0% found this document useful (0 votes)
31 views32 pages

4408 en Anzeige - Und Bedieneinheit Für TDG3 - A5192642

Catalogue tủ nạp ác quy

Uploaded by

Huy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
31 views32 pages

4408 en Anzeige - Und Bedieneinheit Für TDG3 - A5192642

Catalogue tủ nạp ác quy

Uploaded by

Huy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 32

Operating instructions

Indicator and operating unit


of the Model series Thysat TDG3

Description of the menu items of the program in the controller Thysat


TDG3 and operating instructions for the graphical display

Note: Password dang nhap MCU 2500: 002

Date Designation No. 4408GB


Issued: 04.10.06 Mo/Obs p. 1/32 p.
Modified: 02.03.07 Mo kocarek
Approved: 16.08.07 Mohr
E:\Catalogue\Benning Charger\Instruction Manual\MCU 2500\4408 EN ANZEIGE- UND BEDIENEINHEIT FÜR
TDG3(A5192642).DOC
Indicator and operating unit
of the model series Thysat TDG3

Contents
1 Operation of the graphic display ..................................................................4

1.1 Main window .................................................................................................5

2 Main menu .....................................................................................................6

2.1 Measured values ............................................................................................7

2.2 Digital inputs .................................................................................................8

2.3 State ............................................................................................................. 10

2.4 Test .............................................................................................................. 10

2.4.1 Reset hold func. .......................................................................................... 11

2.4.2 Battery test start .......................................................................................... 11

2.4.3 Manual operating mode selection by way of characteristic change-over 12

2.4.4 Relay ........................................................................................................... 12

2.5 Display settings .......................................................................................... 14

2.5.1 Language..................................................................................................... 14

2.5.2 LED test ...................................................................................................... 14

2.5.3 Standard (Std) – Measured value (MV) – Display values 1 and 2 .......... 15

2.5.4 "Contrast" and "brightness" displays ........................................................ 15

2.5.5 Returning to the measured value display .................................................. 16

2.5.6 Backlight ..................................................................................................... 16

2.5.7 Display test ................................................................................................. 16

2.6 System settings ........................................................................................... 16

2.6.1 Nominal values ........................................................................................... 18

2.6.2 Delays .......................................................................................................... 20

2.6.3 Battery test .................................................................................................. 21

02.03.07 Mo 2/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

2.6.4 Configuration flags ..................................................................................... 22

2.6.5 Options / configuration flags ..................................................................... 23

2.6.6 Battery sensor, time and date..................................................................... 23

2.6.7 Boundary value monitoring ....................................................................... 24

2.6.8 Configuration of the individual monitoring systems ............................... 25

2.6.9 Overview ..................................................................................................... 26

2.6.10 Measured value transfer to MCU .............................................................. 28

2.6.11 LED hold function ...................................................................................... 28

2.6.12 Relay hold function .................................................................................... 29

2.6.13 Changing various parameters .................................................................... 30

2.6.14 Calibration* ................................................................................................ 32

2.7 Logbook ...................................................................................................... 32

02.03.07 Mo 3/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

1 Operation of the graphic display


On the 4 buttons of the graphic display, all the release statuses and measured
values of the power supply system can be displayed or set. Critical menu levels
are accessible by means of a password only. Return to the basic status takes
place automatically from any menu item when no button has been actuated for
about 1 minute.

This time can be changed in the menu item display settings.

Figure 1: Display with function keys

The meaning of the 4 LEDs above the display is fixed.

device ON BT operating mode

alarm urgent alarm

Function button assignments on selecting the individual menu items

Conformation of the selected menu item

Return to next higher menu level

Selection of individual menu items within a menu


level

02.03.07 Mo 4/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

1.1 Main window


In the basic state, the display shows alternately two different measured values.
The type of measured value to be displayed is determined in the sub-menu dis-
play settings.

Rectifier voltage Rectifier current


U = 220.0V I = 165.2A

The measuring variable and the measured values are displayed as clear text. If
the text of the measured variable has too many characters and cannot be dis-
played as a whole, a running text is displayed.

The symbol indicates that there is a new log entry present that has not
yet been viewed and acknowledged. If this button is operated, the display
jumps directly to the log entry.

The button allows to jump from the basic display to the main menu.

02.03.07 Mo 5/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

2 Main menu
The main menu is split up in seven sub-groups.

Select the sub-group with the buttons and invoke the selected sub-
menu with the button. Two of the sub-groups, "Test" and "System set-
tings", can be invoked only with the relative password. The button quits
the menu.

Overview of all program levels:

Main menu
Measured values Rectifier voltage
Rectifier current
Battery current
to
Rem. time EC/B/BT
Digital inputs 00 =
01 =
02 =
to
63 =
State 1 . SAT address 0000 <
This device is master
25 . SAT address 0000
This device is not master
27 . SAT address 0000
This device is not master
Test Reset hold func.
Password 1 = _ _ _ Battery test start
Battery cycle test start
Float
Boost
Equal charge
Manual
Direct feed
Relay 1
to
Relay 4

02.03.07 Mo 6/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

Main menu
Display settings Language
LED test
STD display 1
STD display 2
Display contrast
Display brightness
Return to STD disp.
Backlight
Display test
System settings 1 = nominal values
Password 2 = _ _ _ 2 = delays
3 = battery test
to
23= calibration
24= version
Logbook Messages 001 ... 200

Sub-menus in detail:

2.1 Measured values


This display level displays all measured values of the device.

Select the desired measured value with .

The button quits the menu.

Main menu
Measured
values
Rectifier voltage U xxx.x V
Rectifier current I A
Battery current I A
Battery temp. T °C
Device temp. T °C
Earth resistance MΩ MΩ
15 V-supply DC U V
15 V-supply mains U V
Set value U U V

02.03.07 Mo 7/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

Main menu
Measured
values
Set value I I A
Voltage 2 U U
Drawn BT capacity Ah
Battery test time h
BT-test voltage U V
Total current I A
Rem. time EC/B/BT h

2.2 Digital inputs


Assignment, description and status of the digital inputs are displayed.

Main menu
Digital inputs
All inputs
Active inputs

Manual change to the configuration of an input:

Select main menu / signal inputs. Select the input in question with .

Invoke the input with the button / enter the password / select (filter flags) /
operate the button / select.

The check mark on the left side of the row indicates that the function is se-
lected. To set or cancel the check mark, press button . If pressed another
time, the confirmed function is undone again. The button quits the menu.

The individual inputs are listed here:

No. Function Status Circuit


active / inactive inverted
00 External input 1
01 External input 2
02 External input 3
03 External device error
04 Device switch off
05 External input 6

02.03.07 Mo 8/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

No. Function Status Circuit


active / inactive inverted
06 Equal - charge - lock
07 Boost - lock
08 Battery test lock
09 External input 4
10 External input 5
11 Mains error
12 Jumper X41. 3-4
13 Jumper X41 1-2
14 Temp. sensor error
15 Dtemp. sensor error
16 Device temp. high
17 BT discharged
18 Dev. voltage high
19 Dev. current high
20 BT current high
21 Earth fault positive
22 Earth fault negative
23 Unused measuring device 1
24 Unused measuring device 2
25 Unused measuring device 3
26 Device error
27 Battery test error
28 BTC error
29 Urgent alarm
30 Non urgent alarm
31 Mains contactor Off
32 U / I sensor cable error
33 No + 15V DC
34 No + 15 V AC
35 Device temp. off
36 Device hold off
37 Device off
38 > U dynamic
39 Characteristic "Off "
40 Characteristic " Boost "
41 Characteristic " Float charge"

02.03.07 Mo 9/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

No. Function Status Circuit


active / inactive inverted
42 Characteristic " Direct feed "
43 Characteristic " Battery test "
44 Characteristic " Manual "
45 Characteristic " Equal charge "
46 Boost/equal char.
47 BT operating mode
48 Reset hold func.
49 > U dyn. hold
50 > U switch. hold
51 Logbook warning
52 - 62 Not used
63 Off

2.3 State
In this area of the program, the state of the device can be read.

Main menu
State 1 . SAT address 0000 <
Device is ............
25 . SAT address 0000
This device is ............
27 . SAT address 0000
This device is ............

2.4 Test
Menu items of password level 1 : Initiate/Start a function

This level can be accessed only be entering a password. The password is a


number between 0 and 999 and is selected using the UP and DOWN buttons.

Attention!
For safety it is important to change this password after com-
missioning the system.

02.03.07 Mo 10/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

The standard password set by the manufacturer for menu level 1 is "1". This
prevents accidental incorrect operation. The customer is advised to change this
password as soon as possible.

Main menu
Test
Password 1 Reset hold func.
Battery test start
Battery cycle test start
Float
Boost
Equal charge
Manual
Direct feed
Relay 1
Relay 2
Relay 3
Relay 4

2.4.1 Reset hold function


The LEDs on the LED board can be configured so that they maintain their
status. Activation of this menu item causes all functions that are set so as to
maintain their status to return to the initial state (inactive state) if the condition
which has activated them is no longer applicable. The reset button at the front
door below the LED bar has the same function.

2.4.2 Battery test start

Starts the battery test.

When you change over to the characteristic "battery test", the device will
immediately perform a battery test using the parameters that are stored in the
controller. The query "ok" serves only to complete the selection. The test can
be aborted prematurely by switching over to one of the other characteristics.

02.03.07 Mo 11/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

Battery cycle test start

Starts the test of the battery circuit by reducing the charging voltage below the
battery open-circuit voltage. Checks the presence of the battery voltage.

Attention! This function is not possible if two devices without parallel opera-
tion line feed both one common rail. Faulty measurements and er-
roneous messages are possible due to voltage influence!

2.4.3 Manual operating mode selection by way of characteristic change- Formatted: Bullets and Numbering

over
The controller can operate at five different voltage levels that you can select
here. If the device is e.g. set to "float" and if the function "boost" is selected,
then the charging characteristic is switched over immediately.

If another rectifier unit is shunt-connected by way of the internal bus and the
operation mode has not been selected on the master, changeover may take
some time until the changeover command has been sent by way of the bus.

The characteristics boost charging, equal charge and battery test can be dis-
abled separately on the controller. In this case, no switch-over will be per-
formed!

The characteristics:

Float (EL)
Basic setting of the device on start.

Boost (LA)
Second voltage level for the rapid charging of the battery.

Equal charge (AL)


Not on maintenance-free batteries,

Manual (Man)
Required only for special configurations,

Direct feed (Dr)


Only if the rectifier is used as mains unit

2.4.4 Relay
In this function, the selected relay can be checked for function.
When tested, the respective relay is switched to off-position via the test. After
a delay time of 15 seconds, it is switched back to the position held before the
test.

02.03.07 Mo 12/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

Attention!
Relay K3 may only be tested when the rectifier is at no load!!!

In the normal TDG version relay K3 is provided for the circuit of the mains
contactor. If the relay is selected and checked for function, the rectifier
switches off! Switching-on the relay K3 with switching-on the mains contactor
without start-up phase of the controller can get critical under certain circum-
stances. Therefore, relay K3 may always only be tested when the device is at
no load.

02.03.07 Mo 13/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

2.5 Display settings


At this menu level, different settings can be made for the display.

Main menu
Display settings
Language German
English
Optional
LED test LED test
Version : x.xx
= x . SAT address
This device is .....
STD display 1 Rectifier voltage
STD display 2 Rectifier current
Display contrast ....%
Display brightness ....%
Return to STD disp. max. 255 sec.
Backlight .... sec.
Display test

2.5.1 Language
Here, you can select a language. German and English are always stored; a third
language can be optionally programmed.

Press button to select the language. Confirm the selection with the but-
ton . The button quits the menu.

2.5.2 LED test


Initiate the test with button . Quit the test with button .

During the LED test, the version number, the SAT address and "Device is mas-
ter (or slave)" are displayed.

02.03.07 Mo 14/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

2.5.3 Standard (Std) – Measured value (MV) – Display values 1 and 2


In the inactive state, the display shows two measured values alternately.

By default, the ex factory setting is rectifier voltage (DC) and rectifier current
(DC). If another voltage value is desired to be displayed, check whethervoltage
2 is set up for the measurement.

If other values are to be displayed, proceed as follows:

Select STD display 1

Invoke the measured values with the button and select the desired value
with . Confirm your selection with . Quit the menu with .

In the same way, select also value 2 to be displayed.

Selection of the measured values for both displays.

STD display 1 Rectifier voltage


STD display 2 Rectifier current
Battery current
Battery temp.
Device temp.
Earth resistance
15 V-supply DC
15 V-supply mains
Set value U
Set value I
Voltage 2
Drawn BT capacity
Battery test time
BT-test voltage
Total current
Rem. time EC/B/BT

2.5.4 "Contrast" and "brightness" displays


Different illumination situations at the installation site of the device may re-
quire a change of the display setting. Invoke with , improve the setting
with and confirm with . The button quits the menu. (contrast
70 –100%; brightness 0 – 100% )

02.03.07 Mo 15/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

2.5.5 Returning to the measured value display


The display automatically returns to the top menu if you do not press any but-
ton for longer than a defined time. Here, you can set this time (10 - 255 sec-
onds).

2.5.6 Backlight
The backlight of the display will go on as soon as you operate a button. After a
defined time, when no button has been pressed, the backlight is switched off.
This time can be set from 0 to 254 seconds. If you enter 255, the display is
switched to continuous operation. (Setting range 0 – 255 sec.)

2.5.7 Display test


This function checks the display for function.

Here, the entire display is switched dark from the sides and from top and bot-
tom. (The four LEDs located above are also tested.)

After the test, the normal display is resumed.

2.6 System settings


Menu items of password level 2

This level can be accessed only be entering a password.

The password is a number between 0 and 999 is selected using the but-
tons. The standard password set by the manufacturer for menu level 2 is "2".
This prevents accidental incorrect operation. The customer has to change this
password as soon as possible.

For safety it is obligatory to change this password after com-


missioning the system.

At this menu level, all configurations of the device can be adapted or


changed.

This password level must be used by instructed staff only.

Risk of destruction of the device and plant parts like bat-


tery or loads.

02.03.07 Mo 16/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

Main menu
System settings
Password 2 Nominal values
Delays
Battery test
Configuration flags
Options
Battery sensor
Time
Date
Boundary control
Ibat. to MCU index
REarth to MCU ind.
Ext. mains fault
LED hold function
Relay hold function
Temp. regulator
EEP default settings
Password 1
Password 2
Internal address
Address
Charge level in v/c
Current limit
Calibration
Version

For the details of the sub-groups, see the following pages:

02.03.07 Mo 17/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

2.6.1 Nominal values


The following parameters can be changed:

Main menu
System set-
tings
Nominal
Password 2 values
Nominal voltage 1 U xxx.x V
Nominal current1 I A
Battery cells Z
Cell voltage U V
Cod. U 2, jumper X400 U V
Device shunt I A
Battery shunt I A

If the ex factory setting is changed, the following response occurs:

Nominal voltage:

This value serves to calibrate the voltage levels in the controller program.

If the battery type ( PB , NiCd ) or the number of cells of the battery changes
for technical reasons, the changes must only be made in the following menu
items "number of cells" or "cell voltage". By changing the values in the menu
items, all values of the device are changed automatically without further inter-
vention.

Only the " free measuring devices " may be subject to adjustment.

Nominal current:
It is possible to change the nominal current
between 0% and 100% Inom.

Battery cells: Change of the voltage values referred to


V/cell

1
Furthermore, this function is only possible with a test bridge "X40" inserted in the controller.

02.03.07 Mo 18/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

Cell voltage: Adjustable between 0.00V and 3.00V.


At the moment, only two values are processed
in the controller:
Pb 2.0V/c and NiCd 1.2V/c

Cod. U2, jumper X400 Voltage selection 125V/ 250V / 500V


Query of the jumper position with respective
note on manual adjustment.

Device shunt: Change of the nominal current


Shunt value corresponds to the installed cur-
rent shunt of the device. If the shunt is
changed for technical reasons, this value must
also be adjusted.

Battery shunt: Change of the battery current limitation / bat-


tery test analysis
Shunt value corresponds to the installed cur-
rent shunt of the battery. If the shunt is
changed for technical reasons, this value must
also be adjusted.

02.03.07 Mo 19/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

2.6.2 Delays
The following parameters can be changed:

Main menu
System settings
Password 2 Delays
Urgent alarm
Non urgent alarm
Common. mains out
Duration boost (boost)
Delay equal charge
Delay turn on
Sensor fault

The times for the messages may be changed only a little in case of need.

Example: Changing the delay time in the function " urgent alarm ".

In the menu " delays ", invoke the directory "urgent alarm" with the buttons
. Selected sub-group invoked with button . Enter hours, minutes
and seconds with the buttons . The function of the buttons is specified
in the display. The button quits the menu.

Duration boost:
The time for NiCd cells is set to four hours.

Delay equal charge:


During charging processes to commission the battery, an hour value can be en-
tered there (up to 72 hours).

Delay turn on:


The rectifier starts operating with a delay.
The switch-on rush current of the transformer is not delayed.

Sensor fault
Response time after short circuit or sensor line breakage.
The set time should not be altered.

02.03.07 Mo 20/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

2.6.3 Battery test


The following parameters can be changed:

Main menu
System settings
Password 2 Battery test
Duration BT test
Stop BT test
Interval BT test
Duration BTC test
Cancel BTC test
Interval BTC test
Start next BT test
Start next BTC test

Duration BT test: Duration of the battery capacity check

Stop BT test: Voltage value where the test is aborted.

Interval BT test: Time of the day when to start the test.


Date of the start. (not programmed ex factory)

Duration BTC test: Ex factory set to 10 seconds.

Cancel BTC test: Must be below the open-circuit cell voltage.

Interval BTC test: Ex factory set to 24 hours.

Battery test: Recalculating the starting date for the test2.

Start next BTC test: Recalculating the starting date for the test2.

2
Here, no settings can be changed.

02.03.07 Mo 21/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

2.6.4 Configuration flags


The following parameters can be changed:

Main menu
System settings
Password 2 Config. flags
(parallel operation
Addicted characteristic*3 cable)
Sensor via MCU
Flag 3
Flag 4
Flag 5
Flag 6
Parallel operation (decoupling diode)
Device temp. sensor (PT 1000)
Flag 9 (USA buttons)
Flag 10
Flag 11
Flag 12
Flag 13
Flag 14
Flag 15
Flag 16

Attention!
For operation with the function "addicted characteristic / par-
allel operation cable", in addition to this function also the func-
tion "parallel operation / decoupling diodes" must be activated
and under the following menu item options / configuration
flags, the function "voltage regulation".

3
Note: Calibration only with switched-off flags or options

02.03.07 Mo 22/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

2.6.5 Options / configuration flags


The following parameters can be changed:

Main menu
System settings
Password 2 Options
Config. flags
Voltage regulation
Battery - temperature regulator
Option 3
Boost automatic
Error-hold-function
Not implemented: Power-management
Option 7
Option 8

Temperature regulator: regulator is switched on or off

Boost automatic: boost automatic is switched on or off

Power-management: not implemented

2.6.6 Battery sensor, time and date


The following parameters can be changed:

Main menu
System settings
Password 2 Battery sensor?
Battery line! Line length (max. 255 m)
Line-cross-section (max. 255 sqmm)
Time
Time hh :mm:ss
Date
Date dd :mm:yyy y

02.03.07 Mo 23/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

Battery line:
Since there are voltage drops in the lines between charger and battery, it is pos-
sible to balance this voltage drop by increasing the device output voltage auto-
matically. Line lengths between 0 and 255 meters as well as cross sections be-
tween 1.0 and 255 sqmm are programmable. Attention, if this function is acti-
vated, it must be ensured that the loads are not damaged by increasing the de-
vice voltage.

Date and time

Date and time are not protected by a voltage source and must be entered during
commissioning. During short interruptions of both ( AC and DC ) supply volt-
ages of the controller the values are preserved.

Entering the time:

In the menu "system settings" (password query), invoke the directory "time"
with the buttons . Invoked with button . Enter hours, minutes and
seconds with the buttons . The function of the buttons is specified in
the display. The button quits the menu.

2.6.7 Boundary value monitoring


The monitoring functions can be directly changed or created via the indicator
unit. Changes or inputs are to be provided as follows:

In the menu "boundary value monitoring", invoke the sub-menu by operating


the button . Select the desired function, e.g. a free measuring relay with the
designation "GSR monitoring 1":

Log on with . Determine the function of the monitoring and confirm with
.
At the end of the selector list "function", the item "no supervision" is listed. If
this item is selected, the monitoring installation is inactive.

Go back one step with . Select the response point for upper/lower violation
of a measured value with .

Select the monitoring for upper/lower boundary value violation and confirm
with .

A dot on the left side of the display indicates which function is selected.

Jump back one level with and select the boundary value with .

Enter the desired value using the selection keys and confirm with .

Jump back one level by pressing and enter the hysteresis following the
same method.

02.03.07 Mo 24/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

After all values have been entered completely, the input screen can be quit with
.

2.6.8 Configuration of the individual monitoring systems


The following lists represent the configurations of the individual monitoring
systems.

Attention!
The settings of the boundary-value monitoring relays (GSR)
may only be changed with excellent system knowledge.

02.03.07 Mo 25/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

2.6.9 Overview

Main menu
System settings
Password 2 Boundary control see the following list
BT discharged
Dev. voltage high
Dev. current high
BT current high
Earth fault
Device temp. high
GSR monitoring 1
GSR monitoring 2
GSR monitoring 3

Listing of the individual points:


BT discharged Input Rectifier voltage / voltage 2
Upper or lower Lower boundary
Boundary value x.xx V/cell
Hysteresis x.xx V/cell

Device voltage high (DC) Input Rectifier voltage / voltage 2


Upper or lower Upper violation
Boundary value x.xx V/cell max. 3.00 V/cell
Hysteresis x.xx V/cell max. 3.00 V/cell

Rectifier current (DC)


high Input Rectifier current
Upper or lower Upper violation
Boundary value 90%
Hysteresis 10%

BT current high Input Battery current


Upper or lower Upper violation
Boundary value 90%
Hysteresis 10%

Earth fault Input Earth resistance

02.03.07 Mo 26/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

Boundary value x.xx MOHM


Hysteresis x.xx MOHM

Device temp. high Input Device temp.


Upper or lower Upper violation
Boundary value 20°C ... 150°C
Hysteresis 20°C ... 150°C

GSR monitoring Input : ***


1/2/3 Upper or lower :
4
Boundary value 0.0 ... 999.0
4
Hysteresis 0.0 ... 999.0

*** selection of measured


values : Rectifier voltage boundary value V/ cell
Rectifier current boundary value in % -99 to 99
Battery current boundary value in % -99 to 99
Battery temp. boundary value T –20 to 150°C
Device temp. boundary value T –20 to 150°C
Earth resistance boundary value R 0.00 to 1.00 Mohm
15 V-supply DC boundary value U –999 to 999 V
15 V-supply mains boundary value U –999 to 999 V
Set value U boundary value U –999 to 999 V
Set value I boundary value A –999 to 999A
Voltage 2 boundary value 0 – 3.00V/cell
Drawn BT capacity -999 to 999 Ah
Battery test time -999 to 999 h
BT-test voltage -999 to 999 V
Total current - 999 to 999 A
Rem. time EC/B/BT 999 to 999 h
no supervision

4
Voltage details must be entered in V/cell.

02.03.07 Mo 27/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

2.6.10 Measured value transfer to MCU


These measured values can be transferred to the monitoring MCU (option), if
required.

Main menu
System set-
tings
Password 2
Ibat. to MCU index = …..
REarth to MCU ind.= .....
Ext. mains fault = .....*

* Function: Mains failure at the ext. input:

The device is generally equipped with mains monitoring. If a separate mains


monitoring device is required, it can be switched on via contact on a digital
controller input and then takes over the control function of the internal mains
monitoring device.
Input 63 is "OFF", indication 255 states that this function is not used.

2.6.11 LED hold function


In this menu item, the LEDs can be configured in their function.

Main menu
System set-
tings
LED hold function
LED no. Channel Circuit Hold message Time
No. 00 : 00 : 00 h
1 xx - inactive 00 : 00 : 00 h
2 xx
to
13 xx inverted inactive 00 : 00 : 00 h
LCD field LED 1 29 - inactive 00 : 00 : 00 h
LCD field LED 2 30 - inactive 00 : 00 : 00 h
LCD field LED 3 47 - inactive 00 : 00 : 00 h
LCD field LED 4 47 inverted inactive 00 : 00 : 00 h

02.03.07 Mo 28/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

LED Hold Function:

This function allows to determine the functions of the individual LEDs. Usu-
ally, the LEDs are allocated to their functions in the factory. If a free LED is to
be activated, proceed as follows:

In the menu "system settings", invoke the sub-menu "LED hold function" by
operating the button . Select input or function and confirm with .
Select delay time and confirm with . Select config. flags and determine
there whether the function is to be inverted and the error to be hold.

Attention: The number displayed after the LED ( e.g. LED13 ) is not identical
with the number of the LED ( No. 12 ).

2.6.12 Relay hold function


In this menu item, the relays can be configured in their function.

The four relays are located on the controller and can be adjusted in their func-
tion from here. In their basic configuration, they correspond to the Thyrotronic
messaging standard.
Seven further I2C bus relays are programmable ( special board ).

Main menu
System settings
Relay hold function
Relay no. Channel Circuit Hold message Time
No. 00 : 00 : 00 h
01 17 inverted inactive
02 29 inverted hold
03 31 inverted inactive
04 11 inverted inactive

Changing a relay function requires the same procedure as changing a LED


function.

02.03.07 Mo 29/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

2.6.13 Changing various parameters


Password change, voltage/cell, current limitations etc.

Main menu
System
settings
Temp. regulator Temp. corr. factor = -4.0mV / c / K ( -12.5 to 12.5)
Reference temperature 20 °C ( t= 0 to t= 50°C)
Warning text
EEP default settings* EEP default settings !!!!! Do not change!!!!
Password 1 Password 1 1 to 999
Password 2 Password 1 1 to 999
Internal address Internal address xx
Address Address xx
Boost level in V/cell Boost x.xx V/cell max. 2.5 V/cell
Float x.xx V/cell max. 2.5 V/cell
Direct feed x.xx V/cell max. 2.5 V/cell
Battery test x.xx V/cell max. 2.5 V/cell
Manual x.xx V/cell max. 2.5 V/cell
Equal charge x.xx V/cell max. 3.0 V/cell
Current limit Static xxx % I = xxx.x A
Battery circuit xxx % I = xxx.x A
Equal charge xxx % I = xxx.x A

Temperature correction (battery charging) / reference temperature:

These values determine the temperature-dependent battery charging. The fac-


tory settings values are listed in the "Technical data sheet" of the device. The
default setting is 4.0V / C / K. If the curve is to be changed, the temperature
factor and the reference temperature must be considered. The default value of
the program is 20°C.

EEP default settings:


This function allows to completely reset the EEProm values. Consequentially,
the controller must be completely configured and calibrated. A warning text is
displayed!
Furthermore, this function is only possible with a test bridge "X40" inserted in
the controller.

Password 1 and 2 :
Please change both passwords when starting the device. This protects the sys-
tem against unauthorised interventions.

02.03.07 Mo 30/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

Charge level in V/cell:


Here, all factory settings can be changed.

This changes may be made by instructed staff only.

Risk of destruction of plant parts like battery or loads.

Attention! When changing the voltage and current values, it is possible


that the monitoring parameters are not correct anymore.

It is recommended to contact the manufacturer before making the


changes.

Current limits

Static: Current limit of the charging current

Battery circuit: Current limit of the battery charging current


Attention! No discharging current limitation!
The percentages display indicates at 100% the nominal
current of the installed battery shunt.

Equal charge: Current limit of the equalise charging current.

The percentages refer to the battery shunt of the device. The current value set
in factory is listed in the technical data sheet. The default
value is 20% of the nominal current.

02.03.07 Mo 31/32 4408 GB


Indicator and operating unit
of the model series Thysat TDG3

2.6.14 Calibration*
Furthermore, this function is only possible with a test bridge "X40" inserted in
the controller.

Main menu
System set-
tings
Password 2 Calibration
Rectifier current
Rectifier voltage
Voltage 2
Set value I
Set value U
15V-supply mains
15 V-supply DC
Earth resistance
Device temp.
Battery temp.
Battery current

2.7 Logbook
The controller includes a ring buffer with the last 200 fault conditions (the so-
called fault log). You can call up this log at any time from the main menu
while the basic display is active. Then, you can scroll through the entries using
the jog dials. The last entry will always appear first. Use button to delete
all entries.

Main menu
Logbook
Date
Time
Error messages
Status messages

02.03.07 Mo 32/32 4408 GB

You might also like