Screenshots of SAFE

Rebars strips in X and Y direction (2d)

Rebars Strip in (3d)


Soil pressure diagram on footing based on the soil report of having
an allowable soil pressure of 180 kPa

Soil pressure diagram on footing based on the allowable transient


soil pressure bearing capacity of 240 kPa
Footing slab design based on rebar strips at bottom layer

Footing slab design based on rebar strips at top layer


Square footings color assignments based on their thickness and
width

Manual Calculation using MS Excel

Footing 6 and 7 are the critical footings based on the ETABS result
for the base shear at the ground level column since it carries most
of the loads of the structure and is the center column for the 4
storey building with roof deck

Manual design computation for Critical footing (thickness and


width)

Footing 6 :

Assumption width:

B=
√ Allowble Point load
SBC

B=
√ 1170.5kN
180 kPa
=1.95 m

Calculating for the depth of the footing:


Pu 2
( B −( Column width+ depth )2) = 0.75 √ 21 ( 4 ( column width+ depth ) ) (1000)(depth)
B
2
3

1784.43 kN
2
( (2 .6 m)2−( 6 0 0 mm+ depth )2 ) = 0.75
3
√ 21 MPa ( 4 ( 6 0 0 mm+ depth ) ) (1000)(depth)
(2 . 6 m)

depth=613.873 mm

Solving for the thickness:


thickness=depth+ concrete cover+dia . of main ¯¿

thickness=613.873 mm+75 mm+25 mm=713.873 ≈720 mm

Checking the adequacy of the assumed width using CSI SAFE:

If footing width carries SBC than the Allowable SBC, increase the dimension
size

Footing width based on the Allowable SBC = 2900mm

Check for the transient SBC, Transient SBC = 240 kPa

If footing width carries Transient SBC, increase the dimension size

Footing width Based on Transient SBC = 3000mm

Final footing size (square footing) = 3.25 meters