Technical Specification
SUN2000 SUN2000 SUN2000 SUN2000 SUN2000
Technical Specification -5K-MAP0 -6K-MAP0 -8K-MAP0 -10K-MAP0 -12K-MAP0
Max. efficiency 98.4% 98.6% 98.6% 98.6% 98.6%
European weighted efficiency 97.5% 97.7% 98.0% 98.1% 98.2%
Input (PV)
Recommended max. PV power 9,000 Wp 11,000 Wp 14,600 Wp 18,000 Wp 22,000 Wp
Max. input voltage 1 1,100 V
Operating voltage range 2 160 - 1,000 V
Startup voltage 160 V
Rated input voltage 600 V
Max. input current per MPPT 16 A
Max. short-circuit current 22 A
Number of MPP trackers 2
Max. input per MPP tracker 1
Input (DC Battery)
Compatible battery LUNA2000-5/10/15-S0 / LUNA2000-7/14/21-S1
Operating voltage range 600 ~ 980 V
Max. operating current 20 A
Max. charging power 12,000 W
Max. discharging power 5,500 W 6,600 W 8,800 W 11,000 W 12,000 W
Output (On Grid)
Grid connection Three-phase
Rated output power 5,000 W 6,000 W 8,000 W 10,000 W 12,000 W
Max. apparent power 5,500 VA 6,600 VA 8,800 VA 11,000 VA 13,200 VA
Rated output voltage 220 V AC/380 V AC, 230 V AC/400 V AC, 240 V AC/415 V AC 3W/N + PE
Overload capability 110%
Rated AC grid frequency 50 Hz/60 Hz
Max. output current 8.3 A 10.0 A 13.3 A 16.7 A 20.2 A
Adjustable power factor 0.8 leading ... 0.8 lagging
Max. total harmonic distortion ≤ 3%
Output (Off Grid)
Compatible backup device SmartGuard-63A-T0 (3 phase)
Rated output power 5,000 W 6,000 W 8,000 W 10,000 W 12,000 W
Rated output voltage 220 V AC/380 V AC, 230 V AC/400 V AC, 240 V AC/415 V AC 3W/N + PE
110% overload Continuous
150% overload 5 min (3-phase) / 5 min (Single-phase) 1 min (3-phase) / 5 min (Single-phase)
200% overload 10 seconds
Automatic switchover time ≤ 20 ms (with SmartGuard-63A-T0)
Protection Feature
Asymmetric load Yes, supports 100% three-phase asymmetric load
Input-side disconnection device Yes
Anti-islanding protection Yes
DC reverse polarity protection Yes
Insulation detection Yes
DC surge protection Yes, compatible with TYPE II protection class according to EN/IEC 61643-11
AC surge protection Yes, compatible with TYPE II protection class according to EN/IEC 61643-11
Residual current detection Yes
AC overcurrent protection Yes
AC short-circuit protection Yes
AC overvoltage protection Yes
Arc fault protection Yes
Connector temperature detection Yes (PV & Battery connectors)
Ripple receiver control Yes
Battery charging from grid Yes
General Specification
Operating temperature range –25°C - +60°C (–13°F - +140°F)
Relative operating humidity 0 % - 100% RH
Max. operating altitude 4,000 m
Cooling Natural convection
Noise ≤ 29 dB
Display LED Indicators; Integrated WLAN + FusionSolar APP
RS485; WLAN / Ethernet via Smart Dongle-WLAN-FE (Optional)
Communication
4G/3G/2G via Smart Dongle-4G (Optional); EMMA (Optional)
Weight (incl. mounting brackets) 21 kg
Dimensions (incl. mounting brackets) 490 mm x 460 mm x 130 mm
IP rating IP66
Nighttime power < 5.5 W
Optimizer Compatibility
DC MBUS compatible optimizer SUN2000-450W-P2, SUN2000-600W-P
Safety EN/IEC62109-1, EN/IEC62109-2
IEC61727, IEC62116, MEA/PEA, G99, Philippine Grid Code Resolution No. 07, NRS 097-2-1, EN50549-1, VDE4105,
Grid connection standards UTE15-712-1/VFR 2019, UNE217002, NTS631, RD244(UNE217001), PPDS, ROGA, TOR Erzeuger, CEI 0-21:2020-12
V1, C10/C11
*1 The max. input voltage is the upper limit of the DC voltage. Any higher input DC voltage would probably damage the inverter.
*2 Any DC input voltage beyond the operating voltage range may result in inverter malfunction.
Disclaimer: the preceding values are measured by an internal laboratory of Huawei in a specific environment. The actual values may vary with products, software versions, usage
conditions, and environmental factors.
Version No.: 02-202406