DELPHYS BC
Reliable, simple and ready-to-use power protection
from 160 to 300 kVA
Three-phase UPS
The solution for
> Server rooms
> Service sector
> Infrastructure
> Healthcare sector
> Light industrial applications
DEFYS 191 B
DEFYS 200 B
A complete, cost-effective Tailored to your environment
solution • Saves space with a reduced footprint and
• Online double conversion mode with an optimized cabinet size.
output power factor of 0.9 providing 12 % • Low noise level.
more active power compare to UPS with a • Compact, lightweight and easy to install.
power factor of 0.8. • No neutral required on rectifier input.
• Dual input mains allows you to manage • Two-wire battery connection (only +/-).
independent power sources. • Extended battery life and performance
• Increased system availability placing two with exclusive EBS battery charging
UPS in parallel for 1+1 redundancy. management for increased battery life.
• Internal manual bypass for easy
maintenance without power interruption
(1+1 configuration).
• Multilanguage display.
42 General Catalogue 2016
DELPHYS BC
Three-phase UPS
from 160 to 300 kVA
Standard electrical features Standard communication Remote monitoring service
• Dual input mains.
features • LINK-UPS, remote monitoring service that
• Integrated maintenance bypass. • 2 slots for communication options. connects your UPS to your Critical Power
• Backfeed protection: detection circuit. specialist 24/7.
• EBS (Expert Battery System) for battery Communication options
management.
• ADC interface (configurable voltage-free
contacts).
Electrical options
• MODBUS TCP.
• External battery cabinet. • MODBUS RTU.
• External temperature sensor. • PROFIBUS.
• Additional battery chargers. • NET VISION: professional WEB / SNMP
• Shared battery. interface for UPS monitoring and shutdown
• Galvanic isolation transformer. management of several operating systems.
• Parallel kit.
• ACS synchronization system.
Technical data
DELPHYS BC
Sn [kVA] 160 200 300
Pn [kW] 144 180 270
Parallel configuration up to 6 units
INPUT
Rated voltage 400 V 3ph
Voltage tolerance 240 V to 480 V(1)
Rated frequency 50 / 60 Hz ± 10 %
Power factor / THDI 0.99 / < 3 %
OUTPUT
Rated voltage 400 V
Voltage tolerance static load ±1 % dynamic load in accordance with VFI-SS-111
Rated frequency 50 / 60 Hz
Frequency tolerance ± 2 % (configurable from 1 % to 8 %)
Crest factor 3:1
BYPASS
Rated voltage rated output voltage
Voltage tolerance ± 15 % (configurable with from 10 % to 20 %)
Rated frequency 50 / 60 Hz
Frequency tolerance ± 2 % (configurable for Genset compatibility)
EFFICIENCY
Online mode @ 100 % of load up to 94 %
ENVIRONMENT
Operating ambient temperature from 0 °C up to +40(2) °C (from 15 °C to 25 °C for maximum battery life)
Relative humidity 0 % - 95 % without condensation
Maximum altitude 1000 m without derating (max. 3000 m)
Acoustic level at 1 m (ISO 3746) < 68 dBA < 71 dBA
UPS CABINET
Dimensions W x D x H 700 x 800 x 1930 mm 1000 x 950 x 1930 mm
Weight 480 kg 500 kg 830 kg
Degree of protection IP20
Colours RAL 7012, silver grey frontal door
STANDARDS
Safety IEC/EN 62040-1, AS 62040.1.1, AS 62040.1.2
EMC IEC/EN 62040-2, AS 62040.2
Performance IEC/EN 62040-3, AS 62040.3
Product declaration CE, RCM (E2376)
(1) Conditions apply.
General Catalogue 2016 43