Manual UPS R 1 3kVA en Us
Manual UPS R 1 3kVA en Us
User Manual
www.deltapowersolutions.com
Save This Manual
This manual contains important instructions and warnings that you should
follow during the installation, operation, storage and maintenance of this
product. Failure to heed these instructions and warnings will void the warranty.
Copyright © 2014 by Delta Electronics Inc. All Rights Reserved. All rights of this
User Manual (“Manual”), including but not limited to the contents, information,
and figures are solely owned and reserved by Delta Electronics Inc. (“Delta”).
The Manual can only be applied to the operation or the use of this product. Any
disposition, duplication, dissemination, reproduction, modification, translation,
extraction, or usage of this Manual in whole or in part is prohibited without the prior
written permission of Delta. Given that Delta will continuously improve and develop
the product, changes may be made to the information in this Manual at any time
without obligation to notify any person of such revision or changes. Delta will make
all possible efforts to secure the accuracy and the integrity of this Manual. Delta
disclaims any kinds or forms of warranty, guarantee, or undertaking, either expressly
or implicitly, including but not limited to the completeness, faultlessness, accuracy,
non-infringement, merchantability or fitness for a particular purpose of the Manual.
Amplon R Series II
Table of Contents
Table of Contents
Chapter 1 : Important Safety Instructions---------------------------- 1
Chapter 2 : Introduction---------------------------------------------------- 3
2.1 Theory of operation---------------------------------------------- 3
2.2 Feature-------------------------------------------------------------- 4
2.3 Annotation and symbol------------------------------------------ 5
2.4 Front Panel--------------------------------------------------------- 6
2.5 Operation Panel-------------------------------------------------- 6
2.6 Rear Panel--------------------------------------------------------- 8
Chapter 3 : Installation------------------------------------------------------ 9
3.1 Unpacking---------------------------------------------------------- 9
3.2 Before Installation------------------------------------------------ 9
3.3 Installation---------------------------------------------------------- 9
Chapter 4 : Operation------------------------------------------------------14
4.1 Cold start when utility is not present------------------------14
4.2 Turning “ON” the UPS------------------------------------------14
4.3 Turning “OFF” the UPS----------------------------------------15
4.4 UPS self-test------------------------------------------------------15
4.5 Silence function--------------------------------------------------15
4.6 Abnormal Condition---------------------------------------------16
4.7 UPS internal fault------------------------------------------------18
4.8 Derating power---------------------------------------------------19
Chapter 5 : Maintenance--------------------------------------------------20
III
Chapter 6 : Placement------------------------------------------------------21
Chapter 7 : Troubleshooting---------------------------------------------22
Chapter 8 : Communication Interface---------------------------------23
8.1 RS-232-------------------------------------------------------------23
Appendix 1 : Specifications----------------------------------------------25
Appendix 2 : Warranty-----------------------------------------------------26
Amplon R Series IV
Chapter 1 Important Safety Instructions
Safety Instructions:
The UPS contains voltages which are potentially hazardous. All repairs should
be performed by qualified service personnel. The UPS has its own internal en-
ergy source (Battery). The output receptacles may be alive even when the UPS
is not connected to the mains.
Die USV enthält Spannungen die möglicherweise gefährlich sind. Alle Repara-
turen sollten nur von ausgebildeten Monteuren durchgeführt werden. Die USV
hat eine interne Stromversorgung (Batterien). Die Ausgangsanschlüsse können
daher unter Strom stehen auch wenn die USV nicht an das Versorgungsnetz an-
geschlossen ist.
When replacing batteries, always use the same type and quantity as the previ-
ous one. Batteries of:
GES302R/ 3KVA: HR9-12 (BB), HR1234WF2 (CSB)
GES202R/2KVA: GP1270 or GP1272F2(CSB), BP7-12 or
BP7.2-12 (BB), NP7-12 (Yuasa), RT1270 (Ritar)
GES102R/1KVA: GP1270 or GP1272F2 (CSB), BP7-12 or
BP7.2-12 (BB), NP7-12 (Yuasa), RT1270 (Ritar)
HR9-12 (BB), HR1234WF2 (CSB)
Falls Sie die Batterien austauschen, verwenden Sie bitte ausschlieβlich die glei-
che Anzahl und die folgenden Batterietypen:
GES302R/ 3KVA: HR9-12 (BB), HR1234WF2 (34W)
GES202R/2KVA: GP1270 or GP1272F2(CSB), BP7-12 or
BP7.2-12 (BB), NP7-12 (Yuasa), RT1270 (Ritar)
GES102R/1KVA: GP1270 or GP1272F2 (CSB), BP7-12 or
BP7.2-12 (BB), NP7-12 (Yuasa), RT1270 (Ritar)
Do not dispose the battery or batteries in fire as this may explode.
Werfen Sie niemals die Batterien in das Feuer, die Batterien könnten explodi-
eren.
Do not open or mutilate the battery or batteries as released electrolyte is toxic
and harmful to skin and eyes.
Öffnen oder beschädigen Sie nicht die Batterien, ausflieβendes Elektrolyt ist
schädlich für Haut und Augen.
1
A battery can present a risk of electric shock and high short circuit current. The
following precaution should be observed when working on batteries.
* Remove watches, rings or other metal objects.
* Use tools with insulated handles.
Eine Batterie kann eine Gefahr eines elektrischen Schlages und sehr groβer
Kurzschluβ ströme beinhalten. Folgende Vorkehrungen sollten getroffen werden,
wenn Sie mit der Batterie arbeiten.
* Entfernen Sie Uhren, Ringe und andere metallische Objekte.
* Verwenden Sie Werkzeug mit isollierten Griffen.
The equipment is to be operated by fully trained personnels.
Diese Gerät ist nur durch unterwiesenes Personal zu bedienen.
EC conformity declaration:
These devices comply with the regulations of the following guide-lines:
73/23/EEC guide-line of the Council for approximation of the legal regulations of
the EC countries concerning the electrical apparatus within certain voltage toler-
ances, modified by the guide-line RL 93/68/EEC of the Council.
89/336/EEC guide-line of the Council for approximation of the legal regulations
of the EC countries concerning the electromagnetic compatibility, modified by
the guide-lines RL 91/236/EEC... and 93/68/EEC of the Council.
The compliance with the following standards proves the conformity:
~~ EN 50091-1-1
~~ EN 55022/EN 55011, class B
Amplon R Series 2
Chapter 2 Introduction
Chapter 2 : Introduction
PFC Control
Circuit LED Board Control Board
To Control Board
To Auxiliary Power
Battery Bank
To Control Board
To Control Board
Auxiliary
To External Battery Bank Power
3
In case the utility power fail, the AC-DC converter and charger will be off duty. The
DC-DC converter works and converts the battery voltage into DC-BUS voltage. The
DC-AC inverter converts the DC-BUS voltage into AC voltage. This is so called [ON-
BATTERY mode].
The auxiliary power circuit supplies the designated power to all the control circuits.
Because the DC-AC inverter is always working, the DC-DC converter can work
rapidly and replace the AC-DC converter while the utility power fails. Furthermore,
the bypass relay continuously keeps in the position of inverter output to supply the
regulated power for the load. There is no power failure to loading equipment.
2.2 Feature
The UPS, available in 1KVA, 2KVA and 3KVA, is an advanced on-line UPS providing
reliable and consistent sine-wave quality power to vital equipment. It supports
personal computers, networks, servers, telecommunication equipment and a variety
of other facilities. With its outstanding protection features, the unit keeps your
applications safe and running smoothly at all times.
PFC (Power Factor Correction)
With this function, the investment in the capacity of circuit breakers can be
reduced, specially it will be highly regarded as an important feature in critical load
applications.
Complete Protection
On-line double conversion design, pure sine wave output and zero transfer time
provide best protection. With a built-in surge, spike and line noise protection, the
UPS prevents destructive hardware damage and extends system life. The EMI/
RFI filtering design prevents electrical noise from affecting computer operation
and data files. Besides, the UPS provides built-in Fax/ Network cable (RJ11/RJ45)
jacks protecting your hardware from surge, spikes and line-noise that travel along
communication lines, therefore providing you a complete “back door” protection.
Intelligent design
Integrated with a microprocessor, the UPS is able to perform intelligent functions.
The UPS triggers over-voltage protection function and transfers to [On- Battery
mode] even when utility voltage exceeds 280V for 220V Series. In addition, the
UPS can accept large voltage variation of 80V to 280V. Wide Input voltage range
means less battery power usage frequency and longer battery life-span. Besides,
programmable outlet design, suitable for power management, is also included in this
unit.
Amplon R Series 4
Chapter 2 Introduction
!
Read before Operation Maybe Dangerous/Follow Instructions
This symbol indicates the principal on/off switch is in the “ON” position.
5
2.4 Front Panel
Fig 2-4 Front Panel for 1KVA & 2KVA & 3KVA
OVERLOAD
100%
FAULT 75% ON
TEST
50%
BYPASS
OFF
25%
LINE
OPERATION PANEL
A. Button :
1. ON/TEST: The button is used for turning on the UPS, it also can
perform the test function in “ON-LINE mode”. In backup mode, this
button can turn off the buzzer for silence.
Amplon R Series 6
Chapter 2 Introduction
B. LED Display :
2. Line: The LED indicates the condition of UPS input line. If the input
voltage is too low, too high or out of frequency this LED will flash.
When line is blackout or ultra high voltage (>300Vac), this LED will
light off.
4. Fault: The LED indicates that the UPS is fault. The LED Flash
indicates that the UPS is overheat.
5. Level LEDs: The four LEDs indicate the battery capacity in “ON-
BATTERY mode” or UPS load percentage in “ON-LINE mode”.
6. Overload: The LED indicates UPS’ load exceed the rating, after a
limited period, the UPS will transfer to “BYPASS mode” and the LED
will still light on to alarm the user.
7. Load: “Level LEDs” shows the UPS load level when the LED lights
up.
8. Battery: “Level LEDs” shows the current battery capacity when the
LED lights up.
9. Battery low: The LED indicates the battery in battery low condition.
10. Battery replace: The LED indicates the batteries are weak and
suggest the user to replace the batteries.
7
2.6 Rear Panel
The rear panel is explained as follows: (Please refer to fig 2-6.1, 2-6.2)
1. I/P BREAKER: This is used to prevent high input current from the UPS.
2. INPUT SOCKET: AC input utility power supplies to the UPS via the socket.
3. OUTPUT RECEPTACLES: The UPS supplies AC power to the load via these
receptacles.
4. SNMP SLOT: SNMP adapter can be inserted into this port for monitoring UPS
status via network.
5. External Batteries Connector: Used for connecting external battery cabinets to
extend back up time.
6. Fan: DC fans for cooling purpose.
7. TVSS (Transient Voltage Surge Suppressor) (RJ-45/RJ-11 SURGE
PROTECTOR): These connectors are used to prevent damage from surge,
noise and spike traveling form telephone or network line.
8. COMMUNICATION INTERFACE (RS-232): The communication port is used to
communicate PC and UPS. Please refer to section 8 for more information.
Amplon R Series 8
Chapter 3 Installation
Chapter 3 : Installation
3.1 Unpacking
zz Please read this user manual before installing the UPS.
zz This UPS contains batteries which are potentially hazardous to user,
even when the UPS is not connected to the utility power.
zz Before unpacking the UPS, check the packing box. If there are any
visible damage, contact your dealer at once.
This unit is to operate by any individuals with previous training.
This unit should be installed by service personnel.
3.3 Installation
Notice:
AC output need a disconnect device such as a breaker which has to be provided
by others.
The wire length of output power cord connected to the output receptacle or pres-
sure terminal should be less then 10 meters.
The UPS provide with pressure terminal connector for field installed wiring,
the terminal connector should be applied a 13.8 lb-in (1.554 N-m) of tightening
torque.
The over current protection and short circuit protection for the AC output is pro-
vided by internal circuits of UPS and breaker.
Concerning about the battery voltage, ambient temperature and other specifica-
tions of the UPS, please refer to the specification section of this manual.
9
Servicing of batteries should be performed or supervised by personnel knowl-
edgeable of batteries and the required precautions. Keep unauthorized person-
nel away batteries.
When replacing batteries, replace with the same type and number.
1. Connecting to utility power
Connect the IEC plug of power cord to the IEC 320 connector on the UPS.
Plug the other end of the power cord into a two-pole, three-wire, grounding
receptacle only. Avoid using extension cords and adapter plug.
Turn on the input breaker (if the breaker can be turned on) on the rear panel
of UPS.
After that, the fan (in rear panel) will run and all LEDs will light for about
2-3 sec. Meanwhile the CPU inside the UPS setups the initial parameters.
User also can check whether all LEDs are normal or not. The UPS is set in
“STANDBY mode” initially, after a ‘bee’ is heard, the load LED lights on and
the line LED shows AC utility status. Shown as fig 3-1.
OVERLOAD
100%
FAULT 75% ON
TEST
50%
BYPASS
OFF
25%
LINE
Amplon R Series 10
Chapter 3 Installation
11
4. Connecting the load
Calculate power consumption of your loads to ensure that the overload condi-
tion will not happen.
Plug the power cord of the equipment into the output receptacles on the rear
panel of the UPS.
Turn on the equipment connected to the UPS.
Fig 3-3.1
Amplon R Series 12
Chapter 3 Installation
Fig 3-3.2
UPS Connection for 2KVA or 3KVA:
(1) Connected to RS-232 cable
(2) Provides power to PC.
(3) Connected to utility power.
Fig 3-3.2
13
Chapter 4 : Operation
100%
FAULT 75% ON
TEST
50%
BYPASS
OFF
25%
LINE
OVERLOAD
100%
FAULT 75% ON
TEST
50%
BYPASS
OFF
25%
LINE
Amplon R Series 14
Chapter 4 Operation
OVERLOAD
100%
FAULT 75% ON
TEST
50%
BYPASS
OFF
25%
LINE
15
4.6 Abnormal Condition
If certain abnormal condition occurs, the UPS will send the following messages:
zz ON-BATTERY mode: When the UPS is in [ON-BATTERY mode], the on- battery
LED will light on, buzzer beep half second every 2 seconds and then the UPS
will start supplying power to load through batteries. Shown as fig 4-4.
OVERLOAD
100%
FAULT 75% ON
TEST
50%
BYPASS
OFF
25%
LINE
zz OVERLOAD: If the load exceeds the UPS rating, after a limited period, the over-
load LED will light on and buzzer continuous beeping to alarm the user. The user
should unplug some uncritical loads to release the overload condition. Shown as
fig 4-5.
OVERLOAD
100%
FAULT 75% ON
TEST
50%
BYPASS
OFF
25%
LINE
Amplon R Series 16
Chapter 4 Operation
zz BATTERY REPLACE: This LED function is to alert user that the batteries should
be replaced. When the microprocessor in the UPS detects a battery fault, the
UPS alarm will give out three beeps. Each beep lasts for 0.5 seconds and inter-
rupted by an interval of 0.5 seconds. After the initial 3 beeps, the alarm will con-
tinue to sound every one hour. Shown as fig 4-6.
OVERLOAD
100%
FAULT 75% ON
TEST
50%
BYPASS
OFF
25%
LINE
zz BATTERY LOW: This function is to inform user the remaining power capacity
of the batteries. When batteries reach a low level condition, the UPS alarm will
beep half second every 1.5 seconds until running out of battery capacity. Shown
as fig 4-7.
OVERLOAD
100%
FAULT 75% ON
TEST
50%
BYPASS
OFF
25%
LINE
17
zz SHORT CIRCUIT: When the output of the UPS shorts in [ON-LINE mode] or
[ON-BATTERY mode], the UPS will shut down (without output voltage). As soon
as the short circuit is happened, the fault LED will light on and the UPS alarm
will sound continuously. When remove short circuit, the UPS output will recover.
If short circuit is happened in “BYPASS mode”, the UPS will protect itself by trip-
ping the input breaker and shut down. Shown as fig 4-8.
OVERLOAD
100%
FAULT 75% ON
TEST
50%
BYPASS
OFF
25%
LINE
Amplon R Series 18
Chapter 4 Operation
OVERLOAD OVERLOAD
100% 100%
50% 50%
BYPASS BYPASS
OFF OFF
25% 25%
LINE LINE
OVERLOAD OVERLOAD
100% 100%
50% 50%
BYPASS BYPASS
OFF OFF
25% 25%
LINE LINE
19
Chapter 5 : Maintenance
zz Normally, the life of battery is 3 years. But extreme operating condition and envi-
ronment may shorten its life-span.
zz To replace batteries, contact qualified personnel.
zz When UPS has been unused for a period of time, the batteries will discharge
slightly. It is recommended to charge the UPS once every 3 months.
zz Use a vacuum cleaner to get rid of any dust that may rest on the opening of the
fan.
zz Unplug the UPS when it is not used for a long time.
zz When cleaning the plastic case or front panel, only use a soft, dry cloth. If the
case or front panel is very dirty, use a neutral, non-abrasive detergent. Do not
use alcohol or ammonia based solutions.
zz When moving your UPS, always handle it with care.
zz Avoid spilling liquid on the UPS.
zz The equipment should be repaired and installed by individuals with previous
training.
When installing this equipment, it should be noted that the leakage current of the
UPS and its loads must not exceed 3.5mA in total for safety.
Amplon R Series 20
Chapter 6 Placement
Chapter 6 : Placement
You can set the UPS on the Rack , You can make the UPS Erect by the Support
stands also.
To stably install the UPS of 1 & 2 & 3kVA models, you must set up UPS with
supporting stands.
The installation method is as shown below:
21
Chapter 7 : Troubleshooting
“OVERLOAD” LED
lights on and buzzer Overloaded. Remove some critical load.
beeps continuously.
Amplon R Series 22
Chapter 8 Communication Interface
The UPS provides RS-232 protocols in one D-sub 9 connector. Using proper UPS
management software and cable, the UPS can be managed over LAN/intranet/
internet environment.
UPS can be also managed through IE / network management software when it’s
installed an external SNMP card .The detail install method reference to the“SNMP
card user’s manual”
The pin assignment of the D-sub 9 connector is defined as follows:
ASSIGNMENT DESCRIPTION
PIN PIN
RS232
1 GND 5
2 UPS TxD(typical RS-232 level) 6
3 UPS RxD(typical RS-232 level) PNP 7
4 8
9
8.1 RS-232
Pin 2 : PC receives line RS-232 data from UPS.
Pin 3 : PC transmits line RS-232 data to UPS.
Pin 5 : Signal ground.
Pin 7 : Reversed for plug and play function.
The RS-232 communication port provides the following functions:
1) Monitoring charger status
2) Monitoring battery status and condition 6 7 8 9
23
The UPS data is provided at 2400 bps baud rate and made up of 8-bit, 1 stop-bit
and no parity bit. All information is encoded in ASCII format.
HARDWARE:
Amplon R Series 24
Appendix 1 Specifications
Appendix 1 : Specifications
Overload Capacity 105%-125% for 3mins; 125%-150% for 30secs; >150% for 1sec
25
Appendix 2 : Warranty
Seller warrants this product, if used in accordance with all applicable instructions,
to be free from original defects in material and workmanship within the warranty
period. If the product has any failure problem within the warranty period, Seller will
repair or replace the product at its sole discretion according to the failure situation.
This warranty does not apply to normal wear or to damage resulting from improper
installation, operation, usage, maintenance or irresistible force (i.e. war, fire,
natural disaster, etc.), and this warranty also expressly excludes all incidental and
consequential damages.
Maintenance service for a fee is provided for any damage out of the warranty
period. If any maintenance is required, please directly contact the supplier or Seller.
WARNING!
The individual user should take care to determine prior to use whether the
environment and the load characteristic are suitable, adequate or safe for
the installation and the usage of this product. The User Manual must be
carefully followed. Seller makes no representation or warranty as to the
suitability or fitness of this product for any specific application.
Amplon R Series 26
5011358904