0% found this document useful (0 votes)
39 views2 pages

FT - Huawei - SUN2000-5K-12K-MAP0

Uploaded by

projets971
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
39 views2 pages

FT - Huawei - SUN2000-5K-12K-MAP0

Uploaded by

projets971
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

SMART ENERGY

CONTROLLER
SUN2000-5/6/8/10/12K-MAP0

Asymmetric Load Active Safety Future Ready


Three-phase asymmetric output AFCI & RSD (with optimizer) LUNA S0 or S1
200% overload Connector temperature detection Whole home backup (with SmartGuard)

Version No.: 02-202406


SUN2000-5/6/8/10/12K-MAP0
Technical Specification
SUN2000 SUN2000 SUN2000 SUN2000 SUN2000
Technical Specification -5K-MAP0 -6K-MAP0 -8K-MAP0 -10K-MAP0 -12K-MAP0

Max. efficiency 98.4% 98.6% 98.6% 98.6% 98.6%


European weighted efficiency 97.5% 97.7% 98.0% 98.1% 98.2%
Input (PV)
Recommended max. PV power 9,000 Wp 11,000 Wp 14,600 Wp 18,000 Wp 22,000 Wp
Max. input voltage 1 1,100 V
Operating voltage range 2 160 - 1,000 V
Startup voltage 160 V
Rated input voltage 600 V
Max. input current per MPPT 16 A
Max. short-circuit current 22 A
Number of MPP trackers 2
Max. input per MPP tracker 1
Input (DC Battery)
Compatible battery LUNA2000-5/10/15-S0 / LUNA2000-7/14/21-S1
Operating voltage range 600 ~ 980 V
Max. operating current 20 A
Max. charging power 12,000 W
Max. discharging power 5,500 W 6,600 W 8,800 W 11,000 W 12,000 W
Output (On Grid)
Grid connection Three-phase
Rated output power 5,000 W 6,000 W 8,000 W 10,000 W 12,000 W
Max. apparent power 5,500 VA 6,600 VA 8,800 VA 11,000 VA 13,200 VA
Rated output voltage 220 V AC/380 V AC, 230 V AC/400 V AC, 240 V AC/415 V AC 3W/N + PE
Overload capability 110%
Rated AC grid frequency 50 Hz/60 Hz
Max. output current 8.3 A 10.0 A 13.3 A 16.7 A 20.2 A
Adjustable power factor 0.8 leading ... 0.8 lagging
Max. total harmonic distortion ≤ 3%
Output (Off Grid)
Compatible backup device SmartGuard-63A-T0 (3 phase)
Rated output power 5,000 W 6,000 W 8,000 W 10,000 W 12,000 W
Rated output voltage 220 V AC/380 V AC, 230 V AC/400 V AC, 240 V AC/415 V AC 3W/N + PE
110% overload Continuous
150% overload 5 min (3-phase) / 5 min (Single-phase) 1 min (3-phase) / 5 min (Single-phase)
200% overload 10 seconds
Automatic switchover time ≤ 20 ms (with SmartGuard-63A-T0)
Protection Feature
Asymmetric load Yes, supports 100% three-phase asymmetric load
Input-side disconnection device Yes
Anti-islanding protection Yes
DC reverse polarity protection Yes
Insulation detection Yes
DC surge protection Yes, compatible with TYPE II protection class according to EN/IEC 61643-11
AC surge protection Yes, compatible with TYPE II protection class according to EN/IEC 61643-11
Residual current detection Yes
AC overcurrent protection Yes
AC short-circuit protection Yes
AC overvoltage protection Yes
Arc fault protection Yes
Connector temperature detection Yes (PV & Battery connectors)
Ripple receiver control Yes
Battery charging from grid Yes
General Specification
Operating temperature range –25°C - +60°C (–13°F - +140°F)
Relative operating humidity 0 % - 100% RH
Max. operating altitude 4,000 m
Cooling Natural convection
Noise ≤ 29 dB
Display LED Indicators; Integrated WLAN + FusionSolar APP
RS485; WLAN / Ethernet via Smart Dongle-WLAN-FE (Optional)
Communication
4G/3G/2G via Smart Dongle-4G (Optional); EMMA (Optional)
Weight (incl. mounting brackets) 21 kg
Dimensions (incl. mounting brackets) 490 mm x 460 mm x 130 mm
IP rating IP66
Nighttime power < 5.5 W
Optimizer Compatibility
DC MBUS compatible optimizer SUN2000-450W-P2, SUN2000-600W-P

Safety EN/IEC62109-1, EN/IEC62109-2


IEC61727, IEC62116, MEA/PEA, G99, Philippine Grid Code Resolution No. 07, NRS 097-2-1, EN50549-1, VDE4105,
Grid connection standards UTE15-712-1/VFR 2019, UNE217002, NTS631, RD244(UNE217001), PPDS, ROGA, TOR Erzeuger, CEI 0-21:2020-12
V1, C10/C11

*1 The max. input voltage is the upper limit of the DC voltage. Any higher input DC voltage would probably damage the inverter.
*2 Any DC input voltage beyond the operating voltage range may result in inverter malfunction.

Disclaimer: the preceding values are measured by an internal laboratory of Huawei in a specific environment. The actual values may vary with products, software versions, usage
conditions, and environmental factors.