Main cooling fan maintenance procedure:

Maintenance procedure for wall-mounted drives ACS-880-01 involves cleaning of Main cooling fan,
Heat sinks and internal dusting.

 Switch off power supply to VFD and apply LOTO to the breaker.
 Begin by removing the front panel and accessing the main fan(s) located underneath at rear
end.

Fig 1: Location of the fan


Main cooling fan maintenance procedure:

 Unscrew the mounting screws for the fan mounting plate.

Fig 2: Mounting Screws


 Remove the fan from place and unplug the power supply wires.

Fig 3: Power supply connector


 Vessel can access inner space which consists of the capacitor and heat sinks.
Main cooling fan maintenance procedure:

Fig 4: Inner space


 With the help of the clean brush, remove the dust accumulated inside as practical as possible.
 Employ clean air (dry compressed air) to blow away accumulated dust and debris from the heat
sinks.
 Don’t use any aerosol liquid to clean the inner components.
 Subsequently, use a non-fluffy cloth to wipe the heat sinks thoroughly, ensuring the removal of
any remaining particles. Proper cleaning would be necessary.
 Blow from the bottom and top side again to blow away accumulated dust and debris from the
heat sink.

Fig 5: Bottom View of Heat sink Fig 6: Top view of Heat sink

This process is essential for maintaining optimal heat dissipation and preventing overheating issues in
ACS-880-01 wall-mounted drives.