MODBUS COMMUNICATION

PROTOCOL 7M24 - 7M38


7M 1

MODBUS COMMUNICATION PROTOCOL


Modbus protocol enables operation of device on Modbus networks.
For 7M.38.8.400.XXXX with serial communication the Modbus protocol enables multi drop communication via RS485
communication. Modbus protocol is a widely supported open interconnect originally designed by Modicon.
The memory reference for input and holding registers is 30000 and 40000 respectively.

PLASE NOTE
The Modbus table is subject to change without notice.

Communication operates on a master-slave basis where only one device (the master) can initiate transactions called
‘Requests’. The other devices (slaves) respond by supplying the requested data to the master.
This is called the ‘Request - Response Cycle’.
The master could send the MODBUS request to the slaves in two modes:
Unicast mode, where the master sends the request to an individual slave. It returns a replay to the master after the
request is received and processed. A MODBUS transaction consists of two messages.
Each slave should have an unique address.
Broadcast mode, where the master sends a request to all slaves and an answer is never followed. All devices should
accept the broadcast request function. The Modbus address 0 is reserved to identify the broadcast request.

Master to Slave Request


Device address Function Code nx8 bit data bytes Error check

Slave to Master Response


Device address Function Code nx8 bit data bytes Error check

Request
This Master to Slave transaction takes the form:
• Device address: master addressing a slave (Address 0 is used for the broadcast address, which all slave
devices recognize.)
• Function code e.g. 03 asks the slave to read its registers and respond with their contents.
• Data bytes: tells the slave which register to start at and how many registers to read.

Response
This Slave to Master transaction takes the form:
• Device address: to let the master know which slave is responding.
• Function code: this is an echo of the request function code.
• Data bytes: contains the data collected from the slave.
7M 2

Request Frame
Starting Register Register Count CRC
Slave Address Function Code HI LO HI LO LO HI
21 04 00 6B 00 02

Response Frame
Starting Register Register Count CRC
Slave Address Function Code HI LO HI LO LO HI
21 04 00 6B 00 02

Request- response cycle example


Address number of slave: 21
Function code: 04 30000
Starting register HI…LO: 00…6B(16) 107(10) +30000(10) = 30107(10) (Meaning that actual measurement is U1. For further
informations see REGISTER TABLE FOR THE ACTUAL MEASUREMENTS.)
Register count HI…LO: 00…02(16) 2(10) (Two registers: 30107 and 30108)
Data type: T5 (Unsigned Measurement (32 bit) – see table of DATA types decoding)
Register data: FE 00 59 74 (16) 22934 * 10-^(-2) V = 229,34 V

REGISTER TABLE FOR THE ACTUAL MEASUREMENTS


The tables below represent the complete set of MODBUS register map. Register refresh frequency for actual measurement
from register 30105 to register 30190 is one second. Register refresh frequency for energy counters (from 30406 to 30441) is
40 ms. The registers from 30426 to 30441 (1000 x Energy Counter from 30406 to 30413 and from 30418 to 30425) represent
the same energy counters at 1000-times higher resolution. This registers cam be read to calculate the energy difference in
the time interval more accurate.
7M 3

MODBUS COMMUNICATION
PROTOCOL 7M24
7M 4

MODBUS INFO

Read with Register Addresses Contents Data Ind Values / Dependencies


Function Type
Code
Input Registers
30000 Memory Reference
READ ONLY INFO
4 30001 30008 Model Number T_Str16
4 30009 30012 Serial Number T_Str8
4 30013 Software Reference T1 Software version
4 30014 Hardware Reference T_Str2 Hardware version
4 30015 Calibration voltage T16 V/100
4 30017 Calibration current T16 A/100
4 30019 Accuracy class T17 100=1,00
4 30020 MiNet Flag T1 0
4 30024 COM1: Communication Type T1 0 No Communication
2 RS485
13 M-bus
4 30029 I/O 1 T1 0 No I/O
5 Tariff Input
10 Digital input
12 Pulse Output (SO)
4 30030 I/O 2 T1 See I/O 1
4 30044 Status register T1 Bit- Locked
0
Bit- Clock not set
4
4 30070 Measurement module Software ref. T17 100=1,0
4 30071 Measurement module CheckSum T1
4 30072 Meas. m. Calibration Data T1
CheckSum
4 30073 MID Setting Data CheckSum T1
4 30074 Setting Data CheckSum T1
4 30075 Software Checksum T1
4 30076 MID lock status T1 0 unlocked
1 locked
4 30077 30078 Calibration Time Stamp T_unix
4 30079 MID unlock counter T1
4 30080 FW upgrade counter T1
4 30098 Active Communication Port T1 1 COM1
4 30099 Modbus Max. Register Read at Once T1
30100 38999 MEASUREMENTS
READ ONLY INFO
4 39000 Device group T1 5 7M
7M 5

MODBUS MEASUREMENTS

Read with Register Addresses Contents Data Ind Values / Dependencies Multiplicator and
Function Unit
Code
Input Registers
30000 Memory Reference
ACTUAL MEASUREMENTS
4 30101 Phase valid measurement T1 Bit 0 Invalid measurement
phase 1
4 30103 30104 Run time T3 seconds x 1 seconds
4 30105 30106 Frequency T5 x 1 Hz
4 30107 30108 U1 T5 x1V
4 30113 30114 Uavg (phase to neutral) T5 x1V
4 30126 30127 I1 T5 x1A
4 30136 30137 Iavg T5 x1A
4 30138 30139 SI T5 x1A
4 30140 30141 Active Power Total (Pt) T6 x1W
4 30142 30143 Active Power Phase L1 (P1) T6 x1W
4 30148 30149 Reactive Power Total (Qt) T6 x 1 var
4 30150 30151 Reactive Power Phase L1 (Q1) T6 x 1 var
4 30156 30157 Apparent Power Total (St) T5 x 1 VA
4 30158 30159 Apparent Power Phase L1 (S1) T5 x 1 VA
4 30164 30165 Power Factor Total (PFt) T7 x1
4 30166 30167 Power Factor Phase 1 (PF1) T7 x1
4 30172 Power Angle Total (atan2(Pt,Qt)) T17 x1°
4 30173 j1 (angle between U1 and I1) T17 x1°
4 30181 Internal Temperature T17 x 1 °C
4 30182 U1 THD% T16 x1%
4 30188 I1 THD% T16 x1%
I/O STATUS
4 30191 Alarm Status Flags(G1, G2 T1 Bit Group 1 Limit 1 .. 4
0..4
Bit Group 2 Limit 1 .. 4
8..12
4 30193 I/O 1 Value T17
4 30197 External relay status T1 0 Off
1 On
250 Comm. Error
255 Not connected
4 30200 Alarm Status Flags(GE T1 Bit Group E Limit 1 .. 4
0..4
4 30201 Logic functions values T1 Bit 0 Logic function 1
Bit 1 Logic function 2
4 30396 30399 Actual time T_
Time
7M 6
4 30400 CheckSum Status T1 0 No Error (OK)
Bit 0 Error Parameter CRC
Bit 1 Error Firmware CRC
Bit 2 Error MID-lock
Bit 6 Error Measurement
module CheckSum
Bit 7 Error Software Check-
sum
Bit 8 Error Calibration Data
CheckSum
Bit 9 Error MID Setting Data
CheckSum
Bit Error Setting Data
10 CheckSum
4 30401 Energy Counter n1 Exponent T2 Exponent
4 30402 Energy Counter n2 Exponent T2 Exponent
4 30403 Energy Counter n3 Exponent T2 Exponent
4 30404 Energy Counter n4 Exponent T2 Exponent
4 30405 Current Active Tariff T1
4 30406 30407 Energy Counter n1 T3 Mantissa x EXP(Register
30401) x 1 Wh
4 30408 30409 Energy Counter n2 T3 Mantissa x EXP(Register
30402) x 1 Wh
4 30410 30411 Energy Counter n3 T3 Mantissa x EXP(Register
30403) x 1 varh
4 30412 30413 Energy Counter n4 T3 Mantissa x EXP(Register
30404) x 1 varh
4 30414 30415 Energy Counter 1 T3 Mantissa x EXP(Register
30446) x 1 VAh/
varh/Wh
4 30416 30417 Energy Counter 2 T3 Mantissa x EXP(Register
30447) x 1 VAh/
varh/Wh
4 30418 30419 Energy Counter 3 T3 Mantissa x EXP(Register
30448) x 1 VAh/
varh/Wh
4 30420 30421 Energy Counter 4 T3 Mantissa x EXP(Register
30449) x 1 VAh/
varh/Wh
4 30422 30423 Energy Counter 5 T3 Mantissa x EXP(Register
30450) x 1 VAh/
varh/Wh
4 30424 30425 Energy Counter 6 T3 Mantissa x EXP(Register
30451) x 1 VAh/
varh/Wh
4 30426 30427 Energy Counter 7 T3 Mantissa x EXP(Register
30452) x 1 VAh/
varh/Wh
4 30428 30429 Energy Counter 8 T3 Mantissa x EXP(Register
30453) x 1 VAh/
varh/Wh
4 30446 Energy Counter 1 Exponent T2 Exponent
4 30447 Energy Counter 2 Exponent T2 Exponent
4 30448 Energy Counter 3 Exponent T2 Exponent
4 30449 Energy Counter 4 Exponent T2 Exponent
7M 7
4 30450 Energy Counter 5 Exponent T2 Exponent
4 30451 Energy Counter 6 Exponent T2 Exponent
4 30452 Energy Counter 7 Exponent T2 Exponent
4 30453 Energy Counter 8 Exponent T2 Exponent
4 30462 30463 1000 x Energy Counter n1 T3 x 0,1 Wh
4 30464 30465 1000 x Energy Counter n2 T3 x 0,1 varh
4 30466 30467 1000 x Energy Counter n3 T3 x 0,1 Wh
4 30468 30469 1000 x Energy Counter n4 T3 x 0,1 varh
4 30470 30471 1000 x Energy Counter 1 T3 x 0,1 VAh/varh/
Wh
4 30472 30473 1000 x Energy Counter 2 T3 x 0,1 VAh/varh/
Wh
4 30474 30475 1000 x Energy Counter 3 T3 x 0,1 VAh/varh/
Wh
4 30476 30477 1000 x Energy Counter 4 T3 x 0,1 VAh/varh/
Wh
4 30478 30479 1000 x Energy Counter 5 T3 x 0,1 VAh/varh/
Wh
4 30480 30481 1000 x Energy Counter 6 T3 x 0,1 VAh/varh/
Wh
4 30482 30483 1000 x Energy Counter 7 T3 x 0,1 VAh/varh/
Wh
4 30484 30485 1000 x Energy Counter 8 T3 x 0,1 VAh/varh/
Wh
MEASUREMENTS (IEEE 754 )
4 32480 32481 Run time T_float x 1 seconds
4 32484 32485 Uavg (phase to neutral) T_float x1V
4 32488 32489 SI T_float x1A
4 32490 32491 Active Power Total (Pt) T_float x1W
4 32492 32493 Reactive Power Total (Qt) T_float x 1 var
4 32494 32495 Apparent Power Total (St) T_float x 1 VA
4 32496 32497 Power Factor Total (PFt) T_float x1
4 32498 32499 Frequency T_float x 1 Hz
4 32500 32501 U1 T_float x1V
4 32516 32517 I1 T_float x1A
4 32530 32531 Active Power Phase L1 (P1) T_float x1W
4 32536 32537 Active Power Total (Pt) T_float x1W
4 32538 32539 Reactive Power Phase L1 (Q1) T_float x 1 var
4 32544 32545 Reactive Power Total (Qt) T_float x 1 var
4 32546 32547 Apparent Power Phase L1 (S1) T_float x 1 VA
4 32552 32553 Apparent Power Total (St) T_float x 1 VA
4 32554 32555 Power Factor Phase 1 (PF1) T_float x1
4 32560 32561 Power Factor Total (PFt) T_float x1
4 32562 32563 CAP/IND P. F. Phase 1 (PF1) T_float x1
4 32568 32569 CAP/IND P. F. Total (PFt) T_float x1
4 32570 32571 j1 (angle between U1 and I1) T_float x1°
4 32576 32577 Power Angle Total (atan2(Pt,Qt)) T_float x1°
4 32584 32585 Frequency T_float x 1 Hz
4 32588 32589 I1 THD% T_float x1%
4 32594 32595 U1 THD% T_float x1%
32638 32639 Energy Counter n1 T_float x 1 Wh
7M 8

32640 32641 Energy Counter n2 T_float x 1 varh


32642 32643 Energy Counter n3 T_float x 1 Wh
32644 32645 Energy Counter n4 T_float x 1 varh
4 32658 32659 Internal Temperature T_float x 1 °C
ENERGY
4 32750 32751 Aktiv Tariff T_float x1
4 32752 32753 Energy Counter n1 T_float x 1 Wh
4 32754 32755 Energy Counter n2 T_float x 1 varh
4 32756 32757 Energy Counter n3 T_float x 1 Wh
4 32758 32759 Energy Counter n4 T_float x 1 varh
4 32760 32761 Energy Counter 1 T_float x 1 VAh/varh/Wh
4 32762 32763 Energy Counter 2 T_float x 1 VAh/varh/Wh
4 32764 32765 Energy Counter 3 T_float x 1 VAh/varh/Wh
4 32766 32767 Energy Counter 4 T_float x 1 VAh/varh/Wh
4 32768 32769 Energy Counter 5 T_float x 1 VAh/varh/Wh
4 32770 32771 Energy Counter 6 T_float x 1 VAh/varh/Wh
4 32772 32773 Energy Counter 7 T_float x 1 VAh/varh/Wh
4 32774 32775 Energy Counter 8 T_float x 1 VAh/varh/Wh
NOMINAL VALUES
32981 32982 Reserved for nominal aux voltage T_float Unomx
32983 32984 Reserved for nominal aux current T_float Inomx
4 32985 32986 nominal phase voltage T_float Unom x1V
4 32987 32988 nominal phase current T_float Inom x1A
4 32989 32990 nominal phase power T_float Pnom x1W
4 32991 32992 nominal total power T_float Ptot x1W
4 32993 32994 nominal total current T_float Itot x1A
4 32995 32996 nominal frequency T_float Fnom x 1 Hz
4 34999 35000 Run time T3 seconds x 1 seconds
INTERVAL MEASUREMENTS
AVERAGE MEASUREMENTS
4 35500 The last Average interval duration T1 x 0,1 seconds
4 35501 Time since the last average meaure- T1 x 0,1 seconds
ments
4 35502 Average measurements counter T1
4 35503 35504 Timestamp T_unix '= 0 after reset
4 35505 35506 Frequency T5 x 1 Hz
4 35507 35508 U1 T5 x1V
4 35526 35527 I1 T5 x1A
4 35540 35541 Active Power Total (Pt) T6 x1W
4 35542 35543 Active Power Phase L1 (P1) T6 x1W
4 35548 35549 Reactive Power Total (Qt) T6 x 1 var
4 35550 35551 Reactive Power Phase L1 (Q1) T6 x 1 var
4 35556 35557 Apparent Power Total (St) T5 x 1 VA
4 35558 35559 Apparent Power Phase L1 (S1) T5 x 1 VA
4 35564 35565 Power Factor Total (PFt) T7 x1
4 35566 35567 Power Factor Phase 1 (PF1) T7 x1
4 35572 Power Angle Total (atan2(Pt,Qt)) T17 x1°
4 35573 j1 (angle between U1 and I1) T17 x1°
4 35581 Internal Temperature T17 x 1 °C
7M 9

THD HARMONIC DATA


4 35582 U1 THD% T16 x1%
4 35588 I1 THD% T16 x1%
MAXIMUM MEASUREMENTS
4 35600 35604 Reserved
4 35605 35606 Frequency T5 x 1 Hz
4 35607 35608 U1 T5 x1V
4 35626 35627 I1 T5 x1A
4 35640 35641 Active Power Total (Pt) T6 x1W
4 35642 35643 Active Power Phase L1 (P1) T6 x1W
4 35648 35649 Reactive Power Total (Qt) T6 x 1 var
4 35650 35651 Reactive Power Phase L1 (Q1) T6 x 1 var
4 35656 35657 Apparent Power Total (St) T5 x 1 VA
4 35658 35659 Apparent Power Phase L1 (S1) T5 x 1 VA
4 35664 35665 Power Factor Total (PFt) T7 x1
4 35666 35667 Power Factor Phase 1 (PF1) T7 x1
4 35672 Power Angle Total (atan2(Pt,Qt)) T17 x1°
4 35673 j1 (angle between U1 and I1) T17 x1°
4 35681 Internal Temperature T17 x 1 °C
THD HARMONIC DATA
4 35682 U1 THD% T16 x1%
4 35688 I1 THD% T16 x1%
MINIMUM MEASUREMENTS
4 35700 35704 Reserved
4 35705 35706 Frequency T5 x 1 Hz
4 35707 35708 U1 T5 x1V
4 35726 35727 I1 T5 x1A
4 35740 35741 Active Power Total (Pt) T6 x1W
4 35742 35743 Active Power Phase L1 (P1) T6 x1W
4 35748 35749 Reactive Power Total (Qt) T6 x 1 var
4 35750 35751 Reactive Power Phase L1 (Q1) T6 x 1 var
4 35756 35757 Apparent Power Total (St) T5 x 1 VA
4 35758 35759 Apparent Power Phase L1 (S1) T5 x 1 VA
4 35764 35765 Power Factor Total (PFt) T7 x1
4 35766 35767 Power Factor Phase 1 (PF1) T7 x1
4 35772 Power Angle Total (atan2(Pt,Qt)) T17 x1°
4 35773 j1 (angle between U1 and I1) T17 x1°
4 35781 Internal Temperature T17 x 1 °C
THD HARMONIC DATA
4 35782 U1 THD% T16 x1%
4 35788 I1 THD% T16 x1%
RAM logger
4 36000 Measurement parameter T1 See OutTypes
4 36001 Time interval T1 minutes
4 36002 Number of valid results T1
4 36003 Time stamp of last result T2 minutes since mid-
night (<0 if no time)
4 36004 36131 Logger table (newest to oldest) T17 Normalised values
7M 10
MODBUS SETTINGS

Valid with Register Contents Data Ind Values / Dependencies Min Max P.
Function Addresses Level
Codes
Holding Registers
40000 Memory Reference
SYSTEM COMMANDS
16 40001 40002 User Password (L1, L2) T_Str4 A…Z Password to attempt user 0
access level upgrade
16 40003 40005 Factory Password (FAC) T_Str6 A…Z Password to attempt factory 0
access level upgrade
16 40006 40007 Lavel 1 - User password T_Str4 A…Z 1
16 40008 40009 Lavel 2 - User password T_Str4 A…Z 2
3,6 40010 Active Acces Level T1 0 Full protection 0 0 0
6 40011 Manual password T1 1 Lock instrument 0
activation
6 40012 Operator Command T1 1 Save Settings 1 5 1
Register 2 Abort Settings
3 Restart Instrument
6 40014 Reset command register 2 T1 Bit-0 Reset alarm ouptut relay 1 1
Bit-8 Reset alarm ouptut IR
3,6 40015 IR external relay command T1 0 Off 0 1 0
action 1 On
3,6 40030 Select Active Tariff T1 1 6 1
6 40031 Reset energy command T1 Bit- Reset counter 1 .. 8 0 655 1
register 1 0..7 35
GENERAL SETTINGS
3, 6, 16 40101 40120 Description T_ 2
Str40
3, 6, 16 40121 40140 Location T_ 2
Str40
1 1b - Single Phase
3,6 40148 Current input range (%) T16 10000 for 100% 5,00 260,00 2
3,6 40149 Voltage input range (%) T16 10000 for 100% 2,50 100,00 2
3,6 40150 Frequency nominal value T1 Hz 10 1000 2
3, 6, 16 40161 40162 Time T9 1
3, 6, 16 40163 40164 Date T10 1
3,6 40166 Automatic change S/W T1 0 No 0 1 1
time
3,6 40170 LCD configurations T1 Bit 0 Counter description mode 0 1 2
(*0=OBIS code; 1=letters)
3,6 40172 LCD Back Light Intesnity T1 0=No Backlight 0 10 2
3,6 40173 LCD Back Light Time Off T1 Minutes (0=Always on) 0 60 2
3,6 40174 LCD scroll interval T1 Seconds 5 60 2
3,6 40184 LCD scroll parameters 1 T1 Bit 0 Counter n1 (Allways) 1 65535 2
Bit 1 Counter n2
Bit 2 Counter n3
Bit 3 Counter n4
3,6 40185 LCD scroll parameters 2 Bit Counter 1 .. 8 0 65535 2
0..7
7M 11

3,6 40186 LCD scroll parameters 3 Bit 0 Active Power Total (Pt) 0 65535 2
Bit 2 Reactive Power Total (Qt)
Bit 4 Apparent Power Total (St)
Bit 6 Uavg (phase to neutral)
Bit 10 Curent Total
Bit 12 Frequency
Bit 13 Active Tariff
Bit 14 Power Factor Total (PFt)
3,6 40187 LCD scroll parameters 4 Bit 0 Power Angle Total 0 15 2
(atan2(Pt,Qt))
Bit 2 THD of voltage
Bit 3 THD of current
3,6 40188 LCD return mode T1 0 Auto scroll 0 2 2
1 Counter n1
2 Hold page
3,6 40192 Comm. & LCD average T1 10=1,0 sec 0,1 5,0 2
interval
COMMUNICATION
3,6 40202 Port 1: Device Adress T1 1 247 2
(Modbus)
3,6 40203 Port 1: Baud Rate T1 0 Baud rate 1200 1 7 2
1 Baud rate 2400
2 Baud rate 4800
3 Baud rate 9600
4 Baud rate 19200
5 Baud rate 38400
6 Baud rate 57600
7 Baud rate 115200
3,6 40204 Port 1: Stop Bit T1 0 1 Stop bit 0 1 2
1 2 Stop bits
3,6 40205 Port 1: Parity T1 0 No parity 0 2 2
1 Odd parity
2 Even parity
3,6 40206 Port 1: Data Bits T1 0 8 bits 0 0 2
3,6 40207 Port 1: TCP Port T1 1 65535 2
3, 6, 16 40208 40227 Port 1: IP Host name T_ 2
Str40
3, 6, 16 40228 40229 Port 1: IP Address T_ 0
Hex4
3, 6, 16 40230 40231 Port 1: Subnet Mask T_ 0
Hex4
3, 6, 16 40232 40233 Port 1: Default Router T_ 2
Hex4
3, 6, 16 40234 40241 WIFI password T_ 2
Str16
3, 6, 16 40242 40249 WIFI SSID T_ 2
Str16
3,6 40250 Bluetooth ON/OFF T1 0 Off 0 1 2
1 On
IR
7M 12

3,6 40252 Port 2: Device Adress T1 1 247 2


(Modbus)
3,6 40253 Port 2: Baud Rate T1 see Port 1: Baud Rate 3 7 2
3,6 40254 Port 2: Stop Bit T1 see Port 1: Stop Bit 0 1 2
3,6 40255 Port 2: Parity T1 see Port 1: Parity 0 2 2
3,6 40256 Port 2: Data Bits T1 see Port 1: Data Bits 0 0 2
M-bus
3,6 40271 M-bus Primary address T1 0 250 2
3,6 40272 M-bus: Baud Rate T1 0 Baud rate 300 1 5 2
1 Baud rate 600
2 Baud rate 1200
3 Baud rate 2400
4 Baud rate 4800
5 Baud rate 9600
3,6 40273 40274 M-bus Secondary address T3 Digits only (Default = Serial 0 9999 2
number) 9999

ENERGY
1..4 Tariff 1..4
NON-RESETABLE COUNTERS
3,6 40421 Energy Counter n1 T1 0 No Parameter 0 95 2
Parameter 1 Active Power
2 Reactive pover
3 Apparent Power
5 Active Power Phase 1
6 Reactive pover Phase 1
7 Apparent Power Phase 1
3,6 40422 Energy Counter n1 T1 Bit-0 Quadrant I Enabled 0 63 2
Configuration Bit-1 Quadrant II Enabled
Bit-2 Quadrant III Enabled
Bit-3 Quadrant IIII Enabled
Bit-4 Absolute Value
Bit-5 Invert Value
3,6 40423 Energy Counter n1 T2 -3 6 2
Exponent
3,6 40424 Energy Counter n1 Tarif T1 Bit-0 Tarif 1 Enabled 0 63 2
Selector Bit-1 Tarif 2 Enabled
Bit-2 Tarif 3 Enabled
Bit-3 Tarif 4 Enabled
3,6 40425 Energy Counter n2 T1 see Energy Counter n1 0 95 2
Parameter Parameter
3,6 40426 Energy Counter n2 T1 see Energy Counter n1 0 63 2
Configuration Configuration
3,6 40427 Energy Counter n2 T2 see Energy Counter n1 0 6 2
Exponent Exponent
3,6 40428 Energy Counter n2 Tarif T1 see Energy Counter n1 Tarif 0 63 2
Selector Selector
3,6 40429 Energy Counter n3 T1 see Energy Counter n1 0 95 2
Parameter Parameter
7M 13
3,6 40430 Energy Counter n3 T1 see Energy Counter n1 0 63 2
Configuration Configuration
3,6 40431 Energy Counter n3 T2 see Energy Counter n1 0 6 2
Exponent Exponent
3,6 40432 Energy Counter n3 Tarif T1 see Energy Counter n1 Tarif 0 63 2
Selector Selector
3,6 40433 Energy Counter n4 T1 see Energy Counter n1 0 95 2
Parameter Parameter
3,6 40434 Energy Counter n4 T1 see Energy Counter n1 0 63 2
Configuration Configuration
3,6 40435 Energy Counter n4 T2 see Energy Counter n1 0 6 2
Exponent Exponent
3,6 40436 Energy Counter n4 Tarif T1 see Energy Counter n1 Tarif 0 63 2
Selector Selector
3,6 40437 Energy Counter 1 T1 see Energy Counter n1 0 95 2
Parameter Parameter
3,6 40438 Energy Counter 1 T1 see Energy Counter n1 0 63 2
Configuration Configuration
3,6 40439 Energy Counter 1 Exponent T2 see Energy Counter n1 0 6 2
Exponent
3,6 40440 Energy Counter 1 Tarif T1 see Energy Counter n1 Tarif 0 63 2
Selector Selector
3,6 40441 Energy Counter 2 T1 see Energy Counter n1 0 95 2
Parameter Parameter
3,6 40442 Energy Counter 2 T1 see Energy Counter n1 0 63 2
Configuration Configuration
3,6 40443 Energy Counter 2 Exponent T2 see Energy Counter n1 0 6 2
Exponent
3,6 40444 Energy Counter 2 Tarif T1 see Energy Counter n1 Tarif 0 63 2
Selector Selector
3,6 40445 Energy Counter 3 T1 see Energy Counter n1 0 95 2
Parameter Parameter
3,6 40446 Energy Counter 3 T1 see Energy Counter n1 0 63 2
Configuration Configuration
3,6 40447 Energy Counter 3 Exponent T2 see Energy Counter n1 0 6 2
Exponent
3,6 40448 Energy Counter 3 Tarif T1 see Energy Counter n1 Tarif 0 63 2
Selector Selector
3,6 40449 Energy Counter 4 T1 see Energy Counter n1 0 95 2
Parameter Parameter
3,6 40450 Energy Counter 4 T1 see Energy Counter n1 0 63 2
Configuration Configuration
3,6 40451 Energy Counter 4 Exponent T2 see Energy Counter n1 0 6 2
Exponent
3,6 40452 Energy Counter 4 Tarif T1 see Energy Counter n1 Tarif 0 63 2
Selector Selector
3,6 40453 Energy Counter 5 T1 see Energy Counter n1 0 95 2
Parameter Parameter
3,6 40454 Energy Counter 5 T1 see Energy Counter n1 0 63 2
Configuration Configuration
3,6 40455 Energy Counter 5 Exponent T2 see Energy Counter n1 0 6 2
Exponent
3,6 40456 Energy Counter 5 Tarif T1 see Energy Counter n1 Tarif 0 63 2
Selector Selector
7M 14
3,6 40457 Energy Counter 6 T1 see Energy Counter n1 0 95 2
Parameter Parameter
3,6 40458 Energy Counter 6 T1 see Energy Counter n1 0 63 2
Configuration Configuration
3,6 40459 Energy Counter 6 Exponent T2 see Energy Counter n1 0 6 2
Exponent
3,6 40460 Energy Counter 6 Tarif T1 see Energy Counter n1 Tarif 0 63 2
Selector Selector
3,6 40461 Energy Counter 7 T1 see Energy Counter n1 0 95 2
Parameter Parameter
3,6 40462 Energy Counter 7 T1 see Energy Counter n1 0 63 2
Configuration Configuration
3,6 40463 Energy Counter 7 Exponent T2 see Energy Counter n1 0 6 2
Exponent
3,6 40464 Energy Counter 7 Tarif T1 see Energy Counter n1 Tarif 0 63 2
Selector Selector
3,6 40465 Energy Counter 8 T1 see Energy Counter n1 0 95 2
Parameter Parameter
3,6 40466 Energy Counter 8 T1 see Energy Counter n1 0 63 2
Configuration Configuration
3,6 40467 Energy Counter 8 Exponent T2 see Energy Counter n1 0 6 2
Exponent
3,6 40468 Energy Counter 8 Tarif T1 see Energy Counter n1 Tarif 0 63 2
Selector Selector
ALARMS
3,6 41001 Alarm Enable Flags G1, G2 T1 Bit Group 1 Limit 1 .. 4 2
0..4
ALARM GROUP 1
3,6 41004 Compare time delay T1 seconds 0 900 2
3,6 41005 Hysteresis T16 % of compare value, if 0 0,00 10,00 2
then % of nominal value
GROUP 1 Limit 1
3,6 41008 Limit 1 Parameter T1 See OutTypes 0 1023 2
3,6 41009 Limit 1 Function T1 Bit-1 Reserved: Store into 0 80 2
memory (all)
Bit-4 Activate Alarm Output
Bit-6 Limit Condition > (< if 0)
GROUP 1 Limit 2
3,6 41011 Limit 2 Parameter T1 see Limit 1 Parameter 0 127 2
3,6 41012 Limit 2 Function T1 see Limit 1 Function 0 80 2
3,6 41013 Limit 2 Compare value T16 see Limit 1 Compare value -300 +300. 2
.00 00
GROUP 1 Limit 3
3,6 41014 Limit 3 Parameter T1 see Limit 1 Parameter 0 127 2
3,6 41015 Limit 3 Function T1 see Limit 1 Function 0 80 2
3,6 41016 Limit 3 Compare value T16 see Limit 1 Compare value -300. +300. 2
00 00

GROUP 1 Limit 4
3,6 41017 Limit 4 Parameter T1 see Limit 1 Parameter 0 127 2
3,6 41018 Limit 4 Function T1 see Limit 1 Function 0 80 2
7M 15
3,6 41019 Limit 4 Compare value T16 see Limit 1 Compare value -300. +300. 2
00 00
ALARM GROUP 2 See ALARM GROUP 1 2
3,6 41033 Compare time delay T1 seconds 0 900 2
3,6 41034 Hysteresis T16 % of compare value, if 0 0,00 10,00 2
then % of nominal value
GROUP 2 Limit 1
3,6 41037 Limit 1 Parameter T1 see GROUP 1 Limit 1 0 127 2
Parameter
3,6 41038 Limit 1 Function T1 see GROUP 1 Limit 1 0 80 2
Function
3,6 41039 Limit 1 Compare value T16 see GROUP 1 Limit 1 -300 +300. 2
Compare value .00 00
3,6 41040 41042 GROUP 2 Limit 2 See GROUP 1 Limit 1
3,6 41043 41045 GROUP 2 Limit 3 See GROUP 1 Limit 1
3,6 41046 41048 GROUP 2 Limit 4 See GROUP 1 Limit 1
Logic Function 1
3,6 41131 Input 1 T1 0 disabled 0 50 2
1 GROUP 1 Limit 1
2 GROUP 1 Limit 2
3 GROUP 1 Limit 3
4 GROUP 1 Limit 4
9 GROUP 2 Limit 1
10 GROUP 2 Limit 2
11 GROUP 2 Limit 3
12 GROUP 2 Limit 4
33 Group E Limit 1
34 Group E Limit 2
35 Group E Limit 3
36 Group E Limit 4
41 Group 1 (OR all)
42 Group 2 (OR all)
45 Group E (OR all)
46 Group 1 (AND all)
47 Group 2 (AND all)
50 Group E (AND all)
3,6 41132 Input 2 T1 see Input 1 0 50 2
3,6 41133 Input 3 T1 see Input 1 0 50 2
3,6 41134 Input 4 T1 see Input 1 0 50 2
3,6 41135 Function 1 T1 0 AND 0 1 2
1 OR
3,6 41136 Function 2 T1 see Function 1 0 1 2
3,6 41137 Function 3 T1 see Function 1 0 1 2
Logic Function 2
3,6 41139 Input 1 T1 see Logic Function 1 Input 1 0 50 2
3,6 41140 Input 2 T1 see Logic Function 1 Input 1 0 50 2
3,6 41141 Input 3 T1 see Logic Function 1 Input 1 0 50 2
3,6 41142 Input 4 T1 see Logic Function 1 Input 1 0 50 2
3,6 41143 Function 1 T1 see Logic Function 1 0 1 2
Function 1
7M 16
3,6 41144 Function 2 T1 see Logic Function 1 0 1 2
Function 1
3,6 41145 Function 3 T1 see Logic Function 1 0 1 2
Function 1
ALARM GROUP Energy
3,6 41161 Limit 1 Parameter T1 0 disabled 0 44 2
1..8 Counter 1 .. 8
33..36 Counter n1 .. n4
3,6 41162 Limit 1 Function T1 Bit-1 Reserved: Store into 0 80 2
memory (all)
Bit-4 Activate Alarm Output
Bit-6 Alarm Condition > (< if 0)
3,6 41163 41164 Limit 1 Compare value T3 digits in the counter 0 99999 2
resolution 9999
3,6 41165 Limit 2 Parameter T1 see Limit 1 Parameter 0 44 2
3,6 41166 Limit 2 Function T1 see Limit 1 Function 0 1 2
3,6 41167 41168 Limit 2 Compare value T3 see Limit 1 Compare value 0 99999 2
9999
3,6 41169 Limit 3 Parameter T1 see Limit 1 Parameter 0 44 2
3,6 41170 Limit 3 Function T1 see Limit 1 Function 0 1 2
3,6 41171 41172 Limit 3 Compare value T3 see Limit 1 Compare value 0 99999 2
9999
3,6 41173 Limit 4 Parameter T1 see Limit 1 Parameter 0 44 2
3,6 41174 Limit 4 Function T1 see Limit 1 Function 0 1 2
3,6 41175 41176 Limit 4 Compare value T3 see Limit 1 Compare value 0 99999 2
9999
OUTPUTS
3,6 41200 Pulse LED Operation mode 0 Normal mode 0 6 0
1 Test mode P - Fast
2 Test mode P - Fast (Counter
only)
3 Test mode P
4 Test mode Q
5 Test mode Q - Fast
6 Test mode Q - Fast (Counter
only)
3,6 41201 Pulse LED Parameter T1 0 Not set 0 95 2
1..95 see Energy Counter n1
Parameter
3,6 41202 Pulse LED Configuration T1 see Energy Counter n1 0 63 2
Configuration
3,6 41203 Pulse LED No. Of pulses T1 1 65535 2
3,6 41204 Pulse LED Energy unit T1 * 10^(Common Energy 1 65535 2
Counter Exponent)
3,6 41205 Pulse LED Pulse lenght T1 ms 2 1000 2
PULSE OUTPUTS
3,6 41207 Output 1 Function T1 0 Alarm output 0 1 2
1 Pulse output
3,6 41211 Pulse Output 1 Parameter T1 0 Not set 0 95 2
1..95 see Energy Counter n1
Parameter
3,6 41212 Pulse Output 1 T1 see Energy Counter n1 0 63 2
Configuration Configuration
7M 17
3,6 41213 Pulse Output 1 No. Of T1 1 65535 2
pulses
3,6 41214 Pulse Output 1 Energy unit T1 * 10^(Common Energy 1 65535 2
Counter Exponent)
3,6 41215 Pulse Output 1 Pulse lenght T1 ms 2 1000 2
3,6 41216 Pulse Output 1 Tarif T1 Bit-0 Tarif 1 enabled 0 63 2
Selector Bit-1 Tarif 2 enabled
Bit-2 Tarif 3 enabled
Bit-3 Tarif 4 enabled
ALARM OUTPUTS
ALARM OUTPUT IR
3,6 41235 IR External relay operating T1 0 Not connected 0 2 2
mode 1 Manual
2 Alarm output control
3,6 41236 Enabled Alarm groups T1 See ALARM OUTPUT 1 0 255 2
3,6 41237 Output signal T1 See ALARM OUTPUT 1 0 7 2
3,6 41238 Output pulse length T1 Seconds 1 999 2
ALARM OUTPUT 1
3,6 41239 Enabled Alarm groups T1 Bit-0 Group 1 0 255 2
Bit-1 Group 2
Bit-4 Group E
Bit-5 Logic Function 1
Bit-6 Logic Function 2
3,6 41240 Output signal T1 0 Normal 0 7 2
1 Permanent
2 Pulsed
3 Always ON
4 Always OFF
5 Normal inverse
6 Permanent inverse
7 Pulsed inverse
3,6 41241 Output pulse length T1 Seconds 1 999 2
ENERGY snapshot registers
3, 6 41901 Auto freeze interval T1 0 65536 0
[minutes]
3, 6 41902 time to freeze [s] T1 0 65536 0
3 41903 41904 time from freeze [s] T3u
3, 6 41905 Freeze STATUS T1 0 at reset 1 65533 0
65534 at interval
65535 at time to freeze
3 41906 Current Active Tariff T1
3 41907 41908 Energy Counter n1 T3
3 41909 41910 Energy Counter n2 T3
3 41911 41912 Energy Counter n3 T3
3 41913 41914 Energy Counter n4 T3
3 41915 41916 Energy Counter 1 T3
3 41917 41918 Energy Counter 2 T3
3 41919 41920 Energy Counter 3 T3
3 41921 41922 Energy Counter 4 T3
3 41923 41924 Energy Counter 5 T3
7M 18

3 41925 41926 Energy Counter 6 T3


3 41927 41928 Energy Counter 7 T3
3 41929 41930 Energy Counter 8 T3
INTERVAL MEASUREMENTS
3, 6 41990 Interval duration [s/10] T1 600=60,0 sec 0,1 3600 0
3, 6 41991 Time to calculate interval T1 0,1 3600 0
meas. [s/10]
7M 19

MODBUS DATA TYPES

Type Value / Bit Mask Description


T1 Unsigned Value (16 bit)
Example: 12345 stored as 12345 = 3039(16)
T2 Signed Value (16 bit)
Example: -12345 stored as -12345 = CFC7(16)
T3 Signed Long Value (32 bit)
Example: 123456789 stored as 123456789 = 075B CD 15(16)
T4 Short Unsigned float (16 bit)
bits # 15..14 Decade Exponent(Unsigned 2 bit)
bits # 13..00 Binary Unsigned Value (14 bit)
Example: 10000*102 stored as A710(16)
T5 Unsigned Measurement (32 bit)
bits # 31..24 Decade Exponent(Signed 8 bit)
bits # 23..00 Binary Unsigned Value (24 bit)
Example: 123456*10-3 stored as FD01 E240(16)
T6 Signed Measurement (32 bit)
bits # 31..24 Decade Exponent (Signed 8 bit)
bits # 23..00 Binary Signed value (24 bit)
Example: - 123456*10-3 stored as FDFE 1DC0(16)
T7 Power Factor (32 bit)
bits # 31..24 Sign: Import/Export (00/FF)
bits # 23..16 Sign: Inductive/Capacitive (00/FF)
bits # 15..00 Unsigned Value (16 bit), 4 decimal places
Example: 0.9876 CAP stored as 00FF 2694(16)
T8 Time stamp (32 bit)
bits # 31..24 Minutes 00 - 59 (BCD)
bits # 23..16 Hours 00 - 23 (BCD)
bits # 15..08 Day of month 01 - 31 (BCD)
bits # 07..00 Month of year 01 - 12 (BCD)
Example: 15:42, 1. SEP stored as 4215 0109(16)
T9 Time (32 bit)
bits # 31..24 1/100s 00 - 99 (BCD)
bits # 23..16 Seconds 00 - 59 (BCD)
bits # 15..08 Minutes 00 - 59 (BCD)
bits # 07..00 Hours 00 - 24 (BCD)
Example: 15:42:03.75 stored as 7503 4215(16)
T10 Date (32 bit)
bits # 31..24 Day of month 01 - 31 (BCD)
bits # 23..16 Month of year 01 - 12 (BCD)
bits # 15..00 Year (unsigned integer) 1998..4095
Example: 10, SEP 2000 stored as 1009 07D0(16)
T_Str4 Text String 4 characters
(T11) Two characters per 16 bit register
T_Str6 Text String 6 characters
(T12) Two charcters per 16 bit register
7M 20

T_Str8 Text String 8 characters


Two characters per 16 bit register.
T_Str16 Text String 16 characters
Two characters per 16 bit register.
T_Str20 Text String 20 characters
Two characters per 16 bit register.
T16 Unsigned Value (16 bit), 2 decimal places
Example: 123.45 stored as 123.45 = 3039(16)
T17 Signed Value (16 bit), 2 decimal places
Example: -123.45 stored as -123.45 = CFC7(16)
T_Time Time and Date (64 bit)
bits # 63..56 1/100s 00 - 99 (BCD)
bits # 55..48 Seconds 00 - 59 (BCD)
bits # 47..40 Minutes 00 - 59 (BCD)
bits # 39..32 Hours 00 - 24 (BCD)
bits # 31..24 Day of month 01 - 31 (BCD)
bits # 23..16 Month of year 01 - 12 (BCD)
bits # 15..00 Year (unsigned integer) 1998..4095
Example: 15:42:03.75, 10. SEP 2000 stored as 7503 4215 1009 07D0(16)
T_TimeIEC Time and Date (64 bit) = IEC870-5-4 "Binary Time 2a"
bits # 63..55 Reserved
bits # 54..48 Years (0 .. 99)
bits # 47..44 Reserved
bits # 43..40 Months (1 .. 12)
bits # 39..37 Day of Week (1 .. 7)
bits # 36..32 Day of Month (1 .. 31)
bit # 31 Summer Time (0 .. 1): Summer time (1), Standard time (0)
bits # 30..29 Reserved
bits # 28..24 Hours (0 .. 23)
bit # 23 Invalid (0 .. 1): Invalid (1), Valid (0)
bit # 22 Reserved
bits # 21..16 Minutes (0 .. 59)
bits # 15..00 Miliseconds (0 .. 59999)
Example: 15:42, 1. SEP stored as 4215 0109(16)
T_Data Record Data
Size and SubTypes depends on the Actual Memory Part
T_Str40 Text String 40 characters
Two characters per 16 bit register.
T_float IEEE 754 Floating-Point Single Precision Value (32 bit)
bits # 31 Sign Bit (1 bit)
bits # 30..23 Exponent Field (8 bit)
bits # 22..0 Significand (23 bit)
Example: 123.45 stored as 123.45000 = 42F6 E666(16)
T9A Time (16 bit)
7M 21

bits # 15..08 Minutes 00 - 59 (BCD)


bits # 07..00 Hours 00 - 24 (BCD)
Example: 15:42 stored as 4215(16)
T10A Date (16 bit)
bits # 15..08 Day of month 00 - 31 (BCD)
bits # 07..00 Month of year 00 - 12 (BCD)
Example: 30, SEP stored as 3009(16)
T18 Signed Value (16 bit), 4 decimal places
Example: -0.2345 stored as -2345 = F6D7(16)
T_unix Unix time (32 bit)
Bits # 31..00 Seconds since January 1, 1970
Example: 16 May 2012 10:36:46 GMT stored as 4FB3 833E(16)
7M 22

MODBUS COMMUNICATION
PROTOCOL 7M38
7M 23

MODBUS INFO

Read with Register Addresses Contents Data Ind Values / Dependencies


Function Type
Code
Input Registers
30000 Memory Reference
READ ONLY INFO
4 30001 30008 Model Number T_Str16
4 30009 30012 Serial Number T_Str8
4 30013 Software Reference T1 Software version
4 30014 Hardware Reference T_Str2 Hardware version
4 30015 Calibration voltage T16 V/100
4 30017 Calibration current T16 A/100
4 30019 Accuracy class T17 100=1,00
4 30020 MiNet Flag T1 0
4 30024 COM1: Communication Type T1 0 No Communication
2 RS485
13 M-bus
15 WiFi
4 30029 I/O 1 T1 0 No I/O
5 Tariff Input
10 Digital input
12 Pulse Output (SO)
4 30030 I/O 2 T1 See I/O 1
4 30031 I/O 3 T1 See I/O 1
4 30044 Status register T1 Bit- Locked
0
Bit- Clock not set
4
4 30055 30057 Ethernet MAC Address T_Hex6
4 30058 Ethernet Software Reference T1 Ethernet Software version
4 30059 30060 Ethernet: IP Address T_Hex4 Actual Ethernet IP Address
4 30061 phase module 1 Software T17 100=1,0
reference
4 30062 phase module 2 Software T17 100=1,0
reference
4 30063 phase module 3 Software T17 100=1,0
reference
4 30064 phase module 1 CheckSum T1
4 30065 phase module 2 CheckSum T1
4 30066 phase module 3 CheckSum T1
4 30067 phase m. 1 Calibration Data T1
CheckSum
7M 24

4 30068 phase m. 2 Calibration Data T1


CheckSum
4 30069 phase m. 3 Calibration Data T1
CheckSum
4 30070 Measurement module Soft- T17 100=1,0
ware ref.
4 30071 Measurement module Check- T1
Sum
4 30072 Meas. m. Calibration Data T1
CheckSum
4 30073 MID Setting Data CheckSum T1
4 30074 Setting Data CheckSum T1
4 30075 Software Checksum T1
4 30076 MID lock status T1 0 unlocked
1 locked
4 30077 30078 Calibration Time Stamp T_unix
4 30079 MID unlock counter T1
4 30080 FW upgrade counter T1
4 30098 Active Communication Port T1 1 COM1
4 30099 Modbus Max. Register Read T1
at Once
30100 38999 MEASUREMENTS
READ ONLY INFO
4 39000 Device group T1 5 7M
7M 25

MODBUS MEASUREMENTS
Read with Register Contents Data Ind Values / Multiplicator and
Function Addresses Dependencies Unit
Code
Input Registers
30000 Memory Reference
ACTUAL MEASUREMENTS
4 30101 Phase valid measurement T1 Bit 0 Invalid
measurement
phase 1
Bit 1 Invalid
measurement
phase 2
Bit 2 Invalid
measurement
phase 3
4 30103 30104 Run time T3 seconds x 1 seconds
4 30105 30106 Frequency T5 x 1 Hz
4 30107 30108 U1 T5 x1V
4 30109 30110 U2 T5 x1V
4 30111 30112 U3 T5 x1V
4 30113 30114 Uavg (phase to neutral) T5 x1V
4 30115 j12 (angle between U1 and U2) T17 x1°
4 30116 j23 (angle between U2 and U3) T17 x1°
4 30117 j31 (angle between U3 and U1) T17 x1°
4 30118 30119 U12 T5 x1V
4 30120 30121 U23 T5 x1V
4 30122 30123 U31 T5 x1V
4 30124 30125 Uavg (phase to phase) T5 x1V
4 30126 30127 I1 T5 x1A
4 30128 30129 I2 T5 x1A
4 30130 30131 I3 T5 x1A
4 30136 30137 Iavg T5 x1A
4 30138 30139 SI T5 x1A
4 30140 30141 Active Power Total (Pt) T6 x1W
4 30142 30143 Active Power Phase L1 (P1) T6 x1W
4 30144 30145 Active Power Phase L2 (P2) T6 x1W
4 30146 30147 Active Power Phase L3 (P3) T6 x1W
4 30148 30149 Reactive Power Total (Qt) T6 x 1 var
4 30150 30151 Reactive Power Phase L1 (Q1) T6 x 1 var
4 30152 30153 Reactive Power Phase L2 (Q2) T6 x 1 var
4 30154 30155 Reactive Power Phase L3 (Q3) T6 x 1 var
4 30156 30157 Apparent Power Total (St) T5 x 1 VA
4 30158 30159 Apparent Power Phase L1 (S1) T5 x 1 VA
4 30160 30161 Apparent Power Phase L2 (S2) T5 x 1 VA
4 30162 30163 Apparent Power Phase L3 (S3) T5 x 1 VA
4 30164 30165 Power Factor Total (PFt) T7 x1
7M 26

4 30166 30167 Power Factor Phase 1 (PF1) T7 x1


4 30168 30169 Power Factor Phase 2 (PF2) T7 x1
4 30170 30171 Power Factor Phase 3 (PF3) T7 x1
4 30172 Power Angle Total T17 x1°
(atan2(Pt,Qt))
4 30173 j1 (angle between U1 and I1) T17 x1°
4 30174 j2 (angle between U2 and I2) T17 x1°
4 30175 j3 (angle between U3 and I3) T17 x1°
4 30181 Internal Temperature T17 x 1 °C
THD HARMONIC DATA
4 30182 U1 THD% T16 x1%
4 30183 U2 THD% T16 x1%
4 30184 U3 THD% T16 x1%
4 30188 I1 THD% T16 x1%
4 30189 I2 THD% T16 x1%
4 30190 I3 THD% T16 x1%
I/O STATUS
4 30191 Alarm Status Flags(G1, G2 T1 Bit Group 1 Limit
0..4 1 .. 4
Bit Group 2 Limit
8..12 1 .. 4
4 30192 Alarm Status Flags(G3, G4 T1 Bit Group 3 Limit
0..4 1 .. 4
Bit Group 4 Limit
8..12 1 .. 4
4 30193 I/O 1 Value T17
4 30194 I/O 2 Value T17
4 30195 I/O 3 Value T17
4 30197 External relay status T1 0 Off
1 On
250 Comm. Error
255 Not connected
4 30200 Alarm Status Flags(GE T1 Bit Group E Limit
0..4 1 .. 4
7M 27

4 30201 Logic functions values T1 Bit 0 Logic function 1


Bit 1 Logic function 2
Bit 2 Logic function 3
4 30396 30399 Actual time T_
Time
4 30400 CheckSum Status T1 0 No Error (OK)
Bit 0 Error Parameter
CRC
Bit 1 Error Firmware
CRC
Bit 2 Error MID-lock
Bit 3 Error phase
module 1
CheckSum
Bit 4 Error phase
module 2
CheckSum
Bit 5 Error phase
module 3
CheckSum
Bit 6 Error
Measurement
module
CheckSum
Bit 7 Error Software
Checksum
Bit 8 Error Calibration
Data CheckSum
Bit 9 Error MID
Setting Data
CheckSum
Bit 10 Error Setting
Data CheckSum
Bit 11 Error phase
m. 1 Cal. Data
CheckSum
Bit 12 Error phase
m. 2 Cal. Data
CheckSum
Bit 13 Error phase
m. 3 Cal. Data
CheckSum
4 30401 Energy Counter n1 Exponent T2 Exponent
4 30402 Energy Counter n2 Exponent T2 Exponent
4 30403 Energy Counter n3 Exponent T2 Exponent
4 30404 Energy Counter n4 Exponent T2 Exponent
4 30405 Current Active Tariff T1
4 30406 30407 Energy Counter n1 T3 Mantissa x EXP(Register
30401) x 1 Wh
4 30408 30409 Energy Counter n2 T3 Mantissa x EXP(Register
30402) x 1 Wh
7M 28
4 30410 30411 Energy Counter n3 T3 Mantissa x EXP(Register
30403) x 1 varh
4 30412 30413 Energy Counter n4 T3 Mantissa x EXP(Register
30404) x 1 varh
4 30414 30415 Energy Counter 1 T3 Mantissa x EXP(Register
30446) x 1 VAh/
varh/Wh
4 30416 30417 Energy Counter 2 T3 Mantissa x EXP(Register
30447) x 1 VAh/
varh/Wh
4 30418 30419 Energy Counter 3 T3 Mantissa x EXP(Register
30448) x 1 VAh/
varh/Wh
4 30420 30421 Energy Counter 4 T3 Mantissa x EXP(Register
30449) x 1 VAh/
varh/Wh
4 30422 30423 Energy Counter 5 T3 Mantissa x EXP(Register
30450) x 1 VAh/
varh/Wh
4 30424 30425 Energy Counter 6 T3 Mantissa x EXP(Register
30451) x 1 VAh/
varh/Wh
4 30426 30427 Energy Counter 7 T3 Mantissa x EXP(Register
30452) x 1 VAh/
varh/Wh
4 30428 30429 Energy Counter 8 T3 Mantissa x EXP(Register
30453) x 1 VAh/
varh/Wh
4 30430 30431 Energy Counter 9 T3 Mantissa x EXP(Register
30454) x 1 VAh/
varh/Wh
4 30432 30433 Energy Counter 10 T3 Mantissa x EXP(Register
30455) x 1 VAh/
varh/Wh
4 30434 30435 Energy Counter 11 T3 Mantissa x EXP(Register
30456) x 1 VAh/
varh/Wh
4 30436 30437 Energy Counter 12 T3 Mantissa x EXP(Register
30457) x 1 VAh/
varh/Wh
4 30438 30439 Energy Counter 13 T3 Mantissa x EXP(Register
30458) x 1 VAh/
varh/Wh
4 30440 30441 Energy Counter 14 T3 Mantissa x EXP(Register
30459) x 1 VAh/
varh/Wh
4 30442 30443 Energy Counter 15 T3 Mantissa x EXP(Register
30460) x 1 VAh/
varh/Wh
4 30444 30445 Energy Counter 16 T3 Mantissa x EXP(Register
30461) x 1 VAh/
varh/Wh
4 30446 Energy Counter 1 Exponent T2 Exponent
7M 29
4 30447 Energy Counter 2 Exponent T2 Exponent
4 30448 Energy Counter 3 Exponent T2 Exponent
4 30449 Energy Counter 4 Exponent T2 Exponent
4 30450 Energy Counter 5 Exponent T2 Exponent
4 30451 Energy Counter 6 Exponent T2 Exponent
4 30452 Energy Counter 7 Exponent T2 Exponent
4 30453 Energy Counter 8 Exponent T2 Exponent
4 30454 Energy Counter 9 Exponent T2 Exponent
4 30455 Energy Counter 10 Exponent T2 Exponent
4 30456 Energy Counter 11 Exponent T2 Exponent
4 30457 Energy Counter 12 Exponent T2 Exponent
4 30458 Energy Counter 13 Exponent T2 Exponent
4 30459 Energy Counter 14 Exponent T2 Exponent
4 30460 Energy Counter 15 Exponent T2 Exponent
4 30461 Energy Counter 16 Exponent T2 Exponent
4 30462 30463 1000 x Energy Counter n1 T3 x 0,1 Wh
4 30464 30465 1000 x Energy Counter n2 T3 x 0,1 varh
4 30466 30467 1000 x Energy Counter n3 T3 x 0,1 Wh
4 30468 30469 1000 x Energy Counter n4 T3 x 0,1 varh
4 30470 30471 1000 x Energy Counter 1 T3 x 0,1 VAh/varh/Wh
4 30472 30473 1000 x Energy Counter 2 T3 x 0,1 VAh/varh/Wh
4 30474 30475 1000 x Energy Counter 3 T3 x 0,1 VAh/varh/Wh
4 30476 30477 1000 x Energy Counter 4 T3 x 0,1 VAh/varh/Wh
4 30478 30479 1000 x Energy Counter 5 T3 x 0,1 VAh/varh/Wh
4 30480 30481 1000 x Energy Counter 6 T3 x 0,1 VAh/varh/Wh
4 30482 30483 1000 x Energy Counter 7 T3 x 0,1 VAh/varh/Wh
4 30484 30485 1000 x Energy Counter 8 T3 x 0,1 VAh/varh/Wh
4 30486 30487 1000 x Energy Counter 9 T3 x 0,1 VAh/varh/Wh
4 30488 30489 1000 x Energy Counter 10 T3 x 0,1 VAh/varh/Wh
4 30490 30491 1000 x Energy Counter 11 T3 x 0,1 VAh/varh/Wh
4 30492 30493 1000 x Energy Counter 12 T3 x 0,1 VAh/varh/Wh
4 30494 30495 1000 x Energy Counter 13 T3 x 0,1 VAh/varh/Wh
4 30496 30497 1000 x Energy Counter 14 T3 x 0,1 VAh/varh/Wh
4 30498 30499 1000 x Energy Counter 15 T3 x 0,1 VAh/varh/Wh
4 30500 30501 1000 x Energy Counter 16 T3 x 0,1 VAh/varh/Wh
MEASUREMENTS (IEEE 754 )
4 32480 32481 Run time T_ x 1 seconds
float
4 32484 32485 Uavg (phase to neutral) T_ x1V
float
4 32486 32487 Uavg (phase to phase) T_ x1V
float
4 32488 32489 SI T_ x1A
float
4 32490 32491 Active Power Total (Pt) T_ x1W
float
4 32492 32493 Reactive Power Total (Qt) T_ x 1 var
float
7M 30

4 32494 32495 Apparent Power Total (St) T_ x 1 VA


float
4 32496 32497 Power Factor Total (PFt) T_ x1
float
4 32498 32499 Frequency T_ x 1 Hz
float
4 32500 32501 U1 T_ x1V
float
4 32502 32503 U2 T_ x1V
float
4 32504 32505 U3 T_ x1V
float
4 32506 32507 Uavg (phase to neutral) T_ x1V
float
4 32508 32509 U12 T_ x1V
float
4 32510 32511 U23 T_ x1V
float
4 32512 32513 U31 T_ x1V
float
4 32514 32515 Uavg (phase to phase) T_ x1V
float
4 32516 32517 I1 T_ x1A
float
4 32518 32519 I2 T_ x1A
float
4 32520 32521 I3 T_ x1A
float
4 32522 32523 SI T_ x1A
float
4 32528 32529 Iavg T_ x1A
float
4 32530 32531 Active Power Phase L1 (P1) T_ x1W
float
4 32532 32533 Active Power Phase L2 (P2) T_ x1W
float
4 32534 32535 Active Power Phase L3 (P3) T_ x1W
float
4 32536 32537 Active Power Total (Pt) T_ x1W
float
4 32538 32539 Reactive Power Phase L1 (Q1) T_ x 1 var
float
4 32540 32541 Reactive Power Phase L2 (Q2) T_ x 1 var
float
4 32542 32543 Reactive Power Phase L3 (Q3) T_ x 1 var
float
4 32544 32545 Reactive Power Total (Qt) T_ x 1 var
float
4 32546 32547 Apparent Power Phase L1 (S1) T_ x 1 VA
float
4 32548 32549 Apparent Power Phase L2 (S2) T_ x 1 VA
float
7M 31

4 32550 32551 Apparent Power Phase L3 (S3) T_ x 1 VA


float
4 32552 32553 Apparent Power Total (St) T_ x 1 VA
float
4 32554 32555 Power Factor Phase 1 (PF1) T_ x1
float
4 32556 32557 Power Factor Phase 2 (PF2) T_ x1
float
4 32558 32559 Power Factor Phase 3 (PF3) T_ x1
float
4 32560 32561 Power Factor Total (PFt) T_ x1
float
4 32562 32563 CAP/IND P. F. Phase 1 (PF1) T_ x1
float
4 32564 32565 CAP/IND P. F. Phase 2 (PF2) T_ x1
float
4 32566 32567 CAP/IND P. F. Phase 3 (PF3) T_ x1
float
4 32568 32569 CAP/IND P. F. Total (PFt) T_ x1
float
4 32570 32571 j1 (angle between U1 and I1) T_ x1°
float
4 32572 32573 j2 (angle between U2 and I2) T_ x1°
float
4 32574 32575 j3 (angle between U3 and I3) T_ x1°
float
4 32576 32577 Power Angle Total T_ x1°
(atan2(Pt,Qt)) float
4 32578 32579 j12 (angle between U1 and U2) T_ x1°
float
4 32580 32581 j23 (angle between U2 and U3) T_ x1°
float
4 32582 32583 j31 (angle between U3 and U1) T_ x1°
float
4 32584 32585 Frequency T_ x 1 Hz
float
4 32588 32589 I1 THD% T_ x1%
float
4 32590 32591 I2 THD% T_ x1%
float
4 32592 32593 I3 THD% T_ x1%
float
4 32594 32595 U1 THD% T_ x1%
float
4 32596 32597 U2 THD% T_ x1%
float
4 32598 32599 U3 THD% T_ x1%
float
32638 32639 Energy Counter n1 T_ x 1 Wh
float
32640 32641 Energy Counter n2 T_ x 1 varh
float
7M 32

32642 32643 Energy Counter n3 T_ x 1 Wh


float
32644 32645 Energy Counter n4 T_ x 1 varh
float
4 32658 32659 Internal Temperature T_ x 1 °C
float
ENERGY
4 32750 32751 Aktiv Tariff T_ x1
float
4 32752 32753 Energy Counter n1 T_ x 1 Wh
float
4 32754 32755 Energy Counter n2 T_ x 1 varh
float
4 32756 32757 Energy Counter n3 T_ x 1 Wh
float
4 32758 32759 Energy Counter n4 T_ x 1 varh
float
4 32760 32761 Energy Counter 1 T_ x 1 VAh/varh/Wh
float
4 32762 32763 Energy Counter 2 T_ x 1 VAh/varh/Wh
float
4 32764 32765 Energy Counter 3 T_ x 1 VAh/varh/Wh
float
4 32766 32767 Energy Counter 4 T_ x 1 VAh/varh/Wh
float
4 32768 32769 Energy Counter 5 T_ x 1 VAh/varh/Wh
float
4 32770 32771 Energy Counter 6 T_ x 1 VAh/varh/Wh
float
4 32772 32773 Energy Counter 7 T_ x 1 VAh/varh/Wh
float
4 32774 32775 Energy Counter 8 T_ x 1 VAh/varh/Wh
float
4 32776 32777 Energy Counter 9 T_ x 1 VAh/varh/Wh
float
4 32778 32779 Energy Counter 10 T_ x 1 VAh/varh/Wh
float
4 32780 32781 Energy Counter 11 T_ x 1 VAh/varh/Wh
float
4 32782 32783 Energy Counter 12 T_ x 1 VAh/varh/Wh
float
4 32784 32785 Energy Counter 13 T_ x 1 VAh/varh/Wh
float
4 32786 32787 Energy Counter 14 T_ x 1 VAh/varh/Wh
float
4 32788 32789 Energy Counter 15 T_ x 1 VAh/varh/Wh
float
7M 33
4 32790 32791 Energy Counter 16 T_ x 1 VAh/varh/Wh
float
NOMINAL VALUES
32981 32982 Reserved for nominal aux T_ Unomx
voltage float
32983 32984 Reserved for nominal aux T_ Inomx
current float
4 32985 32986 nominal phase voltage T_ Unom x1V
float
4 32987 32988 nominal phase current T_ Inom x1A
float
4 32989 32990 nominal phase power T_ Pnom x1W
float
4 32991 32992 nominal total power T_ Ptot x1W
float
4 32993 32994 nominal total current T_ Itot x1A
float
4 32995 32996 nominal frequency T_ Fnom x 1 Hz
float
4 34999 35000 Run time T3 seconds x 1 seconds
INTERVAL MEASUREMENTS
AVERAGE MEASUREMENTS
4 35500 The last Average interval T1 x 0,1 seconds
duration
4 35501 Time since the last average T1 x 0,1 seconds
meaurements
4 35502 Average measurements T1
counter
4 35503 35504 Timestamp T_ '= 0 after reset
unix
4 35505 35506 Frequency T5 x 1 Hz
4 35507 35508 U1 T5 x1V
4 35509 35510 U2 T5 x1V
4 35511 35512 U3 T5 x1V
4 35513 35514 Uavg (phase to neutral) T5 x1V
4 35515 j12 (angle between U1 and U2) T17 x 1°
4 35516 j23 (angle between U2 and U3) T17 x 1°
4 35517 j31 (angle between U3 and U1) T17 x 1°
4 35518 35519 U12 T5 x1V
4 35520 35521 U23 T5 x1V
4 35522 35523 U31 T5 x1V
4 35524 35525 Uavg (phase to phase) T5 x1V
4 35526 35527 I1 T5 x1A
4 35528 35529 I2 T5 x1A
4 35530 35531 I3 T5 x1A
4 35536 35537 Iavg T5 x1A
4 35538 35539 SI T5 x1A
4 35540 35541 Active Power Total (Pt) T6 x1W
4 35542 35543 Active Power Phase L1 (P1) T6 x1W
7M 34

4 35544 35545 Active Power Phase L2 (P2) T6 x1W


4 35546 35547 Active Power Phase L3 (P3) T6 x1W
4 35548 35549 Reactive Power Total (Qt) T6 x 1 var
4 35550 35551 Reactive Power Phase L1 (Q1) T6 x 1 var
4 35552 35553 Reactive Power Phase L2 (Q2) T6 x 1 var
4 35554 35555 Reactive Power Phase L3 (Q3) T6 x 1 var
4 35556 35557 Apparent Power Total (St) T5 x 1 VA
4 35558 35559 Apparent Power Phase L1 (S1) T5 x 1 VA
4 35560 35561 Apparent Power Phase L2 (S2) T5 x 1 VA
4 35562 35563 Apparent Power Phase L3 (S3) T5 x 1 VA
4 35564 35565 Power Factor Total (PFt) T7 x1
4 35566 35567 Power Factor Phase 1 (PF1) T7 x1
4 35568 35569 Power Factor Phase 2 (PF2) T7 x1
4 35570 35571 Power Factor Phase 3 (PF3) T7 x1
4 35572 Power Angle Total T17 x1°
(atan2(Pt,Qt))
4 35573 j1 (angle between U1 and I1) T17 x1°
4 35574 j2 (angle between U2 and I2) T17 x1°
4 35575 j3 (angle between U3 and I3) T17 x1°
4 35581 Internal Temperature T17 x 1 °C
THD HARMONIC DATA
4 35582 U1 THD% T16 x1%
4 35583 U2 THD% T16 x1%
4 35584 U3 THD% T16 x1%
4 35588 I1 THD% T16 x1%
4 35589 I2 THD% T16 x1%
4 35590 I3 THD% T16 x1%
MAXIMUM MEASUREMENTS
4 35600 35604 Reserved
4 35605 35606 Frequency T5 x 1 Hz
4 35607 35608 U1 T5 x1V
4 35609 35610 U2 T5 x1V
4 35611 35612 U3 T5 x1V
4 35613 35614 Uavg (phase to neutral) T5 x1V
4 35615 j12 (angle between U1 and U2) T17 x1°
4 35616 j23 (angle between U2 and U3) T17 x1°
4 35617 j31 (angle between U3 and U1) T17 x1°
4 35618 35619 U12 T5 x1V
4 35620 35621 U23 T5 x1V
4 35622 35623 U31 T5 x1V
4 35624 35625 Uavg (phase to phase) T5 x1V
4 35626 35627 I1 T5 x1A
4 35628 35629 I2 T5 x1A
4 35630 35631 I3 T5 x1A
4 35636 35637 Iavg T5 x1A
4 35638 35639 SI T5 x1A
4 35640 35641 Active Power Total (Pt) T6 x1W
7M 35

4 35642 35643 Active Power Phase L1 (P1) T6 x1W


4 35644 35645 Active Power Phase L2 (P2) T6 x1W
4 35646 35647 Active Power Phase L3 (P3) T6 x1W
4 35648 35649 Reactive Power Total (Qt) T6 x 1 var
4 35650 35651 Reactive Power Phase L1 (Q1) T6 x 1 var
4 35652 35653 Reactive Power Phase L2 (Q2) T6 x 1 var
4 35654 35655 Reactive Power Phase L3 (Q3) T6 x 1 var
4 35656 35657 Apparent Power Total (St) T5 x 1 VA
4 35658 35659 Apparent Power Phase L1 (S1) T5 x 1 VA
4 35660 35661 Apparent Power Phase L2 (S2) T5 x 1 VA
4 35662 35663 Apparent Power Phase L3 (S3) T5 x 1 VA
4 35664 35665 Power Factor Total (PFt) T7 x1
4 35666 35667 Power Factor Phase 1 (PF1) T7 x1
4 35668 35669 Power Factor Phase 2 (PF2) T7 x1
4 35670 35671 Power Factor Phase 3 (PF3) T7 x1
4 35672 Power Angle Total T17 x1°
(atan2(Pt,Qt))
4 35673 j1 (angle between U1 and I1) T17 x1°
4 35674 j2 (angle between U2 and I2) T17 x1°
4 35675 j3 (angle between U3 and I3) T17 x1°
4 35681 Internal Temperature T17 x 1 °C
THD HARMONIC DATA
4 35682 U1 THD% T16 x1%
4 35683 U2 THD% T16 x1%
4 35684 U3 THD% T16 x1%
4 35688 I1 THD% T16 x1%
4 35689 I2 THD% T16 x1%
4 35690 I3 THD% T16 x1%
MINIMUM MEASUREMENTS
4 35700 35704 Reserved
4 35705 35706 Frequency T5 x 1 Hz
4 35707 35708 U1 T5 x1V
4 35709 35710 U2 T5 x1V
4 35711 35712 U3 T5 x1V
4 35713 35714 Uavg (phase to neutral) T5 x1V
4 35715 j12 (angle between U1 and U2) T17 x1°
4 35716 j23 (angle between U2 and U3) T17 x1°
4 35717 j31 (angle between U3 and U1) T17 x1°
4 35718 35719 U12 T5 x1V
4 35720 35721 U23 T5 x1V
4 35722 35723 U31 T5 x1V
4 35724 35725 Uavg (phase to phase) T5 x1V
4 35726 35727 I1 T5 x1A
4 35728 35729 I2 T5 x1A
4 35730 35731 I3 T5 x1A
4 35736 35737 Iavg T5 x1A
4 35738 35739 SI T5 x1A
7M 36

4 35740 35741 Active Power Total (Pt) T6 x1W


4 35742 35743 Active Power Phase L1 (P1) T6 x1W
4 35744 35745 Active Power Phase L2 (P2) T6 x1W
4 35746 35747 Active Power Phase L3 (P3) T6 x1W
4 35748 35749 Reactive Power Total (Qt) T6 x 1 var
4 35750 35751 Reactive Power Phase L1 (Q1) T6 x 1 var
4 35752 35753 Reactive Power Phase L2 (Q2) T6 x 1 var
4 35754 35755 Reactive Power Phase L3 (Q3) T6 x 1 var
4 35756 35757 Apparent Power Total (St) T5 x 1 VA
4 35758 35759 Apparent Power Phase L1 (S1) T5 x 1 VA
4 35760 35761 Apparent Power Phase L2 (S2) T5 x 1 VA
4 35762 35763 Apparent Power Phase L3 (S3) T5 x 1 VA
4 35764 35765 Power Factor Total (PFt) T7 x1
4 35766 35767 Power Factor Phase 1 (PF1) T7 x1
4 35768 35769 Power Factor Phase 2 (PF2) T7 x1
4 35770 35771 Power Factor Phase 3 (PF3) T7 x1
4 35772 Power Angle Total T17 x1°
(atan2(Pt,Qt))
4 35773 j1 (angle between U1 and I1) T17 x1°
4 35774 j2 (angle between U2 and I2) T17 x1°
4 35775 j3 (angle between U3 and I3) T17 x1°
4 35781 Internal Temperature T17 x 1 °C
THD HARMONIC DATA
4 35782 U1 THD% T16 x1%
4 35783 U2 THD% T16 x1%
4 35784 U3 THD% T16 x1%
4 35788 I1 THD% T16 x1%
4 35789 I2 THD% T16 x1%
4 35790 I3 THD% T16 x1%
RAM logger
4 36000 Measurement parameter T1 See OutTypes
4 36001 Time interval T1 minutes
4 36002 Number of valid results T1
4 36003 Time stamp of last result T2 minutes since
midnight (<0 if
no time)
4 36004 36131 Logger table (newest to oldest) T17 Normalised
values
7M 37

MODBUS SETTINGS
Valid Register Contents Data Ind Values / Dependencies Min Max P.
with Addresses Level
Function
Codes
Holding Registers
40000 Memory Reference
SYSTEM COMMANDS
16 40001 40002 User Password (L1, L2) T_Str4 A…Z Password to attempt user 0
access level upgrade
16 40003 40005 Factory Password (FAC) T_Str6 A…Z Password to attempt factory 0
access level upgrade
16 40006 40007 Lavel 1 - User password T_Str4 A…Z 1
16 40008 40009 Lavel 2 - User password T_Str4 A…Z 2
3,6 40010 Active Acces Level T1 0 Full protection 0 0 0
6 40011 Manual password T1 1 Lock instrument 0
activation
6 40012 Operator Command T1 1 Save Settings 1 5 1
Register 2 Abort Settings
3 Restart Instrument
4 Restart Ethernet
5 Save Settings and Restart
Ethernet
6 40014 Reset command register T1 Bit-0 Reset alarm ouptut relay 1 1
2 Bit-1 Reset alarm ouptut relay 2
Bit-8 Reset alarm ouptut IR
3,6 40015 IR external relay com- T1 0 Off 0 1 0
mand action 1 On
3,6 40030 Select Active Tariff T1 1 6 1
6 40031 Reset energy command T1 Bit-0..7 Reset counter 1 .. 8 0 65535 1
register 1 Bit- Reset counter 9 .. 16
8..15
GENERAL SETTINGS
3, 6, 16 40101 40120 Description T_ 2
Str40
3, 6, 16 40121 40140 Location T_ 2
Str40
3,6 40143 Conection Mode T1 0 No mode 1 5 2
1 1b - Single Phase
2 3b - 3 phase 3 wire balanced
3 4b - 3 phase 4 wire balanced
4 3u - 3 phase 3 wire unbal-
anced
5 4u - 3 phase 4 wire unbal-
anced
3,6 40148 Current input range (%) T16 10000 for 100% 5,00 260,00 2
3,6 40149 Voltage input range (%) T16 10000 for 100% 2,50 100,00 2
3,6 40150 Frequency nominal T1 Hz 10 1000 2
value
7M 38
3,6 40156 Language T1 0 English 0 0 0
1 Francais
2 Deutsch
3 Español
4 Slovenski
5 Pycck
6 Dansk
7 Italiano
8 English US
9 Hrvatski
10 Polski
11 Portuguese
12 Hebrew
13 Serbian
14 Türkçe
40159 Temperature unit T1 0 °C 0 1 2
1 °F
3, 6, 16 40161 40162 Time T9 1
3, 6, 16 40163 40164 Date T10 1
3,6 40166 Automatic change S/W T1 0 No 0 1 1
time
3,6 40170 LCD configurations T1 Bit 0 Counter description mode 0 1 2
(*0=OBIS code; 1=letters)
3,6 40171 LCD Contrast T2 -10 10 2
3,6 40172 LCD Back Light Intesnity T1 0=No Backlight 0 10 2
3,6 40173 LCD Back Light Time Off T1 Minutes (0=Always on) 0 60 2
3,6 40174 LCD scroll interval T1 Seconds 5 60 2
3,6 40175 LCD Custom screen 1 - T1 See OutTypes 0 100 2
Line 1
3,6 40176 LCD Custom screen 1 - T1 See OutTypes 0 100 2
Line 2
3,6 40177 LCD Custom screen 1 - T1 See OutTypes 0 100 2
Line 3
3,6 40178 LCD Custom screen 2 - T1 See OutTypes 0 100 2
Line 1
3,6 40179 LCD Custom screen 2 - T1 See OutTypes 0 100 2
Line 2
3,6 40180 LCD Custom screen 2 - T1 See OutTypes 0 100 2
Line 3
3,6 40181 LCD Custom screen 3 - T1 See OutTypes 0 100 2
Line 1
3,6 40182 LCD Custom screen 3 - T1 See OutTypes 0 100 2
Line 2
3,6 40183 LCD Custom screen 3 - T1 See OutTypes 0 100 2
Line 3
3,6 40184 LCD scroll parameters 1 T1 Bit 0 Counter n1 (Allways) 1 65535 2
Bit 1 Counter n2
Bit 2 Counter n3
Bit 3 Counter n4
3,6 40185 LCD scroll parameters 2 Bit 0..7 Counter 1 .. 8 0 65535 2
Bit Counter 9 .. 16
8..15
7M 39
3,6 40186 LCD scroll parameters 3 Bit 0 Active Power Total (Pt) 0 65535 2
Bit 1 Active Power P1 .. P3 (P12)
Bit 2 Reactive Power Total (Qt)
Bit 3 Reactive Power Q1 .. Q3
(Q12)
Bit 4 Apparent Power Total (St)
Bit 5 Apparent Power S1 .. S3
(S12)
Bit 6 Uavg (phase to neutral)
Bit 7 Voltage U1 .. U3
Bit 8 Uavg (phase to phase)
Bit 9 Voltage U12 .. U31
Bit 10 Curent Total
Bit 11 Curent I1 .. I3 (I12)
Bit 12 Frequency
Bit 13 Active Tariff
Bit 14 Power Factor Total (PFt)
Bit 15 Power Factor PF1 .. PF3
(PF12)
3,6 40187 LCD scroll parameters 4 Bit 0 Power Angle Total 0 15 2
(atan2(Pt,Qt))
Bit 1 Power Angle 1 .. 3 (12)
Bit 2 THD of voltage
Bit 3 THD of current
3,6 40188 LCD return mode T1 0 Auto scroll 0 2 2
1 Counter n1
2 Hold page
3,6 40192 Comm. & LCD average T1 10=1,0 sec 0,1 5,0 2
interval
COMMUNICATION
3,6 40202 Port 1: Device Adress T1 1 247 2
(Modbus)
3,6 40203 Port 1: Baud Rate T1 0 Baud rate 1200 1 7 2
1 Baud rate 2400
2 Baud rate 4800
3 Baud rate 9600
4 Baud rate 19200
5 Baud rate 38400
6 Baud rate 57600
7 Baud rate 115200
3,6 40204 Port 1: Stop Bit T1 0 1 Stop bit 0 1 2
1 2 Stop bits
3,6 40205 Port 1: Parity T1 0 No parity 0 2 2
1 Odd parity
2 Even parity
3,6 40206 Port 1: Data Bits T1 0 8 bits 0 0 2
3,6 40207 Port 1: TCP Port T1 1 65535 2
3, 6, 16 40208 40227 Port 1: IP Host name T_ 2
Str40
3, 6, 16 40228 40229 Port 1: IP Address T_ 0
Hex4
7M 40
3, 6, 16 40230 40231 Port 1: Subnet Mask T_ 0
Hex4
3, 6, 16 40232 40233 Port 1: Default Router T_ 2
Hex4
3, 6, 16 40234 40241 WIFI password T_ 2
Str16
3, 6, 16 40242 40249 WIFI SSID T_ 2
Str16
3,6 40250 Bluetooth ON/OFF T1 0 Off 0 1 2
1 On
IR
3,6 40252 Port 2: Device Adress T1 1 247 2
(Modbus)
3,6 40253 Port 2: Baud Rate T1 see Port 1: Baud Rate 3 7 2
3,6 40254 Port 2: Stop Bit T1 see Port 1: Stop Bit 0 1 2
3,6 40255 Port 2: Parity T1 see Port 1: Parity 0 2 2
3,6 40256 Port 2: Data Bits T1 see Port 1: Data Bits 0 0 2
M-bus
3,6 40271 M-bus Primary address T1 0 250 2
3,6 40272 M-bus: Baud Rate T1 0 Baud rate 300 1 5 2
1 Baud rate 600
2 Baud rate 1200
3 Baud rate 2400
4 Baud rate 4800
5 Baud rate 9600
3,6 40273 40274 M-bus Secondary ad- T3 Digits only (Default = Serial 0 99999 2
dress number) 999

ENERGY
3,6 40401 Active Tariff T1 0 Tariff input 0 6 1
1..4 Tariff 1..4
5..6 Tariff 5..6
3,6 40419 Total Energy Calculation T1 0 Evaluation of the sum of 0 1 2
phases
1 Evaluation of individual
phases
NON-RESETABLE
COUNTERS
7M 41

3,6 40421 Energy Counter n1 T1 0 No Parameter 0 95 2


Parameter 1 Active Power
2 Reactive pover
3 Apparent Power
5 Active Power Phase 1
6 Reactive pover Phase 1
7 Apparent Power Phase 1
9 Active Power Phase 2
10 Reactive pover Phase 2
11 Apparent Power Phase 2
13 Active Power Phase 3
14 Reactive pover Phase 3
15 Apparent Power Phase 3
33 Active Power individual
phases
34 Reactive Power individual
phases
35 Apparent Power individual
phases
3,6 40422 Energy Counter n1 Con- T1 Bit-0 Quadrant I Enabled 0 63 2
figuration Bit-1 Quadrant II Enabled
Bit-2 Quadrant III Enabled
Bit-3 Quadrant IIII Enabled
Bit-4 Absolute Value
Bit-5 Invert Value
3,6 40423 Energy Counter n1 T2 -3 6 2
Exponent
3,6 40424 Energy Counter n1 Tarif T1 Bit-0 Tarif 1 Enabled 0 63 2
Selector Bit-1 Tarif 2 Enabled
Bit-2 Tarif 3 Enabled
Bit-3 Tarif 4 Enabled
Bit-4 Tarif 5 Enabled
Bit-5 Tarif 6 Enabled
3,6 40425 Energy Counter n2 T1 see Energy Counter n1 0 95 2
Parameter Parameter
3,6 40426 Energy Counter n2 Con- T1 see Energy Counter n1 Con- 0 63 2
figuration figuration
3,6 40427 Energy Counter n2 T2 see Energy Counter n1 0 6 2
Exponent Exponent
3,6 40428 Energy Counter n2 Tarif T1 see Energy Counter n1 Tarif 0 63 2
Selector Selector
3,6 40429 Energy Counter n3 T1 see Energy Counter n1 0 95 2
Parameter Parameter
3,6 40430 Energy Counter n3 Con- T1 see Energy Counter n1 Con- 0 63 2
figuration figuration
3,6 40431 Energy Counter n3 T2 see Energy Counter n1 0 6 2
Exponent Exponent
3,6 40432 Energy Counter n3 Tarif T1 see Energy Counter n1 Tarif 0 63 2
Selector Selector
3,6 40433 Energy Counter n4 T1 see Energy Counter n1 0 95 2
Parameter Parameter
7M 42

3,6 40434 Energy Counter n4 Con- T1 see Energy Counter n1 Con- 0 63 2


figuration figuration
3,6 40435 Energy Counter n4 T2 see Energy Counter n1 0 6 2
Exponent Exponent
3,6 40436 Energy Counter n4 Tarif T1 see Energy Counter n1 Tarif 0 63 2
Selector Selector
3,6 40437 Energy Counter 1 Pa- T1 see Energy Counter n1 0 95 2
rameter Parameter
3,6 40438 Energy Counter 1 Con- T1 see Energy Counter n1 Con- 0 63 2
figuration figuration
3,6 40439 Energy Counter 1 Expo- T2 see Energy Counter n1 0 6 2
nent Exponent
3,6 40440 Energy Counter 1 Tarif T1 see Energy Counter n1 Tarif 0 63 2
Selector Selector
3,6 40441 Energy Counter 2 Pa- T1 see Energy Counter n1 0 95 2
rameter Parameter
3,6 40442 Energy Counter 2 Con- T1 see Energy Counter n1 Con- 0 63 2
figuration figuration
3,6 40443 Energy Counter 2 Expo- T2 see Energy Counter n1 0 6 2
nent Exponent
3,6 40444 Energy Counter 2 Tarif T1 see Energy Counter n1 Tarif 0 63 2
Selector Selector
3,6 40445 Energy Counter 3 Pa- T1 see Energy Counter n1 0 95 2
rameter Parameter
3,6 40446 Energy Counter 3 Con- T1 see Energy Counter n1 Con- 0 63 2
figuration figuration
3,6 40447 Energy Counter 3 Expo- T2 see Energy Counter n1 0 6 2
nent Exponent
3,6 40448 Energy Counter 3 Tarif T1 see Energy Counter n1 Tarif 0 63 2
Selector Selector
3,6 40449 Energy Counter 4 Pa- T1 see Energy Counter n1 0 95 2
rameter Parameter
3,6 40450 Energy Counter 4 Con- T1 see Energy Counter n1 Con- 0 63 2
figuration figuration
3,6 40451 Energy Counter 4 Expo- T2 see Energy Counter n1 0 6 2
nent Exponent
3,6 40452 Energy Counter 4 Tarif T1 see Energy Counter n1 Tarif 0 63 2
Selector Selector
3,6 40453 Energy Counter 5 Pa- T1 see Energy Counter n1 0 95 2
rameter Parameter
3,6 40454 Energy Counter 5 Con- T1 see Energy Counter n1 Con- 0 63 2
figuration figuration
3,6 40455 Energy Counter 5 Expo- T2 see Energy Counter n1 0 6 2
nent Exponent
3,6 40456 Energy Counter 5 Tarif T1 see Energy Counter n1 Tarif 0 63 2
Selector Selector
3,6 40457 Energy Counter 6 Pa- T1 see Energy Counter n1 0 95 2
rameter Parameter
3,6 40458 Energy Counter 6 Con- T1 see Energy Counter n1 Con- 0 63 2
figuration figuration
3,6 40459 Energy Counter 6 Expo- T2 see Energy Counter n1 0 6 2
nent Exponent
3,6 40460 Energy Counter 6 Tarif T1 see Energy Counter n1 Tarif 0 63 2
Selector Selector
7M 43
3,6 40461 Energy Counter 7 Pa- T1 see Energy Counter n1 0 95 2
rameter Parameter
3,6 40462 Energy Counter 7 Con- T1 see Energy Counter n1 Con- 0 63 2
figuration figuration
3,6 40463 Energy Counter 7 Expo- T2 see Energy Counter n1 0 6 2
nent Exponent
3,6 40464 Energy Counter 7 Tarif T1 see Energy Counter n1 Tarif 0 63 2
Selector Selector
3,6 40465 Energy Counter 8 Pa- T1 see Energy Counter n1 0 95 2
rameter Parameter
3,6 40466 Energy Counter 8 Con- T1 see Energy Counter n1 Con- 0 63 2
figuration figuration
3,6 40467 Energy Counter 8 Expo- T2 see Energy Counter n1 0 6 2
nent Exponent
3,6 40468 Energy Counter 8 Tarif T1 see Energy Counter n1 Tarif 0 63 2
Selector Selector
3,6 40469 40472 Energy Counter 9 see Energy Counter n1 2
3,6 40473 40476 Energy Counter 10 see Energy Counter n1 2
3,6 40477 40480 Energy Counter 11 see Energy Counter n1 2
3,6 40481 40484 Energy Counter 12 see Energy Counter n1 2
3,6 40485 40488 Energy Counter 13 see Energy Counter n1 2
3,6 40489 40492 Energy Counter 14 see Energy Counter n1 2
3,6 40493 40496 Energy Counter 15 see Energy Counter n1 2
3,6 40497 40500 Energy Counter 16 see Energy Counter n1 2
ALARMS
3,6 41001 Alarm Enable Flags G1, T1 Bit 0..4 Group 1 Limit 1 .. 4 2
G2
3,6 41002 Alarm Enable Flags G3, T1 Bit 0..4 Group 3 Limit 1 .. 4 2
G4
ALARM GROUP 1
3,6 41004 Compare time delay T1 seconds 0 900 2
3,6 41005 Hysteresis T16 % of compare value, if 0 0,00 10,00 2
then % of nominal value
GROUP 1 Limit 1
3,6 41008 Limit 1 Parameter T1 See OutTypes 0 1023 2
3,6 41009 Limit 1 Function T1 Bit-1 Reserved: Store into mem- 0 80 2
ory (all)
Bit-3 Activate LED (red backlight)
Bit-4 Activate Alarm Output
Bit-6 Limit Condition > (< if 0)
GROUP 1 Limit 2
3,6 41011 Limit 2 Parameter T1 see Limit 1 Parameter 0 127 2
3,6 41012 Limit 2 Function T1 see Limit 1 Function 0 80 2
3,6 41013 Limit 2 Compare value T16 see Limit 1 Compare value -300. +300.00 2
00
GROUP 1 Limit 3
3,6 41014 Limit 3 Parameter T1 see Limit 1 Parameter 0 127 2
3,6 41015 Limit 3 Function T1 see Limit 1 Function 0 80 2
3,6 41016 Limit 3 Compare value T16 see Limit 1 Compare value -300. +300.00 2
00
GROUP 1 Limit 4
3,6 41017 Limit 4 Parameter T1 see Limit 1 Parameter 0 127 2
7M 44
3,6 41018 Limit 4 Function T1 see Limit 1 Function 0 80 2
3,6 41019 Limit 4 Compare value T16 see Limit 1 Compare value -300. +300. 2
00 00
ALARM GROUP 2 See ALARM GROUP 1 2
3,6 41033 Compare time delay T1 seconds 0 900 2
3,6 41034 Hysteresis T16 % of compare value, if 0 0,00 10,00 2
then % of nominal value
GROUP 2 Limit 1
3,6 41037 Limit 1 Parameter T1 see GROUP 1 Limit 1 Param- 0 127 2
eter
3,6 41038 Limit 1 Function T1 see GROUP 1 Limit 1 Func- 0 80 2
tion
3,6 41039 Limit 1 Compare value T16 see GROUP 1 Limit 1 Com- -300. +300. 2
pare value 00 00
3,6 41040 41042 GROUP 2 Limit 2 See GROUP 1 Limit 1
3,6 41043 41045 GROUP 2 Limit 3 See GROUP 1 Limit 1
3,6 41046 41048 GROUP 2 Limit 4 See GROUP 1 Limit 1
ALARM GROUP 3 See ALARM GROUP 1
3,6 41062 Compare time delay T1 seconds 0 900 2
3,6 41063 Hysteresis T16 % of compare value, if 0 0,00 10,00 2
then % of nominal value
3,6 41066 41068 GROUP 3 Limit 1 See GROUP 1 Limit 1
3,6 41069 41071 GROUP 3 Limit 2 See GROUP 1 Limit 1
3,6 41072 41074 GROUP 3 Limit 3 See GROUP 1 Limit 1
3,6 41075 41077 GROUP 3 Limit 4 See GROUP 1 Limit 1
ALARM GROUP 4 See ALARM GROUP 1
3,6 41091 Compare time delay T1 seconds 0 900 2
3,6 41092 Hysteresis T16 % of compare value, if 0 0,00 10,00 2
then % of nominal value
3,6 41095 41097 GROUP 4 Limit 1 See GROUP 1 Limit 1
3,6 41098 41100 GROUP 4 Limit 2 See GROUP 1 Limit 1
3,6 41101 41103 GROUP 4 Limit 3 See GROUP 1 Limit 1
3,6 41104 41106 GROUP 4 Limit 4 See GROUP 1 Limit 1
Logic Function 1
7M 45

3,6 41131 Input 1 T1 0 disabled 0 50 2


1 GROUP 1 Limit 1
2 GROUP 1 Limit 2
3 GROUP 1 Limit 3
4 GROUP 1 Limit 4
9 GROUP 2 Limit 1
10 GROUP 2 Limit 2
11 GROUP 2 Limit 3
12 GROUP 2 Limit 4
17 GROUP 3 Limit 1
18 GROUP 3 Limit 2
19 GROUP 3 Limit 3
20 GROUP 3 Limit 4
25 GROUP 4 Limit 1
26 GROUP 4 Limit 2
27 GROUP 4 Limit 3
28 GROUP 4 Limit 4
33 Group E Limit 1
34 Group E Limit 2
35 Group E Limit 3
36 Group E Limit 4
41 Group 1 (OR all)
42 Group 2 (OR all)
43 Group 3 (OR all)
44 Group 4 (OR all)
45 Group E (OR all)
46 Group 1 (AND all)
47 Group 2 (AND all)
48 Group 3 (AND all)
49 Group 4 (AND all)
50 Group E (AND all)
3,6 41132 Input 2 T1 see Input 1 0 50 2
3,6 41133 Input 3 T1 see Input 1 0 50 2
3,6 41134 Input 4 T1 see Input 1 0 50 2
3,6 41135 Function 1 T1 0 AND 0 1 2
1 OR
3,6 41136 Function 2 T1 see Function 1 0 1 2
3,6 41137 Function 3 T1 see Function 1 0 1 2
Logic Function 2
3,6 41139 Input 1 T1 see Logic Function 1 Input 1 0 50 2
3,6 41140 Input 2 T1 see Logic Function 1 Input 1 0 50 2
3,6 41141 Input 3 T1 see Logic Function 1 Input 1 0 50 2
3,6 41142 Input 4 T1 see Logic Function 1 Input 1 0 50 2
3,6 41143 Function 1 T1 see Logic Function 1 Func- 0 1 2
tion 1
3,6 41144 Function 2 T1 see Logic Function 1 Func- 0 1 2
tion 1
3,6 41145 Function 3 T1 see Logic Function 1 Func- 0 1 2
tion 1
7M 46

Logic Function 3
3,6 41147 Input 1 T1 see Logic Function 1 Input 1 0 50 2
3,6 41148 Input 2 T1 see Logic Function 1 Input 1 0 50 2
3,6 41149 Input 3 T1 see Logic Function 1 Input 1 0 50 2
3,6 41150 Input 4 T1 see Logic Function 1 Input 1 0 50 2
3,6 41151 Function 1 T1 see Logic Function 1 Func- 0 1 2
tion 1
3,6 41152 Function 2 T1 see Logic Function 1 Func- 0 1 2
tion 1
3,6 41153 Function 3 T1 see Logic Function 1 Func- 0 1 2
tion 1
ALARM GROUP Energy
3,6 41161 Limit 1 Parameter T1 0 disabled 0 44 2
1..8 Counter 1 .. 8
9..16 Counter 9 .. 16
33..36 Counter n1 .. n4
3,6 41162 Limit 1 Function T1 Bit-1 Reserved: Store into mem- 0 80 2
ory (all)
Bit-4 Activate Alarm Output
Bit-6 Alarm Condition > (< if 0)
3,6 41163 41164 Limit 1 Compare value T3 digits in the counter reso- 0 99999 2
lution 9999
3,6 41165 Limit 2 Parameter T1 see Limit 1 Parameter 0 44 2
3,6 41166 Limit 2 Function T1 see Limit 1 Function 0 1 2
3,6 41167 41168 Limit 2 Compare value T3 see Limit 1 Compare value 0 99999 2
9999
3,6 41169 Limit 3 Parameter T1 see Limit 1 Parameter 0 44 2
3,6 41170 Limit 3 Function T1 see Limit 1 Function 0 1 2
3,6 41171 41172 Limit 3 Compare value T3 see Limit 1 Compare value 0 9999 2
99999
3,6 41173 Limit 4 Parameter T1 see Limit 1 Parameter 0 44 2
3,6 41174 Limit 4 Function T1 see Limit 1 Function 0 1 2
3,6 41175 41176 Limit 4 Compare value T3 see Limit 1 Compare value 0 999 2
999999
OUTPUTS
3,6 41200 Pulse LED Operation 0 Normal mode 0 6 0
mode 1 Test mode P - Fast
2 Test mode P - Fast (Counter
only)
3 Test mode P
4 Test mode Q
5 Test mode Q - Fast
6 Test mode Q - Fast (Counter
only)
3,6 41201 Pulse LED Parameter T1 0 Not set 0 95 2
1..95 see Energy Counter n1
Parameter
3,6 41202 Pulse LED Configuration T1 see Energy Counter n1 Con- 0 63 2
figuration
3,6 41203 Pulse LED No. Of pulses T1 1 65535 2
3,6 41204 Pulse LED Energy unit T1 * 10^(Common Energy 1 65535 2
Counter Exponent)
7M 47
3,6 41205 Pulse LED Pulse lenght T1 ms 2 1000 2
PULSE OUTPUTS
3,6 41207 Output 1 Function T1 0 Alarm output 0 1 2
1 Pulse output
3,6 41208 Output 2 Function T1 see Pulse Output 1 Function 0 1 2
3,6 41211 Pulse Output 1 Param- T1 0 Not set 0 95 2
eter 1..95 see Energy Counter n1
Parameter
3,6 41212 Pulse Output 1 Config- T1 see Energy Counter n1 Con- 0 63 2
uration figuration
3,6 41213 Pulse Output 1 No. Of T1 1 65535 2
pulses
3,6 41214 Pulse Output 1 Energy T1 * 10^(Common Energy 1 65535 2
unit Counter Exponent)
3,6 41215 Pulse Output 1 Pulse T1 ms 2 1000 2
lenght
3,6 41216 Pulse Output 1 Tarif T1 Bit-0 Tarif 1 enabled 0 63 2
Selector Bit-1 Tarif 2 enabled
Bit-2 Tarif 3 enabled
Bit-3 Tarif 4 enabled
Bit-4 Tarif 5 enabled
Bit-5 Tarif 6 enabled
3,6 41217 Pulse Output 2 Param- T1 see Pulse Output 1 Param- 0 95 2
eter eter
3,6 41218 Pulse Output 2 Config- T1 see Energy Counter n1 Con- 0 63 2
uration figuration
3,6 41219 Pulse Output 2 No. Of T1 1 65535 2
pulses
3,6 41220 Pulse Output 2 Energy T1 * 10^(Common Energy 1 65535 2
unit Counter Exponent)
3,6 41221 Pulse Output 2 Pulse T1 ms 2 1000 2
lenght
3,6 41222 Pulse Output 2 Tarif T1 0 63 2
Selector
ALARM OUTPUTS
ALARM OUTPUT IR
3,6 41235 IR External relay operat- T1 0 Not connected 0 2 2
ing mode 1 Manual
2 Alarm output control
3,6 41236 Enabled Alarm groups T1 See ALARM OUTPUT 1 0 255 2
3,6 41237 Output signal T1 See ALARM OUTPUT 1 0 7 2
3,6 41238 Output pulse length T1 Seconds 1 999 2
ALARM OUTPUT 1
3,6 41239 Enabled Alarm groups T1 Bit-0 Group 1 0 255 2
Bit-1 Group 2
Bit-2 Group 3
Bit-3 Group 4
Bit-4 Group E
Bit-5 Logic Function 1
Bit-6 Logic Function 2
Bit-7 Logic Function 3
MODBUS SETTINGS 7M 48
3,6 41240 Output signal T1 0 Normal 0 7 2
1 Permanent
2 Pulsed
3 Always ON
4 Always OFF
5 Normal inverse
6 Permanent inverse
7 Pulsed inverse
3,6 41241 Output pulse length T1 Seconds 1 999 2
3,6 41242 41244 ALARM OUTPUT 2 See ALARM OUTPUT 1 2
ENERGY snapshot reg-
isters
3, 6 41901 Auto freeze interval T1 0 65536 0
[minutes]
3, 6 41902 time to freeze [s] T1 0 65536 0
3 41903 41904 time from freeze [s] T3u
3, 6 41905 Freeze STATUS T1 0 at reset 1 65533 0
65534 at interval
65535 at time to freeze
3 41906 Current Active Tariff T1
3 41907 41908 Energy Counter n1 T3
3 41909 41910 Energy Counter n2 T3
3 41911 41912 Energy Counter n3 T3
3 41913 41914 Energy Counter n4 T3
3 41915 41916 Energy Counter 1 T3
3 41917 41918 Energy Counter 2 T3
3 41919 41920 Energy Counter 3 T3
3 41921 41922 Energy Counter 4 T3
3 41923 41924 Energy Counter 5 T3
3 41925 41926 Energy Counter 6 T3
3 41927 41928 Energy Counter 7 T3
3 41929 41930 Energy Counter 8 T3
3 41931 41932 Energy Counter 9 T3
3 41933 41934 Energy Counter 10 T3
3 41935 41936 Energy Counter 11 T3
3 41937 41938 Energy Counter 12 T3
3 41939 41940 Energy Counter 13 T3
3 41941 41942 Energy Counter 14 T3
3 41943 41944 Energy Counter 15 T3
3 41945 41946 Energy Counter 16 T3
INTERVAL MEASURE-
MENTS
3, 6 41990 Interval duration [s/10] T1 600=60,0 sec 0,1 3600 0
3, 6 41991 Time to calculate inter- T1 0,1 3600 0
val meas. [s/10]
7M 49

MODBUS DATA TYPES


Type Value / Bit Mask Description
T1 Unsigned Value (16 bit)
Example: 12345 stored as 12345 = 3039(16)
T2 Signed Value (16 bit)
Example: -12345 stored as -12345 = CFC7(16)
T3 Signed Long Value (32 bit)
Example: 123456789 stored as 123456789 = 075B CD 15(16)
T4 Short Unsigned float (16 bit)
bits # 15..14 Decade Exponent(Unsigned 2 bit)
bits # 13..00 Binary Unsigned Value (14 bit)
Example: 10000*102 stored as A710(16)
T5 Unsigned Measurement (32 bit)
bits # 31..24 Decade Exponent(Signed 8 bit)
bits # 23..00 Binary Unsigned Value (24 bit)
Example: 123456*10-3 stored as FD01 E240(16)
T6 Signed Measurement (32 bit)
bits # 31..24 Decade Exponent (Signed 8 bit)
bits # 23..00 Binary Signed value (24 bit)
Example: - 123456*10-3 stored as FDFE 1DC0(16)
T7 Power Factor (32 bit)
bits # 31..24 Sign: Import/Export (00/FF)
bits # 23..16 Sign: Inductive/Capacitive (00/FF)
bits # 15..00 Unsigned Value (16 bit), 4 decimal places
Example: 0.9876 CAP stored as 00FF 2694(16)
T8 Time stamp (32 bit)
bits # 31..24 Minutes 00 - 59 (BCD)
bits # 23..16 Hours 00 - 23 (BCD)
bits # 15..08 Day of month 01 - 31 (BCD)
bits # 07..00 Month of year 01 - 12 (BCD)
Example: 15:42, 1. SEP stored as 4215 0109(16)
T9 Time (32 bit)
bits # 31..24 1/100s 00 - 99 (BCD)
bits # 23..16 Seconds 00 - 59 (BCD)
bits # 15..08 Minutes 00 - 59 (BCD)
bits # 07..00 Hours 00 - 24 (BCD)
Example: 15:42:03.75 stored as 7503 4215(16)
T10 Date (32 bit)
bits # 31..24 Day of month 01 - 31 (BCD)
bits # 23..16 Month of year 01 - 12 (BCD)
bits # 15..00 Year (unsigned integer) 1998..4095
Example: 10, SEP 2000 stored as 1009 07D0(16)
T_Str4 Text String 4 characters
(T11) Two characters per 16 bit register
T_Str6 Text String 6 characters
7M 50

(T12) Two charcters per 16 bit register


T_Str8 Text String 8 characters
Two characters per 16 bit register.
T_Str16 Text String 16 characters
Two characters per 16 bit register.
T_Str20 Text String 20 characters
Two characters per 16 bit register.
T16 Unsigned Value (16 bit), 2 decimal places
Example: 123.45 stored as 123.45 = 3039(16)
T17 Signed Value (16 bit), 2 decimal places
Example: -123.45 stored as -123.45 = CFC7(16)
T_Time Time and Date (64 bit)
bits # 63..56 1/100s 00 - 99 (BCD)
bits # 55..48 Seconds 00 - 59 (BCD)
bits # 47..40 Minutes 00 - 59 (BCD)
bits # 39..32 Hours 00 - 24 (BCD)
bits # 31..24 Day of month 01 - 31 (BCD)
bits # 23..16 Month of year 01 - 12 (BCD)
bits # 15..00 Year (unsigned integer) 1998..4095
Example: 15:42:03.75, 10. SEP 2000 stored as 7503 4215 1009
07D0(16)
T_TimeIEC Time and Date (64 bit) = IEC870-5-4 "Binary Time 2a"
bits # 63..55 Reserved
bits # 54..48 Years (0 .. 99)
bits # 47..44 Reserved
bits # 43..40 Months (1 .. 12)
bits # 39..37 Day of Week (1 .. 7)
bits # 36..32 Day of Month (1 .. 31)
bit # 31 Summer Time (0 .. 1): Summer time (1), Standard time (0)
bits # 30..29 Reserved
bits # 28..24 Hours (0 .. 23)
bit # 23 Invalid (0 .. 1): Invalid (1), Valid (0)
bit # 22 Reserved
bits # 21..16 Minutes (0 .. 59)
bits # 15..00 Miliseconds (0 .. 59999)
Example: 15:42, 1. SEP stored as 4215 0109(16)
T_Data Record Data
Size and SubTypes depends on the Actual Memory Part
T_Str40 Text String 40 characters
Two characters per 16 bit register.
T_float IEEE 754 Floating-Point Single Precision Value (32 bit)
bits # 31 Sign Bit (1 bit)
bits # 30..23 Exponent Field (8 bit)
7M 51

bits # 22..0 Significand (23 bit)


Example: 123.45 stored as 123.45000 = 42F6 E666(16)
T9A Time (16 bit)
bits # 15..08 Minutes 00 - 59 (BCD)
bits # 07..00 Hours 00 - 24 (BCD)
Example: 15:42 stored as 4215(16)
T10A Date (16 bit)
bits # 15..08 Day of month 00 - 31 (BCD)
bits # 07..00 Month of year 00 - 12 (BCD)
Example: 30, SEP stored as 3009(16)
T18 Signed Value (16 bit), 4 decimal places
Example: -0.2345 stored as -2345 = F6D7(16)
T_unix Unix time (32 bit)
Bits # 31..00 Seconds since January 1, 1970
Example: 16 May 2012 10:36:46 GMT stored as 4FB3 833E(16)
7M 52

EQUATIONS
7M 53
7M 54