Technical data sheet                                                  NVC24A-MP-RE
Communicative globe valve actuator for 2-way
and 3-way globe valves
• Actuating force 1000 N
• Nominal voltage AC/DC 24 V
• Control modulating, communicative 2...10 V
variable
• Stroke 20 mm
• Communication via Belimo MP-Bus
• Conversion of sensor signals
 Technical data
                                 Electrical data   Nominal voltage                            AC/DC 24 V
                                                   Nominal voltage frequency                  50/60 Hz
                                                   Nominal voltage range                      AC 19.2...28.8 V / DC 21.6...28.8 V
                                                   Power consumption in operation             3.5 W
                                                   Power consumption in rest position         1.5 W
                                                   Power consumption for wire sizing          5.5 VA
                                                   Connection supply / control                Terminals 4 mm² (cable ø4...10 mm)
                                                   Parallel operation                         Yes (note the performance data)
                      Data bus communication       Communicative control                      MP-Bus
                                                   Number of nodes                            MP-Bus max. 8
                                Functional data    Actuating force motor                      1000 N
                                                   Operating range Y                          2...10 V
                                                   Input impedance                            100 kΩ
                                                   Operating range Y variable                 Start point 0.5...30 V
                                                                                              End point 2.5...32 V
                                                   Operating modes optional                   Open/close
                                                                                              3-point (AC only)
                                                                                              Modulating (DC 0...32 V)
                                                   Position feedback U                        2...10 V
                                                   Position feedback U note                   Max. 0.5 mA
                                                   Position feedback U variable               Start point 0.5...8 V
                                                                                              End point 2.5...10 V
                                                   Position accuracy                          ±5%
                                                   Manual override                            with push-button, can be locked
                                                   Stroke                                     20 mm
                                                   Running time motor                         35 s / 20 mm
                                                   Running time motor variable                35...90 s
                                                   Sound power level, motor                   60 dB(A)
                                                   Adaptation setting range                   manual (automatic on first power-up)
                                                   Adaptation setting range variable          No action
                                                                                              Adaptation when switched on
                                                                                              Adaptation after pushing the manual override
                                                                                              button
                                                   Override control                           MAX (maximum position) = 100%
                                                                                              MIN (minimum position) = 0%
                                                                                              ZS (intermediate position, AC only) = 50%
www.belimo.com                                 NVC24A-MP-RE • en-gb • 2024-10-01 • Subject to change                                 1/8
                                       Technical data sheet                                                        NVC24A-MP-RE
 Technical data
                     Functional data    Override control variable                       MAX = (MIN + 33%)...100%
                                                                                        ZS = MIN...MAX
                                        Position indication                             Mechanical, 5...20 mm stroke
                         Safety data    Protection class IEC/EN                         III, Safety Extra-Low Voltage (SELV)
                                        Power source UL                                 Class 2 Supply
                                        Degree of protection IEC/EN                     IP54
                                        Degree of protection NEMA/UL                    NEMA 2
                                        Housing                                         UL Enclosure Type 2
                                        EMC                                             CE according to 2014/30/EU
                                        Certification IEC/EN                            IEC/EN 60730-1 and IEC/EN 60730-2-14
                                        UL Approval                                     cULus according to UL60730-1A, UL60730-2-14
                                                                                        and CAN/CSA E60730-1
                                                                                        The UL marking on the actuator depends on
                                                                                        the production site, the device is UL-compliant
                                                                                        in any case
                                        Type of action                                  Type 1
                                        Rated impulse voltage supply / control          0.8 kV
                                        Pollution degree                                3
                                        Ambient humidity                                Max. 95% RH, non-condensing
                                        Ambient temperature                             0...50°C [32...122°F]
                                        Storage temperature                             -40...80°C [-40...176°F]
                                        Servicing                                       maintenance-free
                             Weight     Weight                                          1.8 kg
 Safety notes
                                       • This device has been designed for use in stationary heating, ventilation and air-conditioning
                                         systems and must not be used outside the specified field of application, especially in aircraft
                                         or in any other airborne means of transport.
                                       • Outdoor application: only possible in case that no (sea) water, snow, ice, insolation or
                                         aggressive gases interfere directly with the device and that it is ensured that the ambient
                                         conditions remain within the thresholds according to the data sheet at any time.
                                       • Only authorised specialists may carry out installation. All applicable legal or institutional
                                         installation regulations must be complied with during installation.
                                       • The switch for changing the direction of motion and so the closing point may be adjusted
                                         only by authorised specialists. The direction of motion is critical, particularly in connection
                                         with frost protection circuits.
                                       • The device may only be opened at the manufacturer's site. It does not contain any parts that
                                         can be replaced or repaired by the user.
                                       • The device contains electrical and electronic components and must not be disposed of as
                                         household refuse. All locally valid regulations and requirements must be observed.
 Product features
                    Operating mode     Conventional operation:
                                       The actuator is connected with a standard control signal of 0...10 V and drives to the position
                                       defined by the control signal. The measuring voltage U serves for the electrical display of the
                                       actuator position 0.5...100% and as control signal for other actuators.
                                       Operation on Bus:
                                       The actuator receives its digital control signal from the higher level controller via the MP-Bus
                                       and drives to the position defined. Connection U serves as communication interface and does
                                       not supply an analogue measuring voltage.
www.belimo.com                     NVC24A-MP-RE • en-gb • 2024-10-01 • Subject to change                                         2/8
                                                   Technical data sheet                                                       NVC24A-MP-RE
 Product features
                         Converter for sensors     Connection option for a sensor (passive or active sensor or switching contact). The MP
                                                   actuator serves as an analogue/digital converter for the transmission of the sensor signal via
                                                   MP-Bus to the higher level system.
                     Parametrisable actuators      The factory settings cover the most common applications. Single parameters can be modified
                                                   with Belimo Assistant 2 or ZTH EU.
               Mounting on third-party valves      The RetroFIT+ actuators for installation on a wide range of valves from various manufacturers
                                                   are comprised of an actuator, bracket, universal valve neck adapter and universal valve stem
                                                   adapter. Adapt the valve neck and valve stem to begin with, then attach the RetroFIT+ bracket
                                                   to the valve neck adapter. Now fit the RetroFIT+ actuator into the bracket and connect it to the
                                                   valve. Whilst taking the position of the valve closing point into account, secure the actuator to
                                                   the bracket and then conduct the commissioning process. The valve neck adapter/actuator
                                                   can be rotated by 360° on the valve neck, provided the size of the installed valve permits.
                    Mounting on Belimo valves      Use standard actuators from Belimo for mounting on Belimo globe valves. The installation of
                                                   RetroFIT+ actuators on Belimo globe valves is technically possible.
                              Manual override      Manual override with push-button possible (the gear train is disengaged for as long as the
                                                   button is pressed or remains locked).
                                                   The stroke can be adjusted by using a hexagon socket screw key (4 mm), which is inserted
                                                   into the top of the actuator. The stroke shaft extends when the key is rotated clockwise.
                     High functional reliability   The actuator is overload protected, requires no limit switches and automatically stops when
                                                   the end stop is reached.
                                Home position      Factory setting: Actuator stem is retracted.
                                                   The first time the supply voltage is switched on, i.e. at the time of commissioning, the actuator
                                                   carries out an adaptation, which is when the operating range and position feedback adjust
                                                   themselves to the mechanical setting range.
                                                   The actuator then moves into the position defined by the control signal.
               Adaptation and synchronisation      An adaptation can be triggered manually by pressing the "Adaptation" button or with Belimo
                                                   Assistant 2. Both mechanical end stops are detected during the adaptation (entire setting
                                                   range).
                                                   Automatic synchronisation after pressing the manual override button is parametrised. The
                                                   synchronisation is in the home position (0%).
                                                   The actuator then moves into the position defined by the control signal.
                                                   A range of settings can be made using Belimo Assistant 2.
                    Setting direction of motion    When actuated, the direction-of-stroke switch changes the direction of motion in normal
                                                   operation.
 Accessories
                                          Tools    Description                                                                 Type
                                                   Service tool, with ZIP-USB function, for parametrisable and                 ZTH EU
                                                   communicative Belimo actuators, VAV controller and HVAC performance
                                                   devices
                                                   Service tool for wired and wireless setup, on-site operation, and           Belimo Assistant 2
                                                   troubleshooting.
                                                   Adapter for Service-Tool ZTH                                                MFT-C
                                                   Connecting cable 5 m, A: RJ11 6/4 ZTH EU, B: 6-pin for connection to        ZK1-GEN
                                                   service socket
                                                   Connecting cable 5 m, A: RJ11 6/4 ZTH EU, B: free wire end for              ZK2-GEN
                                                   connection to MP/PP terminal
                          Electrical accessories   Description                                                                 Type
                                                   Auxiliary switch 2x SPDT add-on                                             S2A-H
                                                   MP-Bus power supply for MP actuators                                        ZN230-24MP
www.belimo.com                                 NVC24A-MP-RE • en-gb • 2024-10-01 • Subject to change                                        3/8
                                                     Technical data sheet                                                       NVC24A-MP-RE
 Accessories
                                       Gateways      Description                                                                Type
                                                     Gateway MP to BACnet MS/TP                                                 UK24BAC
                                                     Gateway MP to Modbus RTU                                                   UK24MOD
                           Mechanical accessories    Description                                                                Type
                                                     Spacer ring for LDM, stroke 20 mm                                          ZNV-203
                                                     Spacer ring for Sauter, stroke 20 mm                                       ZNV-204
                                                     Adapter kit Danfoss                                                        ZNV-205
 Electrical installation
                                                     Supply from isolating transformer.
                                                     Parallel connection of other actuators possible. Observe the performance data.
                                                     Direction of stroke switch factory setting: Actuator stem retracted (▲).
 MP-Bus                                 AC/DC 24 V, modulating
 Further electrical installations
 Functions with basic values (conventional mode)
 Override control with AC 24 V with relay contacts                                                             Override control with AC 24 V with
                                                                                                               rotary switch
www.belimo.com                                  NVC24A-MP-RE • en-gb • 2024-10-01 • Subject to change                                       4/8
                                                  Technical data sheet                                         NVC24A-MP-RE
 Functions with basic values (conventional mode)
 Control remotely 0...100% with       Minimum limit with positioner SG..
 positioner SG..
 Primary/secondary operation (position-dependent)
 Control with 4...20 mA via external resistor
                                                                           Caution:
                                                                           The operating range must be set
                                                                           to DC 2...10 V.
                                                                           The 500 Ohm resistor converts
                                                                           the 4...20 mA current signal to a
                                                                           voltage signal DC 2...10 V.
 Functional check
                                       Procedure
                                       1. Connect 24 V to connections 1
                                       and 2
                                       2. Disconnect connection 3:
                                       – with direction of rotation L:
                                       Actuator rotates to the left
                                       – with direction of rotation R:
                                       Actuator rotates to the right
                                       3. Short-circuit connections 2
                                       and 3:
                                       – Actuator runs in opposite
                                       direction
www.belimo.com                                  NVC24A-MP-RE • en-gb • 2024-10-01 • Subject to change                  5/8
                                                 Technical data sheet                                               NVC24A-MP-RE
 MP-Bus
                                                                      Connection of active sensors
                                                                                                       Max. 8 additional MP-Bus nodes
                                                                                                       • Supply AC/DC 24 V
                                                                                                       • Output signal 0...10 V (max.
                                                                                                       0...32 V)
                                     Max. 8 additional MP-Bus nodes                                    • Resolution 30 mV
 Connection of external switching contact
                                     Max. 8 additional MP-Bus nodes
                                     • Switching current 16 mA @ 24
                                     V
                                     • Start point of the operating
                                     range must be parametrised on
                                     the MP actuator as ≥0.5 V
 Connection of passive sensors
                                                                      1) Depending on the type
                                                                      2) Resolution 1 Ohm
                                                                      Compensation of the measured
                                                                      value is recommended
 Functions with specific parameters (Parametrisation necessary)
 Override control and limiting with AC 24 V with relay contacts                                       Control open/close
www.belimo.com                                NVC24A-MP-RE • en-gb • 2024-10-01 • Subject to change                              6/8
                                                 Technical data sheet                                                        NVC24A-MP-RE
 Further electrical installations
 Functions with specific parameters (Parametrisation necessary)
 Override control and limiting with AC 24 V with rotary switch            Control 3-point with AC 24 V
                                     Caution:
                                     The "Close" function is only
                                     guaranteed if the start point of
                                     the operating range is defined
                                     as min. 0.5 V.
 Operating controls and indicators
                                                 1     Direction of stroke switch
                                                        Switch over:                Direction of stroke changes
                                                 2     Push-button and LED display green
                                                        Off:               No power supply or malfunction
                                                        On:                In operation
                                                        Press button:      Triggers stroke adaptation, followed by standard mode
                                                 3     Push-button and LED display yellow
                                                        Off:                  Standard mode
                                                        On:                   Adaptation or synchronisation process active
                                                        Flickering:           MP-Bus communication active
                                                        Flashing:             Request for addressing from MP client
                                                        Press button:         Confirmation of the addressing
                                                 4     Manual override button
                                                        Press button:      Gear train disengages, motor stops, manual override possible
                                                        Release button:    Gear train engages, standard mode
                                                 5     Service plug
                                                       For connecting parametrisation and service tools
                                                 10    Manual override
                                                        Clockwise:                             Actuator stem extends
                                                        Counterclockwise:                      Actuator stem retracts
www.belimo.com                                NVC24A-MP-RE • en-gb • 2024-10-01 • Subject to change                                       7/8
                                            Technical data sheet                                                    NVC24A-MP-RE
 Service
                         Wired connection   The device can be parametrised by ZTH EU via the service socket.
                                            For an extended parametrisation, Belimo Assistant 2 can be connected.
                                            Connection ZTH EU / Belimo Assistant 2
 Dimensions
 Further documentation
                                            • Tool connections
                                            • Introduction to MP-Bus Technology
                                            • Overview MP Cooperation Partners
                                            • Data sheets for globe valves
                                            • Installation instructions for actuators
                                            • Quick Guide – Belimo Assistant 2
www.belimo.com                          NVC24A-MP-RE • en-gb • 2024-10-01 • Subject to change                               8/8