PowerFlex 753 AC Drive Specifications
PowerFlex 753 AC Drive Specifications
Designed for general purpose applications, the PowerFlex 753 AC drive Isolation Transformers and Input
Line Reactors are available.
offers multiple options and features along with the added benefit of See pages 138…148.
simple integration. The PowerFlex 753 offers standard built-in I/O, making
it an ideal solution for OEMs and system integrators looking to reduce
Integral EMC Filter. External
engineering costs, deliver machines to market faster and meet end-user Common Mode Choke is available.
demand for more productive and safer machines. See page 130 and 1321 Power
Conditioning Products Technical
Data, publication 1321-TD001,
for additional information.
PowerFlex 753 Drive at a Glance
Ratings
200…240V 0.37…132 kW/0.5…200 Hp / 2.2…477 A
1
380…480V 0.75…270 kW / 1.0…400 Hp / 2.1…477 A
575…600V 1.0…300 Hp / 1…289 A
690V 7.5…250 kW / 12…263 A
Motor Control • V/Hz Control • Vector Control with FORCE Technology
• Sensorless Vector Control (with and without encoder)
• Interior Permanent Magnet
Enclosures • IP00/IP20, NEMA/UL Type Open • IP54, NEMA/UL Type 12
2
• Flange Mount
Safety • Safe Torque Off SIL3, PLe, CAT 3 • Safe Speed Monitor SIL3, PLe, CAT 4
Additional • DeviceLogix • Pump Jack and Pump Off for oil well 3
Features • Predictive Diagnostics applications
• Adjustable Voltage Control • Pump and Traverse for fibers applications 4
• Three option slots for I/O, feedback, safety, • Conformal Coating
auxiliary control power, communications • DC Link Choke
(1)
• Indexing • Automatic Device Configuration
2 Multiple communication options for industrial networks available. See page 126 for additional
options.
3 Embedded I/O: 3 digital inputs, 1 relay output, 1 transistor output, 1 analog input, 1 analog output,
and 1 PTC input. See page 126 for additional options.
4 Integral brake resistor on Frames 1…5, optional on Frames 6…7. Resistors are available.
See page 136.
Flange Mount
Frame H W D1 D2 Weight(1)
2 481.8 (18.97) 206.2 (8.12) 148.3 (5.84) 63.7 (2.51) 8 (17)
3 515 (20.28) 260 (10.24) 127.4 (5.02) 84.6 (3.33) 12 (26)
4 535 (21.06) 292 (11.5) 14 (30)
5 611 (24.06) 340 (13.39) 20 (45)
6 665.5 (26.2) 308 (12.13) 208.4 (8.2) 138 (5.43) 38 (84)
7 875 (34.45) 430 (16.93) 96 (212)
(1) Weights are approximate. Refer to 750-TD001, the PowerFlex 750-Series Technical Data, for detailed weight information.
(1) Includes a 1202-C30 interface cable (3 m/9.8 ft) for connection to drive.
(2) Required only when HIM is used as handheld or remote.
(3) Required in addition to 20-HIM-H10 for distances up to a total maximum of 10 m (32.8 ft).
(1) Requires a Communication Carrier Card (20-750-20COMM or 20-750-20COMM-F1). Refer to the Communication Accessories table on page 128 for details.
(2) For use only with DPI External Communications Kits 20-XCOMM-DC-BASE.
(3) Contact Rockwell Automation sales office for availability.
Most legacy communication adapters (20-COMM) can be used with the PowerFlex 753/755. However, the restrictions stated
below do apply.
Frame 1 - It is recommended that the 20-750-20COMM-F1 Communication Carrier Card only be installed in Port 4. Port 5 is
not accessible when this module is installed.
Frames 2 and larger - It is recommended that the 20-750-20COMM Communication Carrier Card be installed in Port 6. By
using Port 4 or 5, the adjacent left port becomes inaccessible to other option modules and it can interfere with network
cable connections.
(1) Chinese, Japanese, and Korean languages are supported at the time of publication.
(2) Requires this adapter firmware version or higher.
(3) Requires firmware version v1.05 or higher of the drive Add-on Profiles for Studio 5000 Logix Designer software.
(4) Controller must be capable of reading/writing 32-bit floating point (REAL) values.
(5) Supports all three modes of operation (RTU, P1, N2).
Communication Accessories
Used with PowerFlex Drive
Description Cat. No. 70 753/755 755TL/TR
Universal Serial Bus™ (USB) Converter includes 2m USB, 20-HIM-H10 and 22-HIM-H10 Cables 1203-USB ✓ ✓ ✓
ControlNet T-tap Straight 1786-TPS — ✓ —
Communication Carrier Card for PowerFlex 750-Series Frame 1 drives 20-750-20COMM-F1 ✓
Communication Carrier Card for PowerFlex 750-Series Frame 2 or higher drives 20-750-20COMM ✓
(1) For kits to be used with CIP Motion instructions, the card can only be used in slot 7 of the PowerFlex 755 drive. It also requires PowerFlex 755 firmware version 12 and higher, and Studio 5000 version 28 and higher.
Safety Options(1)
Used with PowerFlex Drive
Description Cat. No. 70 753 755 755TL/755TR
DriveGuard Safe Torque Off 20A-DG01 ✓ — — —
Hardwired Safe Torque Off 20-750-S — ✓ ✓ ✓
(2) (2)
Hardwired Safe Speed Monitor 20-750-S1 ✓ ✓ ✓
(3)(4)
Networked Safe Torque Off 20-750-S3 — ✓ ✓(3)
Networked Integrated Safety Functions 20-750-S4 — ✓(5)(6) ✓(5)
(1) All PowerFlex 7-series drives can accommodate only one safety option.
(2) Requires the Dual Incremental Encoder or Universal Feedback Option. Also requires the 20-750-EMCSSM1-F8 EMC Option Kit with Frame 8…10 drives.
(3) Requires Studio 5000 version 30 and higher.
(4) Requires PowerFlex 755 firmware version 13 and higher. This option is not allowed while controlling a PowerFlex drive in CIP Motion mode.
(5) Requires Studio 5000 version 31 and higher.
(6) Requires PowerFlex 755 firmware version 14.002 and higher.
Feedback Options
Used with PowerFlex Drive
Description Cat. No. 70 753/755 755TL/755TR
5V/12V Encoder(1) 20A-ENC-1 ✓ — —
(2)
Incremental Encoder 20-750-ENC-1 — ✓ ✓
(2)
Dual Incremental Encoder 20-750-DENC-1 ✓ ✓
Universal Feedback (includes Stegmann, Heidenhain, SSI, Biss, 5V Incremental) 20-750-UFB-1 ✓(3) ✓
(1) Works only with PowerFlex 70 Enhanced Control. Drive is not CE EMC certified when the encoder interface option is installed.
(2) Homing and registration functions are not supported when using this device with Studio 5000 Logix Designer embedded motion instructions. To use these functions, the Universal
Feedback Board (20-750-UFB-1) must be used.
(3) Only for PowerFlex 755 drives.
Other Options
Used with PowerFlex Drive
Description Cat. No. 70 753/755 755TL/755TR
115V AC Interface AK-M9-115VAC-1 ✓ — —
Frame E Flange Gasket AK-M9-GASKET1-E4 ✓
Service Connection Board(1) SK-M9-SCB1 ✓
(1) Provides temporary DPI/HIM connection for NEMA/UL Type 1 and Flange drives with cover removed.
(1) Frame 8 and up drives can be powered from an external 24V DC source, a 20-750-APS is not required.
(2) Exhaust hood is standard on Frames 8…10, IP54-rated cabinets.
(1) Frame 8 and up drives can be powered from an external 24V DC source, a 20-750-APS is not required.
(2) Exhaust hood is standard on Frames 8…10, IP54-rated cabinets.
(3) Frame 8 drive is factory shipped with two L bus bars per phase as standard, Frame 9 drive is factory shipped with four L bus bars per phase as standard, and Frame 10 drive is factory shipped with six L bus bars per
phase as standard.