YVWH Premium-Efficiency Variable Speed

Water-Cooled Screw Chiller


Cooling Capacity: 115 – 440TR
YVWH Premium-Efficiency Variable Speed Screw Chiller

In order to better meet the increasing customer need for high Experience
efficiency and energy saving chiller, Johnson Controls
introduces YVWH premium-efficiency variable speed
water-cooled screw chiller. YVWH, built on YORK ® Innovation
rich experience of chiller products and innovatively
designed and manufactured, surpasses the top
efficiency level of industry standard and helps the
customers achieve the greatest value.
Exceeding

Sustainability

2
YVWH PREMIUM-EFFICIENCY VARIABLE SPEED SCREW CHILLER

Chiller Features

EXPERIENCE INNOVATION
1982 - Pioneered variable vi in twin screw compressor Patented Vi control and advanced CFD simulation ensure the
1995 - Launched highly-efficient refrigerant-cooled DC reactance chiller’s heart- the "compressor" operate efficiently
inverter Innovative design in the rotor profile enhances reliable operation
2004 –Pioneered the application of variable speed drives in air- Patented technology in compressor dampening structure design
cooled chillers for quieter operation
2011 – First to launch a variable speed water-cooled screw chiller Patented technology in hybrid falling-film evaporator design
2017 - Launched the premium-efficiency and environmentally- delivers higher chiller efficiency
friendly screw chiller Intelligent chiller control panel simplifies operation and interaction

EXCEEDING SUSTAINABILITY
Chiller IPLV achieves as high as 11.83, surpasses top China GB R134a refrigerant protects the ozone layer and has no phase out
and AHRI standards date
Optimized motor and flow structure design ensure high Lower refrigerant charge and lower power consumption
compressor efficiency Premium chiller efficiency brings green building effectiveness to
Optimized compressor vi design further enhances partload a remarkable level
performance
Built-in condenser oil separator increases the oil separation
effectiveness
Counterflow subcooler design provides the most optimized
subcooling

3
Mechanical Specifications

General
Each YORK® YVWH variable speed screw chiller will be completely factory-packaged including evaporator, condenser, compressor, motor, touch-
screen control center and all interconnecting unit piping and wiring. The chiller will be painted prior to shipment and will be packaged to protect the
unit during shipment. Performance will be certified in accordance with AHRI Standard 550/590. The initial charge of refrigerant and oil will be supplied
for each unit.

Compressor Heat Exchanger


The new generation twin-screw, semi-hermetic compressor is highly Condenser – The refrigerant circuit water-cooled condenser is a
efficient and reliable. The modular and compact design make the cleanable shell and tube type heat exchanger with seamless external
finned copper tubes rolled into tube plates. The design working
assembly and maintenance simple and easy.
pressure on the water side is 1MPa. The factory offers standard
groove type water pipe connections. Meanwhile HG20615 flange
Patented noise dampening structure design on slide valve improves
type connections can be offered as an option. The refrigerant side
compressor discharge pulsation transmission loss significantly and
has a safety valve with trip pressure of 2.07MPa. The condenser is
reduce chiller noise eventually. manufactured and tested according to China National Standard GB151.

The compressor housing is of grey iron which is optimized through Evaporator – The evaporator utilizes a hybrid falling film design which
Finite Element Analysis(FEA) and 100% qualified by pressure test. contains a balance of flooded and falling film technology to optimize
The rotors is manufactured from forged steel and use high efficiency efficiency, minimize refrigerant charge, and maintain reliable control. A
profiles. The precise machining and flexible coating provide minimal specifically designed spray distributor provides uniform distribution of
clearance for the rotors and reduce the internal leakage significantly. refrigerant over the entire length to yield optimum heat transfer. The
hybrid falling film evaporator design has suction baffles around the
sides and above the falling film section to prevent liquid refrigerant
The compressor incorporates anti-friction bearings with SKF or
carryover into the compressor. A sight glass of 40mm diameter is
FAG brand to reduce power and increase reliability. Cylindrical roller
also equipped on the shell side for refrigerant level observation. The
bearings to handle radial loads, point angular contact ball bearings
design working pressure is 2.1MPa for shell and 1.0MPa for tube side.
to handle axial loads. An adequate supply of oil is available to the
The refrigerant side has a safety valve with trip pressure of 2.07MPa.
compressor at all times by advanced pressure-differential driven oil The refrigerant side is manufactured and tested according to China
system. National Standard GB151. The evaporator shell is covered with 19mm
closed-cell insulation. The factory offers groove type water pipe
The 3-phase asynchronous induction motor utilizes suction gas connections as standard. Meanwhile HG20615 flange type connections
cooling. The motor design is optimized for better efficiency and can be offered as an option. During the installation the contractor
adapted for wide application range. NTC sensors embedded in each should furnish the insulation layer.
phase winding can monitor motor temperature and provide effective
protection for compressor operation. Compact Water Box – A removable Compact Water Box is fabricated
from steel pipe with 1.0MPa design working pressure. Steel
diaphragms are welded inside the water box as per the number of the
Variable Speed Drive flow pass. The factory offers groove type water pipe connections as
The unit-mounted Variable Speed Drive reduces the impact on the standard. Meanwhile HG20615 flange type connections can be offered
as an option. Vent and drain plugs are provided on each evaporator
power grid by decreasing the inrush current at startup, and improves
and condenser water box as standard.
the part-load efficiency dramatically.

4
YVWH PREMIUM-EFFICIENCY VARIABLE SPEED SCREW CHILLER

Capacity Control Codes & Standards


Capacity control is achieved by use of variable speed control and a YVWH meets the following codes & standards:
slide valve to provide fully modulating control from 100% to 15% of • AHRI550/590 and 551/591
full-load. • GB25131-Safety requirements for water chillers (heat pumps) using
the vapor compression cycle
• GB/T18430.1-Water chilling (heat pump) packages using the vapor
Compressor Vi Control (Optional) compression cycle – part 1: Water chilling (heat pump) packages for
Compressor can automatically match the system's pressure ratio industrial & commercial and similar application
change to reduce power consumption and improve the part load
performance.

Oil System
The high efficient oil separation system provides adequate protection
to the unit’s compressor. It is equipped with an oil heater in oil sump
to avoid refrigerant and oil mix when the chiller is not operating. Factory Insulation of Evaporator
During the chiller operation, the system operation pressure Factory-applied thermal insulation of the flexible, closed-cell plastic
automatically transfers the oil in the oil sump back to the compressor. type, 3/4" (19mm) thick is attached with vapor-proof cement to
An oil filter is installed in the oil pipeline to prevent any particles from the evaporator shell, flow chamber, evaporator tube sheets, suction
entering the compressor. connection, and (as necessary) to the auxiliary tubing. This insulation
will normally prevent condensation in environments with relative
humidity up to 75% and dry bulb temperatures ranging from 50° to
Refrigerant System
90°F (10° to 32°C). 1-1/2" (38mm) thick insulation is also available for
An electronic expansion valve controlled by the control center to
relative humidity up to 90% and dry bulb temperatures ranging from
accommodate varying head and load conditions will meter refrigerant
50° to 90°F (10° to 32°C).
flow to the evaporator.

The condenser shell is capable of storing the entire system refrigerant Flow Switch
charge during servicing. The optional service valves need to be
The design working pressure of paddle type flow switch is 1.03MPa
selected to facilitate removal of refrigerant charge from the system.
(Gauge). It is suitable for chilled liquid and condenser liquid pipes.

The unit is equipped with a suction strainer to prevent any foreign


debris introduced to the system during maintenance or service to Paint
be allowed into the motor housing. Motors cooled by refrigerant is
The chiller surface is painted with anticorrosion and durable Caribbean
protected by means of filter or strainer to protect the motor and
blue epoxy primer and propionic acid one-component top coat.
prolong motor life.

Isolation Mounting Pads Shipment


Production covers are provided for the control center and controller
The four 3/4 inch (19.05 mm) thick neoprene pads are shipped loose,
on the unit. Plastic caps or fabrics cover plate are provided for all
for field mounting under the heat exchanger foot supports. The pads
water pipe connectors.
are suitable for typical equipment rooms located on the ground floor.

5
Control Center

Touch Screen Control Center

The YORK® Graphic Display Control Center, furnished as standard


on each chiller, provides the ultimate in efficiency, monitoring, data
recording, chiller protection and operating ease. The control center is
a factory-mounted, wired and tested state-of-the-art microprocessor
based control system for R-134a screw chillers. The panel is
configured with a 7 inch diagonal color liquid Crystal Display(LCD)
touch screen, which makes chiller operation quicker and easier than
ever before. Instead of requiring keystroke after keystroke to hunt for
information on a small monochrome LCD screen, touching the screen
reveals a wide array of information on a large, full-color illustration of
the appropriate component, which makes performance and operation
easier to monitor.
The control panel has independent over-current protection and
provides several terminals for wiring such as Remote Start/Stop,
The LCD display allows graphic display of the chiller, chiller sub-
Flow Switch, Chilled Water Pump and Local or Remote Cycling Device
systems and system parameters; this allows the presentation of
are provided. The Panel also provides field interlocks that indicate
several operating parameters at once. In addition, the operator may
the chiller status. These contacts include a Warning Contact and a
view a graphical representation of the historical operation of the
chiller Run Contact. Pressure transducers sense system pressures and
chiller as well as the present operation. A Status Bar is displayed at
thermistors sense system temperatures. The output of each transducer
all times on all screens. It contains the System-Status Line and Details
is a DC voltage that is analogous to the pressure input. The output of
Line, Access Level, Date and Time.
each thermistor is a DC voltage that is analogous to the temperature it
is sensing.
The locations of various chiller parameters are clearly marked and
instructions for specific operations are provided. The panel verbiage is
The Control Center is standard with MODBUS protocol internally.
available in English or Chinese. Data can be displayed in either English
Setpoints can be changed from a remote location via contact closures
or Metric units.
or through serial communications. The adjustable remote reset
range [up to 20°F (11.1°C)] provides flexible, efficient use of remote
Security access is provided to prevent unauthorized change of
signal depending on reset needs. Serial data interface to the Johnson
setpoints. This is accomplished with three different levels of access
Controls Metasys ® System (BAS) is required through a micro gateway.
and passwords for each level. There are screens, displayed values and
programmable setpoints only available with service level access to the
chiller. They are only displayed when logged in at the service access
level. The Advanced Diagnostics and troubleshooting record clearing
for the chiller and the panel is also included at this access level.

6
YVWH PREMIUM-EFFICIENCY VARIABLE SPEED SCREW CHILLER

Setting by touch screen

System operation information Status information

The operating program is stored in


Safety/normal shutdown nonvolatile memory to eliminate
information: system status, chiller failure due to AC power failure.
system details, date, time and
shutdown cause.

Chiller Control Connecting to building automation system:


Security access is provided to
prevent unauthorized change of
Center a. Remote start/stop
b. Remote setting of chilled water temperature
setpoints. c. Remote mode ready to start
d. Stop contact
e. Run contact
f. External interlock contact

5 parameters can be selected to


show each operation curve. The
A System Details Line displays messages that
curve data can be recorded every
are colored: Green – Normal Operations,
second or every hour and be
Yellow – Warnings/Cycling Shutdowns and
exported by USB flash drive for
Red – Safety Shutdowns
record and analysis .

100 kinds of self-diagnostics, warning and reminder information, 50 latest


warning and cycling shutdown records including exact time of shutdown and
up to 60 parameters

Electrical Features
Soft Start: YVWH provides a soft start without current shock. Displacement Power Factor (DPF): The Variable
The start-up current will never be larger than the rating current, Speed Drive (VSD) design makes 0.95 high DPF achievable in standard
which benefits the customer with lower cost on associated equipment YVWH models at all operating conditions. For traditional non-VSD
and smaller backup generator and quick start function in case of the designed screw chiller, the DPF will reduce when the cooling load goes
shutdown due to power supply failure. down.

1 YVWH
600
r
0.9 ille
ch
w
500 0.8 scre
led
0.7 oo
r-c
400 at
e
0.6 lw
Solid state starter ona
iti
300 0.5 ad
Tr
Star-delta stater 0.4
200 0.3
0.2
100
YVWH
0.1
0 0
0 10 20 30 40 50 20 30 40 50 60 70 80 90 100

Time (ms) Capacity Load (%)


Fig 1 YVWH soft start feature Fig 2 YVWH DPF feature

7
Options
Spring Isolators Thicker Evaporator Insulation
The unit comes with four lose 19mm thick anti-vibration neoprene pads The 38mm thicker insulation is an option in case of relative humidity
as standard for field installation. When the unit is installed on the floor, up to 90% and dry bulb temperatures ranging from 10 to 32˚C. It is
Spring Isolators are recommended to replace the standard neoprene recommended for low temperature or high humidity areas and helps
pads. 4 level adjustable Spring Isolators with non-slip mat will be to avoid the sweat on the surface of the unit.

delivered lose and can be conveniently mounted under the tube sheet.

Refrigerant Isolation Valve


Left/Right Pipe Connection The condenser shell is capable of storing the entire system refrigerant
Left or right piping connection can be chosen according to specific project charge during servicing if the unit is equipped with the optional
isolation valve.
requirement for easy installation.

Sound Attenuator Refrigerant Storage / Recycling System


A refrigerant storage/recycling system is a self-contained package
This option provides higher comfort to the user by lowering the sound
consisting of a refrigerant compressor with oil separator, storage
emission of the chiller.
receiver, water-cooled condenser, filter drier and necessary valves and
hoses to remove, replace and distill refrigerant. All necessary controls
and safety devices are a permanent part of the system. Typically not
required if unit isolation valves are provided.

Central Control System


Jobsite control box Jobsite control box Central control Web interface Connected with BMS
(Cooling tower) (Chiller)

Ethernet / IP & BACnet

Temperature sensor
T1 P P1 Pressure sensor

T4
Temperature sensor
Modulating
V1 Bypass Cooling
valve Load
Temperature
sensor P2
T3 T2 P
FM
Temperature sensor Flow meter Pressure sensor

8
YVWH PREMIUM-EFFICIENCY VARIABLE SPEED SCREW CHILLER

Nomenclature—YVWH180CA50A

Y V W H 180 C A 50 A

YORK® Design Series

Variable Speed 50: 380V-3P-50Hz


53: 400V-3P-50Hz
Water Cooled 55: 415V-3P-50Hz

Premium Efficiency Refrigerant: A-HFC134a

Unit Model Comfort Cooling

Technical Data
Chiller Performance Data
IPLV Full load
Capacity Power COP IPLV with FLA Consulation Evaporator Condenser
Variable Vi Index
Model
Flow Piping Flow Piping
Pressure Pressure
TR kW kW kW/kW kW/kW kW/kW A kW/TR Pass rate Dimension Pass rate Dimension
Drop kPa Drop kPa
l/s mm l/s mm
YVWH115 116.0 407.9 64.98 6.278 10.34 11.12 108 0.5602 4 17.54 125 58.7 4 22.03 125 65.0
YVWH145 146.8 516.1 79.73 6.473 10.23 11.29 131 0.5433 4 22.19 125 69.1 4 27.87 125 77.5
YVWH180 185.4 652.0 102.1 6.384 10.63 11.33 178 0.5509 4 28.04 150 72.5 4 35.21 150 80.9
YVWH225 226.1 795.1 122.8 6.474 10.46 11.10 209 0.5432 4 34.19 150 69.9 4 42.94 150 80.9
YVWH260 264.4 930.0 147.3 6.314 10.39 11.40 246 0.5570 2 39.99 200 43.0 2 50.22 200 45.9
YVWH300 302.6 1064 164.5 6.463 10.77 11.57 276 0.5442 2 45.75 200 48.0 2 57.46 200 48.1
YVWH330 323.9 1139 185.1 6.154 10.39 11.38 309 0.5715 2 48.98 200 25.5 2 61.51 200 31.9
YVWH375 378.8 1332 211.2 6.305 10.56 11.83 352 0.5578 2 57.28 200 35.1 2 71.93 200 36.2
YVWH440 449.0 1579 255.6 6.176 10.36 11.35 427 0.5694 2 67.90 200 42.6 2 85.27 200 50.4

Note:
1. Chilled liquid leaving temperature 6.7°C, flow rate 0.043 l/(s·kW), fouling factor 0.018 m2·K/kW
2. Condenser liquid entering temperature 29.4°C, flow rate 0.054 l/(s·kW), fouling factor 0.044 m2·K/kW
3. The above data is based on Johnson Control’s selection software: AECworks 8.1. Please refer to the latest version of the software for specific projects.

Physical Data
Weight
Refrigerant
Model Refrigerant Circiut Compressor Qty Capacity Control% Oil Charge (L)
Charge (kg) Shipping Weight Operating Weight
kg kg
YVWH115 1 1 15-100% 200 25 3986 4387
YVWH145 1 1 15-100% 200 25 4668 5169
YVWH180 1 1 15-100% 240 33 5712 6350
YVWH225 1 1 15-100% 250 33 6152 6951
YVWH260 1 1 15-100% 360 40 7134 7834
YVWH300 1 1 15-100% 370 40 8065 8894
YVWH330 1 1 15-100% 400 40 8277 9306
YVWH375 1 1 15-100% 410 40 8872 9983
YVWH440 1 1 15-100% 510 40 8872 9983

9
Dimensions
YVWH 115/145/180/225

Model L (mm) W (mm) H (mm) A (mm) B (mm) C (mm) D (mm) E (mm) F (mm)
YVWH115 3118 1710 1968 648 570 190 180 400 435
YVWH145 3131 1797 2000 698 590 195 180 425 450
YVWH180 3156 1975 2124 713 650 230 230 460 520
YVWH225 3153 1995 2254 703 650 230 230 475 510

YVWH 260/300/330/375/440

Model L (mm) W (mm) H (mm) A (mm) B (mm) C (mm) D (mm) E (mm) F (mm)
YVWH260 4807 1925 2304 860 700 195 195 460 485
YVWH300 4835 1988 2304 860 700 195 230 460 520
YVWH330/375/440 4872 2086 2324 860 700 197 229 485 545

Evaporator Water Pipe Connection Condenser Water Pipe Connection


Two pass Four pass Two pass Four pass

B J N F S U W Y

C Control panel K G Control panel P R Control panel T V Control panel X

Evaporator Evaporator Evaporator Evaporator Condenser Condenser Condenser Condenser

Ground Ground Ground Ground

Pipe configuration Pipe configuration Pipe configuration Pipe configuration


Evaporator Evaporator Condenser Condenser
pass Entering Leaving pass Entering Leaving pass Entering Leaving pass Entering Leaving
water water water water water water water water
C B G N R S V W
2 4 2 4
K J P F T U X Y

10
YVWH PREMIUM-EFFICIENCY VARIABLE SPEED SCREW CHILLER

Isolator Floor Layout


Spring Isolator Rubber Isolator

Tube
Sheet Tube
Tube Sheet Tube
The central line Sheet The central line Sheet
of the unit of the unit

Model A (mm) B (mm) C (mm) D (mm) E (mm) F (mm)


YVWH115 2731 1670 2937 1718 152 200
YVWH145 2731 1750 2937 1798 152 200
YVWH180 2731 1960 2937 2008 152 200
YVWH225 2731 1970 2937 2048 152 230
YVWH260 4407 1890 4613 1968 152 230
YVWH300 4407 1960 4613 2038 152 230
YVWH330/375/440 4407 2060 4613 2138 152 230

Wiring Diagram
Remarks: 1. If no "EXT", please short-cut terminal "67"and"60F".
2. The switch (SF, SEL, SRE, SMS) contact impedance is less than 0.5 ohm.
4. Pump is AC220V output load < 5W, alarm and run is contact.
5. Field wiring must also comply with local codes.
POWER(380/400/415V-3P-50HZ)
6. If power is 4 wires (U/V/W/PE), please short-cut terminal "N" and "PE" .
6. Other refer to the schematic diagram .

Custmer
supply

Control center

Breaker

VSD
STARTER
Leaving Heart Waring Leaving Extra Remote
chilled recovery output condenser interlock stop/start
liquid water water flow
pump Leaving pump Running Leaving switch Heart AC/ITS
condenser output chillered recovery AC/HP
liquid pump water flow water flow
switch switch

11
Office Locations
Australia (Sydney) India (Mumbai) Malaysia (Kuala Lumpur)
Tel: +61 (2) 9805 8300 Tel: +91 (22) 6683 7000 Tel: +60 (3) 7628 4300
Fax: +61 (2) 9247 7750 Fax: +91 (22) 6683 7002 Fax: +60 (3) 7874 1180

China (Shanghai) Indonesia (Jakarta) New Zealand (Auckland)


Tel: +86 (21) 2285 7000 Tel: +62 (21) 5366 8500 Tel: +64 (9) 635 0880
Fax: +86 (21) 2285 7599 Fax: +61 (21) 5366 8300 Fax: +64 (9) 633 1862

China (Hong Kong) Japan (Tokyo) Singapore


Tel: +852 2885 4451 Tel: +81 (3) 5738 6100 Tel: +65 6748 0202
Fax: +852 2885 7760 Fax: +81 (3) 5738 6298 Fax: +65 6743 4420

China (Macau) Korea (Seoul) Thailand (Bangkok)


Tel: +853 2875 1820 Tel: +822 1588 9117 Tel: +66 (2) 794 0101
Fax: +853 2875 1825 Fax: +822 6009 9014 Fax: +66 (2) 717 1327-8

PUBL-8533(0319)