You are on page 1/ 3

A6D710-AH01-01 AC axial fan - HyBlade®

sickled blades (S series)

ebm-papst Mulfingen GmbH & Co. KG


Bachmühle 2 · D-74673 Mulfingen
Phone +49 7938 81-0
Fax +49 7938 81-110
[email protected]
www.ebmpapst.com
Limited partnership · Headquarters Mulfingen
County court Stuttgart · HRA 590344

General partner Elektrobau Mulfingen GmbH · Headquarters Mulfingen


County court Stuttgart · HRB 590142

Nominal data

Type A6D710-AH01-01
Motor M6D138-HF

Phase 3~ 3~ 3~ 3~
Nominal voltage VAC 400 400 480 480
Connection Δ Y Δ Y
Frequency Hz 50 50 60 60

Type of data definition ml ml ml ml


Valid for approval / standard CE CE CE CE
Speed min-1 905 730 1060 780
Power input W 1030 690 1700 1030
Current draw A 2.35 1.34 2.87 1.72
Max. back pressure Pa 125 80 170 92
Min. ambient temperature °C -40 -40 -40 -40
Max. ambient temperature °C 80 80 60 60
Starting current A 9 3 10 3.5
ml = Max. load · me = Max. efficiency · fa = Running at free air · cs = Customer specs · cu = Customer unit
Subject to alterations

Data according to ErP directive


Actual Request 2013 Request 2015

Installation category A Overall efficiency ηes % 33.6 29.6 33.6


Efficiency category Static Efficiency grade N 40 36 40
Variable speed drive No Power input Pe kW 0.97
Specific ratio* 1.00 Air flow qv m³/h 10730
* Specific ratio = 1 + pfs / 100 000 Pa Pressure increase pfs Pa 111
Speed n min-1 910
Data definition with optimum efficiency.
The ErP data is determined using a motor-impeller combination in a standardised measurement configuration.

Item no. 10175-5-9980 · Revision 78596 · Release 2014-01-13 · Page 1 / 6

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
A6D710-AH01-01 AC axial fan - HyBlade®
sickled blades (S series)

Technical features

Mass 19.9 kg
Size 710 mm
Surface of rotor Cast in aluminium
Material of terminal box Plastic, fibreglass-reinforced
Material of blades Aluminium sheet insert, sprayed with PP plastic
Number of blades 5
Blade angle -5°
Direction of air flow "V"
Direction of rotation Clockwise, seen on rotor
Type of protection IP 54
Insulation class "F"
Humidity class F3-1
Max. permissible ambient motor + 80 °C
temp. (transp./ storage)
Min. permissible ambient motor - 40 °C
temp. (transp./storage)
Mounting position Any
Condensate discharge holes On rotor and stator sides
Operation mode S1
Motor bearing Ball bearing
Touch current acc. IEC 60990 <= 3.5 mA
(measuring network Fig. 4, TN
system)
Electrical leads Via terminal box
Motor protection Thermal overload protector (TOP) brought out
Cable exit Axial
Protection class I (if protective earth is connected by customer)
Product conforming to standard EN 61800-5-1; EN 60034; CE
Approval VDE; GOST; CCC

Item no. 10175-5-9980 · Revision 78596 · Release 2014-01-13 · Page 2 / 6

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
A6D710-AH01-01 AC axial fan - HyBlade®
sickled blades (S series)

Charts: Air flow 50 Hz


Druck p f s[Pa]für Rho=1,2kg/m^3

qv[cfm]
0 2.000 4.000 6.000 8.000 10.000
180 0,72
175 0,7
170 0,68
165 0,66
160 0,64
155 0,62
150 0,6 Air performance measured as per ISO 5801
145
Installation category A. For detailed
0,58 information on the measuring set-up, please
140 0,56 contact ebm-papst. Suction-side noise
135 0,54 levels: LwA measured as per ISO 13347 /
130 0,52 LpA measured with 1m distance to fan axis.
4 The values given are valid under the
125 0,5
measuring conditions mentioned above and
120 0,48 may vary according to the actual installation
115 0,46 situation. With any deviation from the
110 0,44 standard set-up, the specific values have to
105 0,42
be checked and reviewed with the unit
installed.
100 0,4

p fs_E[IN H2O]
95 0,38
3
pf s[Pa]

90 0,36
85 0,34
8
80 0,32
75 0,3
70 0,28
65 0,26
7
60 0,24
55 0,22
2
50 0,2
45 0,18
40 0,16
6
35 0,14
30 0,12
25 0,1
20 0,08
15 0,06
10 0,04
pf s[P
pf s

5 0,02
[Pa

5 1
a]

0 0
]

0 2.000 4.000 6.000 8.000 10.000 12.000 14.000 16.000 18.000


qv[m^3/h]

Measured values
Conn. U f n Pe I LpAin LwAin LwAout qv pfs
V Hz min-1 W A dB(A) dB(A) dB(A) m3/h Pa
1 Δ 400 50 940 725 2.07 64 71 70 16080 0
2 Δ 400 50 925 859 2.18 62 69 69 13950 50
3 Δ 400 50 915 939 2.26 64 70 69 12060 90
4 Δ 400 50 905 1030 2.35 67 73 72 9910 125
5 Y 400 50 820 542 1.05 61 67 67 14000 0
6 Y 400 50 780 617 1.19 58 65 64 11760 36
7 Y 400 50 755 658 1.27 58 65 64 9845 60
8 Y 400 50 730 690 1.34 61 68 67 7940 80
Conn. = Connection · U = Supply voltage · f = Frequency · n = Speed · Pe = Power input · I = Current draw · LpAin = Sound pressure level inlet side · LwAin = Sound power level inlet side
LwAout = Sound power level outlet side · qv = Air flow · pfs = Pressure increase

Item no. 10175-5-9980 · Revision 78596 · Release 2014-01-13 · Page 5 / 6

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

You might also like