information
Environmental Ratings
Requirements Value
Ambient air temperature for indoor type enclosures -10°C to +40°C (14°F to 104°F)
Ambient air temperature for equipment storage -25°C to +65°C (-40°F to 149°F)
Altitude 1000 m/ 3300 ft *Reference to altitude de-rating chart in table
Humidity Rating 85%, non-condensing for indoor enclosures
Breaker Derating
The Emax power breakers do not undergo any changes in their rated performance up to an altitude of 6600 ft (2000m).
As the altitude increases the atmospheric properties alter in terms of composition, dielectric capacity, cooling power and pressure.
Therefore the breaker undergoes the following derating:
Structure
The MNS-MCC assembly consists of one or more enclosed ver- The horizontal bus compartment is separated from the area for
tical sections with an area for mounting units, a vertical wireway mounting units and the vertical wireway by use of the multifunc-
for motor lead and control wire connections, and bus compart- tion separator and barriers.
ment. The end panels are designed to allow the addition of
future. Each section also includes a top and bottom horizontal Lifting eyes are provided as a standard on the roof of the enclo-
wireway for ground bus and cable guide rail. sure to allow lifting by the use of a crane.
Withdrawable Unit
Pilot Devices
Operation Handle
Vertical Wireway
Unit Handles
Door Locks
OL Reset Button
Multi-functional
Separator
Mechanical Interlock
Contact Holder
Standard Finish
The standard finish color is light gray textured paint (ANSI 61).
The pain comes standard with a gloss: G40 +/- 10. The finish
is Hammer Tone. The standard painting process is an electro-
static powder coat paint system utilizing polyester powder coat
paint. The completed finish has minimum 2 mils dry film thick-
ness. The process includes cleaning any grease or deficient
phosphate, rinsing, spray coating, oven drying, electrostatic
powder spray paint coating, and oven baking.
Frame
The basic elements of the frames are: rigid C-channel rails of 12
and 14 gauge thickness galvanized steel with holes at 1inch (25
mm) intervals. The parts of the frame are secured with thread-
forming screws and require no maintenance. The corner joints
are carried out by means of pressure plates and secured with
thread-forming screws.
Available Dimensions
The standard structural height of the MNS-MCC is 88 inches The standard motor control center section has a width of 20
(2200 mm) with a top 6 inch (150 mm) wireway, a bottom 7 inch inches (500 mm) wide. Incoming sections and other types of
(175 mm) horizontal wireway for ground bus access and ad- sections range from 20 inches (500 mm) to 40 inches (1000
ditional wiring space. The balance of the vertical compartment, mm) depending on size, application, and amperage of the sec-
72 inches (1800 mm) is available for mounting withdrawable or tion. The MNS-MCC depth is 20 inches (500 mm).
plug-in units. There are 2 additional inches added to the total
height with the lifting eyes and the banner with the ABB logo
and product name.
Horizontal Wireways
The top horizontal wireway is 6 inches (150 mm) high. The
wireway provides access the guide rail and cable connections.
The horizontal wireway is covered by a 6 inch (150 mm) high
14-gauge steel hinged door secured by a steel quarter-turn
latch.
Nameplates
Line Up Nameplate
Each MCC line up is provided with an engraved stainless steel
nameplate located in the middle of the vertical wireway door of
each line up. The nameplate includes the following information:
− − Model Type
− − Rated Voltage, Current, Phases, and Wires
− − Short Circuit and Frequency
− − Construction Type
− − Control Voltage
−− Space Heater Voltage
− − Manufacturing Year
− − Project No
− − Weight
− − Nameplate Part Number
Section Nameplate
Each MCC section is provided with an engraved white back-
ground with black lettering phenoloic section nameplate located
in the top portion of the vertical wireway door or cover for other
types of sections. The nameplate includes the following infor-
mation:
−− Order number
− − Manufacturing Date
− − Enclosure Type
−− Bus Bar Voltage, Short circuit, Current and Frequency Rat-
ings
− − Control Voltage
− − Serial Number
− − Nameplate Part Number
MNS-MCC
Order No. - Nominal Voltage - V Cicuit diagram -
Type - Nominal Current - A Frequency - Hz
Nominal power - HP Fusing - A
Control voltage - V
Unit location -
2TDA080012P0002
NEMA-1A (gasketed)
The MNS-MCC standard enclosure is NEMA-1A (gasketed).
The enclosures are deadfront, metal-enclosed structures. All
front doors, side panels, and rear panels or doors are painted
using textured electrostatic powder type paint. The enclosure is
appropriate for installations with normal atmospheric conditions.
It is intended for use primarily to provide a degree of protection
against limited amounts of falling dirt.
Standard Features
−− ANSI 61 textured paint color
− − 4 inch vertical wireway
− − Barriers between each section
−− Removable, steel top plates over conduit entrance
−− Cable wire tray in top of unit wireway
− − Gasketing on all doors
− − Lifting eyes
Available Options
− − 8 inch vertical wireway
− − Bottom plates
Standard Features
−− ANSI 61 textured paint color
− − 4 inch vertical wireway
− − Barriers between each section
−− Removable, steel top plates over conduit entrance
−− Cable wire tray in top of unit wireway
− − Gasketing on all doors
− − Lifting eyes
− − All units are gasketed
− − Gasketing is provided between sections
− − Louvers and filters are provided on all vents
Available Options
− − 8 inch vertical wireway
− − Bottom plates
The bus bars are connected to the adjacent section at each end
by means of shipping bus splice bar kits which are provided on
the left side of each shipping split. The bus splice kits are ac-
cessible through the front side in the vertical wireway. The bus
splice kits are secured by grade 5 hardware.
The vertical distribution busbars run A, B, and C phase from The vertical distribution busbars are available in ratings of 800A
left to right. The bars are used for connecting plug-in and at 65kA and 1600A at 100kA. The embedded busbars are
withdrawable units. The distribution bars are L-shaped and are silver-plated copper standard with an option for tin-plated.
embedded into the multi-function separator made of insulat-
ing material, non-flammable, and non-hygroscopic material. For 1600A vertical distribution busbar applications a double
The separator provides a degree of protection IP20 (protec- busbar system is used.
tion against ingress of solid foreign objects equal or greater
than 12.5 mm) and separates main horizontal bus and the unit
wireway.
Vertical Distribution
Bus Bar
Multi-functional
Separator
The ground bus is rated as follows: 1 bar of 1 3/16 inch x 3/8 As a standard the ground bus is provided with several 0.4 inch
inch, rated 400A. The length of the bar is dependent on the (10 mm) holes for each section in order for them to accept
MCC shipping unit lengths. As a standard ground bus, ABB ground lugs for any load that may require a ground conductor.
offers a bare copper bus. The protective connection bar is ar- The ground bars and connection bars are punched accordingly
ranged vertically in the cable compartment. which allow the bars to be mounted in the section.
Withdrawable Units
The other type of unit available on the MCC is the withdrawable The withdrawable unit consists of the following:
unit. The standard unit sizes are: 6”, 12”, 18”, 24”, 30”, 36”, − − Hinged front cover that is secured by a quarter-turn latch
42”, 46”, and 48”. Withdrawable units are used to house NEMA which allows ease of accessibility to the components inside
Size 00 to Size 5 starters. the unit from the front side.
− − Two handles attached to the front cover for ease of removing
The withdrawable compartment consists of the following: the unit from the MCC structure.
− − Compartment bottom steel plate with roller. − − A rotary handle for operation.
− − Guide rails for the units. − − Sheet metal side wall with one end of the pull-apart terminal
− − Sheet metal side wall with the outgoing control plug. blocks.
− − Outgoing cable connection unit − − Roller wheel for mechanically interlocking the device.
− − Plug-in contacts to connect to the multi-function wall and
distribution bus.
The uppermost withdrawable unit compartment is covered by a − − Plug-in contacts for motor lead connections.
compartment bottom pIate. The top cover for the lower com- − − Electrical components such as starters, contactors, control
partments is the bottom plate of the compartment above. power transformers, indicating lights, and metering and con-
trol products.
Withdrawable Units
Withdrawable unit feeder connections to the distribution bar The main switch is operated via a rotary operating handle which
system are done directly via the contact holder of the withdraw- is used for mechanically and electrically interlocking the unit.
able units. Outgoing cables are connected via plug-in-contacts The rotary handle mechanically interlocks by means of an isolat-
to the outgoing cable connection unit (main circuit) and via ter- ing position mechanism located on the front bottom portion of
minal blocks (auxiliary circuit). The outgoing cable connection each unit and a locking rod.
units are fastened directly to the frame.
Figure Position of Rotary Handle Position of Module Main and Control Circuits
ISOLATED The module is 30 mm drawn out of All main and control circuits are open
the section. and disconnected and the unit can
be withdrawn.
Withdrawn
Contactor
Combination Motor Starter Units
The MNS-MCC offers four types of combination starters: full
voltage non-reversing (FVNR), full voltage reversing (FVR),
two-speed one winding (2S1W), and two-speed two winding
(2S2W). Combination starters mount in a withdrawable unit for
NEMA Sizes 00 to 5. The unit sizes range from 6 inches to 48 Overload
inches depending on the NEMA Size and its content. For the
larger NEMA Size 6 and 7 the units are mounted fixed in a full
height unit.
Softstarters Units
The softstarter units from the MNS-MCC are mounted in a with-
drawable unit or in a full height. Softstarter units are available Main Disconnect
for NEMA Size 2 to Size 6. There two types of softstarter units Device
offered are: softstart reversing and softstart non-reversing.
The ratings for the softstarter units are: up to 400 HP (500 A).
Please refer to the coordination tables section in this guide for
further information. Contactor
Thermal Overloads Thermal overload relays are 3 pole. The motor current flows
TA thermal overload relays are used with A Line contactors through their bimetals (1 per phase) which are indirectly heated.
for the protection of motors having a nominal voltage of up to Under the effect of the heating, the bimetals bend; cause the
600VAC max per UL/CSA (690VAC). relay to trip and the position of the auxiliary contacts to change.
Digital Display
The PST display gives you information presented in plain words
— in your language. You can choose between 14 languages
including English, German, Italian, Chinese, Finnish, Swedish,
French, Spanish, Dutch, Russian, Turkish, Polish, Czech and
Portuguese. On the PST display, you get all the information you
need to setup, adjust and trouble-shoot. This makes the PST
extremely easy to handle and reduces the risk of misinterpreta-
tions.
At any time, you can read output current, output voltage, num-
ber of starts, total run time and motor temperature on the dis-
play. If a fault should occur, this is also indicated on the display.
The fault messages are presented in clear text in the selected
language.
Application macros
−− 2-wire, 3-wire, Alternate, Motor Potentiometer, Hand/Auto,
PID & Torque Control
Power Range
−− 1-phase supply 240V, 0.5 to 3 Hp
− − 3-phase supply 240V, 0.5 to 15 Hp
− − 3-phase supply 480V, 0.5 to 30 Hp
Features
− − Sensorless Vector Motor Control
−− (8) Sequence programming
−− Optimized interfaces for users and machines
− − Built-in brake chopper as standard
− − Built-in 2nd environment EMC filter
− − IP 20 (Finger Safe)
Highlights/Options
− − NEMA 1 Enclosure Kit
− − UL, cUL approved
− − FlashDrop with DrivePM (Parameter Manager)
− − MPOT (Speed Pot, Start/Stop & Fwd/Rev Switch)
−− Modbus, Modbus TCP, EtherNet IP, Profibus, DeviceNet,
CAN
− − Unified height and depth
− − Coated boards as standard
− − Pulse train frequency input
−− I/O (2 AI, 2AO, 5 DI, 1 RO, 1DO)
Application macros
− − ABB standard, 3-wire, Alternate, Motor Potentiometer, Hand/
Auto, PID, PFC & Torque Control
Power Range
− − 3-phase supply 240V, 1 to 100 Hp
− − 3-phase supply 480V, 1.5 to 550 Hp
− − 3-phase supply 600V, 2 to 150 HP
Features
− − IP21 (NEMA 1) & IP54 (NEMA 12)
− − Scalar, Open Loop, and Closed Loop Vector
− − Built-in brake chopper up to 15Hp
−− Built-in 1st environment EMC filter
Highlights/Options
−− UL, cUL approved (600V product is CSA only)
− − FlashDrop with DrivePM (Parameter Manager)
− − Start-up Assistants (Diagnostic, Maintenance, Start-up, PID
Controller, Real-time Clock, Serial Comm, Drive Optimizer)
− − DeviceNet, ControlNet, Profibus, Modbus TCP, EtherNet IP,
CAN Open, ProfiNet IO
− − Patented swinging choke for superior harmonic reduction
− − Coated boards as standard
− − Flange Mounting
−− I/0 (2 Al, 2 AO, 6 DI, 3 RO)
Application macros
−− ABB standard, 3-wire, Alternate, Motor Potentiometer, Hand/
Auto, PID, PFC & Torque Control
Power Range
−− 3-phase supply 240V, 1 to 100 Hp
− − 3-phase supply 480V, 1.5 to 550 Hp
− − 3-phase supply 600V, 2 to 150 HP
Features
− − IP21 (NEMA 1) & IP54 (NEMA 12)
−− Scalar, Open Loop, and Closed Loop Vector
−− Built-in brake chopper up to 15Hp
− − Built-in 1st environment EMC filter
Highlights/Options
− − UL, cUL approved (600V product is CSA only)
− − FlashDrop with DrivePM (Parameter Manager)
− − DeviceNet, ControlNet, Profibus, Modbus TCP, EtherNet IP,
CAN Open, ProfiNet IO
− − Patented swinging choke for superior harmonic reduction
− − Coated boards as standard
− − Flange Mounting
−− I/0 (2 Al, 2 AO, 6 DI, 3 RO)
Circuit Breakers
The circuit breakers utilized as disconnecting means in the
MNS-MCC are ABB Tmax molded case breakers. The Tmax
are UL489 certified and offer the following features:
There are two types of molded case breakers used in the units
of an MNS-MCC: MCP and Thermal Magnetic type. The MCP
circuit breakers are used to protect three phase asynchronous
motors in combination with a contactor and a thermal overload
relay.
Circuit breaker
with magnetic
only trip unit
Contactor
Thermal relay
M Motor
3~
ABB offers two different protection types for MCP breakers: The thermal magnetic breakers are used in protection of al-
−− A magnetic only trip unit (MA) for Tmax T2 with adjustable ternating and direct current networks with a range of us from
threshold between 6…12 X ln 15A to 800A. They allow the protection against overload
− − An electronic trip unit with only an instantaneous short circuit with a thermal device (with fixed threshold for T2and T4 and
protection I, PR2221DS-I for Tmax T4, T5, and T6, and adjustable threshold for T4, T5, and T6) realized using the
PR231/P for Tmax T7 bimetal technique and protection against short-circuit with a
magnetic device.
Incoming line cable connections entering the MNS-MCC either Main Disconnects
the top or bottom can be easily terminated onto either: Main Incoming cables may also be easily terminated on a main circuit
Lugs Only (MLO) or to a Main Disconnect. All incoming line breaker. For amperages up to 1200A an ABB Tmax molded
types comply with NEC wiring bending requirements as adopted case breaker is used in a plug-in unit. It is mounted on a plate
by UL. and connected to the multi-function wall with the plug-in con-
tacts in the vertical wireway. The entire unit is securely fastened
MLO Section to the frame with self-tapping screws. For 1600, 2000, 2500,
Up to 800A rated horizontal bus, cables may be terminated on and 3000A mains an ABB Emax power breaker is used in its
crimp or mechanical lugs mounted on the plug-in main lug unit own section. The breaker is connected to the horizontal bus via
which is plugged in the multi-function wall. The plug-in main lug bus bar. The Emax breaker is fixed mounted.
unit allows for top or bottom entry of the cables. It is located
on the multi-function wall according to what the incoming is. Please see Layout section in this document for Emax main
breaker layouts.
MLO terminations for 1200A, 1600A, 2000A, 2500A, 3200A,
and 4000A the MNS-MCC requires the use of a full vertical sec-
tion.
Maintenance Switch
Description
The maintenance switch is used to manually change the circuit
breaker’s Instantaneous protection settings to a preprogrammed
set of values by means of a door mounted switch.
Application
The maintenance switch concept is used when the customer re-
quires a faster tripping time when personnel are working in and
around the switchgear. The circuit breaker stores preset values
(Value A = “Normal” and Value B = “Maintenance”) with regards
to the instantaneous settings. These values are determined
by the customer and programmed into the circuit breaker trip
unit. “Normal” values are specified for regular operation of the
switchgear, “Maintenance” values are specified for when work
is being performed on the switchgear. The values can be easily
changed by means of the maintenance switch located on the
circuit breaker compartment door.
Required Parts
−− PR123 Trip Unit for the Emax circuit breaker.
− − Blue indicating light (to be blinking when in maintenance
mode)
− − ABB 2 position changeover switch, 4 pole, with padlockable
handle in both positions.
Example Schematics
Withdrawable Units
Dimensions 6” Unit 12” Unit 18” Unit 24” Unit 30” Unit 36” Unit 48” Unit
Width 16” 16” 16” 16” 16” 16” 16”
(400 mm) (400 mm) (400 mm) (400 mm) (400 mm) (400 mm) (400 mm)
Height 6” (6E) 12E 18E 24E 30E 36E 48E
Depth 16” 16” 16” 16” 16” 16” 16”
Sections without busbar compartment Sections with busbar compartment Sections with cable and busbar compartment;
cable entry only to the cable compartment
MCC Mounting
Notes:
Top Wireway Four bolts per vertical section will fasten the MCC through its
Compartment internal mounting angle to the foundation; the hardware required
Main Busbars for a successful installation is HSL-3 M8/20 or Hex Bolt M8X20
Grade 8.8 depending on the surface its being installed. See the
following illustrations and tables for general dimensions. Exact
dimensions matching your equipment can be found on the
Main Busbars elevation drawings shipped with your MCC.
The installation of switchgears having the cable entries at the
Compartment bottom requires a foundation with an opening or a cable duct.
The sections should preferably be installed on a base frame
which is either embedded in the concrete floor or rests as a false
floor on supports.
Bottom Wireway
Compartment
Ground Bar
Front View Side View Fastening through welding
Cable Compartment
12E 600
18E 1000
20W Full 1200
24W Full 4000
ACS350, ACS550, and ACS850 Variable Frequency Drives with Circuit Breakers
208- Rated Drive Power Withdrawable
VFD Module 480V 600V Disconnect
240V Current Frame wire or Fixed
Type Size (HP) (HP) Means
(HP) A size Size Configuration
12 1.5 5 na 6.7 R1 10 awg
ACS350 18 5 10 na 17.6 T4x100BW R3 10 awg Withdrawable
24 10 25 na 31 R4 8 awg
30 7.5 10 10 24.2 T4x060BW R2 10 awg
42 15 25 20 46.2 T4x100BW R3 6 awg Withdrawable
ACS550
48 30 60 50 88 T4x150BW R4 2 awg
Full 75 150 125 221 T5x400BW R6 2/0 awg (2) Fixed
30 7.5 20 na 27 T4x050TW R3 10 awg Withdrawable
ACS800
Full 60 150 150 180 T4x250BW R6 2 awg (2) Fixed
ACS350, ACS550, and ACS850 Variable Frequency Drives with Fusible Disconnect
208- Rated Fuse Drive Withdrawable
VFD Module 480V 600V Disconnect Bussmann Power wire
240V Current Rating Class Frame or Fixed
Type Size (HP) (HP) Means fuse Size
(HP) A (A) size Configuration
30 7.5 10 10 24.2 OS60J12 60 J DFJ R2 10 awg
42 15 25 20 46.2 OS100J12 80 J DFJ R3 6 awg Withdrawable
ACS550
48 30 60 50 88 OS200J12 200 J DFJ R4 2 awg
Full 75 125 125 221 OS600J21 450 J DFJ R6 2/0 awg (2) Fixed
30 7.5 15 na 24.2 OS60J12 60 J DFJ R3 10 awg
Withdrawable
ACS800 36 na 20 na 31 OS100J12 70 J DFJ R3 10 awg
Full 60 150 150 180 OS400J12 350 J DFJ R6 2 awg (2) Fixed
TA200DU110 TA200DU150
130 40 50 100 N/A T4#250E5W TA200DU135
TA200DU135 E200DU200-10
E16DU2.7-10 TA25DU1.8
T4045SF1 6 (150 mm) 6E
E16DU6.3-10 TA25DU2.4 N/A 10 AWG Withdrawable
T4050PSF1 12 (300 mm) 12E
TA25DU1.4 TA25DU4.0
4 AWG
E80DU80-10 TA75DU42 12 (300 mm) 12E
N/A T4075PSF1 6 AWG Withdrawable
TA75DU80 TA75DU52 18 (450 mm) 18E
8 AWG
E80DU80-10 T4075PSF1 8 AWG
TA75DU42 TA75DU52 Withdrawable 12 (300 mm) 12E
TA75DU42 T6075PS1 10 AWG
T4075PSF1 6 AWG 12 (300 mm) 12E
E80DU80-10 TA75DU52 E80DU80-10 TA75DU52 Withdrawable
T6075PS1 8 AWG 18 (450 mm) 18E
N/A N/A T4150PSF1 2/0 AWG (2) Withdrawable 42 (1050 mm) 42E
T6250PS1
E800DU800-10 E800DU800-10 Bus Bars Full Full Section 72E
T4250PSF1
10
E16DU18.9-10 TA25DU14
0 10.6 3 3 5 5 OS30AJ12 15 J LPJ A16N0-30-10-84
TA25DU8.5
20
20
16.8 5 5 10 10 OS30AJ12 J LPJ E45DU30-10 TA25DU19
30
1 A26N1-30-10-84
40
24.2 7.5 7.5 N/A N/A OS60J12 J LPJ E45DU45-10 TA25DU32
45
110
150 TA200DU135 TA200DU110
124 40 40 100 100 OS200J12
175 E200DU200-10
4 200 J LPJ A145N4-30-11-84
225
300 E320DU320-10 TA450DU235
212 75 75 150 200 OS400J12
350 TA450DU185
5 400 J LPJ A260N5-30-11-84
450
344 125 125 250 350 OS600J21 500 J LPJ E500DU500-10
6 600 AF460N6-3011-70
700
414 150 150 350 400 OS800L12 L KRP-C E500DU500-10
800
E45DU30-10 TA25DU25 N/A N/A T4050PSF1 10 AWG Withdrawable 12 (300 mm) 12E
E80DU80-10 TA75DU52 N/A N/A T4075PSF1 8 AWG Withdrawable 12 (300 mm) 12E
N/A N/A E80DU80-10 TA45DU45-10 T6075PS1 10 AWG Withdrawable 12 (300 mm) 12E
E80DU80-10 TA75DU32
E80DU80-10 TA75DU25 T4075PSF1
E80DU80-10 TA75DU32 E45DU45-10 TA75DU42 10 AWG Withdrawable 18 (450 mm) 18E
E45DU45-10 TA75DU32 T6075PS1
TA75DU25
E80DU80-10 TA75DU80
E80DU80-10 TA75DU80 N/A T4075PSF1 4 AWG Withdrawable 24 (600 mm) 24E
E140DU140-10 TA110DU90
N/A N/A E80DU80-10 TA75DU42 T4075PSF1 10 AWG Withdrawable 18 (450 mm) 18E
2 AWG
TA200DU90 TA200DU110 TA200DU90 TA200DU110 T4150PSF1
E200DU200-10 TA200DU110 4 AWG Withdrawable 30 (750 mm) 30E
E200DU200-10 TA200DU150 E200DU200-10 TA80DU80 T6150PS1
6 AWG
E200DU200-10 TA200DU150 N/A N/A T4150PSF1 2 AWG Withdrawable 36 (900 mm) 36E
2 AWG
E320DU320-10 TA450DU235 E320DU320-10 TA450DU235 E320DU320-10 TA450DU235 T4250PSF1 2 AWG (2)
Withdrawable 42 (1050 mm) 42E
TA450DU185 TA450DU185 TA450DU185 TA200DU150 T6250PS1 2/0 AWG
2/0 AWG (2)
E320DU320-10 TA450DU310 E320DU320-10 TA450DU310 N/A T4250PSF1 2/0 AWG (2) Full Full Section 72E
T4150PSF1
E500DU500-10 E500DU500-10 E500DU500-10 Bus Bars Full Full Section 72E
T6150PS1
TA450DU310 E320DU320-10
248 75 100 200 200 T5#400E5W E320DU320-10 TA450DU235
TA450DU235
E45DU30-10
TA25DU19 N/A T4050PSF1 10 AWG Withdrawable 18 (450 mm) 18E
TA25DU14
T4075PSF1
E80DU80-10 TA75DU32 E80DU80-10 TA75DU32 10 AWG Withdrawable 18 (450 mm) 18E
T6075PS1
4 AWG
E80DU80-10 TA75DU63
N/A T4075PSF1 6 AWG Withdrawable 18 (450 mm) 18E
TA75DU42 TA75DU80
8 AWG
N/A E80DU80-10 TA75DU42 T6075PS1 10 AWG Withdrawable 18 (450 mm) 18E
E80DU80-10 E80DU80-10
T4075PSF1 8 AWG
TA75DU42 TA75DU52 Withdrawable 18 (450 mm) 18E
T6075PS1 6 AWG
TA75DU63 TA75DU63
E80DU80-10 TA75DU80 N/A T4075PSF1 4 AWG Withdrawable 18 (450 mm) 18E
E200DU200-10
N/A T6150PS1 6 AWG Withdrawable 36 (900 mm) 36E
TA80DU80
E200DU200-10 TA200DU090 E200DU200-10 TA200DU090 T4150PSF1
4 AWG Withdrawable 36 (900 mm) 36E
TA200DU110 TA200DU110 T6150PS1
2 AWG
E200DU200-10 TA200DU135 N/A T4150PSF1 Withdrawable 36 (900 mm) 36E
4 AWG
E320DU320-10 TA200DU150 T4250PSF1 2 AWG
N/A Withdrawable 42 (1050 mm) 42E
TA450DU185 T6250PS1 2/0 AWG
E320DU320-10 TA450DU235 2 AWG (2)
N/A T4250PSF1 Withdrawable 48 (1200 mm) 48E
TA450DU185 2/0 AWG
T4250PSF1 2/0 AWG (2)
TA450DU310 E320DU320-10 TA450DU235 E320DU320-10 Withdrawable 48 (1200 mm) 48E
T6250PS1 2 AWG (2)
T4150PSF1
E500DU500-10 E500DU500-10 2/0 AWG (2) Full Full Section 72E
T6150PS1
T4150PSF1
E500DU500-10 E500DU500-10 Bus Bars Full Full Section 72E
T6150PS1
T6250PS1
E800DU800-10 E800DU800-10 Bus Bars Full Full Section 72E
T4250PSF1
30“ PST72-600-70
80 T4N100E5W T4150PSF1 4 AWG Withdrawable
36“ PST85-600-70