Configuration of
CFC Logic on digsi
4 with Siemens
Relays
Configuration of Masking
I/O
Open digsi 4 > create new file > connect the relay.
Go to settings > select masking I/O.
To make own configuration. Right click > insert group in after...
User-def will be created > Right click on user-def drag & drop single point
(SP)
Now configure BI source by right click > select H (active with voltage).
Also configure BO source same by right click > select U (Unlatched) or L
(latched).
NOTE: L (Latched) for when output gets high it will remain high until
you reset the relay. Same method for LED configuration.
After configure BI BO of User-def. configure Destination > C > right
click > X.
NOTE: If this is not configured, it will not show in CFC charts.
Same for configure output signals to shows in CFC chart
Source > C > Right click > X.
Configuring Logic in CFC
chart
Open Digsi 4 > Create new file > connect the relay.
Goto settings > CFC charts.
For adding own new configuration. Right click > Insert CFC chart.
Now open CFC chart. You can able to see logic gates on left side.
Left side section is for connecting & Shows inputs signal. Right side
is for output.
Now drag & drop the logic which you want.
For connecting Input & Output on logic. Click on Input section in
logic > Interconnection to address > Select which you have created
on User-def.
NOTE: Make sure that hardwiring done on
the relay & do configuration with exact BI &
BO.