Product data sheet
Specifications
Circuit breaker frame, ComPact
NS800N, 50kA/415VAC, 800A,
fixed, electrically operated, without
trip unit, 3P
33280
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range ComPact
Range of produc ComPact NS630b...1600
Device short name Compact NS800N
Product or component type Basic frame
Device application Distribution
Number of poles 3P
[In] rated current 800 A at 50 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
Network type AC
Network frequency 50/60 Hz
Suitability for isolation Yes conforming to EN/IEC 60947-2
Utilisation category Category B
[Icu] rated ultimate short-circuit 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Performance level N 50 kA 415 V AC
Control type Motor mechanism
Mounting mode Fixed
Complementary
[Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand 8 kV conforming to IEC 60947-2
voltage
[Ics] rated service short-circuit 30 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation)
breaking capacity 22 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation)
37 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation)
37 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation)
37 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation)
[Icw] rated short-time withstand 19.2 kA 1 s conforming to IEC 60947-2
current
Integral instant protection 40 kA
Mechanical durability 10000 cycles conforming to IEC 60947-2
Electrical durability 2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2
Feb 6, 2024 1
4000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2
5000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2
6000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Power losses 15 W
Mounting support Backplate
Connection pitch 70 mm
Protection type Without protection
Height (H) 327 mm
Width (W) 210 mm
Depth (D) 147 mm
Environment
Standards IEC 60947-2
Product certifications ASEFA
LCIE
ASTA
Pollution degree 3 conforming to IEC 60947
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to EN 50102
Ambient air temperature for -25…70 °C
operation
Ambient air temperature for -50…85 °C
storage
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 25.0 cm
Package 1 Width 40.0 cm
Package 1 Length 40.0 cm
Package 1 Weight 20.708 kg
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation REACh Declaration
EU RoHS Directive Compliant with Exemptions
Mercury free Yes
China RoHS Regulation China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information
RoHS exemption information Yes
Environmental Disclosure Product Environmental Profile
Circularity Profile No need of specific recycling operations
Circularity Profile
WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins
PVC free Yes
Contractual warranty
Warranty 18 months
2
Feb 6, 2024
Recommended replacement(s)
Feb 6, 2024 3