Vigilant Catalog u Intelligent Input-Output

Synchronization
Output Module
S3424

GSA-CC1S, MCC1S
7300-1483:
0115

Patented

Overview Standard Features


GSA-CC1S and MCC1S Synchronization Output Modules are • Provides UL 1971-compliant auto-sync output for visual
intelligent analog addressable devices that form part of Vigilant’s signals
Signature line of products. The actual operation of the GSA-CC1S Use for connecting a supervised output circuit to a supervised
and MCC1S is determined by the “personality code” selected by 24 Vdc riser input and synchronizing multiple notification appli-
the installer, which is downloaded to the module from the Signa- ance circuits.
ture loop controller during system configuration.
• Functions as an audible signal riser selector
Depending on their assigned personality, Synchronization Output Use as a synch module or for connecting supervised 24 Vdc
Modules may be used as a signal power riser selector to provide Audible/Visible signal circuits, or 25 and 70 VRMS Audio
synchronization of fire alarm signals across multiple zones, or for Evacuation and Telephone circuits to their power inputs.
connecting, upon command from the loop controller, supervised • Built-in ring-tone generator
Class B signal or telephone circuits to their respective power When configured for telephone circuits, the GSA-CC1S gener-
inputs. The power inputs may be polarized 24 Vdc to operate au- ates its own ring-tone signal, eliminating the need for a sepa-
dible and visible signal appliances or 25 and 70 VRMS to operate rate ring-tone circuit.
audio evacuation speakers and firefighter’s telephones.
• Automatic device mapping
Signature modules transmit information to the loop controller
regarding their circuit locations with respect to other Signature
devices on the wire loop.
• Electronic addressing
Programmable addresses are downloaded from the loop con-
troller, a PC, or the SIGA-PRO Signature Program/Service Tool;
there are no switches or dials to set.
• Intelligent device with microprocessor
All decisions are made at the module to allow lower com-
munication speed with substantially improved control panel
response time and less sensitivity to line noise and loop wiring
properties; twisted or shielded wire is not required.

Page 1 of 4 D ATA S H E E T M85001-0543


Not to be used for installation purposes. Issue 3.1
Application Installation
The GSA-CC1S mounts to a standard North American two-gang The GSA-CC1S: mounts to North American 2-1/2 inch (64 mm)
electrical box, making it ideal for locations where only one module deep 2-gang boxes and 1-1/2 inch (38 mm) deep 4 inch square
is required. Separate I/O and data loop connections are made to boxes with 2-gang covers and GSA-MP mounting plates. The
each module. terminals are suited for #12 to #18 AWG (2.5 mm2 to 0.75 mm2)
wire size.
The GSA-MCC1S is part of the UIO family of plug-in Signature
Series modules. It functions identically to the GSA-CC1S, but
takes advantage of the modular flexibility and easy installation that
characterize all UIO modules. Two- and six-module UIO mother-
boards are available. These can accommodate individual risers for
each on-board module, or risers that are shared by any combina-
tion of its UIO modules. All wiring connections are made to termi-
nal blocks on the motherboard. UIO assemblies may be mounted
in Edwards enclosures.

Personality Codes
The operation of the GSA-CC1S is determined by their sub-type
code or “Personality Code”. The code is selected by the installer GSA-MCC1S: mount the UIOxR motherboard inside a suitable
depending upon the desired application and is downloaded from Edwards enclosure with screws and washers provided. Plug the
the loop controller. module into any available position on the motherboard and secure
Personality Code 5: Signal Power or Audio Evacuation (sin- the module to the motherboard with the captive screws. Wiring
gle riser). Configures the module for use as a Class B Audible/ connections are made to the terminals on the motherboard (see
Visible Signal power (24 Vdc polarized) or Audio Evacuation (25 wiring diagram). UIOxR motherboard terminals are suited for #12
or 70 VRMS) power selector. The ring-tone generator is disabled. to #18 AWG (2.5 mm2 to 0.75 mm2) wire size.
The output circuit is monitored for open or shorted wiring. If a UIO Motherboard
short exists, the control panel inhibits the activation of the audible/ 6-32
visible signal circuit to prevent connection to the power circuit. Self-tapping
screws
Personality Code 6: Telephone with ring-tone (single riser).
Configures the module for use as a Telephone power selector.
When a telephone handset is plugged into its jack or lifted from its Plug-in (UIO) Captive
Module screws
hook, the module generates its own Ring-Tone signal. A separate
ring-tone circuit is not needed. The module sends this signal to
the control panel to indicate that an off-hook condition is present.
When the system operator responds to the call, the ring-tone #6 Flat washers
signal is disabled.
Cabinet or electrical enclosure
Personality Code 25: Visual Signal Synchronization. This
personality code configures the module to provide synchronization
of fire alarm signals across multiple zones. It functions as a signal
power (24 Vdc) riser selector. The output wiring is monitored for Electronic Addressing
open circuits and short circuits. A short circuit will cause the fire
The loop controller electronically addresses each module saving
alarm control panel to inhibit the activation of the audible/visual
valuable time during system commissioning. Setting complicated
signal circuit so the riser is not connected to the wiring fault.
switches or dials is not required. Each module has its own unique
serial number stored in its “on-board memory”. The loop control-
ler identifies each device on the loop and assigns a “soft” address
Warnings & Cautions to each serial number. If desired, the modules can be addressed
using the SIGA-PRO Signature Program/Service Tool.
This module will not operate without electrical power. As fires fre-
quently cause power interruption, we suggest you discuss further
safeguards with your fire protection specialist.
Testing & Maintenance
Edwards recommends that these modules be installed according The module’s automatic self-diagnosis identifies when it is defec-
to latest recognized edition of national and local fire alarm codes. tive and causes a trouble message. The user-friendly maintenance
program shows the current state of each module and other perti-
nent messages. Single modules may be turned off (de-activated)
Compatibility temporarily, from the control panel.
These modules are part of Vigilant’s Signature Series intelligent Scheduled maintenance (Regular or Selected) for proper system
processing and control platform. They are compatible with VM, operation should be planned to meet the requirements of the
and VS Series control panels. Authority Having Jurisdiction (AHJ). Refer to current NFPA 72 and
ULC CAN/ULC 536 standards.

Page 2 of 4 D ATA S H E E T M85001-0543


Not to be used for installation purposes. Issue 3.1
Typical Wiring

GSA-CC1S (Standard Mount) GSA-MCC1S (UIO Mount)


Personality Typical Speaker Circuit Personality Typical Speaker Circuit
Code 5 Code 5
UL/ULC Listed UL/ULC Listed
47KW EOL 47KW EOL

Personality Typical Telephone Circuit Personality Typical Telephone Circuit


Code 6 Code 6
UL/ULC Listed UL/ULC Listed
47KW EOL 47KW EOL

Personality Enhanced Integrity and Genesis Devices Personality Enhanced Integrity and Genesis Devices
Code 25 Code 25
UL/ULC Listed UL/ULC Listed
47KW EOL 47KW EOL

1 23 4
UIO(R) series motherboard

10 9 Data In+ 4 - Riser 1 Out


- 3
2
+-
Riser 1 In
Signature 4 1 +
CC1S Data 3 TB14
2
Circuit 1
TB7

473387352
8 7 6 5 4 3 2 1
Data Out
+

MCC1S
-

CAT NO.
4
TB1 3
2
1
Green LED (Normal) TB15
Riser out (+) Red LED (Active)
To next device
Riser out (-) 1 23 4
Riser in (+) -
From control panel Data out (+) Riser 1 In +
- Riser 1 Out
To next device or EOL resistor. +
Riser in (-) Data out (-)
Data in (+)
From Signature Controller
or Previous Device
Data in (-)

Multiple CC1(S) modules using the MIRBPS’s sense inputs

Notification appliance circuit (NAC)


TB1
NAC1/
+

UL listed
AUX1 EOL 15 KW
NAC2/
+

AUX2 Notification appliance circuit (NAC)


UL listed
+

NAC3/
AUX3 EOL 15 KW
+

NAC4/
AUX4
200 mA AUX
TB5

Continuous
+

IN
Sense 1 COM
OUT EOL 47 K
+

IN
Sense 2 COM
OUT EOL 47 K
NO + +
Trouble COM
10 9 10 9
NC
TB2 CC1(S) module CC1(S) module
8765 4 321 8765 4 321

[1] [1]
+ + + +

[3]

Page 3 of 4 D ATA S H E E T M85001-0543


Not to be used for installation purposes. Issue 3.1
Specifications
Catalog Number GSA-CC1S GSA-MCC1S
North American 2½ inch (64 mm)
deep two-gang boxes and 1½
Plugs into UIO2R, UIO6R or UIO6
Mounting inch (38 mm) deep 4 inch square
Contact us... Motherboards
boxes with 2-gang covers and
Email: [email protected] GSA-MP mounting plates
Web: www.vigilant-fire.com
Description Synchronization Output Module
Vigilant is an EDWARDS brand. 50 (factory set)
Type Code
1016 Corporate Park Drive Uses one module address
Address Requirements
Mebane, NC 27302
Wiring Terminations Suitable for #12 to #18 AWG (2.5 mm² to 0.75mm²)
© 2013 UTC Fire & Security Americas Standby = 223µA
Corporation, Inc. All rights reserved. Operating Current
Specifications subject to change
Activated = 100µA
without notice. Edwards is part of UTC Operating Voltage 15.2 to 19.95 Vdc (19 Vdc nominal)
Climate, Controls & Security, a unit of 24 Vdc = 2 amps
United Technologies Corporation. 25 V Audio = 50 watts
Output Rating
70 V Audio = 35 watts
Construction High Impact Engineering Polymer
Operating: 32°F to 120°F (0°C to 49°C)
Storage and Operating
Storage: -4°F to 140°F (-20°C to 60°C)
Environment
Humidity: 0 to 93% RH
Green LED - Flashes when polled Red LED - Flashes when in alarm/
LED Operation
active
Compatibility Use with: Signature Loop Controller under MIR3 version 2.0 or higher
Agency Listings UL, ULC, CSFM, MEA

Ordering Information
Catalog Shipping Wt.
Description
Number lbs (kg)
GSA-CC1S Synchronization Output Module (Standard Mount) - UL/ULC Listed 0.5 (0.23)
GSA-MCC1S Synchronization Output Module (UIO Mount) - UL/ULC Listed 0.18 (0.08)

Related Equipment
27193-21 Surface Mount Box - Red, 2-gang 2 (1.2)
27193-26 Surface Mount Box - White, 2-gang 2 (1.2)
Universal Input-Output Module Board w/Riser Inputs
GSA-UIO2R 0.32 (0.15)
- Two Module Positions
Universal Input-Output Module Board w/Riser Inputs
GSA-UIO6R 0.62 (0.28)
- Six Module Positions
GSA-UIO6 Universal Input-Output Module Board - Six Module Positions 0.56 (0.25)
235196P Bi-polar Transient Protector 0.01 (0.05)
Multifunction Fire Cabinet - Red,
MFC-A 7.0 (3.1)
supports Signature Module Mounting Plates
GSA-MP1 Signature Module Mounting Plate, 1 footprint 1.5 (0.70)
GSA-MP2 Signature Module Mounting Plate, 1/2 footprint 0.5 (0.23)
GSA-MP2L Signature Module Mounting Plate, 1/2 extended footprint 1.02 (0.46)
11-05-14

Page 4 of 4 D ATA S H E E T M85001-0543


Not to be used for installation purposes. Issue 3.1