Submittal Ref.

#: SQJMB001020_1

Design Envelope Split-Coupled Vertical In-Line Pump


Model: Series Design Envelope Sensorless 4300 8019-011.0 with Suction Guide and Flo-Trex Valve
Project name: Representative:
Location: Phone number:
Date submitted: 10/28/2024 8:26 AM e-mail:
Engineer: Submitted by: Widjaja, Sandi
Application design data
Tag number: Pompa Chiller (27LPS, Configuration: Single
IP55,with VSD)
Service: Suction pressure: 0 ft
Equipment Location: Fluid: Non-Potable Fluid - Water
Qty: 1 Operating temperature: 60 °F
Total system flow: 27 L/s Duty flow per pump: 27 L/s
System head: 300 kPa Viscosity: 31 SSU
Environment: Indoors Specific gravity: 1.0000
Total dissolved solids: 0 ppm Safety factor % flow: 0%
Efficiency at Design: 80.29 % Safety factor % head: 0%
NPSHR: 45.41 kPa Total Absorbed Power: 10.08 kW
Min. maintained 120 kPa Impeller diameter: 174 mm
pressure*:
PEIvl: Not applicable ERvl: Not applicable
CEI: Not applicable ERCEI: Not applicable
Standby qty: 0 Pump/motor run qty: 1
Outlet velocity: 18.57 ft/s Load Profile Location: NA
Climate Zone Type: NA Building Type: NA
Time Period: 8760 (1 Year)
Redundancy %: N/A

*If minimum maintained system pressure is not known, default is 40% of design head.
Materials of construction
Construction: Stainless Steel Fitted Impeller: 316 Stainless Steel
Rating: PN-16 Pump shaft: 316 Stainless Steel
Connections: PN-16 Flanges Inlet: 80mm, Flush line: Braided Stainless Steel
Outlet: 80mm
Casing (volute): Cast iron, e-coated Casing o-ring: Confined Non-Asbestos Fiber
Stub Shaft: N/A

Mechanical seal data


Seal type: Outside Balanced Rotating face: Resin Bonded Carbon
Manufacturer code: C-SSC AB2 Stationary seat: Sintered Silicon Carbide
Springs: Stainless Steel Secondary seal: Viton
Rotating hardware: Stainless Steel Maximum total dissolved 2000 PPM
solids (TDS)****:
Electrical data
Supplier: Armstrong Insulation class: Class F Insulation
Size: 11 kW Motor type: Permanent Magnet
Frame size: 132 Efficiency: IE5

www.armstrongfluidtechnology.com 10/28/2024 8:26:38 AM, Ref. #SQJMB001020_1 Page 1 of 5


Enclosure: TEFC Power supply: 415/3/50
Operating speed @ 100% 2924 rpm Operating speed @ 50% 2032 rpm
flow: flow***:
***Based on minimum pressure setting of 40% of design head.
****Note: Please ensure proper seal is selected by inputting Total Dissolved Solids (TDS) in PPM in ADEPT if water quality is
poor at site. Also select Flush Line Filter or Cyclone Separator if there are other contaminants in the fluid

DEPM controller data


Sensorless control: Yes - Quadratic press control Communication port: RS 485
Communication protocol (*): Default Field Reconfigurable Analog inputs: 2 (current or voltage)
Enclosure: UL Type 12/IP55 Analog outputs: 1 (current or voltage)
Fused disconnect switch: None Digital inputs: 2 (programmable)
Control orientation: L1 Digital outputs: 2 (programmable)
Expansion card: None Cooling: Not Applicable
Absorbed Power/BHP at 50% 5.54 kW Ambient temperature: -10°C to 45°C (up to 999.74 m
load/flow and 55% of design elevation)
head:
Meets ASHRAE 90.1: No EMI/RFI control: Integrated filter to meet EN61800-
3
Harmonic suppression: Integrated DC link reactor**
(*): If Default - Field reconfigurable is selected, Default from factory will be BACnet MS/TP and can be reconfigured in the field.
** The IVS control is a low harmonic control with a built-in DC link reactor equivalent in performance to a 5% AC line reactor. This
does not guarantee performance to any system wide harmonic specification or the costs to meet a system wide specification.

Performance curve
--Control Data—
Series 4300 1. Hmax @ 48.73 Hz:
NPSHR: 45.41 kPa
DEPM IVS Sensorless Intersection Pt: 27 l/s @ 300 kpa
80-190 @ 2924 rpm kwa=10.08 kW, eff=80.29 %%,
500 %bepq=6 %%
56 61 *PT-784-0-0
3300 rpm 66 ANSI/HI 14.6
71 2. Control (QPC) @ 44.51 Hz:
450 NPSHR: 35.81 kPa
75 Intersection Pt: 23.63 L/s @ 257.81
kPa
400 78 kwa=7.58 kw, eff=80.23%,
%bepq=96.03%
2924 rpm 80
350 3. Control (QPC) @ 40.29 Hz:
NPSHR: 27.02 kPa
Intersection Pt: 19.98 L/s @ 218.57
300 80 kPa
kwa=5.47 kw, eff=79.7%,
78
Head (kPa)

%bepq=89.69%
250 75
4. Control (QPC) @ 36.07 Hz:
71 NPSHR: 19.16 kPa
66 Intersection Pt: 15.93 L/s @ 182.66
200 kPa
61 kwa=3.73 kw, eff=77.94%,
56 %bepq=79.96%
150
5. Control (QPC) @ 31.85 Hz:
1655 rpm NPSHR: 12.34 kPa
100 11 kW Intersection Pt: 11.07 L/s @ 150.26
kPa
System kwa=2.3 kw, eff=72.19%,
50 %bepq=62.91%
900 rpm 6. Hmin: 120 kPa 27.63 Hz:
NPSHr NPSHR: 6.16 kPa
0 5 10 15 20 25 30 35 40 45 50 Intersection Pt: 0 L/s @ 120 kPa
(Head Q Min) Setting= 40% Hmax

Water, spgr=1.0000 Flow (L/s)


3.3.269-de74d024 / 55768

Design envelope pumping unit capability


Operating point Flow Head Efficiency

www.armstrongfluidtechnology.com 10/28/2024 8:26:38 AM, Ref. #SQJMB001020_1 Page 2 of 5


Full capability at 100% design flow 27 L/s 338.39 kPa 80.23%
Design point 27 L/s 300 kPa 80.29 %
50% average flow (with default load profile) 13.5 L/s 165 kPa 75.81 %
Motor Capability @ Rated Speed 11.08 Kw

Operating limits (temperature - pressure)

Maximum pressure: 16 bar

Maximum temperature: 120 °C

All Pump casings are hydrostatically tested to requirements of ANSI/HI 14.6 standard.

Options
Sensorless Bundle: Yes DEPC Parallel Sensorless: No
Energy Performance Bundle: No Protection Bundle: No
Dual Season Setup: No Zone Optimization Bundle: No

Cooling Heating
Q1: N/A Q2: N/A
H1: N/A H2: N/A
H1min: N/A H2min: N/A
Maximum Flow: N/A Minimum Flow: N/A

Optional Services
On-Site Pump Commissioning: Cost not Included Extended Warranty: No
Pump Manager: Yes,Standard (1 Include Spare Parts Qty: 0
Year Pump Manager
Professional

Dimensional data (not for construction)


Side view Top view

www.armstrongfluidtechnology.com 10/28/2024 8:26:38 AM, Ref. #SQJMB001020_1 Page 3 of 5


Weight: 422.4 lb [191.6 kg], Units of measure: inches [millimeters]
• R = minimum lifting clearance required above motor
• Coupling guard and flush line (not shown) are supplied
• Tolerance of ± 0.125 inch (± 3 mm) should be used
• For certified dimensions, please contact your Armstrong representative
• Pump equipped with casing drain plug and ¼ inch NPT suction and
discharge gauge ports

Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 80 PN-16 200 8 160 M16
Outlet 80 PN-16 200 8 160 M16
*Equally spaced straddling centreline

Flow Readout Accuracy


The Design Envelope model selected will provide flow reading on the pump touchscreen & digitally for the BMS. The flow
readout will be factory tested to ensure ± 5% accuracy.
Custom options
Other (Describe product and specific option required) - 1) IP55+rainhood for outdoor condition 2) Pump performance test
report 3) Pump QAQC & vibration test report 4) Motor routine test report 5) Impeler balancing report

Selected options
Testing: Factory Test
Seal Environment Accessories: None
Pump Export Package: Yes - Ready for Container
Pre-Wired Control Bridge: No
Sensorless Bundle: Sensorless control
Constant flow control
Constant pressure control
Flow readout

Design Envelope pumps offer industry-leading efficiency and performance management capabilities for significantly reduced
energy consumption. Armstrong has undertaken a multi-year project to transition our pump offering to an integrated design
that use Design Envelope Permanent Magnet technology for even greater operating cost savings. In the sizes currently
equipped with Design Envelope Permanent Magnet motors, the pumps are also more compact and lighter than our standard

www.armstrongfluidtechnology.com 10/28/2024 8:26:38 AM, Ref. #SQJMB001020_1 Page 4 of 5


Design Envelope pumps.
Please note that depending on the pump sizes, your shipment may include a combination of:
• Design Envelope Permanent Magnet pumps
• Design Envelope Permanent Magnet pumps with IVS controls
• Design Envelope Pumps with IE3 efficiency induction motors and IVS controls

www.armstrongfluidtechnology.com 10/28/2024 8:26:38 AM, Ref. #SQJMB001020_1 Page 5 of 5


Submittal Ref. #: SQJMB001020_1

Suction guide
Model: SG-63
Project name: FY24_ID_Indonesia DC Representative: Sandi Widjaja
Location: Phone number:
Date submitted: 10/28/2024 8:26 AM e-mail: [email protected]
Engineer: Submitted by: Widjaja, Sandi
Application design data
Tag Qty Model Pipe Pump Design Pressure Associated pump
Conn.size Conn.size flowrate Drop*
Pompa 1 SG-63 DN150 DN80 27 L/s 0.7 ft Design Envelope Sensorless
Chiller 4300 8019-011.0
(27LPS,
IP55,wi
th VSD)
*at design flow

Materials of construction
SG-63
Body: Cast Iron Cover gasket: Synthetic fiber
Guide vanes: Cast Iron Strainer: Stainless Steel,0.188"(5mm)Perf..
Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel

*Remove start up strainer after 24 hours of pump operation

Operating limits (temperature - pressure)

SG-63-Suction Guide-PN-16

Maximum pressure: 16 bar


Maximum temperature: 150 C

Units are hydrostatically tested to 150% of


maximum working pressure

www.armstrongfluidtechnology.com 10/28/2024 8:26:38 AM, Ref. # SQJMB001020_1 Page 1 of 2


Dimensional data (not for construction)
SG-63 Weight: 120.57 lb [54.69 kg]
Side view Top view

Not to scale
Units of measure: inches [millimeters]
Tolerance of +/- 0.125 inch (+/- 3 mm) should be used
For certified dimensions, please contact your Armstrong representative

www.armstrongfluidtechnology.com 10/28/2024 8:26:38 AM, Ref. # SQJMB001020_1 Page 2 of 2


Submittal Ref. #: SQJMB001020_1

Flo-trex valve
Model: FTV-5FA-Flo-Trex Valve-PN-16-Angle
Project name: FY24_ID_Indonesia DC Representative: Sandi Widjaja
Location: Phone number:
Date submitted: 10/28/2024 8:26 AM e-mail: [email protected]
Engineer: Submitted by: Widjaja, Sandi

Application design data


Tag Qty Model Size Config Pipe Design Pressure Associated pump
Inlet/Outlet Type flowrate Drop*
Pomp 1 FTV-5FA DN125 Angle Flanged 27 L/s 3.03 ft Design Envelope Sensorless
a 4300 8019-011.0
Chille
r
(27LP
S,
IP55,
with
VSD)

*at design flow

Materials of construction
FTV-5FA-Flo-Trex Valve-PN-16-Angle
Body: Cast Iron Spring: 302 Stainless Steel
Disc: Brass O rings: BUNA N
Seat: EPDM 2 metering ports: NPT Brass Body with EPT Check and Gasketed Cap
Stem: 416 Stainless Steel 2 drain tappings: 1/4in with Brass Plug

Operating limits (temperature - pressure)

FTV-5FA-Flo-Trex Valve-PN-16-Angle

Maximum pressure: 16 bar


Maximum temperature: 150 C

www.armstrongfluidtechnology.com 10/28/2024 8:26:38 AM, Ref. #SQJMB001020_1 Page 1 of 2


Dimensional data (not for construction)
Model: FTV-5FA-Flo-Trex Valve-PN-16-Angle Weight: 108 lb [48.99 kg]
Side view Front view

Not to scale
Units of measure: inches [millimeters]
Tolerance of +/- 0.125 inch (+/- 3 mm) should be used
For certified dimensions, please contact your Armstrong representative

www.armstrongfluidtechnology.com 10/28/2024 8:26:38 AM, Ref. #SQJMB001020_1 Page 2 of 2


Quote Reference: SQJMB001020_1
Quote Name:
Project Name: FY24_ID_Indonesia DC
Date: 2024-10-28

Recommended Spare Parts and Kits

Item Description
No.

Design Envelope and Commercial Pumps

Available spare parts and kits for Design Envelope Sensorless 4300 8019-011.0 with Suction Guide and Flo-
Trex Valve

Part/Kit Armstrong Includes


Part number

Pump Casing Gasket Parts 8426401-003 Gasket

Pump Mechanical Seal Parts 8975002-304 Mechanical Seal

Design Envelope Pump Controller Parts 880100-006 LCD resistive Touch Screen, IVS102 LCD-
Kit PCBholder, PCB board w/o firmware, DEPC
LCD support foam

Pump Split Coupling Parts Kits 8428904-000K Split Coupling, Collar, set screw, Key,
Capscrew & Washer

STD Flush Braided Hose 8939031-720 Braided hose Assembly


1.0

Front Shroud w/o fused disconnect Kit 8428951-000K shroud, Screws & washers

Touchscreen Cover Parts Kit 8429041-106K Screen Cover Frame, Screen Cover Door,
Pin,Tape & Bazel

Weather Shield Replacement Kit 8428954-000K Awning shield, Screws & Washer

IVS102 DEPC Screen Replacement Kit 880100-009 LCD Resistive Touch Screen, Display Guard
0.7mm

Spare Filter 8975000-303 filter-cartridge

Note: List above is the complete list of all available spare parts or kits for the pump size mentioned and not a
commitment of inclusion in project supply scope.
Ensure required spare parts and kits are configured with pump separately. More details of those selected
parts/kits (if any) shall be included in earlier page(s).
Quote Reference: SQJMB001020_1
Quote Name:
Project Name: FY24_ID_Indonesia DC
Date: 2024-10-28

Recommended Spare Parts and Kits


Design Envelope and Commercial Pumps

Available spare parts and kits for Design Envelope Sensorless 4300 8019-011.0 with Suction Guide and Flo-
Trex Valve

Part/Kit Armstrong Includes


Part number

Pump Casing Gasket Parts 8426401-003 Gasket

Pump Mechanical Seal Parts 8975002-304 Mechanical Seal

Design Envelope Pump Controller Parts 880100-006 LCD resistive Touch Screen, IVS102 LCD-
Kit PCBholder, PCB board w/o firmware, DEPC
LCD support foam

Pump Split Coupling Parts Kits 8428904-000K Split Coupling, Collar, set screw, Key,
Capscrew & Washer

STD Flush Braided Hose 8939031-720 Braided hose Assembly


2.0

Front Shroud w/o fused disconnect Kit 8428951-000K shroud, Screws & washers

Touchscreen Cover Parts Kit 8429041-106K Screen Cover Frame, Screen Cover Door,
Pin,Tape & Bazel

Weather Shield Replacement Kit 8428954-000K Awning shield, Screws & Washer

IVS102 DEPC Screen Replacement Kit 880100-009 LCD Resistive Touch Screen, Display Guard
0.7mm

Spare Filter 8975000-303 filter-cartridge

Note: List above is the complete list of all available spare parts or kits for the pump size mentioned and not a
commitment of inclusion in project supply scope.
Ensure required spare parts and kits are configured with pump separately. More details of those selected
parts/kits (if any) shall be included in earlier page(s).
Quote Reference: SQJMB001020_1
Quote Name:
Project Name: FY24_ID_Indonesia DC
Date: 2024-10-28

Recommended Spare Parts and Kits


Design Envelope and Commercial Pumps

Available spare parts and kits for 4300 - 80-190 - 2p - 11 kW - (Factory Choice Motor) with Suction Guide
and Flo-Trex Valve

Part/Kit Armstrong Includes


Part number

Pump Casing Gasket Parts 8426401-003 Gasket

Pump Mechanical Seal Parts 8975002-304 Mechanical Seal

3.0 Pump Split Coupling Parts Kits 8427745-000K Split Coupling, Collar, Capscrew & Washer

STD Flush Braided Hose 8939031-720 Braided hose Assembly

Spare Filter 8975000-303 filter-cartridge

Note: List above is the complete list of all available spare parts or kits for the pump size mentioned and not a
commitment of inclusion in project supply scope.
Ensure required spare parts and kits are configured with pump separately. More details of those selected
parts/kits (if any) shall be included in earlier page(s).

Design Envelope and Commercial Pumps

Available spare parts and kits for 4300 - 80-190 - 2p - 11 kW - (Factory Choice Motor) with Suction Guide
and Flo-Trex Valve

Part/Kit Armstrong Includes


Part number

Pump Casing Gasket Parts 8426401-003 Gasket

Pump Mechanical Seal Parts 8975002-304 Mechanical Seal

4.0 Pump Split Coupling Parts Kits 8427745-000K Split Coupling, Collar, Capscrew & Washer

STD Flush Braided Hose 8939031-720 Braided hose Assembly

Spare Filter 8975000-303 filter-cartridge

Note: List above is the complete list of all available spare parts or kits for the pump size mentioned and not a
commitment of inclusion in project supply scope.
Ensure required spare parts and kits are configured with pump separately. More details of those selected
parts/kits (if any) shall be included in earlier page(s).
Quote Reference: SQJMB001020_1
Quote Name:
Project Name: FY24_ID_Indonesia DC
Date: 2024-10-28

Recommended Spare Parts and Kits


Design Envelope and Commercial Pumps

Available spare parts and kits for 4300 - 80-190 - 2p - 11 kW - (Factory Choice Motor) with Suction Guide
and Flo-Trex Valve

Part/Kit Armstrong Includes


Part number

Pump Casing Gasket Parts 8426401-003 Gasket

Pump Mechanical Seal Parts 8975002-304 Mechanical Seal

5.0 Pump Split Coupling Parts Kits 8427745-000K Split Coupling, Collar, Capscrew & Washer

STD Flush Braided Hose 8939031-720 Braided hose Assembly

Spare Filter 8975000-303 filter-cartridge

Note: List above is the complete list of all available spare parts or kits for the pump size mentioned and not a
commitment of inclusion in project supply scope.
Ensure required spare parts and kits are configured with pump separately. More details of those selected
parts/kits (if any) shall be included in earlier page(s).
Quote Reference: SQJMB001020_1
Quote Name:
Project Name: FY24_ID_Indonesia DC
Date: 2024-10-28

Recommended Spare Parts and Kits


Design Envelope and Commercial Pumps

Available spare parts and kits for Design Envelope Sensorless 4300 8019-011.0 with Suction Guide and Flo-
Trex Valve

Part/Kit Armstrong Includes


Part number

Pump Casing Gasket Parts 8426401-003 Gasket

Pump Mechanical Seal Parts 8975002-304 Mechanical Seal

Design Envelope Pump Controller Parts 880100-006 LCD resistive Touch Screen, IVS102 LCD-
Kit PCBholder, PCB board w/o firmware, DEPC
LCD support foam

Pump Split Coupling Parts Kits 8428904-000K Split Coupling, Collar, set screw, Key,
Capscrew & Washer

STD Flush Braided Hose 8939031-720 Braided hose Assembly


6.0

Front Shroud w/o fused disconnect Kit 8428951-000K shroud, Screws & washers

Touchscreen Cover Parts Kit 8429041-106K Screen Cover Frame, Screen Cover Door,
Pin,Tape & Bazel

Weather Shield Replacement Kit 8428954-000K Awning shield, Screws & Washer

IVS102 DEPC Screen Replacement Kit 880100-009 LCD Resistive Touch Screen, Display Guard
0.7mm

Spare Filter 8975000-303 filter-cartridge

Note: List above is the complete list of all available spare parts or kits for the pump size mentioned and not a
commitment of inclusion in project supply scope.
Ensure required spare parts and kits are configured with pump separately. More details of those selected
parts/kits (if any) shall be included in earlier page(s).

You might also like