TECHNICAL DESCRIPTION
DELIVERY LOCATION:
TECHNICAL DESCRIPTION
DCM AIR COOLED CONDENSING UNITS
kW Circuits #
CU‐01 PAS‐6006 SCX 160.9 4 1
CU‐02 PAS‐4006 SCX 104.4 2 1
CU‐03 PAS‐6006 SCX 175.0 4 1
TOP VIEW
GENERAL SPECIFICATIONS
Air Flow Model / Frame
50 mm injected Polyurethane 45
kg/m³ 1,546 kg
Coil Air Velocity Air Density Outside Sheet Material Base Height
1.2101 kg/m³ 1.3 mm Electrostatic Prepainted
2.34 m/s Galvanized Steel Sh. 130 mm
Inside Sheet Material Motor Power
1 mm Galvanized Steel Sh.M.ZS 11 kW
Total Cooling Capacity Total Sensible Capacity
160.92 kW 132.12 kW
SUPPLY CONNECTION
Connection Type Control Type Pressure Drop
Flange 0 Pa
Air Flow Dimensions Air Velocity
7.53 m³/s W 898 mm x H 898 mm 9.34 m/s
MIXING MODULE WITH TWO DAMPERS (M1)
Connection Type Condensation Pan Pressure Drop Section Weight
50 % 50 %
DOORS (M1)
ID Type Handle Type Size Position Hinge Position Alignment Opposing Door
1 Standard (Handle + Hinge) With Lock 525 mm x 1,400 mm Right Left Right
ACCESSORIES (M1)
FILTER (M2)
Air Flow Condensation Pan Slide Type Hygienic Spare Filter Section Weight
7.53 m³/s None 225.5 kg
Filter Type
G4 Panel
Initial / Final / Design P.Drop Air Velocity Size/Quantity Size/Quantity Size/Quantity Size/Quantity
72 Pa / 150 Pa / 111 Pa 2.54 m/s 292x592x48/5 592x592x48/6
Filter Type
F9 Bag
Initial / Final / Design P.Drop Air Velocity Size/Quantity Size/Quantity Size/Quantity Size/Quantity
183 Pa / 250 Pa / 216 Pa 2.54 m/s 592x592x600/6 292x592x600/5
* Frame sealing applied.
ACCESSORIES (M3)
Shaft Power
8.24 kW
Fan Speed Running Frequency
1075 rpm (Max. 1500 rpm) 50.00 Hz
Fan Outlet Air Velocity Air Density
9.34 m/s 1.2264 kg/m³
1 Standard (Handle + Hinge) With Lock 525 mm x 1,400 mm Right Left Left
ACCESSORIES (M4)
Bulk Head Light,Sight Glass,On-Off Switch,Flexible Connector
Project Customer
Dreem Factory – Face lift
Model Ref
PAS-6006 SCX CU-01
Capacity (Btu/hr) Capacity (KW) Ambient Temperature (°C) Air Oulet Temp. (°C)
551,726 160.92 40.0 48.7
PERFORMANCE & Power Input (hp) Power Input (KW) EER (
BTU/HR
/W) COP
INPUT DATA 77.33 57.71 9.56 2.79
Weight (kg) Capacity Control (%) Main Power
1400 0 - 25 - 50 - 75 - 100 380/3/50
Type Flow Rate (CMH) Piping (Liquid/Gas)
Multi-pass cross finned tube 78,880 (7/8 - 1 3/8) Ø
CONDENSER Fan Type Q'TY x Motor Power (hp)
Axial fan 8 x 1.0
Type Q'TY x Power Intput (hp) Lubricant type
Hermetic Scroll 4 X 17.3 POE Oil
COMPRESSOR RLA (Amp) LRA (Amp) Comp. Model No. Of Circuits
34 174 ZP 182KCE 4
Refrigerant Evaporating Temp. (°C) Suction Temp. (°C) Condensing Temp. (°C)
R-410A 4.7 4.5 52.7
REFRIGERANT Subcooling (K) Superheat (K) Charge (kg)
8.3 8.3 4 x 11.6
High Pressure Switch Low Pressure Switch Filter Driers Hot Gas By Pass
SAFETY DEVICE &
Internal Overload External Overload Magnetic Contactor Shutt Off Valve
ACCESSORY Temperature Controller Expansion Valve Phase Failur Devise Control Switch
9/4/2024
Simulation Outputs
TOP VIEW
GENERAL SPECIFICATIONS
Air Flow Model / Frame
50 mm injected Polyurethane 45
kg/m³ 955 kg
Coil Air Velocity Air Density Outside Sheet Material Base Height
1.2101 kg/m³ 1.3 mm Electrostatic Prepainted
2.37 m/s Galvanized Steel Sh. 130 mm
Inside Sheet Material Motor Power
1 mm Galvanized Steel Sh.M.ZS 7.5 kW
Total Cooling Capacity Total Sensible Capacity
104.42 kW 79.05 kW
SUPPLY CONNECTION
Connection Type Control Type Pressure Drop
Flange 0 Pa
Air Flow Dimensions Air Velocity
4.2 m³/s W 638 mm x H 638 mm 10.32 m/s
MIXING MODULE WITH TWO DAMPERS (M1)
Connection Type Condensation Pan Pressure Drop Section Weight
50 % 50 %
DOORS (M1)
ID Type Handle Type Size Position Hinge Position Alignment Opposing Door
1 Standard (Handle + Hinge) With Lock 525 mm x 1,400 mm Right Left Right
ACCESSORIES (M1)
FILTER (M2)
Air Flow Condensation Pan Slide Type Hygienic Spare Filter Section Weight
4.2 m³/s None 160.5 kg
Filter Type
G4 Panel
Initial / Final / Design P.Drop Air Velocity Size/Quantity Size/Quantity Size/Quantity Size/Quantity
66 Pa / 150 Pa / 108 Pa 2.4 m/s 292x592x48/2 592x592x48/4
Filter Type
F9 Bag
Initial / Final / Design P.Drop Air Velocity Size/Quantity Size/Quantity Size/Quantity Size/Quantity
170 Pa / 250 Pa / 210 Pa 2.4 m/s 592x592x600/4 292x592x600/2
* Frame sealing applied.
ACCESSORIES (M3)
Shaft Power
6.12 kW
Fan Speed Running Frequency
1759 rpm (Max. 2350 rpm) 50.00 Hz
Fan Outlet Air Velocity Air Density
10.32 m/s 1.2264 kg/m³
1 Standard (Handle + Hinge) With Lock 525 mm x 1,400 mm Right Left Left
ACCESSORIES (M4)
Bulk Head Light,Sight Glass,On-Off Switch,Flexible Connector
Project Customer
Dreem Factory – Face lift
Model Ref
PAS-4006 SCX CU-02
Capacity (Btu/hr) Capacity (KW) Ambient Temperature (°C) Air Oulet Temp. (°C)
358,011 104.42 40.0 47.6
PERFORMANCE & Power Input (hp) Power Input (KW) EER (BTU/HR/W) COP
INPUT DATA 51.20 38.21 9.37 2.73
Weight (kg) Capacity Control (%) Main Power
750 0 - 50 - 100 380/3/50
Type Flow Rate (CMH) Piping (Liquid/Gas)
Multi-pass cross finned tube 57,800 (7/8 - 1 5/8) Ø
CONDENSER Fan Type Q'TY x Motor Power (hp)
Axial fan 4 x 2.0
Type Q'TY x Power Intput (hp) Lubricant type
Hermetic Scroll 2 X 21.6 POE Oil
COMPRESSOR RLA (Amp) LRA (Amp) Comp. Model No. Of Circuits
38.2 219 ZP 232KCE 2
Refrigerant Evaporating Temp. (°C) Suction Temp. (°C) Condensing Temp. (°C)
R-410A 4.6 4.3 52.5
REFRIGERANT Subcooling (K) Superheat (K) Charge (kg)
8.3 8.3 2 X 11.5
High Pressure Switch Low Pressure Switch Filter Driers Hot Gas By Pass
SAFETY DEVICE &
Internal Overload External Overload Magnetic Contactor Shutt Off Valve
ACCESSORY Temperature Controller Expansion Valve Phase Failur Devise Control Switch
9/4/2024
Simulation Outputs
TOP VIEW
GENERAL SPECIFICATIONS
Air Flow Model / Frame
50 mm injected Polyurethane 45
kg/m³ 2,079 kg
Coil Air Velocity Air Density Outside Sheet Material Base Height
1.2101 kg/m³ 1.3 mm Electrostatic Prepainted
2.4 m/s Galvanized Steel Sh. 130 mm
Inside Sheet Material Motor Power
1 mm Galvanized Steel Sh.M.ZS 18.5 kW
Total Cooling Capacity Total Sensible Capacity
175 kW 139.13 kW
SUPPLY CONNECTION
Connection Type Control Type Pressure Drop
Flange 0 Pa
Air Flow Dimensions Air Velocity
11 m³/s W 1,130 mm x H 1,130 mm 8.61 m/s
MIXING MODULE WITH TWO DAMPERS (M1)
Connection Type Condensation Pan Pressure Drop Section Weight
50 % 50 %
DOORS (M1)
ID Type Handle Type Size Position Hinge Position Alignment Opposing Door
1 Standard (Handle + Hinge) With Lock 525 mm x 1,400 mm Right Left Right
ACCESSORIES (M1)
FILTER (M2)
Air Flow Condensation Pan Slide Type Hygienic Spare Filter Section Weight
11 m³/s None 281.1 kg
Filter Type
G4 Panel
Initial / Final / Design P.Drop Air Velocity Size/Quantity Size/Quantity Size/Quantity Size/Quantity
64 Pa / 150 Pa / 107 Pa 2.33 m/s 292x592x48/3 592x592x48/12
Filter Type
F9 Bag
Initial / Final / Design P.Drop Air Velocity Size/Quantity Size/Quantity Size/Quantity Size/Quantity
164 Pa / 250 Pa / 207 Pa 2.33 m/s 592x592x600/12 292x592x600/3
* Frame sealing applied.
ACCESSORIES (M3)
Shaft Power
15.2 kW
Fan Speed Running Frequency
921 rpm (Max. 1100 rpm) 50.00 Hz
Fan Outlet Air Velocity Air Density
8.61 m/s 1.2264 kg/m³
1 Standard (Handle + Hinge) With Lock 525 mm x 1,400 mm Right Left Left
ACCESSORIES (M4)
Bulk Head Light,Sight Glass,On-Off Switch,Flexible Connector
Project Customer
Dreem Factory – Face lift
Model Ref
PAS-6006 SCX CU-03
Capacity (Btu/hr) Capacity (KW) Ambient Temperature (°C) Air Oulet Temp. (°C)
600,000 175.00 40.0 49.3
PERFORMANCE & Power Input (hp) Power Input (KW) EER (
BTU/HR
/W) COP
INPUT DATA 78.83 58.83 10.20 2.97
Weight (kg) Capacity Control (%) Main Power
1400 0 - 25 - 50 - 75 - 100 380/3/50
Type Flow Rate (CMH) Piping (Liquid/Gas)
Multi-pass cross finned tube 78,880 (7/8 - 1 3/8) Ø
CONDENSER Fan Type Q'TY x Motor Power (hp)
Axial fan 8 x 1.0
Type Q'TY x Power Intput (hp) Lubricant type
Hermetic Scroll 4 X 17.7 POE Oil
COMPRESSOR RLA (Amp) LRA (Amp) Comp. Model No. Of Circuits
34 174 ZP 182KCE 4
Refrigerant Evaporating Temp. (°C) Suction Temp. (°C) Condensing Temp. (°C)
R-410A 7.4 7.2 53.5
REFRIGERANT Subcooling (K) Superheat (K) Charge (kg)
8.3 8.3 4 x 12.1
High Pressure Switch Low Pressure Switch Filter Driers Hot Gas By Pass
SAFETY DEVICE &
Internal Overload External Overload Magnetic Contactor Shutt Off Valve
ACCESSORY Temperature Controller Expansion Valve Phase Failur Devise Control Switch
9/4/2024
Simulation Outputs
Digital Room
Thermostats
INSTALLATION MANUAL
APPLICATION
DR is a serie of Digital Room Thermostats, provides a single stage, temperature control. Table 1 shows all the
available models. All models can be provided with 24, 120, 220 Vac.
These thermostats are mercury free and require no battery. All set points are kept permanently by
non-volatile memory.
1
DR - SERIE
SPECIFICATIONS
POWER SUPPLY
24 VAC system 18 – 30 VAC, 50/60 Hz
120 VAC system 96 – 144 VAC, 50/60 Hz
220 VAC system 198 – 250 VAC, 50/60 Hz
TEMPERATURE :
Temperature accuracy ± 1 °C
Storage temperature 0 – 70 °C
Ambient temperature 10 – 50 °C
Setting temperature range 18 – 30 °C (64 – 88 °F)
INSTALLATION
Read these instructions thoroughly before installing product. Failure to follow these instructions could
damage the product or cause a hazardous condition. Check the voltage and current ratings on the
product to ensure that it is suitable for your application. Installer must be a trained, experienced
service technician. Check product for proper operation after installation.
CAUTION
Damage to heating and cooling system may occur. Disconnect power from the equipment at the main
breaker/fuse block while installing the thermostat.
Mounting Location
Mount the thermostat approximately 5 ft. (1.5m) above the floor in a location that is free from direct
sunlight, heat from appliances, hot or cold air from ducts, concealed pipes and chimneys, and drafts or
dead spots behind doors or in corners. Do not mount on exterior wall, if possible. Failure to locate
thermostat mounting as indicated will result in poor temperature control.
Note : Level thermostat mounting is for appearance only and is not required for proper thermostat operation.
2
DR - SERIE
Mount the thermostat on the wall by having it on Put the cover back. See Fig. 6.
the screws. See Fig. 3.
Lift and open the cover, pull it up to remove. Tighten screw to secure the cover. See Fig. 7.
See Fig. 4.
3
DR - SERIE
WIRING DIAGRAM
4
DR - SERIE
SET UP
All thermostats are factory set up according to the Model No. Legend listed on the back side of the plastic
casing. However it can be alternated by the programming.
WARNING
Failure to set up according to the application may damage the heating and cooling system.
Set up mode
Press and hold TEMP & and TEMP ³ and FAN buttons at the same time for 3 seconds, the display will
show the existing set up as per Table 2.
Note : If POWER button is pressed before exiting from the set up mode (Section d above), the system
will exit from the existing mode without changing the setup program.
OPERATION
Power
Press POWER to turn on/off the air conditioner. When turn on, it will operate according to the last program
setting.
Mode/Sweep
For Cool + Sweep version, button is a SWEEP button used to turn on/off the sweep motor.
For other versions, this is a MODE button used to select the operation mode.
5
DR - SERIE
Fan
Press FAN button to select the fan speed in the following sequence.
Auto mode
The speed will be adjusted according to the difference between the room and the setting temperature.
S If the difference is 3°C or more, the fan will run at high speed.
S If the difference is 2°C, the fan will run at medium speed.
S If the difference is 1°C, or lower, the fan will run at low speed.
Temperature setting
Press TEMP & or TEMP ³ button for setting the temperature in a range of 18 - 30°C or 64 - 88 °F.
LED at will show the new setting for 5 seconds.
Compressor delay
In a model with compressor delay feature, there will be 3 minute time delay before the compressor can
restart.
Compressor status
LED at shows the status of the compressor/valve/heater.
Auto Restart
All the setting parameters are kept in the non volatile memory. When there is a power failure and back to
normal, the system will resume its operation with the same setting parameters.