PRODUCT-DETAILS

A110-30-11-80
A110-30-11 220-230V 50Hz / 230-240V 60Hz
Contactor

General Information
Extended Product Type A110-30-11-80
Product ID 1SFL451001R8011
EAN 7320500141595
Catalog Description A110-30-11 220-230V 50Hz / 230-240V 60Hz Contactor
A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-
Long Description pass and Distribution application up to max 1000 V.Operated with control voltage, versions
from 24….690 AC, 50 and 60 Hz

Ordering
Minimum Order Quantity 1 piece
Customs Tariff Number 85364900
Replacement Product ID 1SFL427001R1311
(NEW)

Popular Downloads
Data Sheet, Technical 1SBC100192C0206
Information
Instructions and Manuals 5309660-60
Dimension Diagram 53540923-1

© 2023 ABB. All rights reserved. 2023/06/09 Subject to change without notice
A110-30-11-80 2

Dimensions
Product Net Width 102 mm
Product Net Depth / 123.5 mm
Length
Product Net Height 148 mm
Product Net Weight 1.8 kg

Technical
Number of Main Contacts 3
NO
Number of Main Contacts 0
NC
Number of Auxiliary 1
Contacts NO
Number of Auxiliary 1
Contacts NC
Rated Operational Voltage Main Circuit 1000 V
Rated Frequency (f) Main Circuit 50 / 60 Hz
Conventional Free-air acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 160 A
Thermal Current (I th )

Rated Operational Current (690 V) 40 °C 160 A


AC-1 (I e ) (690 V) 55 °C 145 A
(690 V) 70 °C 130 A
Rated Operational Current (415 V) 55 °C 110 A
AC-3 (I e ) (440 V) 55 °C 100 A
(500 V) 55 °C 100 A
(690 V) 55 °C 82 A
(1000 V) 55 °C 30 A
(380 / 400 V) 55 °C 110 A
(220 / 230 / 240 V) 55 °C 110
Rated Operational Power (415 V) 59 kW
AC-3 (P e ) (440 V) 59 kW
(500 V) 59 kW
(690 V) 75 kW
(1000 V) 40 kW
(380 / 400 V) 55 kW
(220 / 230 / 240 V) 30 kW
Rated Breaking Capacity 8 x Ie AC-3
AC-3
Rated Making Capacity 10 x Ie AC-3
AC-3
Short-Circuit Protective gG Type Fuses 200 A
Devices
Rated Short-time at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 800 A
Withstand Current Low at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 175 A
Voltage (I cw ) at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 350 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1320 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 500 A
Maximum Breaking cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1160 A
Capacity cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 800 A
Maximum Electrical (AC-1) 300 cycles per hour
Switching Frequency (AC-2 / AC-4) 150 cycles per hour
(AC-3) 300 cycles per hour
Rated Operational Current (110 V) 2 Poles in Series, 40 °C 160 A
DC-1 (I e ) (220 V) 3 Poles in Series, 40 °C 160 A

Rated Operational Current (110 V) 2 Poles in Series, 40 °C 160 A


DC-3 (I e ) (220 V) 3 Poles in Series, 40 °C 160 A

Rated Operational Current (110 V) 2 Poles in Series, 40 °C 160 A


DC-5 (I e ) (220 V) 3 Poles in Series, 40 °C 160 A

Rated Insulation Voltage acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
(U i ) acc. to UL/CSA 600 V

© 2023 ABB. All rights reserved. 2023/06/09 Subject to change without notice
A110-30-11-80 3

Rated Impulse Withstand Main Circuit 8 kV


Voltage (U imp )

Mechanical Durability 10 million


Maximum Mechanical 3600 cycles per hour
Switching Frequency
Coil Operating Limits (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit 50 Hz 220 ... 230 V
Voltage (U c ) 60 Hz 230 ... 240 V

Coil Consumption Holding at Max. Rated Control Circuit Voltage 50 Hz 22 V·A


Holding at Max. Rated Control Circuit Voltage 60 Hz 26 V·A
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 350 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 450 V·A
Operate Time Between Coil De-energization and NC Contact Closing 7 ... 15 ms
Between Coil De-energization and NO Contact Opening 10 ... 18 ms
Between Coil Energization and NC Contact Opening 7 ... 22 ms
Between Coil Energization and NO Contact Closing 10 ... 25 ms
Connecting Capacity Main Bar 30 mm²
Circuit Flexible with Cable End 2 x 6 ... 35 mm²
Rigid 1 x 10 ... 95 mm²
Connecting Capacity Flexible with Ferrule 2x 0.75 ... 2.5 mm²
Auxiliary Circuit Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible 1x0.75 ... 2.5 mm²
Solid 2 x 1 ... 4 mm²
Stranded 2 x 1 .... 4 mm²
Degree of Protection acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Connecting Terminals M8 hexagon socket screw with single connector
(delivered in open
position) Main Poles
Terminal Type Cable Clamp

Technical UL/CSA
Maximum Operating Main Circuit 600 V
Voltage UL/CSA
General Use Rating (600 V AC) 140 A
UL/CSA
Horsepower Rating (200 V AC) Three Phase 30 hp
UL/CSA (208 V AC) Three Phase 30 hp
(220 ... 240 V AC) Three Phase 40 hp
(440 ... 480 V AC) Three Phase 75 hp
(550 ... 600 V AC) Three Phase 100 hp

Environmental
Ambient Air Temperature Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C
Close to Contactor for Storage -60 ... +80 °C
Maximum Operating Without Derating 3000 m
Altitude Permissible
Resistance to Shock acc. Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock
to IEC 60068-2-27 Direction: A 20 g
Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock
Direction: A 20 g
Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock
Direction: B1 10 g
Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock
Direction: C1 20 g
Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock
Direction: C2 20 g
Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock
Direction: B1 5 g
Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock
Direction: B2 15 g
Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock
Direction: C1 20 g
Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock

© 2023 ABB. All rights reserved. 2023/06/09 Subject to change without notice
A110-30-11-80 4

Direction: C2 20 g
RoHS Status Following EU Directive 2011/65/EU

Certificates and Declarations (Document Number)


BV Certificate 07172/D0 BV
CB Certificate SE-69487
CQC Certificate CQC2002010304008904
CQC2009010304353526
CSA Certificate 314005
Declaration of Conformity 2020980304001630
- CCC 2020980304001078
Declaration of Conformity 2CMT2015-005436
- CE
Declaration of Conformity 2CMT2020-006118
- UKCA
DNV Certificate DNV_E-12191
Environmental Information 1SFC101001D0201
GL Certificate GL_99358-97HH
Instructions and Manuals 5309660-60
LOVAG Certificate SE-9645071-2
LR Certificate LR_12-70027-E1
REACH Declaration 2CMT2021-006202
RINA Certificate ELE060313XG/001
RMRS Certificate RMRS_12-03683-315
RoHS Information 2CMT2021-006277

Container Information
Package Level 1 Units box 1 piece
Package Level 1 Width 130 mm
Package Level 1 Depth / 265 mm
Length
Package Level 1 Height 162 mm
Package Level 1 Gross 2 kg
Weight
Package Level 1 EAN 7320500141595

Classifications
Object Classification Code Q
ETIM 4 EC000066 - Magnet contactor, AC-switching
ETIM 5 EC000066 - Magnet contactor, AC-switching
ETIM 6 EC000066 - Power contactor, AC switching
ETIM 7 EC000066 - Power contactor, AC switching
ETIM 8 EC000066 - Power contactor, AC switching
eClass V11.0 : 27371003
UNSPSC 39121529
IDEA Granular Category 4755 >> Contactors
Code (IGCC)

© 2023 ABB. All rights reserved. 2023/06/09 Subject to change without notice
A110-30-11-80 5

Categories

Low Voltage Products and Systems → Control Products → Contactors → Block Contactors
Robotics → Robots → Articulated Robots → IRB 6400

© 2023 ABB. All rights reserved. 2023/06/09 Subject to change without notice

You might also like