CAT Advanced series

Circuit Breaker Analyzers & Timers


• Robust design for field use
• Accurate measurement in high voltage environment
• Both Sides Grounded feature for AIS and GIS (optional)
• Built-in micro ohmmeter (up to 500 A)
• Dynamic resistance measurement
• Detailed analysis of test results using DV-Win software
• Database of circuit breakers test plans

Description
The CAT Advanced series circuit breaker Multiple operations, such as Open-Close and
analyzers & timers are stand-alone or a PC- Open-Close-Open, can be initiated by using a
controlled digital instruments for circuit breakers predefined delay time or by sensing a breaker’s
condition assessments. CAT Advanced series contact position.
records graphs of both, open and close coil
The circuit breaker operation can be initiated in
currents and displacements of the HV and MV
different ways (for instance from a control room,
circuit breaker moving parts.
by a local switch or externally by a testing
The timing channels record closing and device) depending on a testing condition. The
opening of the arcing, resistor and auxiliary several time measurement triggers are available
contacts. The main contact channels can also to record a measurement in a various testing
measure the resistance value of the pre-insertion condition:
resistors (if present in the circuit breaker).
• external trigger
Furthermore, the main contact timing channels
can also measure main arcing contacts operation
• analog channels
time of AIS (Air Insulated Substation) circuit • auxiliary channels
breakers with both sides grounded (BSG). • coil control channel

CAT Advanced series provides an easy selection


of different operational modes: The auxiliary inputs are used to monitor dry and
wet auxiliary contacts. The six coil control analog
• Open (O) channels can measure and record coil currents
• Close (C) simultaneously (OPEN and CLOSE), up to 35 A
• Reclose (O-0,3s-C) AC/DC.
• Trip free (CO)
• O-0,3s-CO Built-in micro-ohmmeter provides high current
for dynamic and static resistance measurement,
• Open-Close (O-C)
as well as for BSG timing measurement of GIS
• Close-Open (C-O) (Gas Insulated Substation) and Dead tank AIS
• Open-Close-Open (O-C-O) (Air Insulated Substation) circuit breakers.
• First trip (O)
The additional six voltage analog channels have Three transducer channels provide measuring
four selectable voltage ranges available (±1 V, displacement of the circuit breaker moving parts,
±5 V, ±60 V and ±300 V AC/DC). They are used to contact wipe, over-travel, rebound, damping time
monitor: and an average velocity. Either an analog or a
• Measurement of coil resistance (simultaneously digital transducer can be connected to these
for 3 coils – during open or close sequence) universal channels.
• Circuit-breaker substation battery voltage,
Test results are printed on the 112 mm (4.4 inch)
• DC and AC currents during the “First trip” test,
thermal printer (optional accessory) in tabular
• CT secondary currents for BSG test on GIS
and graphical form.
• Other types of analog signals that may be
relevant.

Application

The list of the instrument applications includes:

• Simultaneous timing measurement of up to 12 main contacts (4 breaks per phase) including


pre-insertion resistors (if present in the circuit breaker) and 6 auxiliary contacts

• Resistance measurement of the pre-insertion resistors (if present in the circuit breaker)

• Evaluation of synchronization between the circuit breaker poles

• Measurement of the coil currents, voltages and resistance simultaneously for 6 coils

• Evaluating the state of substation’s batteries by graphically showing the voltage value

• Measurement of displacement, contact wipe, over-travel, rebound, damping time and average

velocity of the breaker’s moving parts

• Anti-pumping relay test

• “First trip” test

• Static resistance measurement

• Dynamic resistance measurement


B-CATADV-118-EN, 2023-02-06

Minimum operating voltage test (when used as CAT & SAT test system)

• Measurement of spring-charging motor time, current and voltage (both DC and AC power supply

voltage, when used as CAT & SAT test system)

2
CAT Advanced series
Circuit Breaker Analyzers & Timer
Features

1 - Mains power supply input 7 - Current clamps voltage supply 13 - Breaker state indicator
90 – 264 V AC;50 Hz – 60 Hz 24 V voltage output for current clamps Indicates CLOSE or OPEN breaker
position.
2 - PC communication 8 - Coil supply input
USB interface Separated voltage supply inputs for 14 - Micro Ohmmeter
open and close coil control. (built-in micro ohmmeter – up to 500 A
3 - Flash drive DC) for static and dynamic contact
Used for a direct download of test 9 - Motion transducer inputs resistance measurement (not available
results on a USB memory stick. Intended for measuring displacement with CAT64A and CAT124A)
of circuit breaker’s moving parts.
4 - Thermal printer (optional) 15 - Alphanumeric keypad
(Built-in 112 mm (4.4 inch) wide) 10 - Auxiliary inputs Used for entering breaker data,
Graphic and numeric printout of contact Used for timing measurement of dry or test data and control functions
and travel wave form wet auxiliary contacts.
16 - LCD display
5 - Main contacts inputs 11 - READY button 20 characters by 4 Lines; LCD display
Used for timing of the main and pre- Prepares the instrument for the start of with backlight, viewable in bright
insertion resistor contacts, and for the the test sunlight
resistance measurement of the pre-
insertion resistors. 12 - Coil control outputs & external
trigger input
6 - Analog channels inputs Used for operating the circuit breaker
B-CATADV-118-EN, 2023-02-06

Used for a voltage measurement of an OPEN and CLOSE coil or external


analog signal that may be relevant. trigger feature.

3
CAT Advanced series
Circuit Breaker Analyzers & Timer
Timing measurement

Timing measurement of the mechanical 60 Hz). Maximum difference between the


operations is one of the most important tests to instants of contacts touching within series
determine real condition of the circuit breaker. connected interrupter units shall not exceed a
Timing measurement tests fulfill all the 1/6 of a cycle of rated frequency (3,33 ms at 50
requirements defined by IEC 62271-100 and Hz; 2,78 ms at 60 Hz).
IEEE C37.09.
Auxiliary contacts are mechanically driven by the
In three-phase systems, not only the contacts in operating mechanism and are used for control
a single pole have to operate simultaneously, and indication of main contacts’ state. There are
but all poles must also operate at the same time. no general requirements, related to timing
All contacts must be synchronized, within a measurement of auxiliary contacts, described in
certain tolerance limit. IEC® and IEEE® standards. Anyway, in order to
assess condition of high-voltage circuit breakers,
Synchronization between the circuit breaker
it is important to check their operation.
poles during opening shall not exceed 1/6 of the
rated frequency cycle (3,33 ms at 50 Hz; 2,78 Type "a" contact follows circuit breaker main
ms at 60 Hz) and during closing shall not exceed contact position and must close/open ahead of
1/4 of the rated frequency cycle, as well (5,0 ms the closing/opening of the main contact. Type
at 50 Hz; 4,17 ms at 60 Hz). "a" contact is connected in series with the open
coil and interrupts the open coil circuit when the
Simultaneous measurements within a single
circuit breaker opens.
phase are important in situations where a
number of contacts are connected in series. The "b" contact must open/close when the
operating mechanism has released its stored
The maximum difference between the instants of
energy in order to close/open the breaker. Type
contact separation within series connected
"b" contact is connected in series with the
interrupter units shall not exceed 1/8 of a cycle
closing coil, interrupting the closing coil circuit
of rated frequency (2,50 ms at 50 Hz; 2,08 ms at
when the circuit breaker closes.
B-CATADV-118-EN, 2023-02-06

Connecting the main contact timing cables to a Live Tank circuit breaker with 4 breaking elements per phase
along with auxiliary timing cables to a test object

4
CAT Advanced series
Circuit Breaker Analyzers & Timer
Connecting the main contact timing cables to a Dead Tank circuit breaker with 1 breaking element per phase
along with auxiliary timing cables to a test object

Both Sides Grounded

Utilities and service companies increase their the circuit breaker prior to testing, and to
emphasis and demands on the safety reinstall the ground(s) after testing is complete.
regulations. Regulations and laws (IEEE This procedure is not desirable as it introduces a
Standard 510-1983) require all objects to be possibility that the ground may not be
grounded on both sides before any reconnected after the test, presenting a safety
maintenance work is performed on the object. hazard.
In all substations grounding on both sides of the
circuit breaker contacts is the best way to Both Sides Grounded (BSG) timing
provide safety If the circuit breaker (CB) is not measurement feature of Live Tank AIS (Air

grounded on both sides, there is a risk of Insulated Substation) circuit breakers


enables safe and fast testing in high voltage
appearance of induced high voltages and
substations, without removing the safety ground
currents at the ungrounded terminals. These
connections on both sides of the circuit breaker.
safety grounds also eliminate any static
No additional modules or remote boxes are
discharge in the circuit breaker contact and
required.
conduct any line power close to the circuit
Each main contact timing channel is able to
breaker while the personnel are working.
detect main contacts state in case when both
B-CATADV-118-EN, 2023-02-06

terminals are grounded. Therefore, for this


These earth grounds present a short-circuit
measurement same main contact cables are
condition to the traditional test equipment, and
used as for conventional timing measurement.
therefore the circuit breaker always looks to be
in the closed state. In practice, it is necessary to
remove at least one of the safety grounds from
5
CAT Advanced series
Circuit Breaker Analyzers & Timer
Both Sides Grounded (BSG) of GIS (Gas Built-in micro ohmmeter (up to 500 A) is used as
Insulated Substation) feature enables timing a DC current source. A connection from a
measurement of GIS circuit breakers contact current source to circuit breaker terminals is
time without having to remove detachable performed with current cables which further
shunts for grounding of GIS circuit breaker branch each in three cables, providing in that
terminals. The same method is used for timing way the equal current distribution through all
measurement of Dead Tank AIS (Air Insulated three main contacts.
Substation) circuit breakers contact time with The AC transformer based current probes are
any type of grounding system being applied to connected to accessible CT secondary
both sides of the bushings. terminals. The current AC probes, which outputs
Method is based on the DC current generation are connected to analog channels inputs, will
through the main circuit and measurement detect a change in the response signals when
voltage or current response on the CT the circuit breaker contact is opened or closed.
secondary during CB operation.
B-CATADV-118-EN, 2023-02-06

Timing measurements on Gas Insulated Switchgear (GIS) with grounding on both sides
6
CAT Advanced series
Circuit Breaker Analyzers & Timer
Motion measurement

Motion measurement of the high voltage circuit


breakers’ contact system is of crucial importance
for assessing a condition of the test object. The
three motion transducer channels can acquire
data from 3 linear or rotary motion transducers.
Each channel can be configured for either an
analog or a digital transducer.
Due to universal transducer channels design, a
user can connect a variety of motion transducers
available on the market.
Performance values such as stroke, over-travel,
rebound, contact wipe are obtained as a result
Digital rotary transducer mounted on ABB LTB 245 kV
of the measurement. These values can be
SF6 circuit breaker
compared to the manufacturer’s reference data
and data acquired from previous measurements. User is usually allowed to mount transducers on
This provides indications about potential wear of accessible parts of the circuit breaker’s
the breaker. mechanical linkage. Beside this, instrument
often records rotary motion, even it is known the
Average velocity is calculated between the two main contacts motion is linear. As a result,
points on the motion curve. The upper point is motion results obtained do not represent real
defined as a distance in length or time elapsed movement of the main contacts, but just linear or
from the breaker’s closed position, or contact- nonlinear interpretation of the main contacts
separation point. The lower point is determined moving parts displacement. DV-Win software
based on the upper point. It can either be a provides transfer function feature which allows
distance below the upper point or a time before user to define linear or non-linear parameters in
the upper point. Up to 5 zones for average order to obtain actual displacement values of the
velocity calculation can be selected. main contact moving parts.
B-CATADV-118-EN, 2023-02-06

7
CAT Advanced series
Circuit Breaker Analyzers & Timer
Coil current measurement

The IEC 62271-100 standard states that it is 3) until it hits a buffer bringing it to a rest (point
desirable to record the coil currents waveform, 3). If the current values at points 2 and 3 are
since it provides information about coils’ higher than specified and the time at point 3 is
condition (e.g. increased friction of the plungers, longer than specified, it may indicate a friction of
burned insulation, short-circuited part of the the plunger and latch. With the plunger at rest,
winding), the latch for release of the operating the current increases to the saturation level (DC
mechanism (e.g. increased friction) and the current, which is proportional to the coil
operating mechanism (e.g. if there is reduced resistance, point 4). If the current value from
operating mechanism speed that can be seen point 4 to point 5 deviates from specific it may
based on the opening time of auxiliary contacts). indicate a burned insulation or short-circuited
part of the winding of coil. Meanwhile, the latch
When the opening or closing command is
unlocks operating mechanism, releasing the
initiated, the coil is energized (point 1) and the
stored energy to open the main breaker
current rises causing a magnetic field to apply a
contacts. Typically, after a short delay the
force on the iron plunger. When the force on the
auxiliary contacts open, disconnecting the
plunger exceeds the retaining force the plunger
opening coil from the control voltage (point 5).
begins to move (point 2). The motion of the iron
As the coil is de-energized the current drops
plunger induces an EMF in the coil, effectively
quickly to zero in accordance with the coil
reducing the current.
inductance (point 6). Longer time than specified
The combined mass of the plunger and the latch at points 5 and 6 may indicate auxiliary contact
continue to move at a reduced velocity causing malfunction or insufficient driving energy of the
a further reduction in the coil current (points 2 to operating mechanism.
B-CATADV-118-EN, 2023-02-06

8
CAT Advanced series
Circuit Breaker Analyzers & Timer
Connecting the coil control cables to 3 open and 3 close coils of the single pole controlled circuit breaker

Static resistance measurement

The built-in micro ohmmeter generates up to The DC current is generated through the closed
500A true DC ripple free current with an circuit breaker contacts. Voltage drop is
automatically regulated test ramps. The measured between terminals of the circuit
resistance measurement is using the well-known breakers. The resistance is calculated using the
Kelvin’s four point’s method. Ohm’s law R=U/I.
B-CATADV-118-EN, 2023-02-06

Micro Ohmmeter cable connection Micro Ohmmeter cable connection


on a live tank circuit breaker on a dead tank circuit breaker

9
CAT Advanced series
Circuit Breaker Analyzers & Timer
High – Precision module (built-in)

The high-precision module is newly developed CAT Advanced series with the built-in High
built-in addition to micro ohmmeter available Precision Module may be used for
in CAT Advanced series. It provides an applications on very small resistance
increased precision and offers a highly measurements of non-inductive test objects.
accurate contact resistance measurement in This requirement is usually met at resistance
the range from 1 μΩ to 30 μΩ, with 0,01 μΩ inspections of generator circuit breakers,
resolution. welding joints, GIS testing, etc.

DRM (Dynamic Resistance Measurement)

The built-in micro ohmmeter can also be used related to the arcing contact condition. The
for the DRM. DRM test is performed by injecting injected current value should be as high as
a current through the breaker contact and possible but no less than 100 A, to provide a
simultaneously monitoring the voltage drop reliable voltage drop reading, thus allowing an
across the breaker contact as well as the current easier detection of the arcing contact.
flow during the breaker operation. The DRM test CAT36, CAT66 and CAT126 models incorporate
requires the circuit breaker analyzer with a high- the most powerful micro ohmmeter generating
resolution measurement. up to 500 A.
The resistance curve, as a function of a contact
travel can be used to reveal potential problems
B-CATADV-118-EN, 2023-02-06

10
CAT Advanced series
Circuit Breaker Analyzers & Timer
First trip test

“First trip” analysis is important to determine a learned from the coil current waveform recorded
condition of the coil operating mechanism. during the “First trip” test.
Circuit breaker spends most of its lifetime
Since the breaker is in service, the conventional
conducting a current without any operation.
way of off-line timing measurement with timing
Once the protective relay detects a problem, the
cables across the interrupter cannot be used.
circuit breaker, that was idle for maybe a year or
Instead of main contact timing cables, three
longer, has to operate as fast as possible.
current probes are used. These current probes
However, if the circuit breaker has not been
show current flowing through the secondary side
operated for a long time, the friction of the trip
of the current transformer for each phase. The
latch release mechanism may increase.
instant when the current stops flowing, reveals
Information about the latch friction, open circuit
the breaker open time.
contacts, insufficient spring tension, can be

Connecting the DC current probes for measurement of the coil current and
AC current probes to the line currents during the “First trip” test

CAT & SAT as Circuit Breaker Test System


The CAT Advanced series circuit breaker analyzers & timers can be coupled with DV Power Coil
Analyzer SAT II series. When connected to DV-Win software these two instruments create one test
B-CATADV-118-EN, 2023-02-06

system (control and reporting done with the same software). The SAT40A II series can be used as a
power supply unit for measurement of spring-charging motor current and voltage as well as
determination of minimum trip voltage of circuit breaker coils.

11
CAT Advanced series
Circuit Breaker Analyzers & Timer
DV-Win software
Acquisition and Analysis
DV-Win software provides acquisition and analysis of the test results, as well as control of all the CAT
Advanced series functions from a PC. It supports measurements process and step by step guidance
through the entire test procedure, providing faster, easier, and safer testing.

Graphical presentation
Graphical presentation of a variety of measurements and timing test results uses cursors and powerful
zoom functions for detailed analysis. Colors, grids, scales, and positioning of the test data are all
controlled by the user. DV-Win supports automatic unit conversion (e.g.: cycles to seconds or mm to
inches). The test records can be exported in .dwc file format for further analysis.

Database
Results are automatically stored and organized in the database on your PC and are available for analysis
and reporting. Each test can be automatically assessed according to manufacturer specifications or
based on your individual limit values.
DV-Win software database can be updated with over 500 test plans of different apparatus commonly
used in most utilities and substations. This valuable benchmark data used for test results evaluation is
provided upon request.

Reports
DV-Win automatically generates reports including all asset-related information and performed tests. This
gives you a comprehensive overview of the test object, test results and assessment. You can easily
B-CATADV-118-EN, 2023-02-06

adapt test reports, for example, by choosing from different types of result tables and diagrams and by
providing comments on every test. Furthermore, you can incorporate your company logo, photos and
other test results.

12
CAT Advanced series
Circuit Breaker Analyzers & Timer
DV-Win features

• Full control of the CAT functions from a PC


• Capability to simultaneously control CAT, SAT and RMO series models to create one test system
• Data base library of Circuit Breakers (optional)
• Downloading the test results from the instrument
• Acquisition and analysis of the test results
• The test results can be viewed, edited, saved, printed and exported
• Viewing and overlaying several graphs, for an easy test result comparison
• Selecting the measurement points and intervals using the two cursors
• Zoom and pan graph feature
• Specific test sequence setup
• Creation of predefined test plans for an easy and quick field testing
• Customized configuration of the test result graphs
B-CATADV-118-EN, 2023-02-06

13
CAT Advanced series
Circuit Breaker Analyzers & Timer
Technical data
Main contact inputs Time measurement
• Number of contact inputs: up to 12 (3 x 4), Time measurement resolution:

4 per phase, depending on the model • 0,025 ms for 1 s test duration (sampling rate 40 kHz)

• Each channel detects main and pre-insertion • 0,1 ms for 2 s test duration (sampling rate 10 kHz)*
resistor contacts. • 1 ms for 20 s test duration (sampling rate 1 kHz)
- Closed ≤ 10 Ω,
• 10 ms for 200 s test duration (sampling rate100 Hz)
- Resistor contacts range 10 Ω to 5 kΩ,
Time accuracy ±0,01% of the reading ± 0.1 ms
- Open ≥ 5 kΩ
*0,1 ms for 10 s test duration is available upon request
Open circuit voltage: 20 V DC
Short circuit current: 100 mA
Breaker operation
• Each channel measures resistance of
• Close (C)
pre-insertion resistors
• Open (O)
• Close-Open (C-O)
Auxiliary inputs • Open-Close (O-C)

• Number of channels: 6, galvanically isolated • Open-Close-Open (O-C-O)

• User selectable: dry or wet


• First trip test
User can select any desired test sequence
• Contact sensing (dry):
Open circuit voltage 20 V DC ± 20%
Current measurement
Short circuit current 25 mA ± 20%
Closed threshold <600 Ω ± 30%. • Current measurement for Open and Close coil,
6 channels, Hall-Effect sensor
Open threshold> 600 Ω ± 30%.
• Range ±35 A AC/DC to 5 kHz
• Voltage sensing (wet): • Resolution: 25 mA
Working voltage up to 300 V DC, 250 V AC • Accuracy ± (0,5 % rdg + 0,1 % FS)
Open state threshold <8 V, insensitive to polarity. • Graphic presentation: currents waveform is
displayed with resolution of 0,1ms
Closed state threshold> 13 V, insensitive to polarity.

• Overcurrent and overvoltage protection


Coil resistance measurement
• 3 coils simultaneously (Open or Close)

Coil driver • Measuring range / Resolution


• Number of channels: 6 (3 open and 3 close coil) 1 Ω - 99,9 Ω / 0,1 Ω
100 Ω – 999 Ω / 1 Ω
• 6 separate outputs for coil triggering
• Typical accuracy ± (0,5 % rdg + 0,5 % FS)
• Driver characteristics: 300 V DC/ACmax,
35 A DC/ACmax
• Electronic drivers: it provides superior Universal transducer inputs
timing control
• 3 digital travel transducer channels
B-CATADV-118-EN, 2023-02-06

• Overcurrent and overvoltage protection


Digital rotary transducers: 2500ppr
• Coil supply inputs for open and close coil:
300 V DC/ACmax, 35 A DC/ACmax
• 3 analog travel transducer channels

• Analog transducer input measurement resolution: 16 bit.


• Internal supply for linear transducer: 5 V DC

14
CAT Advanced series
Circuit Breaker Analyzers & Timer
Time measurement triggers Printer (optional)

• External trigger: 2 channels (Open 1 & Close 1), • Thermal printer


input voltage: 10 V – 300 V AC/DC • Graphic and numeric printout
• Coil currents: threshold level user selectable
• Paper width 112 mm / 4.4 in
• Auxiliary inputs
The print density is guaranteed within range: 5°C to 40°C, 20 to
• Analog inputs: threshold level user selectable 85% relative humidity, non-condensing

Analog inputs Dimensions and weight


• 6 channels – Coil current measurement • Dimensions (W x H x D):
• 6 Voltage channels, each channel has four 480 mm x 197 mm x 395 mm
measurement ranges: ±1 V, ±5 V, ±60 V and ±300 V 18.89 in x 7.75 in x 15.55 in
AC/DC
• Weight:
• Typical accuracy: from 10,7 kg (23.5 lbs) up to 13.2 kg (29.1 lbs)
± (0,1% rdg + 0,05% FS) up to 10 V AC /DC
depending on the model and built-in features
± (0,5% rdg + 0,1% FS) up to 300 V AC/DC

Mains power supply


The analog inputs are isolated with respect to all other
circuits • Connection according to IEC/EN60320-1;
UL498, CSA 22.2
DC output
• Mains supply: 90 V - 264 V AC
• 24 V voltage supply for current clamps • Frequency: 50/60 Hz

Static resistance measurement • Input power (max.):


o 100 VA (without use of Micro Ohmmeter)
• Built-in Micro Ohmmeter with up to 500 A, depending
o 1500 VA (with use of Micro Ohmmeter 200 A)
on the model
o 3900 VA (with use of Micro Ohmmeter 500 A)
• Current range 5 A - 500 A
• Max. load voltage 6,2 V Applicable Standards
• Resistance range 0 µΩ - 999,9 mΩ
• Installation/overvoltage: category II
• Resolution 0,1 µΩ
• Pollution: degree 2
• Accuracy ± (0,1 % rdg + 0,1 % FS)
• Safety: LVD 2014/35/EU (CE Conform)
Dynamic resistance measurement Standard EN 61010-1
• EMC: Directive 2014/30/EU (CE Conform)
• Voltage and current measuring channels Standard EN 61326-1:2006
• DRM sampling rate 40 kHz (0,025 ms time • CAN/CSA-C22.2 No. 61010-1
resolution)
• Resolution 16 bit Environmental conditions
• Breaker operations available for DRM test: • Operating temperature:
o Open (O) -10 ºC - + 55 ºC / 14 ºF - +131 ºF
o Close (C) • Storage & transportation:
o O – C (auto reclose) -40 ºC - + 70ºC / -40 ºF - +158 ºF
o C – O (make brake) • Humidity 0 % - 95 % relative humidity, non-
condensing
Internal Memory
Warranty

B-CATADV-118-EN, 2023-02-06

Store up to 500 test records (including numerical


and graphical results) • 3 years + additional 1 (one) year upon registration on
DV Power official website

All specifications herein are valid at ambient temperature of + 25 °C


and standard accessories.
Specifications are subject to change without notice.

15
CAT Advanced series
Circuit Breaker Analyzers & Timer
Accessories

Main contact cables 5 m (16.4 ft)


Main contact cables 5 m (16.4 ft) with Main contact cables 5 m (16.4 ft) with SCT
with SCT clamps (four breaks per
SCT clamps (two breaks per phase) clamps (one break per phase)
phase)
(CM-05-65MXST) (CM-05-34MXST)
(CM-05-12MXST)

Coil control cable set 5 m


Coil control cable 5 m
(16.4 ft) with banana
Main contacts extensions Main contacts extensions (16.4 ft) with banana plugs
plugs
cables 10 m (32.8 ft)* cables 10 m (32.8 ft)* (Three-pole control - 2 coil
(Single-pole control - 6
(E6-10-12MXFX) (E3-10-65MXFX) channels)
coil channels)
(CO-05-00C5B1)
(CO-05-6BC5B1)

Coil supply cable set Sense cables 2 x 10 (32.8 Current cables 2 x 10 m 50 Current cables 2 x 10 m
4 x 5 m 2,5 mm2 (16.4 ft) ft) m with alligator clamps mm2 (32.8 ft, 0 AWG) with 25 mm2 (32.8 ft, 3 AWG) with
with banana plugs A2 battery clamps battery clamps
(CS-05-02BPBP) (S2-10-02BPA2) (C2-10-50VMB3) (C2-10-25LMB1)

Current cables with


Auxiliary contacts cable Analog channels cable set
branch connectors 2 x (3
set 12 x 5 m (16.4 ft) with 12 x 5 m (16.4 ft) with Cable bag
B-CATADV-118-EN, 2023-02-06

x 5 m, 16 mm2) with SCT


banana plugs* banana plugs* (CABLE-BAG-00)
clamps (C6BC-05-
(AX-05-02BPBP) (AN-05-02BPBP)
16GMST)

16
CAT Advanced series
Circuit Breaker Analyzers & Timer
Cable plastic case - Cable plastic case with
Plastic transport case
medium size wheels - large size
(HARD-CASE-PC)
(CABLE-CAS-02) (CABLE-CAS-W3)

Current clamp 30/300 A


Current clamp 30/300 A AC Current clamp 1 A / 1 V
power supplied from the
with internal battery supply and cable 5 m with banana Test Shunt 600 A / 60 mV
instrument with adapter
and extension 5 m plugs (SHUNT-600-MK)
5m
(CACL-0300-08) (CACL-ACBP-05)
(CACL-0300-07)

Digital rotary transducer Digital rotary transducer Universal transducer Three phase digital rotary
with 5 m (16.4 ft) with 5 m connection cable mounting kit (extended transducer kit (with 5 m
connection cable with accessories version) connection cable)
(DRT-250-C605) (DRT-SET-0005) (UTM-KIT-0001) (TPH-DRTS-050)

Linear analog transducer


Online first trip test kit – Online first trip test kit - -
(TLH) 225 mm with 5 m Doble transducer adapter
Three-pole control Single-pole control
connection cable** (DTA-BOX-C002)
(ONFTT-KIT-01) (ONFTT-KIT-00)
B-CATADV-118-EN, 2023-02-06

(LAT-225-C305)
*The above cables are also available in several lengths and terminations.
**The above linear analog transducers are available in several lengths.
Please contact DV Power for more information

17
CAT Advanced series
Circuit Breaker Analyzers & Timer
CAT Advanced series - models
CAT35

Main contact inputs Static resistance measurement:


Number of contact inputs: 3 (3 x 1), 1 per phase Built-in Micro Ohmmeter 200 A

Auxiliary contact inputs: 6 Optional:


Analog contact inputs: 6 High precision module (built-in)

Coil control outputs: 6 BSG on Live Tank AIS


Transducer inputs: 3 BSG on Dead Tank AIS

CAT36

Main contact inputs Static resistance measurement:


Number of contact inputs: 3 (3 x 1), 1 per phase Built-in Micro Ohmmeter 500 A
Optional:
Auxiliary contact inputs: 6
Analog contact inputs: 6 High precision module (built-in)
Coil control outputs: 6 BSG on Live Tank AIS
Transducer inputs: 3 BSG on Dead Tank AIS
BSG on GIS

CAT64A

Main contact inputs Static resistance measurement: Not


Number of contact inputs: 6 (3 x 2), 2 per phase available
Optional:
Auxiliary contact inputs: 6
BSG on Live Tank AIS
Analog contact inputs: 6
Coil control outputs: 6
Transducer inputs: 3

CAT65

Main contact inputs Static resistance measurement:


Number of contact inputs: 6 (3 x 2), 2 per phase Built-in Micro Ohmmeter 200 A

Auxiliary contact inputs: 6 Optional:


Analog contact inputs: 6 High precision module (built-in)
Coil control outputs: 6 BSG on Live Tank AIS
Transducer inputs: 3 BSG on Dead Tank AIS

CAT66

Main contact inputs Static resistance measurement


Number of contact inputs: 6 (3 x 2), 2 per phase Built-in Micro Ohmmeter 500 A
Optional:
Auxiliary contact inputs: 6
High precision module (built-in)
Analog contact inputs: 6
BSG on Live Tank AIS
Coil control outputs: 6
B-CATADV-118-EN, 2023-02-06

BSG on Dead Tank AIS


Transducer inputs: 3
BSG on GIS

18
CAT Advanced series
Circuit Breaker Analyzers & Timer
CAT124A

Main contact inputs Static resistance measurement: Not


Number of contact inputs: 12 (3 x 4), 4 per phase available

Auxiliary contact inputs: 6 Optional:


BSG on Live Tank AIS
Analog contact inputs: 6
Coil control outputs: 6
Transducer inputs: 3

CAT125

Main contact inputs Static resistance measurement:


Number of contact inputs: 12 (3 x 4), 4 per phase Built-in Micro Ohmmeter 200 A

Auxiliary contact inputs: 6 Optional:


Analog contact inputs: 6 High precision module (built-in)
Coil control outputs: 6 BSG on Live Tank AIS
Transducer inputs: 3 BSG on Dead Tank AIS

CAT126

Main contact inputs Static resistance measurement


Number of contact inputs: 12 (3 x 4), 4 per phase Built-in Micro Ohmmeter 500 A

Auxiliary contact inputs: 6 Optional:


High precision module (built-in)
Analog contact inputs: 6
BSG on Live Tank AIS
Coil control outputs: 6 BSG on Dead Tank AIS
Transducer inputs: 3 BSG on GIS

Order info

Instrument Article No
Circuit Breaker Analyzer & Timer CAT35 CAT3500-N-01
Circuit Breaker Analyzer & Timer CAT36 CAT3600-N-01
Circuit Breaker Analyzer & Timer CAT64A CAT64A0-N-01
Circuit Breaker Analyzer & Timer CAT65 CAT6500-N-01
Circuit Breaker Analyzer & Timer CAT66 CAT6600-N-01
Circuit Breaker Analyzer & Timer CAT124A CAT124A-N-01
Circuit Breaker Analyzer & Timer CAT125 CAT1250-N-01
Circuit Breaker Analyzer & Timer CAT126 CAT1260-N-01

Included accessories
Windows based DV-Win PC software including USB cable
Mains power cable
Ground (PE) cable
B-CATADV-118-EN, 2023-02-06

Plastic transport case

19
CAT Advanced series
Circuit Breaker Analyzers & Timer
Standard accessories Article No

Main contact cables


Main contact cables 5 m (16.4 ft) with SCT clamps (for CAT35, CAT36) CM-05-34MXST
Main contact cables 5 m (16.4 ft) with SCT clamps (for CAT64A, CAT65, CAT66) CM-05-65MXST
Main contact cables 5 m (16.4 ft) with SCT clamps (for CAT124A, CAT125, CAT126) CM-05-12MXST
Main contact cables extension
Main contact cables extension 10 m (32.8 ft) (for CAT35, CAT36, CAT64A, CAT65, CAT66) E3-10-65MXFX
Main contact cables extension 10 m (32.8 ft) (for CAT124A, CAT125, CAT126) E6-10-12MXFX
Control cabinet cables
Coil control cable set 5 m (16.4 ft) with banana plugs
CO-05-6BC5B1
(Single-pole control -6 coil channels)
Jumper cable 1 x 15 cm 2,5 mm2 with banana plugs with retractable isolation (red) (x 6) JCR-15-2REBP
Jumper cable 1 x 15 cm 2,5 mm2 with banana plugs with retractable isolation (black) (x 6) JCB-15-2REBP
Test probe with grip jaws (black) (x 3) TESTPR-GJ-B0
Test probe with grip jaws (red) (x 3) TESTPR-GJ-R0
Coil supply cable set 4 x 5 m 2,5 mm2 (16.4 ft, 13 AWG) with banana plugs CS-05-02BPBP
Auxiliary contacts cable set 12 x 5 m (16.4 ft) with banana plugs AX-05-02BPBP
Analog channels cable set 12 x 5 m (16.4 ft) with banana plugs AN-05-02BPBP
Current cables
Current cables 2 x 10 m 50 mm2 (32.8 ft, 0 AWG) with battery clamps
C2-10-50VMB3
(for CAT36, CAT66 and CAT126)
Current cables 2 x 10 m 25 mm2 (32.8 ft, 3 AWG) with battery clamps
C2-10-25VMB1
(for CAT35, CAT65 and CAT125)
Sense cables
Sense cables 2 x 10 m (32.8 ft) with alligator clamps
S2-10-02BPA1
(for CAT35, CAT36, CAT65, CAT66, CAT125 and CAT126)
Cable cases
Cable plastic case - large size (x 2) CABLE-CAS-03

Optional accessories and features Article No

Both Sides Grounded (BSG) of AIS (Air Insulated Substation) Live Tank Circuit Breaker
for CAT3x Advanced series (3 channels - one break per phase) BSG-CATII-00
(available with CAT35 and CAT36)
Both Sides Grounded (BSG) of AIS (Air Insulated Substation) Live Tank Circuit Breaker
for CAT6x and CAT12x Advanced series (6 channels - two breaks per phase) BSG-CATII-01
(available with CAT65, CAT66, CAT125 and CAT126)
Both Sides Grounded (BSG) of AIS (Air Insulated Substation) Dead Tank Circuit
Breaker for CAT Advanced series BSG-CATDTB-0
(available with CAT35, CAT36, CAT65, CAT66, CAT125 and CAT126 )
BSG on GIS feature for CAT Advanced series (available with CAT36, CAT66 and CAT126) BSG-CATGIS-0
Current cables with branch connectors 2 x (3 x 5 m, 16 mm2) with SCT clamps C6BC-05-16GMST
Extension cables 2 x 5 m 50 mm2 E2-05-50VMVF
AC Current clamp 1 A / 1 V and cable 5 m with banana plugs CACL-ACBP-05
Built-in high precision measurement module
RMO-HPMM-DG0
(available with CAT35, CAT36, CAT65, CAT66, CAT125 and CAT126 )
Current clamp 30/300 A power supplied from the instrument with adapter 5 m (16.4 ft) CACL-0300-07
B-CATADV-118-EN, 2023-02-06

Current clamp 30/300 A with internal battery supply and extension 5 m (16.4 ft) CACL-0300-08
Thermal printer 112 mm (4.4 inch) (built-in) PRINT-112-01
Thermal paper roll PRINT-112-RO
Cable plastic case with wheels - large size CABLE-CAS-W3
20
CAT Advanced series
Circuit Breaker Analyzers & Timer
Control cabinet cables
Coil control cable set 10 m with banana plugs (Single-pole control -6 coil channels) CO-10-6BC5B1
Coil control cable set 15 m with banana plugs (Single-pole control -6 coil channels) CO-15-6BC5B1
Coil control cable 5 m with banana plugs (Three-pole control - 2 coil channels) CO-05-00C5B1
Coil control cable 10 m with banana plugs (Three-pole control - 2 coil channels) CO-10-00C5B1
Coil control cable 15 m with banana plugs (Three-pole control - 2 coil channels) CO-15-00C5B1
Coil supply cable set 4 x 2 m 2,5 mm2 (6.5 ft, 13 AWG) with banana plugs CS-02-02BPBP
Coil supply cable set 4 x 5 m 2,5 mm2 (16.4 ft, 13 AWG) with banana plugs CS-05-02BPBP
Coil supply cable set 4 x 10 m 2,5 mm2 (32.8 ft, 13 AWG) with banana plugs CS-10-02BPBP
Coil supply cable set 2 x 2 m 2,5 mm2 with banana plugs C2-02-02BPBP
Coil supply cable set 2 x 5 m 2,5 mm2 with banana plugs C2-05-02BPBP
Coil supply cable set 2 x 10 m 2,5 mm2 with banana plugs C2-10-02BPBP
Jumper cable 1 x 15 cm 2,5 mm2 with banana plugs (black) JCB-15-2BPBP
Jumper cable 1 x 15 cm 2,5 mm2 with banana plugs (red) JCR-15-2BPBP
Auxiliary contacts cable set 12 x 5 m with banana plugs AX-05-02BPBP
Auxiliary contacts cable set 12 x 10 m with banana plugs AX-10-02BPBP
Auxiliary contacts cable set 12 x 15 m with banana plugs AX-15-02BPBP
Analog channels cable set 12 x 5 m with banana plugs AN-05-02BPBP
Analog channels cable set 12 x 10 m with banana plugs AN-10-02BPBP
Analog channels cable set 12 x 15 m with banana plugs AN-15-02BPBP
Main contact cables
Main contact cables 3 m (9.8 ft) with SCT clamps ( for CAT35, CAT36) CM-03-34MXST
Main contact cables 3 m (9.8 ft) with SCT clamps ( for CAT64A, CAT65, CAT66) CM-03-65MXST
Main contact cables 3 m (9.8 ft) with SCT clamps ( for CAT124A, CAT125, CAT126) CM-03-12MXST
Main contact cables 3 m (9.8 ft) with alligator clamps ( for CAT35, CAT36) CM-03-34MXA2
Main contact cables 5 m (16.4 ft) with alligator clamps ( for CAT35, CAT36) CM-05-34MXA2
Main contact cables 3 m (9.8 ft) with alligator clamps ( for CAT64A, CAT65, CAT66) CM-03-65MXA2
Main contact cables 5 m (16.4 ft) with alligator clamps ( for CAT64A, CAT65, CAT66) CM-05-65MXA2
Main contact cables 3 m (9.8 ft) with alligator clamps ( for CAT124A, CAT125, CAT126) CM-03-12MXA2
Main contact cables 5 m (16.4 ft) with alligator clamps ( for CAT124A, CAT125, CAT126) CM-05-12MXA2
Main contact cables extension
Main contact cables Extension 5 m (16.4 ft) ( for CAT35, CAT36, CAT64A, CAT65, CAT66) E3-05-65MXFX
Main contact cables Extension 5 m (16.4 ft) ( for CAT124A, CAT125, CAT126) E6-05-12MXFX
Main contact cables Extension 15 m (49.2 ft) ( for CAT35, CAT64A, CAT65, CAT66) E3-15-65MXFX
Main contact cables Extension 15 m (49.2 ft) ( for CAT124A, CAT125, CAT126) E6-15-12MXFX
Current cables
Current cables 2 x 5 m 50 mm2 (32.8 ft, 0 AWG) with battery clamps
C2-05-50VMB3
(for CAT36, CAT66 and CAT126)
Current cables 2 x 15 m 70 mm2 (49.2 ft, 00 AWG) with battery clamps
C2-15-70VMB3
(for CAT36, CAT66 and CAT126)
Current cables 2 x 5 m 25 mm2 (32.8 ft, 3 AWG) with battery clamps
C2-05-25VMB1
(for CAT35, CAT65 and CAT125)
Current cables 2 x 15 m 35 mm2 (49.2 ft, 2 AWG) with battery clamps
C2-15-35VMB1
(for CAT35, CAT65 and CAT125)
Sense cables
Sense cables 2 x 5 m (32.8 ft) with alligator clamps A2 S2-05-02BPA2
Sense cables 2 x 15 m (49.2 ft) with alligator clamps A2 S2-15-02BPA2
B-CATADV-118-EN, 2023-02-06

21
CAT Advanced series
Circuit Breaker Analyzers & Timer
Transducers
Digital rotary transducer with 5 m (16.4 ft) connection cable DRT-250-C605
Digital rotary transducer with 10 m (32.8 ft) connection cable DRT-250-C610
Digital rotary transducer with 5 m (16.4 ft) connection cable with accessories DRT-SET-0005
Digital rotary transducer with 10 m (32.8 ft) connection cable with accessories DRT-SET-0010
Linear analog transducer (TLH) 150 mm (5.9 in) with 5 m (16.4 ft) connection cable and
LAT-150-C305
linear transducer rod
Linear analog transducer (TLH) 225 mm (8.85 in) with 5 m (16.4 ft) connection cable
LAT-225-C305
and linear transducer rod
Linear analog transducer (TLH) 300 mm (11.8 in) with 5 m (16.4 ft) connection cable
LAT-300-C305
and linear transducer rod
Linear analog transducer (TLH) 500 mm (19.68 in) with 5 m (16.4 ft) connection cable
LAT-500-C305
and linear transducer rod
Three phase digital rotary transducer kit (with 5 m connection cable) TPH-DRTS-005
Online first trip test kit - Three-pole control for CAT Advanced series ONFTT-KIT-01
Online first trip test kit - Single-pole control for CAT Advanced series ONFTT-KIT-00
Transducer mounting kits
Universal transducer mounting kit UTM-KIT-0000
Universal transducer mounting kit - extended version UTM-KIT-0001
Doble transducer adapter DTA-BOX-C002
Big clamping base UTM-LCB-0080
Small clamping base UTM-SCB-0030
Articulated arm UTM-AA-0288
Carrier (L profile) for digital rotary transducer DRT-CRL-0090
Carrier for analog rotary transducer ART-CRL-0000
Linear transducer rod LAT-ROD-0000
Bellow coupling (M6) DRT-COUP-003
Bellow coupling (M10) DRT-COUP-001
Magnet UTM-MAG-0800
Four mechanical adapters 10 mm (M6, M8, M10, M12) DRT-MADP-004
Four mechanical adapters 6 mm (M6, M8, M10, M12) DRT-MADP-604
B-CATADV-118-EN, 2022-06-27

B-CATADV-118-EN
Date published: 2023-02-06
Subject to change without notice