GA 90+-160 (2018) AIB EN Wuxi 9829317862-Compressed
GA 90+-160 (2018) AIB EN Wuxi 9829317862-Compressed
Instruction book
Atlas Copco
            Instruction book
            Original instructions
            COPYRIGHT NOTICE
            Any unauthorized use or copying of the contents or any part thereof is prohibited.
            This applies in particular to trademarks, model denominations, part numbers and
            drawings.
2019 - 12
No. 9829 3178 62
www.atlascopco.com
                                                                                                                                  Instruction book
Table of contents
1 Safety precautions..........................................................................................................5
2 General description...................................................................................................... 11
2.1 INTRODUCTION.................................................................................................................................11
3.1 CONTROLLER...................................................................................................................................29
2                                                                                                                                    9829 3178 62
Instruction book
4 Installation.....................................................................................................................54
4.5 PICTOGRAPHS................................................................................................................................. 71
5 Operating instructions................................................................................................. 78
5.3 STARTING....................................................................................................................................... 82
5.7 STOPPING.......................................................................................................................................88
6 Maintenance.................................................................................................................. 91
9829 3178 62                                                                                                                                             3
                                                                                                                                   Instruction book
7 Integrated dryer............................................................................................................ 98
7.1 INTRODUCTION.................................................................................................................................98
9 Problem solving..........................................................................................................117
10 Technical data.............................................................................................................119
10.3 LIMITS..........................................................................................................................................120
4                                                                                                                                     9829 3178 62
Instruction book
1 Safety precautions
Explanation
Danger to life
Warning
Important note
                           If the machine is equipped with an automatic restart after voltage failure function and if
                           this function is active, be aware that the machine will restart automatically when the
                           power is restored if it was running when the power was interrupted!
          6. Never play with compressed air. Do not apply the air to your skin or direct an air stream at
             people. Never use the air to clean dirt from your clothes. When using the air to clean
             equipment, do so with extreme caution and wear eye protection.
          7. The owner is responsible for maintaining the unit in safe operating condition. Parts and
             accessories shall be replaced if unsuitable for safe operation.
          8. It is prohibited to walk or stand on the unit or on its components.
9829 3178 62                                                                                                        5
                                                                                                  Instruction book
        9. If compressed air is used in the food industry and more specifically for direct food contact, it
           is recommended, for optimal safety, to use certified Class 0 compressors in combination
           with appropriate filtration depending on the application. Please contact your customer center
           for advice on specific filtration.
6                                                                                                   9829 3178 62
Instruction book
        12. The electrical connections must correspond to the applicable codes. The machines must be
            earthed and protected against short circuits by fuses in all phases. A lockable power
            isolating switch must be installed near the compressor.
        13. On machines with automatic start/stop system or if the automatic restart function after
            voltage failure is activated, a sign stating "This machine may start without warning" must be
            affixed near the instrument panel.
        14. In multiple compressor systems, manual valves must be installed to isolate each
            compressor. Non-return valves (check valves) must not be relied upon for isolating pressure
            systems.
        15. Never remove or tamper with the safety devices, guards or insulation fitted on the machine.
            Every pressure vessel or auxiliary installed outside the machine to contain air above
            atmospheric pressure must be protected by a pressure relieving device or devices as
            required.
        16. Piping or other parts with a temperature in excess of 70˚C (158˚F) and which may be
            accidentally touched by personnel in normal operation must be guarded or insulated. Other
            high temperature piping must be clearly marked.
        17. For water-cooled machines, the cooling water system installed outside the machine has to
            be protected by a safety device with set pressure according to the maximum cooling water
            inlet pressure.
        18. If the ground is not level or can be subject to variable inclination, consult the manufacturer.
        19. If the device is a dryer and no free extinguishing system is present in the air net close to the
            dryer, safety valves must be installed in the vessels of the dryer.
                          Also consult following safety precautions: Safety precautions during operation and
                          Safety precautions during maintenance.
                          These precautions apply to machinery processing or consuming air or inert gas.
                          Processing of any other gas requires additional safety precautions typical to the
                          application which are not included herein.
                          Some precautions are general and cover several machine types and equipment; hence
                          some statements may not apply to your machine.
9829 3178 62                                                                                                      7
                                                                                                  Instruction book
        6. Keep all bodywork doors shut during operation. The doors may be opened for short periods
           only, e.g. to carry out routine checks. Wear ear protectors when opening a door.
           On machines without bodywork, wear ear protection in the vicinity of the machine.
        7. People staying in environments or rooms where the sound pressure level reaches or
           exceeds 80 dB(A) shall wear ear protectors.
        8. Periodically check that:
               • All guards are in place and securely fastened
               • All hoses and/or pipes inside the machine are in good condition, secure and not
                 rubbing
               • No leaks occur
               • All fasteners are tight
               • All electrical leads are secure and in good order
               • Safety valves and other pressure relief devices are not obstructed by dirt or paint
               • Air outlet valve and air net, i.e. pipes, couplings, manifolds, valves, hoses, etc. are in
                 good repair, free of wear or abuse
               • Air cooling filters of the electrical cabinet are not clogged
        9. If warm cooling air from compressors is used in air heating systems, e.g. to warm up a
           workroom, take precautions against air pollution and possible contamination of the breathing
           air.
       10. On water-cooled compressors using open circuit cooling towers, protective measures must
           be taken to avoid the growth of harmful bacteria such as Legionella pneumophila bacteria.
       11. Do not remove any of, or tamper with, the sound-damping material.
       12. Never remove or tamper with the safety devices, guards or insulations fitted on the machine.
           Every pressure vessel or auxiliary installed outside the machine to contain air above
           atmospheric pressure shall be protected by a pressure relieving device or devices as
           required.
       13. Yearly inspect the air receiver. Minimum wall thickness as specified in the instruction book
           must be respected. Local regulations remain applicable if they are more strict.
                         Also consult following safety precautions: Safety precautions during installation and
                         Safety precautions during maintenance.
                         These precautions apply to machinery processing or consuming air or inert gas.
                         Processing of any other gas requires additional safety precautions typical to the
                         application which are not included herein.
                         Some precautions are general and cover several machine types and equipment; hence
                         some statements may not apply to your machine.
8                                                                                                   9829 3178 62
Instruction book
         3. Use only genuine spare parts for maintenance or repair. The manufacturer will disclaim all
            damage or injuries caused by the use of non-genuine spare parts.
         4. All maintenance work shall only be undertaken when the machine has cooled down.
         5. A warning sign bearing a legend such as "Work in progress; do not start" shall be attached
            to the starting equipment.
         6. Persons switching on remotely controlled machines shall take adequate precautions to
            ensure that there is no one checking or working on the machine. To this end, a suitable
            notice shall be affixed to the remote start equipment.
         7. Close the compressor air outlet valve and depressurize the compressor before connecting
            or disconnecting a pipe.
         8. Before removing any pressurized component, effectively isolate the machine from all
            sources of pressure and relieve the entire system of pressure.
         9. Never use flammable solvents or carbon tetrachloride for cleaning parts. Take safety
            precautions against toxic vapors of cleaning liquids.
        10. Scrupulously observe cleanliness during maintenance and repair. Keep dirt away by
            covering the parts and exposed openings with a clean cloth, paper or tape.
        11. Never weld or perform any operation involving heat near the oil system. Oil tanks must be
            completely purged, e.g. by steam cleaning, before carrying out such operations. Never weld
            on, or in any way modify, pressure vessels.
        12. Whenever there is an indication or any suspicion that an internal part of a machine is
            overheated, the machine shall be stopped but no inspection covers shall be opened before
            sufficient cooling time has elapsed; this to avoid the risk of spontaneous ignition of the oil
            vapor when air is admitted.
        13. Never use a light source with open flame for inspecting the interior of a machine, pressure
            vessel, etc.
        14. Make sure that no tools, loose parts or rags are left in or on the machine.
        15. All regulating and safety devices shall be maintained with due care to ensure that they
            function properly. They may not be put out of action.
        16. Before clearing the machine for use after maintenance or overhaul, check that operating
            pressures, temperatures and time settings are correct. Check that all control and shut-down
            devices are fitted and that they function correctly. If removed, check that the coupling guard
            of the compressor drive shaft has been reinstalled.
        17. Every time the separator element is renewed, examine the discharge pipe and the inside of
            the oil separator vessel for carbon deposits; if excessive, the deposits should be removed.
        18. Protect the motor, air filter, electrical and regulating components, etc. to prevent moisture
            from entering them, e.g. when steam cleaning.
        19. Make sure that all sound-damping material and vibration dampers, e.g. damping material on
            the bodywork and in the air inlet and outlet systems of the compressor, is in good condition.
            If damaged, replace it by genuine material from the manufacturer to prevent the sound
            pressure level from increasing.
        20. Never use caustic solvents which can damage materials of the air net, e.g. polycarbonate
            bowls.
        21. Only if applicable, the following safety precautions are stressed when handling
            refrigerant:
                • Never inhale refrigerant vapors. Check that the working area is adequately ventilated; if
                  required, use breathing protection.
                • Always wear special gloves. In case of refrigerant contact with the skin, rinse the skin
                  with water. If liquid refrigerant contacts the skin through clothing, never tear off or
                  remove the latter; flush abundantly with fresh water over the clothing until all refrigerant
                  is flushed away; then seek medical first aid.
9829 3178 62                                                                                                 9
                                                                                             Instruction book
                        Also consult following safety precautions: Safety precautions during installation and
                        Safety precautions during operation.
                        These precautions apply to machinery processing or consuming air or inert gas.
                        Processing of any other gas requires additional safety precautions typical to the
                        application which are not included herein.
                        Some precautions are general and cover several machine types and equipment; hence
                        some statements may not apply to your machine.
Dismantling
      Once the end of life of the machine is reached, please follow next steps:
        1. Stop the machine.
        2. Check all safety precautions mentioned in the previous chapters to secure safe handling
           (e.g. LOTO, cool-down, depressurize, discharge, ...).
        3. Separate the harmful from the safe components (e.g. drain oil from oil containing parts).
        4. Refer to the disposal topic mentioned below.
      The equipment is labelled in accordance with the European Directive 2012/19/EU with the
      crossed-out wheelie bin symbol.
      At the end of life-time of the electric and electronic equipment (EEE) it must be taken to separate
      collection.
      For more information check with your local waste authority, customer center or distributor.
10                                                                                             9829 3178 62
Instruction book
2 General description
2.1 Introduction
General
General view
        GA are oil-injected screw compressors, driven by an electric motor and enclosed in a sound-
        insulated bodywork.
        GA 90+ and GA 110 up to GA 160 are air-cooled compressors.
        GA 90+ W and GA 110 W up to GA 160 W are water-cooled compressors.
        GA are single-stage compressors.
        The following features are available as an option:
Full-Feature
        A refrigerant dryer is fully integrated into the bodywork of the compressor. This "all-in-one"
        feature reduces the required space for installation and provides savings on piping installation
        costs.
Energy recovery
        The compressor is provided with an Atlas Copco energy recovery system to recover the major
        part of the compression heat and heat losses of the drive motor gathered in hot water without any
        influence on the compressor performance.
9829 3178 62                                                                                              11
                                                                                              Instruction book
TT-TN or IT network
      The compressor control panel is designed to be connected to either a TT-TN or IT electrical
      power network. The design of these networks is described in the IEC 60950 standard.
12                                                                                              9829 3178 62
Instruction book
Flow diagram
Air-cooled version
9829 3178 62                                       13
                                                             Instruction book
Water-cooled version
     Reference   Description
     1           Air inlet
     2           Energy recovery circuit (optional)
     3           Condensate drain, compressor
     4           Condensate drain, Full-Feature compressor
     5           Air outlet
14                                                             9829 3178 62
Instruction book
         Reference         Description
         6                 Cooling water circuit
Position of components
Air flow
        Air comes in through filter (AF) and unloader (UA) and is compressed in the compressor element
        (E).
        A mixture of compressed air and oil flows into the air receiver/oil separator (AR), where oil and air
        are separated.
        The air flows through the minimum pressure valve (Vp), the air cooler (Ca) and the condensate
        trap to the air outlet.
        Minimum pressure valve (Vp) prevents the receiver pressure from dropping below a minimum
        pressure and includes a check valve which prevents blow-back of compressed air from the net.
        Full-Feature compressors have a dryer after the air cooler.
Oil circuit
        The air receiver (AR) removes most of the oil from the air/oil mixture by centrifugal action. The oil
        collects in the lower part of the air receiver (AR) which serves as oil tank.
        The oil separator removes the remaining oil.
9829 3178 62                                                                                               15
                                                                                            Instruction book
      The oil circuit has a thermostatic bypass valve that prevents that the oil flows through the oil
      cooler (Co) when the oil temperature is low.
      Air pressure forces the oil from air receiver (AR) through the oil filter (OF).
      The filtered oil flows through the cooling channels of the drive motor to the compressor element
      (E) and the lubrication points.
      The oil circuit has an extra thermostatic bypass valve that will send extra oil to the compressor
      element when the oil temperature is getting too high.
      Reference          Designation
      Dac                Automatic condensate drain outlet
      Dmc                Manual condensate drain outlet
16                                                                                            9829 3178 62
Instruction book
        A condensate trap is installed downstream of the air cooler to prevent condensate from entering
        the air outlet pipe. The trap is provided with a level sensor and solenoid valve for automatically
        draining condensate and with a manual drain valve.
        This condensate can contain small amounts of oil and should be processed according to local
        environmental legislation.
        On Full-Feature units, the condensate formed in the dryer collects in the lower part of the heat
        exchanger/evaporator. When the condensate in the electronic drain reaches a certain level, it is
        drained via the automatic drain outlet (Dac)
Cooling system
        On air-cooled compressors, the air and oil coolers are cooled by dual-speed fans.
        Water-cooled compressors are provided with a cooling water system, including oil and air
        coolers.
Elektronikon
        The compressor is controlled by the Elektronikon® regulator.
        The regulator keeps the net pressure within programmable pressure limits by automatically
        loading and unloading the compressor depending on the air consumption.
Unloader
        The unloader is mounted on the compressor stage inlet and connected to the air filter outlet.
        During the regulation of the compressor pressure, the unloader can appear in 4 modes:
         1. Unload
         2. Pre-load
         3. Load
         4. Delayed unload
         Reference        Designation
         1                Element inlet
         2                L/UL solenoid valve Y1
         3                Controlled bypass valve Y11 (Blow-By)
         4                Blow-off hole
         5                Calibrated by-pass
9829 3178 62                                                                                             17
                                                                                        Instruction book
Unload mode
Pre-Load mode
18                                                                                        9829 3178 62
Instruction book
Load mode
          1. Load/Unload valve (Y1) is powered (Y1 opened resulting in blow-off valve closed).
          2. The unloader opens and allows further pressure rise above 2.5 bar (36.3 psi).
          3. The Blow-By valve (Y11) is not powered (closed).
        When the air demand drops and the pressure reaches the unload level, the compressor switches
        to unload mode, the oil separator pressure is expanded through blow-off hole (BO) and the above
        sequence repeats.
          1. Load/Unload valve (Y1) is not powered (Y1 closed resulting in blow-off valve open).
          2. The unloader closes.
          3. The Blow-By valve (Y11) is powered (open).
              a. Extra air is sucked in.
              b. Vessel pressure is gradually decreasing.
          4. When the vessel pressure reaches 6.5 bar (94.3 psi), the unit will go into unload mode.
9829 3178 62                                                                                            19
                                                                                                Instruction book
General description
                          The maximum allowed pressure at the water side of the heat exchanger is 10 bar (145
                          psi).
       The energy required in any compression process is mainly transformed into heat. The major part
       of the compression heat is dissipated through the oil system. The Atlas Copco energy recovery
       systems are designed to recover most of the above-mentioned heat as warm or hot water without
       any adverse influence on the compressor performance.
       After the compression stage, the oil is separated from the compressed air. The compressed air
       flows to the aftercooler and the oil flows to the oil cooler. The energy in the oil can be recovered
       by installing a heat exchanger in front of the oil cooler.
       The energy recovery systems can be applied as low temperature rise / high water flow systems
       (e.g. central heating in closed water circuits) or as high temperature rise / low water flow systems
       (e.g. pre-heating of boiler feed water in open water circuits).
Main components
       The system mainly comprises:
          •    Oil/water heat exchanger (HE)
          •    Energy recovery valve (Y152)
          •    Oil by-pass valve (Y151)
          •    Temperature sensors for water inlet and outlet
          •    The necessary pipes, brackets, bolts, etc.
Installation
       The package includes:
         • a general by-pass system, to shut down the energy recovery system
         • a by-pass system to prevent the oil outlet temperature from dropping below the minimum
           value.
           When the Energy Recovery system is working, this by-pass system makes the oil flow
           through the Energy Recovery heat exchanger instead of the normal oil cooler
20                                                                                                9829 3178 62
Instruction book
Text on figure
        pd = 4.23 F2 + 1.62 F
        With:
          • pd = pressure drop in kPa
          • F = water flow in l/s
The pressure drops calculated with the formulas above are indicative.
9829 3178 62                                                                                 21
                                                           Instruction book
22                                                           9829 3178 62
Instruction book
Flow diagram
        The recovery water enters the unit at the heat exchanger inlet connection. In the heat exchanger
        the compression heat is transferred from the compressor to the water. The water leaves the heat
        exchanger via the outlet connection.
Installation
        The compressor frame is prepared for the Energy Recovery system. Before mounting the
        installation, the two laser prepared holes in the canopy must be cut out.
Operation
        The compressor oil flow is controlled by two thermostatic valves (Y151 and Y152). Y152 controls
        the oil flow over the energy recovery cooler and Y151 controls the oil flow through the oil cooler
        and thus the element outlet temperature. Ex factory the thermostat setting of Y151 is chosen in a
        way that the element outlet temperature is 90 °C (194 °F) +/- 5 °C (9 °F).
        Recoverable Energy
        The graphs of the Principal data section below represent the performance for each power variant
        at reference working pressure. The curves represent the limits of the energy recovery area and
        were obtained with the temperature of the element outlet as indicated in the graph. All points
        below the curve with Tc = 85 °C (185 °F) are possible working points where the recovered energy
        is maximized for lower element outlet temperatures.
        The formula to calculate the amount of recovered energy is:
        Q (kW) = 4.2 x q (l/s) x dT (°C)
        with
           • q = water flow in l/s
           • dT = temperature difference between water at inlet and outlet
        Selection of the thermostatic valve
        To avoid condensate in the oil circuit, it is very important that the element outlet temperature
        always exceeds the condensation temperature. In worst case conditions (e.g. air inlet of 46 °C
        (115 °F) and relative humidity (R.H.) of 50 %), tc (compressor outlet stage temperature) should
        be above 85 °C (185 °F) for units with working pressures up to 10 bar (150 psi). This means that:
        to prevent condensation in these worst case conditions, the curves with tc= 85 °C (185 °F) are
9829 3178 62                                                                                            23
                                                                                                Instruction book
     the lower limit of the energy recovery (for compressors with working pressure up to 10 bar (150
     psi)).
     If the air inlet temperature and R.H. are known, tc can be lower than the limits above and can be
     calculated from the curves below. The compressor stage outlet temperature should exceed this
     value by adapting the thermostatic valve Y151 in the thermostatic valve housing of the oil cooling
     system of the standard compressor. To obtain a higher element outlet temperature (with a high
     energy recovery water flow and/or low energy recovery water inlet temperature) (to get a higher
     water outlet temperature), a thermostatic valve with an indicated temperature higher than the
     standard factory mounted has to be mounted in the thermostatic valve housing of the oil cooling
     system of the standard compressor. A list of standard thermostat settings for Y151 can be found
     below.
     The cooling water circuit of the energy recovery is by default protected against steam generation
     by a compressor shut down at cooling water temperatures of the energy recovery of 95 °C (203
     °F). When the thermostat valve selection is done for a compressor stage outlet temperature
     running above 95 °C (203 °F), the compressor might trip at this limit value. This could happen
     whenever the heat dissipation in the customer's installation stops (e.g. when the pump in the
     customer's installation stops) or the heat dissipation is lower than the heat recovered from the
     compressor. This results in a gradual temperature increase on the energy recovery cooling
     medium system until the shut-down value has been reached. In this case following measures can
     be taken to prevent an unwanted shut down:
        • Manually switch off energy recovery by use of the hand wheel.
        • Ask an Atlas Copco technician to increase the shut down value of the cooling water
          temperature of the energy recovery in the Elektronikon controller. It is advised to choose a
          temperature higher than the selected compressor element outlet temperature but at least 5
          °C (9 °F) below the boiling point of the applied cooling medium and never higher than 120
          °C (248 °F).
                       The thermostatic valve of the energy recovery (Y152) always needs to have an
                       indicated temperature equal to or higher than that of the thermostatic valve in the
                       thermostatic valve housing of the oil cooling system of the standard compressor.
24                                                                                                9829 3178 62
Instruction book
Text on figure
9829 3178 62                                                                            25
                                                                                            Instruction book
Calculation examples
Text on figure
      Example point X
      High temperature rise, low water flow application, e.g. pre-heating of boiler feed water in open
      circuit:
         •   Compressor unit: GA 160 - 50 Hz
         •   Working pressure: 8 bar / 116 psi
         •   Water flow: 0.6 l/s / 1.27 cfm
         •   Water inlet temperature: 31 °C / 88 °F
         •   Water outlet temperature: 85 °C / 185 °F
      The formula to calculate the amount of recovered energy results in (2):
         • 4.2 x 0.6 x (85 - 31) = 136 kW ( ± as indicated on the curve)
      The outlet temperature for a water flow of 0.6 l/s can be calculated backwards from formula (2):
         • Toutlet = 31 + (136 / (4.2 x 0.6)) = 85 °C (185 °F)
      Total pressure drop on waterside is (1):
         • pd = (4.23 x 0.6²) + (1.62 x 0.6) = 2.5 kPa = 25 mbar (0.36 psi)
      Example point Y
      Low temperature rise, high water flow application, e.g. central heating in closed circuit:
         •   Compressor unit: GA 160 - 50 Hz
         •   Working pressure: 8 bar / 116 psi
         •   Water flow: 4 l/s / 0.87 cfm
         •   Water inlet temperature: 47.5 °C / 117.5 °F
26                                                                                            9829 3178 62
Instruction book
9829 3178 62                                                                                              27
                                                                                    Instruction book
     • Wear a safety helmet when working in the area of overhead or lifting equipment.
     • Protect hands to avoid injury from hot machine parts, e.g. during draining of oil.
     • Protection caps, bags, etc. must be removed before connecting the pipes.
     • Water hoses must be of correct size and suitable for the working pressure.
     • The water connections must be free of strain.
     • Pipe work or other parts with a temperature in excess of 70 ˚C (158 ˚F) must be guarded or
       insulated. Other high-temperature pipe work must be clearly marked.
     • The water system installed outside the machine has to be protected by a safety device with
       set pressure according to the maximum cooling water inlet pressure.
     • All maintenance work shall only be undertaken when the machine has cooled down.
     • Never weld or perform any operation involving heat near the oil system.
28                                                                                    9829 3178 62
Instruction book
3.1 Controller
Introduction
        The controller has following functions:
           •   Controlling the unit
           •   Protecting the unit
           •   Monitoring components subject to service
           •   Automatic restart after voltage failure (ARAVF)
                            A number of time based automatic start/stop commands may be programmed. Take into
                            account that a start command will be executed (if programmed and activated), even after
                            manually stopping the unit.
9829 3178 62                                                                                                   29
                                                                                                    Instruction book
       Shutdown warning
       A shutdown warning level is a programmable level below the shutdown level.
       If one of the measurements exceeds the programmed shutdown warning level, a message will
       appear on the display and the general alarm LED will light up to warn the operator before the
       shutdown level is reached.
       The message disappears as soon as the warning condition disappears.
Service warning
       A number of service operations are grouped as a Service Plan. Each Service Plan has a
       programmed time interval. If the service timer exceeds a programmed value, this will be indicated
       on the display to warn the operator to carry out the service actions belonging to that Service Plan.
                          If the function is activated and provided the regulator was in the automatic operation
                          mode, the unit will automatically restart if the supply voltage to the module is restored.
                          The ARAVF label (see section Pictographs) shall be glued near to the controller.
30                                                                                                    9829 3178 62
Instruction book
Control panel
9829 3178 62                                                                                             31
                                                                       Instruction book
Menu icons
Inputs
Outputs
Counters
Service Plan
Service History
                             Service
                             functions
Clean Screen
                                                     Remaining
                                                     Running Time
32                                                                       9829 3178 62
Instruction book
Regulation
                                      Control
                                      Parameters
Fan
                                                              Internal
                                                              SmartBox
Auto Restart
CAN Settings
Localisation Language
Date/Time
Units
User Password
Help
Information
Status icons
         Icon         Description
                      Motor Stopped
9829 3178 62                                                                        33
                                                         Instruction book
Running Unloaded
Manual Unload
Running Loaded
Failed to Load
Manual Stop
System icons
      Icon     Description
               Basic User
Advanced User
Service User
Antenna 25%
34                                                         9829 3178 62
Instruction book
Antenna 50%
Antenna 75%
Antenna 100%
Energy recovery
Dryer
Element
Drain(s)
Analogue Output
Menu
Reset
Auto Restart
Filter(s)
Cooler
Valve(s)
Power Meter
Input icons
         Icon      Description
                   Pressure
9829 3178 62                                             35
                                                                                                Instruction book
Temperature
Special Protection
Open
Closed
                        This chapter gives a general survey of available icons. Not all icons mentioned in this
                        chapter are applicable to every machine.
Function
      The Main screen is the screen that is shown automatically when the voltage is switched on. It is
      switched off automatically after a few minutes when there is no touch input.
Description
36                                                                                                 9829 3178 62
Instruction book
Function
        The screen is used to directly access some frequently used functions.
Procedure
        The Quick access screen can be viewed by swiping left, starting from the main screen.
Description
Through this screen, several important settings can be viewed and modified.
9829 3178 62                                                                                                      37
                                                                                                  Instruction book
       Function              Description
       Setpoints             Several setpoints can be modified by tapping this icon.
       Control mode          The control mode can be changed by tapping this icon.
                                • Local control via start/stop buttons
                                • Remote control via digital input(s)
                                • LAN control via the network.
                             When in Remote or LAN control, the start/stop buttons on the controller will not work.
       Display language      The display language of the controller can be changed by tapping this icon.
       Manual unload (only When tapped, the machine will go in Manual unload mode until the icon is tapped
       on fixed speed units) again.
       Week timer            Week timers can be set by tapping this icon.
       Remaining running     The Remaining running time can be set and modified by tapping this icon.
       time
       Internal SmartBox     The reception quality of the internal antenna can be monitored.
                             Each bar represents 25% reception strength. If the four bars are filled, the reception
                             strength is 100%. If only one bar is filled, the reception strength is just 25%.
       Auto restart          Auto restart can be activated by tapping this icon.
Function
      This screen is used to display the different menus where settings can be viewed or changed.
Procedure
      The Menu screen can be viewed by tapping the Menu button or by swiping right, starting from the
      main screen.
Description
38                                                                                                  9829 3178 62
Instruction book
Menu structure
        Operating the controller can be done by swiping through screens and tapping icons or menu
        items.
        This is the main menu structure. The structure can be different depending on the configuration of
        the unit.
9829 3178 62                                                                                                  39
                                                               Instruction book
Function
      This screen is used to display the following submenus:
         • Status
         • Inputs
         • Outputs
         • Counters
         • Aux. Equipment
      These submenus can be entered by tapping the icons.
Procedure
      To enter the Data menu screen:
       1. Tap the Menu button
       2. Tap the Data icon
Description
       Reference    Designation
       (1)          Status menu
       (2)          Inputs menu
       (3)          Outputs menu
       (4)          Counters menu
       (5)          Auxiliary equipment menu
Status menu
      Tap the Status icon to enter the Status menu.
40                                                               9829 3178 62
Instruction book
        If an alarm is active, it can be viewed by tapping the alarm message. To reset an alarm, tap the
        reset button (1).
Inputs menu
        Tap the Inputs icon to enter the Inputs menu.
Outputs menu
        Tap the Outputs icon to enter the Outputs menu.
Counters menu
        Tap the Counters icon to enter the Counters menu.
9829 3178 62                                                                                                 41
                                                                                         Instruction book
This menu shows an overview of all actual hours and counters of the unit and controller.
Function
      This screen is used to display the following submenus:
         • Service
         • Service functions (Only visible as advanced user)
         • Clean screen
      These submenus can be entered by tapping the icons.
Procedure
      To enter the Service menu screen:
       1. Tap the Menu button
       2. Tap the Service icon
42                                                                                         9829 3178 62
Instruction book
Description
         Reference    Designation
         (1)          Service
         (2)          Service functions (Only visible as advanced user)
         (3)          Clean screen
Service menu
        Tap the Service icon to enter the Service menu.
        This menu shows the remaining Running Hours and the remaining Real Time Hours until the next
        service. The first row (A) shows the Running Hours when the first service is needed (green), the
        second row shows the Real Time Hours (blue)
        A service overview can be viewed by tapping icon (1).
        The service plan can be viewed by tapping icon (2). Through this menu, the service plan can be
        modified:
         1. Tap the desired service plan. A selection screen will pop up.
         2. Change the Running Hours by tapping ‘–’ or ‘+’.
         3. Confirm by tapping ‘V’ or decline by tapping ‘X’.
        The service history can be viewed by tapping icon (3).
        When a service plan interval is reached, a message will appear on the screen. When service has
        been performed, the service timer can be reset by tapping the reset button (4).
9829 3178 62                                                                                         43
                                                                                           Instruction book
      Depending on the machine, this menu can have a different set of functions. Many of them are
      password protected, as they are only accessible for authorized personnel.
Clean screen
      Tap the Clean Screen icon to start the 15 seconds countdown to perform cleaning of the
      touchscreen.
The touchscreen and the start and stop button become inactive for 15 seconds.
Function
      This screen is used to set up to 4 different week timers with each up to 8 settings per day.
      The week timers can be activated through this screen.
      A Remaining Running Time can be set from 5 up to 240 minutes.
Procedure
      To enter the Week Timer menu screen:
       1. Tap the Menu button
       2. Tap the Week Timer icon
44                                                                                           9829 3178 62
Instruction book
Description
Function
        This screen is used to display the saved data in case of an alarm.
        These submenus can be entered by tapping the icons.
Procedure
        To enter the Event history menu screen:
         1. Tap the Menu button
         2. Tap the Event History icon
Description
9829 3178 62                                                                                                   45
                                                                                            Instruction book
      Reference     Designation
      (1)           Saved Data
Saved data
      Tap the Saved Data icon to enter the Saved Data menu.
      Scroll through the items swiping up and down in this list. The event date and time is shown at the
      right side of the screen.
      Press on one of the items in the list for more information reflecting the status of the unit when the
      shutdown occurred.
Function
      This screen is used to display the following submenus:
         • Alarms
         • Regulation
         • Control Parameters
           Only visible if the machine has adaptable parameters.
         • Aux. Equipment parameters
         • Auto Restart
      These submenus can be entered by tapping the icons.
Procedure
      To enter the Machine settings menu screen:
       1. Tap the Menu button
       2. Tap the Machine Settings icon
46                                                                                            9829 3178 62
Instruction book
Description
         Reference     Designation
         (1)           Alarms menu
         (2)           Regulation menu
         (3)           Control Parameters menu
         (4)           Aux. Equipment Parameters menu
         (5)           Auto Restart menu
Alarms menu
        Tap the Alarms icon to enter the Alarms menu.
Regulation menu
        Tap the Regulation icon to enter the Regulation menu.
9829 3178 62                                                                                           47
                                                                                        Instruction book
      When tapping a list item, a selection screen pops up. The user can modify the setting by tapping
      ‘–’ or ‘+’ and can confirm by tapping ‘V’ or decline by tapping ‘X’.
      Change a selection
      When tapping a list item, a selection screen pops up. The user can change the selection by
      swiping up or down and confirm by tapping ‘V’ or decline by tapping ‘X’.
48                                                                                        9829 3178 62
Instruction book
        Through this menu, the automatic restart can be activated. The activation is password protected.
        The automatic restart settings can also be changed.
        Enter a password
        When tapping a password protected item, a selection screen pops up. The user can enter the
        password by swiping up or down to select the desired number. Once the 4 digits are entered, the
        user can confirm by tapping ‘V’ or decline by tapping ‘X’.
        Modify a setting
        When clicking a list item, a selection screen pops up. The user can modify the setting by tapping
        ‘–’ or ‘+’ and can confirm by tapping ‘V’ or decline by tapping ‘X’.
Function
        This screen is used to display the following submenus:
           • Network Settings
           • Localisation
           • User Password
           • Help
           • Information
        These submenus can be entered by tapping the icons.
Procedure
        To enter the Controller Settings menu screen:
         1. Tap the Menu button
         2. Tap the Controller Settings icon
Description
9829 3178 62                                                                                            49
                                                                                          Instruction book
       Reference    Designation
       (1)          Network Settings menu
       (2)          Localisation menu
       (3)          User Password menu
       (4)          Help menu
       (5)          Information menu
      Ethernet Settings
      The list of Ethernet Settings is shown. When ethernet is turned off, the settings can be modified.
      CAN Settings
      The list of CAN Settings is shown. When CAN is turned off, the settings can be modified.
      Modify a setting
      When tapping a list item, a selection screen pops up. The user can modify the setting by tapping
      ‘–’ or ‘+’ and can confirm by tapping ‘V’ or decline by tapping ‘X’.
      Change a selection
      When tapping a list item, a selection screen pops up. The user can change the selection by
      swiping up or down and confirm by tapping ‘V’ or decline by tapping ‘X’.
Localisation menu
      Tap the Localisation icon to enter the Localisation menu.
      Language
      The language setting of the controller can be modified through this menu.
      Date/Time
50                                                                                          9829 3178 62
Instruction book
        The date and time settings of the controller can be modified through this menu.
        Units
        The units displayed can be modified through this menu.
        Modify a setting
        When tapping a list item, a selection screen pops up. The user can modify the setting by tapping
        ‘–’ or ‘+’ and can confirm by tapping ‘V’ or decline by tapping ‘X’.
        Change a selection
        When tapping a list item, a selection screen pops up. The user can change the selection by
        swiping up or down and confirm by tapping ‘V’ or decline by tapping ‘X’.
        The user password can be activated or deactivated through this menu. Enter and confirm a user
        password to activate, repeat to deactivate.
        Enter a password
        When tapping a password protected item, a selection screen pops up. The user can enter the
        password by swiping up or down to select the desired number. Once the 4 digits are entered, the
        user can confirm by tapping ‘V’ or decline by tapping ‘X’.
Help menu
        Tap the Help icon to enter the Help menu.
        This menu can show a link to the web page of your supplier, a helpdesk phone number or other
        helpful information.
Information menu
        Tap the Information icon to enter the Information menu.
9829 3178 62                                                                                           51
                                                                                             Instruction book
Function
      Through this pop-up screen the access level settings can be viewed or changed.
Procedure
      The Access Level screen can be viewed or changed by tapping the Access Level button at the
      upper right corner of the screen.
Description
52                                                                                             9829 3178 62
Instruction book
Tap the Service access level icon (1) and confirm (2).
        The screen information bar (1) now shows the current status of the unit instead of the machine
        serial number.
        The Received Signal Strength Indicator (RSSI) value is now shown in the Internal SmartBox
        menu. See Quick access screen.
        In the service menu, an extra menu item is now available. See Service menu.
9829 3178 62                                                                                             53
                                                                             Instruction book
4 Installation
Compressor dimensions
54                                                                             9829 3178 62
Instruction book
9829 3178 62                                                              55
                                                                             Instruction book
56                                                                             9829 3178 62
Instruction book
9829 3178 62                                                                                 57
                                                                               Instruction book
58                                                                               9829 3178 62
Instruction book
Reference table
         Reference                       Description
         (1)                             Data plate
         (2)                             Electrical cable entry (cable box, optional CTS kit)
         (3)                             Air-cooled compressor: Cooling air outlet
                                         Air-cooled compressor: Dryer cooling air outlet
                                         Water-cooled compressor: Canopy ventilation outlet
         (4)                             Air-cooled compressor: Dryer cooling air inlet
         (5)                             Cubicle ventilation inlet
         (6)                             4 slotted holes
         (7)                             Compressor air inlet
                                         Air-cooled compressor: Cooling air inlet
                                         Water-cooled compressor: Canopy ventilation inlet
         (8)                             Compressed air outlet
         (9)                             Manual drain, compressor
         (10)                            Automatic drain, compressor
         (11)                            Automatic drain, dryer
9829 3178 62                                                                                     59
                                                                             Instruction book
      Reference              Description
      (12)                   Energy recovery water outlet
      (13)                   Energy recovery water inlet
      (14)                   Water-cooled compressor: Cooling water inlet
                             Air-cooled compressor: Not used
      (15)                   Water-cooled compressor: Cooling water outlet
                             Air-cooled compressor: Not used
      (16)                   Centre of gravity
      (17)                   Detail C
60                                                                             9829 3178 62
Instruction book
Text on figures
         Reference   Description
         (1)         Install the compressor on a level floor suitable for taking its weight.
         (2)         Compressed air outlet valve (not in scope of supply).
         (3)         For SI units
                     Delivery pipe:
                     The maximum pipe length can be calculated as follows:
                     L = (dp x d5 x p) / (450 x Qc1.85)
                     L = Length of pipe in m
                     dp = Pressure drop (recommended maximum = 0.1 bar)
                     d = Inner diameter of the outlet pipe in mm
                     p = Absolute pressure at the compressor outlet in bar(a)
                     Qc = Free air delivery of the compressor in l/s
                     The connection of the air delivery pipe is made on top of the main air net pipe in order
                     to minimize carry-over of possible condensate residue.
         (3)         For British/American units:
                     Delivery pipe:
                     The maximum pipe length can be calculated as follows:
                     L = 1470 ( (dp x d5 x p) / (Qc1.85) )
                     L = Length of pipe in ft
                     dp = Pressure drop (recommended maximum = 1.45 psi)
                     d = Inner diameter of the outlet pipe in inch
                     p = Absolute pressure at the compressor outlet in psi
                     Qc = Free air delivery of the compressor in cfm
                     The connection of the air delivery pipe is made on top of the main air net pipe in order
                     to minimize carry-over of possible condensate residue.
9829 3178 62                                                                                               61
                                                                                           Instruction book
     Reference   Description
     (4)         For SI units
                 Ventilation:
                 The inlet grid(s) and ventilation fan must be installed in such a way that any re-
                 circulation of cooling air to the compressor is avoided. The air velocity to the grid(s) has
                 to be limited to 5 m/s
                 The maximum allowable pressure drop over all cooling ducts together is 30 Pa
                 The maximum air temperature at the compressor intake opening is 46 °C (50 °C for
                 HAT version), minimum 0 °C
                 The required ventilation to limit the compressor room temperature can be calculated as
                 follows:
                 Qv = 0.92N / dT (air-cooled unit)
                 Qv = 0.1N / dT (water-cooled unit)
                 Qv= Required ventilation capacity in m3/s
                 N = Shaft input of the compressor in kW
                 dT = Compressor room temperature over the outdoor temperature in °C
     (4)         For British/American units:
                 Ventilation:
                 The inlet grid(s) and ventilation fan must be installed in such a way that any re-
                 circulation of cooling air to the compressor is avoided. The air velocity to the grid(s) has
                 to be limited to 5 m/s
                 The maximum allowable pressure drop over all cooling ducts together is 4.35 x 10 psi
                 The maximum air temperature at the compressor intake opening is 114.8 °F (122 °F for
                 HAT version), minimum 32 °F
                 The required ventilation to limit the compressor room temperature can be calculated as
                 follows:
                 Qv = 2845 x (0.92N) / dT (air-cooled unit)
                 Qv = 2845 x (0.1N) / dT (water-cooled unit)
                 Qv= Required ventilation capacity in cfm
                 N = Shaft input of the compressor in hP
                 dT = Compressor room temperature over the outdoor temperature in °F
     (5)         Drain pipes to condensate collector. The drain pipes may not enter in the collector.
                 Individual drain pipes may not be interconnected to avoid interference
                 Compressor condensate contains oil. Depending on local legislation, it is recommended
                 to install an oil/water separator (consult Atlas Copco)
     (6)         Control cubicle with monitoring panel
     (7)         Main cable entry
     (8)         Cooling water inlet pipe (only water-cooled unit)
     (9)         Cooling water outlet pipe (only water-cooled unit)
     (10)        Minimum free area to be reserved for the compressor installation
     (11)        Ventilation proposals
     (12)        Air-cooled compressor
     (13)        Water-cooled compressor
     (A)         Cooling air outlet (air-cooled unit)
                 Dryer cooling air outlet (air-cooled Full-Feature unit)
                 Canopy ventilation outlet (water-cooled unit)
     (B)         Compressor air inlet
                 Cooling air inlet (air-cooled unit)
                 Canopy ventilation inlet (water-cooled unit)
     (C)         Cubicle ventilation air inlet (high ambient temperature unit)
     (D)         Dryer cooling air inlet (only air-cooled Full-Feature unit)
62                                                                                           9829 3178 62
Instruction book
         Reference   Description
         (1)         Customer's installation
         (2)         Customer
         (3)         6 fuses
         (4)         3 fuses if possible
         (5)         Compressor
9829 3178 62                                   63
                                                                                        Instruction book
     Reference   Description
     (6)         Compressor motor
                 To preserve the protection degree of the electric cubicle and to protect its components
                 from dust from the environment, it is mandatory to use a proper cable gland when
                 connecting the supply cable to the compressor.
                 Warnings
                   • Obey local regulations if they are stricter than the regulations mentioned in this
                     document.
                   • Obey the applicable electrical directives when installing and connecting the
                     compressor to the power circuit:
                        • IEC 60204-1
                        • IEC 60364-5-52
                        • CSA/UL
                                • UL: UL508A
                                • CSA: C22.2
                   • The voltage on the compressor terminals must not deviate more than 10% of the
                     nominal voltage. It is however highly recommended to keep the voltage drop over
                     the supply cables at nominal current below 5% of the nominal voltage (IEC
                     60204-1).
                   • Use the original cable entry.
                   • Full load (compressor) package currents are calculated and available on Technical
                     data sheet. For cable section selection purposes, we suggest to add 10% to
                     compensate for any under-voltages that might occur in the installation.
                   • Use copper wires only.
                   • Caution
                        • Always double-check the fuse size versus the calculated cable size. If
                            required, reduce the fuse size or enlarge the cable size.
                        • Cable length should not exceed the maximum length according to IEC 60204
                            (table.10).
                   • Display the fuse type information next to the fuse holder of the mains branch.
                   • Connect the power cable with the correct cable lugs on the terminals in the
                     electrical cabinet.
                   • Do not connect more than one (1) cable lug at one side of a contactor terminal or
                     copper bar, unless specified otherwise.
                   • Respect a minimum of 10 mm IEC (1/2” CSA/UL branch circuit) between stripped
                     cable ends for low voltage installations.
                   • Fuses are maximum allowed values to protect installed compressor electrical
                     panel.
                   • Apply the listed cable sections on main supply cables AND earth cable.
                   • Do not exceed the ambient temperature listed in the Limits section to avoid cable
                     damage.
                   • Mount all cables on a horizontally ventilated cable tray.
                   • Do not stack or group cables as this avoids heat dissipation.
                   • Connect the power cable with the correct (CSA certified) cable lugs on the
                     terminals in the electrical cabinet.
                   • Respect a minimum distance of 10 mm (0.4") between stripped cable ends.
                   • Use only the prescribed cable types:
                        • IEC: XLPE 90 °C (194 °F)
                        • CSA-UL: (R, RW, T) multicore 110 °C (230 °F)
                   • Display the fuse type information next to the fuse holder of the mains branch.
64                                                                                         9829 3178 62
Instruction book
Package current
        The Package current mentioned on the technical data sheet is defined as follows:
          • Package current is the current the compressor uses:
              • At reference conditions
              • At 100 % load
              • At maximum pressure
              • At nominal voltage
              • Before service interval (so including fouled filters, etc…)
        The pre-described fuses on the technical data sheet are the maximum main fuses to protect the
        installed compressor electrical panel.
9829 3178 62                                                                                                65
                                                                                   Instruction book
Cable configuration
66                                                                                   9829 3178 62
Instruction book
         Cable section     30 °C         40 °C        45 °C       50 °C        55 °C
         25 mm²            < 127 A       < 116 A      < 110 A     < 104 A      < 97 A
         35 mm²            < 158 A       < 144 A      < 137 A     < 130 A      < 120 A
         50 mm²            < 192 A       < 175 A      < 167 A     < 157 A      < 146 A
         70 mm²            < 246 A       < 224 A      < 214 A     < 202 A      < 187 A
         95 mm²            < 298 A       < 271 A      < 259 A     < 244 A      < 226 A
9829 3178 62                                                                                            67
                                                                                        Instruction book
       Cable section    30 °C        40 °C        45 °C        50 °C        55 °C
       120 mm²          < 346 A      < 315 A      < 301 A      < 284 A      < 263 A
       150 mm²          < 399 A      < 363 A      < 347 A      < 327 A      < 303 A
       185 mm²          < 456 A      < 415 A      < 397 A      < 374 A      < 347 A
       240 mm²          < 538 A      < 490 A      < 468 A      < 441 A      < 409 A
       300 mm²          < 621 A      < 565 A      < 540 A      < 509 A      < 472 A
      Maximum allowable current in function of the ambient temperature for installation method F
      (Single-core cables with 3 loaded conductors and maximum conductor temperature 90 °C)
       Cable section    30 °C        40 °C        45 °C        50 °C        55 °C
       25 mm²           < 135 A      < 123 A      < 117 A      < 110 A      < 103 A
       35 mm²           < 169 A      < 154 A      < 147 A      < 139 A      < 128 A
       50 mm²           < 207 A      < 188 A      < 180 A      < 170 A      < 157 A
       70 mm²           < 268 A      < 244 A      < 233 A      < 220 A      < 204 A
       95 mm²           < 328 A      < 298 A      < 285 A      < 269 A      < 249 A
       120 mm²          < 383 A      < 349 A      < 333 A      < 314 A      < 291 A
       150 mm²          < 444 A      < 404 A      < 386 A      < 364 A      < 337 A
       185 mm²          < 510 A      < 464 A      < 443 A      < 418 A      < 388 A
       240 mm²          < 607 A      < 552 A      < 528 A      < 498 A      < 461 A
       300 mm²          < 703 A      < 639 A      < 611 A      < 576 A      < 534 A
       400 mm²          < 823 A      < 749 A      < 716 A      < 674 A      < 625 A
68                                                                                        9829 3178 62
Instruction book
9829 3178 62                                                                                             69
                                                                                          Instruction book
      Note: The above table has been prepared for user convenience. Only the latest editions of the UL
      standard and its amendment(s) are to be considered as the official documents.
       Ampacity          Size of PE
       < 90 A            8 AWG
       < 125 A           6 AWG
       < 150 A           6 AWG
       < 200 A           4 AWG
       < 225 A           2 AWG
       < 400 A           1/0 AWG
       < 500 A           1/0 AWG
       < 800 A           2/0 AWG
       < 1000 A          3/0 AWG
             Note: The above table has been prepared for user convenience. Only the latest editions of
             the UL standard and its amendment(s) are to be considered as the official documents.
70                                                                                          9829 3178 62
Instruction book
        Always check the voltage drop over the cable (less than 5 % of the nominal voltage is
        recommended).
4.5 Pictographs
Other locations
9829 3178 62                                                                                        71
                                                                                                 Instruction book
      Reference         Description
      13                Automatic condensate drain
      14                Automatic condensate drain for optional oil/water separator (type OSD)
      15                Manual condensate drain
      16                Stop the compressor before maintenance or repair
      17                Warning: under tension
      18                Read Instruction book before starting the compressor
      19                Switch off the voltage and depressurize the compressor before maintenance or repair
      20                Before connecting the compressor electrically, consult the Instruction book for the motor
                        rotation direction
      21                Torques for steel (Fe) or brass (CuZn) bolts
      22                Consult the Instruction book before greasing
      23                Switch off the voltage before removing the protecting cover inside the electric cabinet
      24                Oil the gaskets, screw on the filters and tighten by hand (approx. one half turn)
      25                Consult the Instruction book before maintenance or repair
      26                Cooling water inlet
      27                Cooling water outlet
      28                Oil outlet
General
      Cooling water needs to fulfill requirements in order to avoid problems of scaling, fouling,
      corrosion or bacterial growth. No general recommendation can encompass the effects of all
      combinations of the various compounds, solids and gases typically found in cooling water in
      interaction with different materials. Therefore the recommendations formulated in our cooling
      water specifications are a general guide line for acceptable coolant quality. However, where strict
      limits apply, a statement is made in the specification.
      The water requirements refer to untreated water. When water is treated, some parameters will
      change. Water treatments should be carried out by a specialized water treatment company,
      taking the responsibility for the performance of the treated cooling water and the compatibility
      with the materials in the cooling circuit. This includes not only the selection of the appropriate
      additives, but also the correct application, monitoring of concentrations and properties, prevention
      of sludge formation and maintenance of the system. This applies also to treatment with anti-
      freeze products. They should be provided with suitable stabilizers and inhibitors.
      Specifications also depend on the criteria mentioned below:
        • the type of cooling circuit:
              • open
                   • Single Pass
72                                                                                                 9829 3178 62
Instruction book
• closed loop
         Reference                 Description
         (1)                       Machine
         (2)                       Heat exchanger
         (3)                       Cooling tower
         (4)                       Make up water
         (5)                       Blowdown
         (6)                       Standard Atlas Copco specification
             • the application:
                  • standard (max water temperature 65°C / 149°F at the outlet)
                  • Energy Recovery (water temperature up to 95°C / 203°F)
        A full instruction for handling cooling water data is available at Atlas Copco.
        In case water is not in line with recommended values or if any doubt, please refer to Atlas Copco.
Technical specifications
9829 3178 62                                                                                                        73
                                                                                                           Instruction book
                       Parameter                       Remarks
       1               pH                              For stainless steel systems without other materials, pH can be
                                                       down to 6.
                                                       For closed loop systems, higher pH values are possible
       2               Conductivity                    Conductivity and TDS linked with conversion factor (theoretical
                                                       factor possible, but practical determination recommended at
                                                       least once)
       6               Ryznar Stability Index (RSI) Recommended actions : see table for RSI
       7               Chlorine                        or shock treatment max. 2 ppm for 30 min/day
       8               Chlorides                       (*) Limit 200 ppm applicable when RSI < 5.6 or RSI > 7.5
       10              Sulphates                       Rejection < 2000 ppm. To be measured for calculating RSI.
       11              Chemical Corrosion Index        Index = (Chlorides + Sulphates + Nitrates) / (M-Alkalinity) (all
                                                       expressed in meq/l)
       15              Ammonium                        limit not applicable for Cu-free systems
       16              Suspended Solids (max           No particles > 10µ allowed. (Particles <0.5µ not considered).
                       10µ)
       18              Biology                         Anaerobic biology in closed system never allowed.
74                                                                                                           9829 3178 62
Instruction book
        on different materials, but the equilibrium of the water (scaling or corrosive) is only determined by
        its actual pH value and by the saturation pH value (pHs).
        The saturation pH value is determined by the relationship between the calcium hardness, the
        total alkalinity, the total solids concentration and the temperature.
        The Ryznar Stability Index is calculated as follows :
        RSI = 2*pHs - pH
         Symbol            Explanation
         pH                Measured pH (at room temperature) of water sample
         pHs               pH at saturation
         Symbol    Calculation
         A         (10log(TDS) - 1) / 10
         B         13.12 x 10log(°C+273) + 34.55
         C         10
9829 3178 62                                                                                                 75
                                                                                              Instruction book
76                                                                                              9829 3178 62
Instruction book
9829 3178 62                                                                            77
                                                                                             Instruction book
5 Operating instructions
Warning
Outdoor/altitude operation
       If the compressor is installed outdoors or if the air inlet temperature can be below freezing point,
       precautions must be taken. In this case, and also if operating at high altitude, consult Atlas
       Copco.
Moving/lifting
       The compressor can be moved by a lift truck using the slots in the frame. Make sure that the
       forks protrude from the other side of the frame. The compressor can also be lifted after inserting
       beams in the slots. Make sure that the beams cannot slide and that they protrude from the frame
       equally. The chains must be held parallel to the bodywork by chain spreaders in order not to
       damage the compressor. The lifting equipment must be placed in such a way that the
       compressor is lifted perpendicularly. Lift gently and avoid twisting.
78                                                                                             9829 3178 62
Instruction book
General preparations
         Step          Action
         1             Install the compressor, see the sections Dimension drawing, Installation proposal and
                       Main fuses and supply cables.
         2             Stick labels near the control panel to warn the operator that:
                          • the compressor may start automatically after a voltage failure
                          • the compressor is automatically started and stopped
                          • the compressor may be remotely controlled
         3             A number of VCI (Volatile Corrosion Inhibitor) plates are provided inside the bodywork to
                       protect the compressor against corrosion. Remove the plates.
         4             If the compressor has not run for the past 6 months, it is required to improve the
                       lubrication of the compressor element before starting. Fill up the compressor element as
                       described in section Oil change (paragraph: Filling the compressor element with oil).
         5             Check the oil level. The oil level should reach the bottom of the oil filler neck (FC).
                       The minimum level should reach the oil sight-glass (GI) when the compressor is
                       stopped.
                       If needed, top up the oil.
                       Take care that no dirt drops into the oil system.
                       Refit and tighten the filler plug (FC).
Transport fixtures
9829 3178 62                                                                                                     79
                                                                                                     Instruction book
       Step               Action
       1                  The gear casing, motor support and air receiver supports are secured to the frame,
                          immobilizing the vibration dampers during transport.
       2                  Remove the bushes (1) from the gear casing supports and the motor support.
       3                  Remove the brackets fitted next to the air receiver supports.
Electric cabinet
       Step               Action
       1                  Check that the electrical connections correspond to the local codes. The installation
                          must be earthed and protected by fuses in all phases. An isolating switch must be fitted.
       2                  Check the wires on the transformers for correct connection.
       3                  Check the setting of the circuit breakers.
Water circuit
       Step               Action
       1                  Check that the cooling water drain valves (customer’s installation) in the inlet and outlet
                          lines are closed.
       2                  Check that the water shut-off valves (customer’s installation) are open.
       3                  Open the water regulating valve and check for water flow.
Start up
       Step               Action
       1                  Close the drain valves (see the section Cooling and condensate system).
       2                  Switch on the voltage.
       3                  On air-cooled compressors, check the rotation direction of the fan motor. The fan is
                          visible through the grating in the air inlet panel (see section Dimension drawing). The
                          correct rotation direction is indicated by arrows on the fan inlet plate.
                          On Full-Feature compressors, open the door of the dryer compartment and check the
                          rotation direction of the fan motors of the condenser. The correct rotation direction is
                          indicated by an arrow.
       4                  If the rotation direction is wrong, press the emergency stop button, switch off the voltage
                          and reverse two incoming electric lines.
                          If the rotation direction of the fan motor is wrong, consult your Atlas Copco customer
                          centre.
       5                  Run the compressor for a few minutes and check that it is operating normally.
80                                                                                                     9829 3178 62
Instruction book
Warning
Control panel
9829 3178 62                                                                                                    81
                                                                                                Instruction book
Procedure
       Step            Action
       1               Switch on the voltage. The voltage sign (5) lights up.
       2               Close the condensate drain valves.
       3               Open the air outlet valve.
       4               Check the oil sight-glass. Minimum level should reach the oil sight-glass when the
                       compressor is stopped.
       5               Open the water shut-off valves and the water regulating valve.
5.3 Starting
Warning
Control panel
82                                                                                                9829 3178 62
Instruction book
Procedure
         Step            Action
         1               Press the start button. The compressor starts running in unloaded condition. The
                         operation sign (4) lights up.
         2               Approx. 10 seconds later (programmable), the compressor starts running loaded.
                         The status icon on the display of the controller changes from the running unloaded icon
                         to the running loaded icon.
         3               On water-cooled compressors, regulate the cooling water flow with the compressor
                         running loaded. Adjust the water flow to obtain the most suitable air temperature at the
                         outlet of the compressor elements. The temperature must be between 2 and approx. 7
                         ˚C (4 and approx. 13 ˚F) above the relevant temperature in the diagram.
9829 3178 62                                                                                                   83
                                                                                                Instruction book
       Reference       Name
       A               Air inlet temperature in ˚C
       B               Condensation temperature in ˚C
       C               Effective working pressure in bar
       D               Relative air humidity in %
Warning
                       The operator should immediately stop the machine in case of oil leaks internally in the
                       machine as well as externally and consult a competent technician to resolve the cause.
                       The machine should not be restarted before the problem has been remedied.
                       The load cycle of the compressor must be limited to maximum two cycles per minute.
Description
84                                                                                                9829 3178 62
Instruction book
          4. On Full-Feature compressors, regularly check the pressure dew-point on the display of the
             control panel. The pressure dew-point will deviate from nominal if the air inlet conditions or
             volume differ from nominal.
Warning
                           Before carrying out any maintenance, repair work or adjustment, stop the compressor,
                           press the emergency stop button and switch off the voltage. Close the air outlet valve
                           and open the manual condensate drain valve.
9829 3178 62                                                                                                    85
                                                                                              Instruction book
Description
        1. Regularly check the display for readings and messages. Normally, the main display is
           shown.
        2. Always check the display and remedy the trouble if the warning sign (2) is alight or blinks.
           The display will show a service message if a service plan interval has been exceeded or if a
           service level for a monitored component has been exceeded. Carry out the service actions
           of the indicated plans or replace the component and reset the relevant timer.
           Regularly check the Inputs and Outputs menus for a quick look at the compressor status.
86                                                                                                9829 3178 62
Instruction book
Description
Control panel
        General
        Normally, the compressor runs in automatic operation, i.e. the electronic regulator loads, unloads,
        stops and restarts the compressor automatically. Operation sign (4) is then alight.
        If required, the compressor can be unloaded manually. In this case, the compressor is switched
        out of automatic operation i.e. the compressor remains running unloaded unless it is loaded
        again manually.
        Manual unloading
9829 3178 62                                                                                                  87
                                                                                               Instruction book
      To unload the compressor manually, touch the manual load/unload button (1) on the display.
      When the button is touched, the compressor starts running unloaded and the operation sign (4)
      fades. The manual load/unload icon starts blinking.
      Manual loading
      To put the compressor back into automatic operation, press the manual load/unload button (1) on
      the display. When the button is touched, the operation sign (4) lights up and the compressor
      starts running loaded in case the air net pressure drops below the programmed level. The
      manual load/unload icon darkens.
                       If the Load or Unload icons are not displayed on the bottom line of the screen, make
                       sure to return to the Main screen first.
5.7 Stopping
88                                                                                               9829 3178 62
Instruction book
Procedure
                       Frequently stopping the compressor using the emergency stop button may damage the
                       compressor. Only use the emergency stop button in case of emergency.
         Step             Action
         1                Press stop button (6). The compressor will coast down and then stop.
         2                To stop the compressor in case of emergency, press the emergency stop button. The
                          warning sign (2) starts flashing. After remedying the trouble, unlock the emergency stop
                          button by pulling it back.
         3                Close the air outlet valve.
         4                Open the condensate drain valves.
         5                Switch off the voltage.
         6                On water-cooled compressors, close the water shut-off valves.
         7                On water-cooled compressors, if the compressor is installed in a room where freezing
                          temperatures are expected, drain the cooling system by opening the drain valves in the
                          water inlet and outlet pipes (customer's installation).
         Step             Action
         1                Stop the compressor and close the air outlet valve.
         2                Switch off the voltage and disconnect the compressor from the mains.
         3                Depressurize the compressor by opening the drain valve and loosening the oil filler plug
                          one turn.
         4                Shut off and depressurize the part of the air net which is connected to the outlet valve.
                          Disconnect the compressor air outlet pipe from the air net.
         5                Drain the oil and condensate circuits.
                          On water-cooled compressors, drain the water circuits.
         6                Disconnect the compressor condensate piping from the condensate drain net.
         7                On water-cooled compressors, disconnect the cooling water pipes from the compressor.
9829 3178 62                                                                                                     89
                                                                                           Instruction book
Instructions
        1. This vessel may only be used for separating oil from compressed air and this within the
           limits of pressure and temperature as specified on the nameplate.
        2. A safety valve must be installed by the user to protect the vessel against overpressure. The
           protection must ensure that the pressure will not permanently exceed the maximum
           allowable working pressure.
        3. The user must take precautions to ensure that the vessel operates in the temperature range
           between -10 °C (14 °F) and 120 °C (248 °F).
        4. To guarantee a proper operation, the intake air must be filtered.
        5. A draining valve must be foreseen by the user to protect the vessel against overfilling by oil.
        6. The vessel must be mounted in an installation that will operate at atmospheric pressure.
        7. The user must avoid storing/installing the separator in badly ventilated rooms, near heating
           sources or inflammable substances. The user must protect the vessel by a casing in case of
           outdoor erection.
        8. Pipe connections must be mounted tension free by means of flexible couplings.
        9. The vessel must be mounted with the foreseen attachment points. In areas with risk of
           earthquakes or installations subjected to reaction forces and moments of inertia from
           supporting constructions, anchor pads must be used.
       10. The vessel must be foreseen with an earthing.
       11. The user must make the customer aware of possible high surface temperature of the vessel.
       12. The user must provide the customer with instructions regarding safe emptying, cleaning,
           inspecting (also internally), maintenance and daily operation.
       13. After the vessel has been opened, the original bolts must be used for closing. Herewith the
           maximum torque has to be respected.
       14. No modifications may be carried out on the vessel by welding, drilling or by any other way of
           mechanical operation, without written permission of the manufacturer.
       15. This vessel was designed and manufactured respecting the functional specifications. An
           inspection of the inside is for this reason not really necessary as long as the vessel is used
           within the limits and applications for which it has been designed. However it is possible that
           local legislation requires an internal inspection.
90                                                                                           9829 3178 62
Instruction book
6 Maintenance
Warning
General
        When servicing, replace all removed gaskets, O-rings and washers.
9829 3178 62                                                                                                               91
                                                                                             Instruction book
                      When operating in a dusty atmosphere, inspect the air filters more frequently.
                      Always use Atlas Copco filters.
                      The separator element must also be replaced when the pressure difference over the
                      element exceeds 0.8 bar (12 psi). Check the pressure drop when the compressor is
                      running loaded and preferably with a stable working pressure.
                      Damaged flexibles must be replaced immediately.
Service agreements
      Atlas Copco Customer Centres have a range of service agreements to suit your needs:
         •   An Inspection Plan
         •   A Preventive Maintenance Plan
         •   A Warranty+ Plan
         •   A Total Responsibility Plan
      Contact your Customer Centre to set up a tailor-made service agreement. It will ensure optimum
      operational efficiency, minimize downtime and reduce the total life cycle costs.
Service plan
      A number of service operations are grouped (called Level A, Level B, Level C...). Each level
      stands for a number of service actions to be carried out at the time intervals programmed in the
      Elektronikon regulator.
      When a level is reached, a message will appear on the screen. After carrying out all service
      actions, the interval timers must be reset using the “Reset” key in the “Service” menu. Consult
      your Atlas Copco Service Centre.
Foodgrade oil
      Foodgrade oil is a unique high quality synthetic lubricant, specially created for oil-injected screw
      compressors that provide air for the food industry. This lubricant keeps the compressor in
      excellent condition. Foodgrade oil can be used for compressors operating at ambient
      temperatures between 0 ˚C (32 ˚F) and 40 ˚C (104 ˚F).
92                                                                                             9829 3178 62
Instruction book
Important
Important
Warning
9829 3178 62                                                                                             93
                                                          Instruction book
94                                                          9829 3178 62
Instruction book
Procedure
         Step       Action
         1          Run the compressor until warm.
                    Stop the compressor.
                    Close the air outlet valve.
                    Switch off the voltage.
                    Wait a few minutes.
                    Depressurize by unscrewing the plug only one turn to permit any pressure in the system
                    to escape.
         2          Loosen the vent plugs on top of the oil coolers.
         3          Drain the oil by removing the drain plugs.
                    Plugs are fitted on the:
                       • Air receiver / Oil separator with drain point
                       • Element outlet
                       • Drive motor
                       • Gearbox
                       • Oil coolers of air-cooled compressors
                       • Oil filter housing
                       • Hose between the oil filter housing and oil coolers of water-cooled compressors
                    Tighten the plugs after draining.
         4          Remove the filler plug.
                    Fill the air receiver / oil separator with oil until the level reaches the filler opening.
                    Refit and tighten the plug.
                    Tighten the vent plug of the oil cooler.
         5          Disconnect the air inlet hose from the inlet valve.
                    Pour 10 liter of oil into the compressor stage.
                    Reinstall the air inlet hose.
         6          Run the compressor for a few minutes to allow the oil cooler by-pass valve to open.
                    Stop the compressor.
                    Wait a few minutes.
         7          Depressurize the system by unscrewing the plug only one turn to permit any pressure in
                    the system to escape.
                    Remove the plug.
                    Fill the air receiver / oil separator with oil until the level reaches the filler opening.
                    Tighten the filler plug.
         8          After carrying out all service actions in the relevant “Service Plan”, reset the service
                    warning.
                    Refer to the Service menu section.
Warning
                    Stop the compressor and switch off the voltage. The operator must apply all relevant
                    Safety precautions.
9829 3178 62                                                                                                     95
                                                                                                     Instruction book
Procedure
        Step              Action
        1                 Stop the compressor, close the air outlet valve and switch off the voltage. Wait a few
                          minutes and depressurize the air receiver by unscrewing the oil filler plug (of the air
                          receiver) only one turn to permit any pressure in the system to escape.
        2                 Use an oil pan to avoid possible oil spillage. Unscrew the oil filters only one turn and
                          wait a few minutes to let the oil of the filter flow back into the oil separator. Remove the
                          oil filters.
        3                 Clean the filter seats on the manifold. Oil the gaskets of the new filters and screw the
                          filters into place until the gaskets contact their seats. Then tighten with a maximum
                          torque of 10 Nm.
        4                 Tighten the oil filler plug (of the air receiver).
        5                 Reset the service warning after carrying out all service actions in the relevant Service
                          Plan. Refer to the Service menu section.
96                                                                                                     9829 3178 62
Instruction book
Procedure
         Step              Action
         1                 Stop the compressor, close the air outlet valve and switch off the voltage. Wait a few
                           minutes and depressurize the air receiver by unscrewing the oil filler plug (of the air
                           receiver) only one turn to permit any pressure in the system to escape.
         2                 Unscrew the bolts fixing the small vessel covers marked to have an oil separator
                           element below them.
         3                 Remove the oil separator cartridges and replace them by new cartridges. Mind correct
                           angular positioning of the cartridges.
         4                 Tighten the oil filler plug (of the air receiver).
         5                 Reset the service warning after carrying out all service actions in the relevant Service
                           Plan. Refer to the Service menu section.
Procedure
        Run the compressor, e.g. once a week, until warm plus 5–10 minutes. Load and unload the
        compressor a few times to operate the components of the unloading/loading system.
                           If the compressor is going to be stored without running from time to time, protective
                           measures must be taken. Consult the Atlas Copco Customer Centre.
General
        Service kits comprise all parts needed for servicing components and offer the benefits of genuine
        Atlas Copco parts while keeping the maintenance budget low. All service tools are in IQ2
        Inteliquater and the Business Portal.
9829 3178 62                                                                                                         97
                                                                                         Instruction book
7 Integrated dryer
7.1 Introduction
Description
      The air dryer removes moisture from compressed air by cooling the air to near freezing point.
      This causes water to condense. The condensate is automatically drained. The air is warmed up
      before leaving the dryer (approx. 5 ˚C (9 ˚F) below the incoming air temperature).
      The air dryer cools down the compressed air to the preset temperature. Any formed condensate
      is automatically drained.
      The electronic regulator keeps the pressure dew-point stable at no load by opening or closing the
      solenoid valve of the hot-gas by-pass.
      On air-cooled dryers, the condenser has a cooling fan controlled by a pressure sensor.
      Water-cooled dryers have a water regulating valve in the water outlet of the condenser.
      The descriptions mentioned in this book are valid for both air-cooled and water-cooled dryers.
General view
Air-cooled dryer
98                                                                                         9829 3178 62
Instruction book
Water-cooled dryer
Position of components
Water-cooled dryer
9829 3178 62                                  99
                                                           Instruction book
Air-cooled dryer
      1   Heat exchanger
      2   On air-cooled dryers, cooling fan(s)
          On water-cooled dryers, water regulating valve
      3   On air-cooled dryers, air-cooled condenser
          On water-cooled dryers, water-cooled condenser
      4   Sight-glass
      5   Refrigerant compressor
      6   Liquid separator
      7   Thermostatic expansion valve
      8   Refrigerant dryer/filter
      9   Non-return valve
Flow diagram
Air-cooled dryer
Water-cooled dryer
      Reference   Name
      301a        Air/air heat exchanger
      301b        Air/refrigerant heat exchanger
      111         Condensate separator
      410         Non-return valve
         Reference         Name
         403               Air-cooled condenser (air-cooled version)
                           Water-cooled condenser (water-cooled version)
         408               Fan blower (air-cooled version)
                           Water regulating valve (water-cooled version)
         407               Thermostatic expansion valve
         90                Pressure shut-down switch
         405               Refrigerant dryer/filter
         401               Liquid separator
         412               Hot-gas by-pass valve
         402               Refrigerant compressor
         411               Solenoid valve
         406               Sight-glass
         89, 90            Temperature sensor
         90                Pressure sensor
         413               Automatic drain
      refrigerant contains moisture, indicating that the refrigerant dryer/filter (405) needs to be
      replaced.
Description
      The condenser pressure must be kept as constant as possible to obtain stable operation,
      therefore:
         • For air-cooled versions, the regulator stops and starts the cooling fans
         • For water-cooled versions, the water regulating valve in the water outlet regulates the
           cooling water flow
        When at partial or no load the dew-point pressure stays below the set-point, the regulator opens
        solenoid valve (411) and hot, high-pressure gas is fed through hot-gas by-pass valve (412) to the
        evaporator circuit to prevent the evaporator temperature from dropping below 0 ˚C (32 ˚F).
Description
         1               Inlet
         2               Supply line
         3               Pilot valve
         4               Diaphragm
         5               Sensor
         6               Collector
         7               Valve seat
         8               Outlet
      The condensate enters the electronic water drain via inlet (1) and accumulates in collector (6). A
      capacitive sensor (5) continuously measures the liquid level.
      The pilot valve (3) is activated as soon as the collector is filled up to a certain level. Diaphragm
      (4) opens outlet (8), discharging the condensate.
      When the collector has been emptied, the outlet closes quickly without wasting compressed air.
      When the controller registers a malfunction, the red alarm LED on the control panel of the
      electronic water drain starts flashing, a warning appears on the display of the regulator and the
      electronic drain valve will automatically change to the alarm mode, opening and closing the valve
      according to a sequence as shown below . This condition continues until the fault is remedied. If
      the fault is not remedied automatically, maintenance is required.
Control panel
      Briefly press the TEST button and check that the valve opens for condensate discharge.
      Checking the alarm signal
         • Press and hold the test button for at least 1 minute.
         • Check that the alarm LED flashes.
Dryer protection
        The high-pressure shut-down switch stops the compressor motor when the pressure in the
        refrigerant circuit reaches the upper set-point of the switch.
        After tripping:
           • The switch must be reset manually by pressing its reset knob and by pressing the Cancel/
             escape key on the controller.
        The compressor motor has a built-in thermic protection. If the thermic protection trips, the
        compressor motor will be stopped. The compressor will restart when the motor windings have
        cooled down, which may take up to 3 hours.
7.6 Regulation
General description
        The electronic regulator automatically controls the dryer, i.e.:
           • keeps the pressure dew-point stable
           • stops the dryer whenever necessary
           • restarts the dryer when required
        In general, the regulator has following functions:
           • controlling the dryer
           • protecting the dryer
Important
Safety precautions
       When handling refrigerant R404A or R410A (refer to dryer data plate), all applicable safety
       precautions must be observed. The following points are stressed:
          • Contact of refrigerant with the skin will cause freezing. Special gloves must be worn and, if
            there is contact with the skin, the skin should be rinsed with water. On no account may
            clothing be removed.
          • Fluid refrigerant will also cause freezing of the eyes; therefore, safety glasses must be worn.
          • Refrigerants R404A and R410A are poisonous. Do not inhale refrigerant vapors. Check that
            the working area is adequately ventilated.
       When removing the side panels of the dryer, be aware that internal elements such as the pipes
       can reach a temperature of 120 ˚C (248 ˚F). Therefore, wait until the dryer has cooled down
       before removing the side panels.
       Before starting any maintenance or repairs, switch off the voltage. Isolate the dryer from the air
       net.
Local legislation
       Local legislation may impose that:
          • Work on the refrigerant circuit of the cooling dryer or on any equipment which influences its
            function must be carried out by an authorized control body.
          • The installation should be checked once a year by an authorized control body.
Service agreements
       Customer Centres have a range of service agreements to suit your needs:
          • An Inspection Plan.
          • A Preventive Maintenance Plan.
          • A Total Responsibility Plan.
       Contact your Customer Centre to arrange a tailor-made service agreement. This will ensure
       optimum operational efficiency, minimize downtime and reduce the total life cycle costs.
General
        The following remarks should be kept in mind:
             • Keep the dryer clean.
             • On air-cooled dryers, brush or blow off the finned surface of the condenser regularly.
               On water-cooled dryers, regularly check for water leaks.
             • Inspect and clean the electronic water drain once a year .
Attention
                            Use only authorized parts. Any damage or malfunction caused by the use of
                            unauthorized parts is not covered by Warranty or Product Liability.
                            Apply all relevant Safety precautions.
                            Before carrying out any maintenance or repairs on the dryer, stop the dryer and switch
                            off the voltage.
                            Open the isolating switch to prevent an accidental start.
                            Isolate the dryer from the air net.
Warning
                          Stop the compressor, close the air outlet valve, press the emergency stop button and
                          switch off the voltage. The operator must apply all relevant Safety precautions.
Procedure
         Step             Action
         1                Remove the filter elements (1).
         2                Fit the new filter elements (1).
         3                Reset the service warning after carrying out all service actions in all applicable service
                          plans. Refer to the service menu section of the regulator.
8.2 Coolers
Warning
                          Stop the compressor, press the emergency stop button and switch off the voltage. The
                          operator must apply all relevant Safety precautions.
Procedure
         Step            Action
         1               Open the service door at the cooler side.
         2               Remove the service panel (1) at the cooler side.
         3               Remove any dirt form the coolers with a fibre brush, brush in the direction of the fins.
                         Also remove any dirt from the fans.
         4               Clean the coolers with an air jet in the reverse direction to normal flow. Use low
                         pressure air; if necessary, the pressure may be increased up to 6 bar (e) (87 psig).
         5               If it is necessary to clean the coolers with a cleaning agent, consult Atlas Copco.
         6               Mount the service panel.
         7               Close the door.
Warning
                         Stop the compressor and switch off the voltage. The operator must apply all relevant
                         Safety precautions.
Testing
9 Problem solving
Warning
                            Before carrying out any maintenance, repair work or adjustment, stop the compressor,
                            press the emergency stop button and switch off the voltage. Close the air outlet valve
                            and open the manual condensate drain valves.
                            Open and lock the isolating switch.
                            The operator must apply all relevant Safety precautions.
Control panel
         Reference          Name
         1                  Start button
         2                  Stop button
         3                  Warning sign
         4                  Service sign
         5                  Operation sign
         6                  Voltage sign
      Multiple shut-down
      If there are multiple sequential failures with short time intervals on a specific shut-down functionality,
      consult your Atlas Copco Customer Centre.
10 Technical data
Important
                   The readings are valid when operating under reference conditions. See the
                   section Reference conditions.
                   Normally the main display is shown, indicating the actual air outlet pressure and
                   the actual compressor status. The arrow down key allows the operator to call up
                   other information such as actually measured pressures and temperatures.
Important readings
Reference conditions
10.3 Limits
Limits
                                                                                              Q41, Q42
             Model             Working pressure (bar)          Supply voltage (V)   Q40 (A)
                                                                                                (A)
            GA 90+                      5.5                           400             10        1.3
            GA 90+                      7.5                           400             8         1.9
            GA 90+                      8.5                           400             8         1.9
            GA 90+                       10                           400             8         1.9
            GA 110                      5.5                           400             12        1.9
            GA 110                      7.5                           400             8         1.9
            GA 110                      8.5                           400             8         1.9
            GA 110                       10                           400             8         1.9
            GA 132                      5.5                           400             12        1.9
            GA 132                      7.5                           400             10        1.3
                                                                                       Q41, Q42
          Model          Working pressure (bar)       Supply voltage (V)    Q40 (A)
                                                                                         (A)
          GA 132                   8.5                       400              8          1.9
          GA 132                   10                        400              8          1.9
          GA 160                   7.5                       400              12         1.9
          GA 160                   8.5                       400              10         1.3
          GA 160                   10                        400              8          1.9
                                                                                        Q41, Q42
           Model          Working pressure (psi)      Supply voltage (V)     Q40 (A)
                                                                                          (A)
          GA 90+                   75                        380               9.5        1.45
          GA 90+                   100                       380               6.7          2
          GA 90+                   125                       380               6.7          2
          GA 90+                   150                       380               6.7          2
          GA 90+                   75                        440               9.5        1.45
          GA 90+                   100                       440               6.7          2
          GA 90+                   125                       440               6.7          2
          GA 90+                   150                       440               6.7          2
          GA 90+                   75                        460               9.5        1.45
          GA 90+                   100                       460               6.7          2
          GA 90+                   125                       460               6.7          2
          GA 90+                   150                       460               6.7          2
                                                                             Q41, Q42
             Model   Working pressure (psi)   Supply voltage (V)   Q40 (A)
                                                                               (A)
            GA 110            75                     380             12         2
            GA 110            100                    380             6.7        2
            GA 110            125                    380             6.7        2
            GA 110            150                    380             6.7        2
            GA 110            75                     440             12         2
            GA 110            100                    440             6.7        2
            GA 110            125                    440             6.7        2
            GA 110            150                    440             6.7        2
            GA 110            75                     460             12         2
            GA 110            100                    460             6.7        2
            GA 110            125                    460             6.7        2
            GA 110            150                    460             6.7        2
            GA 132            75                     380             12         2
            GA 132            100                    380             9.5       1.45
            GA 132            125                    380             6.7        2
            GA 132            150                    380             6.7        2
            GA 132            75                     440             12         2
            GA 132            100                    440             9.5       1.45
            GA 132            125                    440             6.7        2
            GA 132            150                    440             6.7        2
            GA 132            75                     460             12         2
            GA 132            100                    460             9.5       1.45
            GA 132            125                    460             6.7        2
            GA 132            150                    460             6.7        2
            GA 160            100                    380             12         2
            GA 160            125                    380             9.5       1.45
            GA 160            150                    380             6.7        2
            GA 160            100                    440             12         2
            GA 160            125                    440             9.5       1.45
            GA 160            150                    440             6.7        2
            GA 160            100                    460             12         2
            GA 160            125                    460             9.5       1.45
            GA 160            150                    460             6.7        2
No. 9829 3178 62 / 2019 - 12 - Printed in Atlas Copco Wuxi. All rights reserved. Designs and specifications are subject to change without notice or obligation.