SK TIE4-PE-M12-V2A                                             Part number: 275 274 034
Connection extension
Protective earthing connection SK 200E size 1 - 3
Scope of delivery
1x     PE connection bit with O-ring
1x     Hexagonal nut                                  M8
1x     Serrated lock washer                           M8
1x     Washer                                         M6
1x     Spring lock washer                             A6
1x     Hexagonal nut                                  M6
Field of use
Optional protective earthing to meet the requirements for fixed installation according to
DIN EN 61800-5-1 for conductor cross-sections up to 10 mm² (Cu) or as second protective earthing
connection. Among other things, this is mandatory if a NORDA C Flex (SK 2xxE, size 1 to 3) frequency
inverter is wall-mounted in ATE X Zone 22 / 3D. The PE connection bit is screwed into the left or right
side of one of the 3 lower M12 option slots (6L to 8L or 6R to 8R) of the connection unit.
Dimensions
                                                                                           Details in
                                                                                           millimetres
Installation / option locations
       Device series              Recommended option                  Option locations
                                       location
          SK 200E
     Frequency inverter
                                 6R / 6L, 7R / 7L, 8R / 8L
      connecting unit
     SK TI4-x-2xx-x (-C)
                Technical Information / Datasheet                        SK TIE4-PE-M12-V2A
                           Connection extension                    TI 275274034    V 1.0     3517        en
Connection extension – SK TIE 4-PE-M12-V2A
Assembly
1      Remove the M12 blind plug from one of the side option slots
st     (right/left) of the frequency inverter.
2      Fasten the PE connection b it into the connection unit with the
n      contact serrated lock washer and the M8 hexagon nut (tightening
d      torque 6 Nm).
                                                                           Connection unit - inside view
3.     The protective earthing conductor with ring cable lug is fastened
       with the washer, the spring lock washer and the M6 hexagon nut to
       the outside of the PE-connection b it with a torque of 3 Nm.
                                                                           Connection unit - outside view
       Connection extension SK TIE4-PE-M12-V2A, mounted on the
       connection unit of an SK 200E frequency inverter, with the
       protective earthing conductor connected.
Further documentation (www.nord.com)
    Document      Designation
     BU 0200      SK 2xxE f requency inv erter manual
     TI 80-0019   The dimensioning of the
                  protectiv e conductor