 Technical data
                         Electrical data   Nominal voltage                            AC 24...240 V / DC 24...125 V
                                           Nominal voltage frequency                  50/60 Hz
                                           Nominal voltage range                      AC 19.2...264 V / DC 19.2...137.5 V
                                           Power consumption in operation             20 W
                                           Power consumption in rest position         6W
                                           Power consumption for wire sizing          with 24 V 20 VA / with 230 V 52 VA
                                           Auxiliary switch                           2 x SPDT, 1 x 10° / 1 x 0...90° (ex works 85°)
                                           Switching capacity auxiliary switch        1 mA...3 (0.5 inductive) A, AC 250 V
                                           Connection supply                          Terminals 2.5 mm²
                                           Connection control                         Terminals 1.5 mm²
                                           Connection auxiliary switch                Terminals 2.5 mm²
                                           Parallel operation                         Yes (note the performance data)
                       Functional data     Torque motor                               160 Nm (parameterized for D6250W/WL)
                                           Communicative control                      MP-Bus
                                                                                      BACnet MS/TP (Details see seperate document
                                                                                      “PICS”)
                                           Positioning signal Y                       DC 0...10 V
                                           Positioning signal Y note                  Input impedance 100 kΩ
                                           Operating range Y                          DC 2...10 V
                                           Operating range Y variable                 DC 0.5...10 V
                                                                                      4...20 mA
                                           Position feedback U                        DC 2...10 V
                                           Position feedback U note                   Max. 0.5 mA
                                           Position feedback U variable               DC 0.5...10 V
                                           Position accuracy                          ±5%
                                           Manual override                            with hand crank, can be fixed in any position
                                           Running time motor                         35 s / 90°
                                           Motor running time variable                30...120 s
                                           Sound power level motor                    68 dB(A)
                                           Position indication                        Mechanically (integrated)
                                 Safety    Protection class IEC/EN                    II reinforced insulation
                                           Protection class UL                        II reinforced insulation
                                           Protection class auxiliary switch IEC/EN   II reinforced insulation
                                           Degree of protection IEC/EN                IP66 + IP67
                                           Degree of protection NEMA/UL               NEMA 4X, UL Enclosure Type 4X
                                           EMC                                        CE according to 2014/30/EU
                                           Low voltage directive                      CE according to 2014/35/EU
                                           Certification IEC/EN                       IEC/EN 60730-1 and IEC/EN 60730-2-14
                                           Certification UL                           cULus according to UL 60730-1A, UL 60730-2-
                                                                                      14 and CAN/CSA E60730-1:02
                                           Mode of operation                          Type 1
                                           Rated impulse voltage supply               4 kV
                                           Rated impulse voltage control              0.8 kV
                                           Rated impulse voltage auxiliary switch     2.5 kV
                                           Control pollution degree                   3
                                           Ambient temperature                        -30...50°C
                                           Non-operating temperature                  -40...80°C
                                           Ambient humidity                           95% r.h., non-condensing
                                           Maintenance                                Maintenance-free
    Technical data
                           Mechanical data       Connection flange                          F07 (F05 only with accessory)
    Safety notes
                                                 • This device has been designed for use in stationary heating, ventilation and air
                                         !         conditioning systems and must not be used outside the specified field of application,
                                                   especially in aircraft or in any other airborne means of transport.
                                                 • Caution: Power supply voltage!
                                                 • Only authorised specialists may carry out installation. All applicable legal or
                                                   institutional installation regulations must be complied during installation.
                                                 • Apart from the connection box, the device may only be opened at the manufacturer’s
                                                   site. It does not contain any parts that can be replaced or repaired by the user.
                                                 • The device contains electrical and electronic components and must not be disposed
                                                   of as household refuse. All locally valid regulations and requirements must be
                                                   observed.
    Product features
                        Fields of application    The actuator is particularly suitable for utilisation in outdoor applications and is
                                                 protected against the following weather conditions:
                                                 - UV radiation
                                                 - dirt / dust
                                                 - rain / snow
                                                 - Humidity
                      Converter for sensors      Connection option for two passive sensors. This means the analogue sensor signal
                                                 can be easily digitised and transferred via field bus to the higher level system.
               Parameterisable actuators         The factory settings cover the most common applications.
                                                 The Belimo Assistant App is required for parameterisation via Near Field
                                                 Communication (NFC) and simplifies commissioning. Moreover, it provides a variety of
                                                 diagnostic options.
                                                 The ZTH EU service tool provides a selection of both diagnostic and setting options.
                     Simple direct mounting      Simple direct mounting on the butterfly valve. The mounting orientation in relation to
                                                 the butterfly valve can be selected in 90° (angle) increments.
                            Manual override      The valve can be manually operated using a hand crank. Unlocking is carried out
                                                 manually by removing the hand crank.
                             Internal heating    An internal heater prevents condensation buildup.
                                                 Thanks to the integrated temperature and humidity sensor the built-in heater
                                                 automatically switches on and off.
                   High functional reliability   The actuator is overload protected, requires no limit switches and automatically stops
                                                 when the end stop is reached.
                       Flexible signalization    The actuator has one auxiliary switch with a fixed setting (10°) and one adjustable
                                                 auxiliary switch (0...90°).
Accessories
                                                 Description                                                              Type
                                  Gateways       Gateway MP for BACnet MS/TP, AC/DC 24 V                                  UK24BAC
                                                 Gateway MP to Modbus RTU, AC/DC 24 V                                     UK24MOD
                                                 Gateway MP to LonWorks, AC/DC 24 V, LonMark certified                    UK24LON
                                                 Gateway MP to KNX, AC/DC 24 V, EIBA certified                            UK24EIB
                                                 Description                                                              Type
                     Electrical accessories      Connection cable 5 m, A+B: RJ12 6/6, To ZTH/ZIP-USB-MP                   ZK1-GEN
                                                 Description                                                              Type
                   Mechanical accessories        Position indicator and tappet shaft, F07, square, SW 17                  ZPR01
                                                 Tappet shaft, F07, square, SW 17                                         ZPR02
                                                 Position indicator and tappet shaft, F05, square, SW 14                  ZPR03
Accessories
                                           Description                                                                             Type
                                           Retrofit adapter kit, F05/F07, flat head/ square, SW 17                                 ZPR05
                                           Retrofit adapter kit, F05/F07, square 45° turned, SW 14                                 ZPR06
                                           Retrofit adapter kit with ring, F07, square 45° turned, SW 17                           ZPR08
                                           Retrofit adapter kit with ring, F07, flat head/ square, SW 14                           ZPR09
                                           Retrofit adapter kit, F05/F07, flat head/ square, SW 14                                 ZPR10
                                           Retrofit adapter kit, F05/F07, square 45° turned, SW 18                                 ZPR11
                                           Retrofit adapter kit, F05/F07, flat head/ square, SW 16                                 ZPR12
                                           Hand crank for PR-actuator                                                              ZPR20
                                           Description                                                                             Type
                           Service Tools   Smartphone app for easy commissioning, parameterising and                               Belimo Assistant
                                           maintenance                                                                             App
                                           Service tool for parametrisable and communicative Belimo actuators /                    ZTH EU
                                           VAV controller and HVAC performance devices
                                           Description                                                                             Type
                                Sensors    Duct/Immersion Temperature Sensor 50 mm x 6 mm PT1000                                   01DT-1BH
                                           Duct/Immersion Temperature Sensor 100 mm x 6 mm PT1000                                  01DT-1BL
                                           Duct/Immersion Temperature Sensor 150 mm x 6 mm PT1000                                  01DT-1BN
                                           Duct/Immersion Temperature Sensor 200 mm x 6 mm PT1000                                  01DT-1BP
                                           Duct/Immersion Temperature Sensor 300 mm x 6 mm PT1000                                  01DT-1BR
                                           Duct/Immersion Temperature Sensor 450 mm x 6 mm PT1000                                  01DT-1BT
                                           Duct/Immersion Temperature Sensor 50 mm x 6 mm Ni1000                                   01DT-1CH
                                           Duct/Immersion Temperature Sensor 100 mm x 6 mm Ni1000                                  01DT-1CL
                                           Duct/Immersion Temperature Sensor 150 mm x 6 mm Ni1000                                  01DT-1CN
                                           Duct/Immersion Temperature Sensor 200 mm x 6 mm Ni1000                                  01DT-1CP
                                           Duct/Immersion Temperature Sensor 300 mm x 6 mm Ni1000                                  01DT-1CR
                                           Duct/Immersion Temperature Sensor 450 mm x 6 mm Ni1000                                  01DT-1CT
Electrical installation
Wiring diagrams
T1 Com
T2 Com
 N L Y1 Y2 (N)                   N L Y1 Y2 (N)
                                                                               U5/MP
                                                     - Com
Com
                                                                                                                         D+
                                                                          Y3
                                                                                                              T2
                                                                                                T1
D-
    Electrical installation
Connection auxiliary switch
       230 V + 230 V
        24 V + 24 V
       230 V + 24 V
        24 V + 230 V
S1 S2 S3 S4 S5 S6
A 10% B 0...100%
    N L
                                +24VDC Out
T1 Com
T1 Com
T2 Com
    N L Y1 Y2 (N)
                                                     U5/MP
                                             Y3Out
                       - Com
Com
                                                                                                         D+
                                                                                              T2
                                                                                T1
D-
                                                                                                                                            GND
                                                                                                                                            DC (0)2...10 V
                                                                                                                                            DC 2...10 V
                                +24VDC Out
+24VDC Out
    N L Y1 Y2 (N)                                                       N L Y1 Y2 (N)
                                                     U5/MP
                                                                                                                                    U5/MP
                       - Com
                                                                                                         - Com
                                             Y3
Y3
 Functions
Functions for actuators with specific parameters (Parametrisation with Belimo Assistant App necessary)
Open-close control
 N L                                                                                                 N L
GND GND
DC 2...10 V DC 2...10 V
                                                                                                                             +24VDC Out
                             +24VDC Out
N L Y1 Y2 (N) N L Y1 Y2 (N)
                                                                                                                                               U5/MP
                                                U5/MP
                                                                                                                     - Com
                     - Com
                                                                                                                                          Y3
                                           Y3
3-point control
 N L
GND
DC 2...10 V
          0
                             +24VDC Out
 N L Y1 Y2 (N)
                                                U5/MP
                     - Com
Y3
Power Y1 Y2 Control
Control 4...20 mA
 N L
                                                                        (-)
                                                                                       4...20 mA
                                                                        (+)
                                                                        DC 2...10 V
                             +24VDC Out
T1 Com
T2 Com
 N L Y1 Y2 (N)
                                                U5/MP
                     - Com
Com
                                                                                           D+
                                           Y3
                                                                                T2
                                                                  T1
D-
Positioner SG..
 N L                                                    SGA24
                     - + Y Z                            SGF24
                     1 2 3 4                            SGE24
                              +24VDC Out
T1 Com
T2 Com
 N L Y1 Y2 (N)                                                                                                                                         Note
                                                U5/MP
                     - Com
Com
                                                                                T2
                                                                  T1
D-
    Functions
Connection on the MP-Bus
       GND
                                                                                                 A)
       MP
    N L
                            +24VDC Out
T1 Com
T2 Com
    N L Y1 Y2 (N)
                                               U5/MP
                    - Com
Com
                                                                                            D+
                                          Y3
                                                                                 T2
                                                                   T1
                                                                                                 D-
       Power                Control                               Sensor                RS485
                                                                                                                                A) Additional actuators (max. 8)
Network topology
N L
                                                                                                      1)              2)
                             +24VDC Out
T1 Com
T2 Com
    N L Y1 Y2 (N)
                                               U5/MP
Com
                                                                                                                                1) Resistance range
                                                                                            D+
                                          Y3
                                                                                 T2
                                                                   T1
D-
                                                                                                      2 kΩ...10 kΩ    1Ω        2) Resolution
       Power                Control                               Sensor                RS485                                   - Suitable for Ni1000 and PT1000
                                                                                                      10 kΩ...55 kΩ   10 Ω
                                                                                                                                - Suitable Belimo types 01DT-…
 Functions
Connection BACnet MS/TP
             GND
              D+
              D-
N L N L
 N L Y1 Y2 (N)                                                                      N L Y1 Y2 (N)
                                         Com
                                                                                                      Com
                                                D+
                                                                                                            D+
                                                       D-
                                                                                                                 D-
     Power                                RS485                                         Power           RS485
       GND
        D+
        D-
GND
N L DC (0)2...10 V
                                                            DC 2...10 V
                            +24VDC Out
T1 Com
T2 Com
 N L Y1 Y2 (N)
                                               U5/MP
                   - Com
Com
                                                                                            D+
                                         Y3
                                                                               T2
                                                                 T1
D-
                                                                      S5 S6   S5 S6
                                                                                          !      Note         Perform settings on the actuator only in deenergised state.
                                   A           10° S1                   S4      S4
                                                   S2 S3
                                                           3
                                           S5 S6   S5 S6
                                                                                      1       Gear disengagement
                                             S4      S4
                o
               pe
                n
                                                                                              Opening the manual override cover and adjusting the hand crank.
                                                                                              Manual override is possible.
                    S1 S2 S3   S4 S5 S6
                                                                                      4       Terminals
                               4                                                              Connect continuity tester to S4 + S5 or to S4 + S6.
                                                                                              If the auxiliary switch should switch in the opposite direction, rotate the hand
                                                                                              crank by 180°.
 Service
                    NFC connection     Belimo equipment marked with the NFC logo can be operated with the “Belimo
                                       Assistant App”.
                                       Requirement:
                                       - NFC-capable Android smartphone
                                       - Belimo Assistant App (Google Play Store)
Align smartphone on the actuator so that both NFC antennas are superposed.
Service Tools connection The actuator can be parameterised by the ZTH EU via the service socket.
                                                                                 MP
                                                                                 USB
i esc OK
 Dimensions [mm]
                                    Dimensional drawings
                                                                                                 >100
                                                                                                137
                                                               223
                                       60                        259
                                                  pe
                                                     o
                                                 n
                                                                                                202
                                                                   pe
                                                                       o
                                                                   n
319
 Further documentation
                                • Overview Valve-actuator combinations
                                •    Data sheets for butterfly valves
                                •    Installation instructions for actuators and/or butterfly valves
                                •    General notes for project planning
                                •    Overview MP Cooperation Partners
                                •    Tool connections
                                •    Introduction to MP-Bus Technology