Technical data sheet                                                                   LF24-S
Rotary actuator fail-safe for adjusting dampers
in technical building installations
• Air damper size up to approx. 0.8 m²
• Torque motor 4 Nm
• Nominal voltage AC/DC 24 V
• Control Open/close
• with integrated auxiliary switch
 Technical data
                                  Electrical data    Nominal voltage                                AC/DC 24 V
                                                     Nominal voltage frequency                      50/60 Hz
                                                     Nominal voltage range                          AC 19.2...28.8 V / DC 21.6...28.8 V
                                                     Power consumption in operation                 5W
                                                     Power consumption in rest position             2.5 W
                                                     Power consumption for wire sizing              7 VA
                                                     Power consumption for wire sizing note         Imax 5.8 A @ 5 ms
                                                     Auxiliary switch                               1x SPDT, 0...100%
                                                     Switching capacity auxiliary switch            1 mA...3 A (0.5 A inductive), DC 5 V...AC 250 V
                                                     Connection supply / control                    Cable 1 m, 2x 0.75 mm²
                                                     Connection auxiliary switch                    Cable 1 m, 3x 0.75 mm²
                                                     Parallel operation                             Yes (note the performance data)
                                 Functional data     Torque motor                                   4 Nm
                                                     Torque fail-safe                               4 Nm
                                                     Direction of motion motor                      selectable by mounting L/R
                                                     Direction of motion fail-safe                  selectable by mounting L/R
                                                     Manual override                                No
                                                     Angle of rotation                              Max. 95°
                                                     Angle of rotation note                         Adjustable 37...100% with integrated
                                                                                                    mechanical limitation
                                                     Running time motor                             75 s / 90°
                                                     Running time fail-safe                         <20 s @ -20...50°C / <60 s @ -30°C
                                                     Sound power level, motor                       50 dB(A)
                                                     Mechanical interface                           Universal shaft clamp 8...16 mm
                                                     Position indication                            Mechanical
                                                     Service life                                   Min. 60'000 fail-safe positions
                                     Safety data     Protection class IEC/EN                        III, Safety Extra-Low Voltage (SELV)
                                                     Protection class auxiliary switch IEC/EN       II, reinforced insulation
                                                     Degree of protection IEC/EN                    IP54
                                                     EMC                                            CE according to 2014/30/EU
                                                     Low voltage directive                          CE according to 2014/35/EU
                                                     Certification IEC/EN                           IEC/EN 60730-1 and IEC/EN 60730-2-14
                                                     Hygiene test                                   According to VDI 6022 Part 1 / SWKI VA
                                                                                                    104-01, cleanable and disinfectable, low
                                                                                                    emission
                                                     Type of action                                 Type 1.B
www.belimo.com                                    LF24-S • en-gb • 2023-12-12 • Subject to change                                           1/3
                                                  Technical data sheet                                                                   LF24-S
 Technical data
                                   Safety data     Rated impulse voltage supply / control          0.8 kV
                                                   Rated impulse voltage auxiliary switch          2.5 kV
                                                   Pollution degree                                3
                                                   Ambient humidity                                Max. 95% RH, non-condensing
                                                   Ambient temperature                             -30...50°C [-22...122°F]
                                                   Storage temperature                             -40...80°C [-40...176°F]
                                                   Servicing                                       maintenance-free
                                       Weight      Weight                                          1.5 kg
 Safety notes
                                                  • This device has been designed for use in stationary heating, ventilation and air-conditioning
                                                    systems and must not be used outside the specified field of application, especially in aircraft
                                                    or in any other airborne means of transport.
                                                  • Outdoor application: only possible in case that no (sea) water, snow, ice, insolation or
                                                    aggressive gases interfere directly with the device and that it is ensured that the ambient
                                                    conditions remain within the thresholds according to the data sheet at any time.
                                                  • Only authorised specialists may carry out installation. All applicable legal or institutional
                                                    installation regulations must be complied with during installation.
                                                  • The device may only be opened at the manufacturer's site. It does not contain any parts that
                                                    can be replaced or repaired by the user.
                                                  • Cables must not be removed from the device.
                                                  • To calculate the torque required, the specifications supplied by the damper manufacturers
                                                    concerning the cross-section and the design, as well as the installation situation and the
                                                    ventilation conditions must be observed.
                                                  • The device contains electrical and electronic components and must not be disposed of as
                                                    household refuse. All locally valid regulations and requirements must be observed.
 Product features
                             Operating mode       The actuator moves the damper to the operating position at the same time as tensioning the
                                                  return spring. The damper is turned back to the safety position by spring energy when the
                                                  supply voltage is interrupted.
                      Simple direct mounting      Simple direct mounting on the damper shaft with a universal shaft clamp, supplied with an
                                                  anti-rotation device to prevent the actuator from rotating.
                  Adjustable angle of rotation    Adjustable angle of rotation with mechanical end stops.
                    High functional reliability   The actuator is overload protected, requires no limit switches and automatically stops when
                                                  the end stop is reached.
                            Flexible signalling   With adjustable auxiliary switch (0...100%)
 Accessories
                         Electrical accessories   Description                                                                 Type
                                                  Auxiliary switch 2x SPDT                                                    S2A-F
                                                  Feedback potentiometer 1 kΩ                                                 P1000A-F
                      Mechanical accessories      Description                                                                 Type
                                                  Shaft extension 170 mm ø10 mm for damper shaft ø6...16 mm                   AV6-20
                                                  Shaft clamp reversible, clamping range ø16...20 mm                          K6-1
                                                  Ball joint suitable for damper crank arm KH8 / KH10                         KG10A
                                                  Ball joint suitable for damper crank arm KH8                                KG8
                                                  Damper crank arm Slot width 8.2 mm, clamping range ø10...18 mm              KH8
                                                  Actuator arm, clamping range ø8...16 mm, Slot width 8.2 mm                  KH-LF
www.belimo.com                                LF24-S • en-gb • 2023-12-12 • Subject to change                                             2/3
                                                 Technical data sheet                                                               LF24-S
 Accessories
                                                 Description                                                               Type
                                                 Angle of rotation limiter, with end stop                                  ZDB-LF
                                                 Form fit adapter 8x8 mm                                                   ZF8-LF
                                                 Mounting kit for linkage operation for flat installation                  ZG-LF1
                                                 Mounting kit for linkage operation for side installation Slot width 6.2   ZG-LF3
                                                 mm
                                                 Anti-rotation mechanism 180 mm, Multipack 20 pcs.                         Z-ARS180L
 Electrical installation
                                                 Supply from isolating transformer.
                                                 Parallel connection of other actuators possible. Observe the performance data.
 Wire colours:
 1 = black
 2 = red
 S1 = violet
 S2 = red
 S3 = white
 Wiring diagrams
 AC/DC 24 V, open/close              Auxiliary switch
 Dimensions
 Spindle length
                           Min. 84
                           Min. 20
 Clamping range
www.belimo.com                                LF24-S • en-gb • 2023-12-12 • Subject to change                                          3/3