1 2 3 4 5 6 7 8
SINGLE LINE DIAGRAM
PRIMARY EQUIPMENT INDEX
DEVICE ID DEVICE NAME QTY PN
-QAB SF6 CIRCUIT BREAKER 1 HD4/Z-R-NEW
-SFS32 -SFS31 -SFS34 -BR16
-BAD CAPACITIVE VOL.DIVIDER 3 DID-35-ZJ1-35(C) QAB
LOCAL/SUPERVISORY TRIP/NORMAL/CLOSE ON/OFF SELECTOR
SELECTOR SWITCH CB OPERATE SWITCH AUTO RECLOSING SWITCH SPER1B1C4
-BCT1 CURRENT TRANSFORMER 1 CTA-OT-D7K313-0229
B
-BCT2 CURRENT TRANSFORMER 1 CTA-OT-D7K313-0229 P1* -BCG1 PQ -PGM -BR40
3
800; 400/1,5P20,15VA -TW1 -TW2
-BCT3 CURRENT TRANSFORMER 1 CTA-OT-D7K313-0229 -BCG2 DPT643-15F DPT643-15F
3
REF615 Ion 92040 ELITE448 SAD
800; 400/1A CLASS X
3
RED615
800; 400/1,CL0.2S,7.5VA Tariff Metering
3
Main
2000,1000/1A, PX
(Uk=400V,Rct<= 10 ohms, 3
Check
Ie<=100mA )on all ratio Exisiting BBP
-QCE EARTH SWITCH 1 GCE-EK6
P2
C
-FCF HV Fuse 3 FLX-OT4050020I440N BAD
of ABB (XIAMEN) Switchgear CO. LTD. and shall not be used,
This drawing and information contained thereon is the property
reproduced for any purpose ,or shown to third parties without
the written consent of ABB (XIAMEN) Switchgear CO. LTD.
-QBT VT TRUCK 1 QTV-AZ1
-QCE -PU
EK6
BAT1 VOLTAGE TRANSFORMER 1 VTS-OTD33224111123
-FA FCF
XRNP-3*2A
BAT2 VOLTAGE TRANSFORMER 1 VTS-OTD33224111123
BAT3 VOLTAGE TRANSFORMER 1 VTS-OTD33224111123 BAT
33/rt3: 0.11/rt3 : 0.11/rt3 : 0.11/rt3 kV D
FA SURGE ARRESTER 3 SAA-MWK36 0.2, 15VA
0.5, 15VA
3P, 15VA
LEGEND
BCG1 : Relay REF 615
PQ : Power Quality Meter - Ion 92040
BCG2 : Relay RED 615
BR40: Fault Annunciator SAD
PGM: Meter ELITE448
PU: Voltage Indicator DXN-Q
REV. DATE
E
DESCRIPTION(FOR CLIENT)
F
REV.
DRAWN Bijing Guo TITLE FUNCTION = F1 SHEET NO. 1
CHECKED Neal SINGLE LINE DIAGRAM SCALE 1:1 TOTAL PAGES 25
APPROVED Season CONTRACT NO. ABB XIAMEN PROJECT DRAWING NO.
REV. DESCRIPTION(FOR ABB INTERNAL) REV. DATE FIRST DATE 2021/8/17
503263035 SWITCHGEAR CO. LTD. Extension of DISI 132/33 kV Substation XZS3.2-17952-A01-F1-S
Ion 92040
L1 Power Quality L2 PowerLogic™ ION9000 L3
L1 L2 L3 L4
Power Quality
Ion 92040
PowerLogic™ ION9000