Product datasheet

Specifications

Modular contactor, TeSys GC,


AC-7a, 16A, 1NO+1NC, 220 to
240VAC 50Hz coil
GC1611M5

Main
Range TeSys

Product Name TeSys GC

Product Or Component Type Modular contactor

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Device Short Name GC16

Contactor Application Lighting


Heating
Motor control

Complementary
Utilisation Category AC-7B
AC-7A

Poles Description 2P

Power Pole Contact Composition 1 NO + 1 NC

[Ue] Rated Operational Voltage <= 250 V AC

[Ie] Rated Operational Current 16 A AC-7A


5 A AC-7B

Operating Position 30°/vertical

Control Circuit Type AC at 50 Hz

[Uc] Control Circuit Voltage 220...240 V AC 50 Hz

[Uimp] Rated Impulse Withstand 4 kV


Voltage
[Ith] Conventional Free Air 16 A (at 50 °C) for power circuit
Thermal Current
Irms Rated Making Capacity 40 A at 400 V AC for power circuit conforming to IEC 61095

Rated Breaking Capacity 40 A at 400 V for power circuit conforming to IEC 61095

[Icw] Rated Short-Time Withstand 128 A 40 °C - 10 s for power circuit


Current 40 A 40 °C - 30 s for power circuit

Associated Fuse Rating 16 A gL at <= 440 V for power circuit

Average Impedance 2.5 mOhm - Ith 16 A 50 Hz for power circuit

[Ui] Rated Insulation Voltage 500 V conforming to IEC 61095


500 V conforming to VDE 0110

Electrical Durability AC-7A: 100000 cycles


AC-7B: 100000 cycles

Power Dissipation Per Pole 0.65 W

Control Type Remote control

Mounting Mode Clip-on

Excluding VAT, FCA Jabal Ali & are subject to change – check with your local distributor.

5 Jun 2024 1
Mounting Support DIN rail

Standards IEC 60947-5


IEC 61095

Connections - Terminals Control circuit: screw clamp terminals 1 cable(s) 2.5 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 2.5 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1.5 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1.5 mm²solid without cable end
Power circuit: screw clamp terminals 1 cable(s) 6 mm²flexible without cable end
Power circuit: screw clamp terminals 2 cable(s) 4 mm²flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 6 mm²flexible with cable end
Power circuit: screw clamp terminals 2 cable(s) 1.5 mm²flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 6 mm²solid without cable end
Power circuit: screw clamp terminals 2 cable(s) 4 mm²solid without cable end

Tightening Torque Control circuit: 0.8 N.m - on screw clamp terminals


Power circuit: 0.8 N.m - on screw clamp terminals

Operating Time 10...25 ms opening


10...30 ms closing

Mechanical Durability 1000000 cycles

Maximum Operating Rate 300 cyc/h 50 °C

Control Circuit Voltage Limits Drop-out: 0.2...0.75 Uc at 50 Hz (at <50 °C)


Operational: 0.85...1.1 Uc at 50 Hz (at <50 °C)

Inrush Power In Va 15 VA 50 Hz (at 20 °C)

Hold-In Power Consumption In Va 3.8 VA 50 Hz (at 20 °C)

Heat Dissipation 1.3 W at 50/60 Hz

Environment
Ip Degree Of Protection IP40 conforming to VDE 0106 (in enclosure)
IP20 conforming to VDE 0106

Protective Treatment TC

Ambient Air Temperature For -5…50 °C


Operation
Ambient Air Temperature For -40…70 °C
Storage
Operating Altitude <= 3000 m

Mechanical Robustness Shocks contactor open: 10 Gn for 11 ms


Shocks contactor closed: 15 Gn for 11 ms
Vibrations contactor open: 2 Gn, 5...300 Hz
Vibrations contactor closed: 3 Gn, 5...300 Hz

Total Number Of 18 Mm Modules 1

Height 81 mm

Width 17.5 mm

Depth 62.5 mm

Net Weight 0.11 kg

Quantity Per Set Set of 12

Colour White

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 8.000 cm

2 5 Jun 2024
Package 1 Width 9.500 cm

Package 1 Length 23.000 cm

Package 1 Weight 115.000 g

Unit Type Of Package 2 BB1

Number Of Units In Package 2 12

Package 2 Height 8.000 cm

Package 2 Width 9.500 cm

Package 2 Length 23.000 cm

Package 2 Weight 1.443 kg

Unit Type Of Package 3 S03

Number Of Units In Package 3 96

Package 3 Height 30.000 cm

Package 3 Width 30.000 cm

Package 3 Length 40.000 cm

Package 3 Weight 12.045 kg

Contractual warranty
Warranty 18 months

5 Jun 2024 3
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

4 5 Jun 2024