Data Sheet

Stop/Check valve & Check valve


Type SCA-X and CHV-X

Designed to open at very low differential pressures, allow favourable flow conditions and
are easy to disassemble for inspection and service

SCA-X are check valves with a built-in shut-off


valve function. SCA-X valves are avilable in
angleway versions.

CHV-X are check valves only. CHV-X are


available in both angleway and straightway
versions.

The valves are designed to open at very low


differential pressures, allow favourable flow
conditions and are easy to disassemble for
inspection and service.

The SCA-X is equipped with vented cap and has


internal backseating enabling the spindle seal
to be replaced whilst the valve still under
pressure.

Laser cut V-ports provide excellent opening


characteristics (SCA-X/CHV-X 50-125).

The valve cone has a built-in flexibility to


ensure a precise and tight closing towards the
valve seat. A well balanced dampening effect
between the piston and the cylinder gives an
optimal protection during low loads and
against pulsations.

AI250986497520en-001102
Stop/Check valve & and Check valve, type SCA-X and CHV-X

Features

• Modular Concept:
◦ Each valve housing is available with several different connection types and sizes
◦ Possible to convert SCA-X or CHV-X to any other product in the FlexlineTM SVL family (Hand operated
regulating valve, shut-off valve or strainer) just by replacing the complete top part
• Fast and easy valve overhaul service. It is easy to replace the top part and no welding is needed
• Designed to open at a very low differential pressure of 0.04 bar (0.58 psig)
• Designed with a built-in damping chamber preventing valve flutter in case of low refrigerant velocity and/or low
density
• Each valve is clearly marked with type, size and performance range. Additional ID ring to be installed when
preparing for Ammonia Heat Pump or Propylene application
• Easy to disassemble for inspection and service
• Internal backseating enables replacement of the spindle seal whilst the valve is active, i.e. under pressure
• Optimal flow characteristics ensuring quick opening to the fully open position
• Protection against pulsation by built-in damping facility
• Housing and bonnet material is low temperature steel according to requirements of the Pressure Equipment
Directive and other international classification authorities
• Equipped with Stainless steel bolts
• Classification: DNV, CRN, BV, EAC etc. To get an updated list of certification on the products please contact your
local Danfoss Sales Company

© Danfoss | Climate Solutions | 2022.12 AI250986497520en-001102 | 2


Stop/Check valve & and Check valve, type SCA-X and CHV-X

Applications

Below diagram shows the check & stop valve SCA-X in the discharge line of a screw compressor unit. The SCA-X
valve in the discharge line prevents “back condensation” in the oil separator as well as pressure equalising through
the compressor.

Compared to an ordinary stop and check valve arrangement the combined stop/check valve solution, as shown, is
easier to install and has lower flow resistance.

Installation of the SCA-X/CHV-X in the economizer line is not recommended.

For horizontal installation of the function module; please contact Danfoss.

Figure 1: Flow diagram

SCA-X
Oil separator

Compressor

Oil cooler
M148G0005_1
Danfoss

© Danfoss | Climate Solutions | 2022.12 AI250986497520en-001102 | 3


Stop/Check valve & and Check valve, type SCA-X and CHV-X

Media

Refrigerants
Applicable to HCFC, HFC, R717 (Ammonia), R744 (CO2), Propane, Butane, Iso-Butane and Ethane.

R717 Heat Pump and Propylene applications with replaced O-ring.

New refrigerants
Danfoss products are continually evaluated for use with new refrigerants depending on market requirements.

When a refrigerant is approved for use by Danfoss, it is added to the relevant portfolio, and the R number of the
refrigerant (e.g. R513A) will be added to the technical data of the code number. Therefore, products for specific
refrigerants are best checked at store.danfoss.com/en/, or by contacting your local Danfoss representative.

© Danfoss | Climate Solutions | 2022.12 AI250986497520en-001102 | 4


Stop/Check valve & and Check valve, type SCA-X and CHV-X

Product specification

Pressure and temperature data


Table 1: Pressure and temperature data
Features Description
Temperature range -60 °C /+150 °C (-76 °F/+302 °F).
Max. working pressure 52 bar (754 psi)

Design
Housing
The housing is made from special, cold resistant steel.

Valve cone
Valve cone with built in metallic stop - prevents damage to teflon ring in case of overtightening.

Damping chamber
The chamber is filled with refrigerants (gas or liquid), which provides a damping effect when the valve opens and
closes.

Spindle (SCA-X)
Made of polished stainless steel, which is ideal for O-ring sealing.

Packing Gland (SCA-X)


The “full temperature range” packing gland is the standard for the entire SVL platform.

This ensures perfect tightness throughout the whole temperature range: -60/+150 °C (-76/+302 °F).

Installation
Figure 2: Example of marking ring, CHV-X

The valve must be mounted vertically with the cone downwards.

The valve is designed to resist very high internal pressure. However, the piping system in general should be
designed to avoid liquid traps and reduce the risk of hydraulic pressure caused by thermal expansion.

For further information refer to installation guide for SCA-X/CHV-X.

If cold refrigeration oil having low viscosity enters and settles in the damping chamber, problems with the check
valve may arise. Consequently, it may be necessary to modify the valve for more viscous liquids by enlarging the
hole to the damping chamber.

© Danfoss | Climate Solutions | 2022.12 AI250986497520en-001102 | 5


Stop/Check valve & and Check valve, type SCA-X and CHV-X

Material specification
SCA-X 15 - 40, CHV-X 15 - 40 and CHV-X 15 - 40
Table 2: SCA-X 15 - 40 and CHV-X 15 - 40
SCA-X 15 - 40 CHV-X 15 - 40 CHV-X 15 - 40
M148G0008_1
Danfoss

17
15
12 15

M148G0009_1
12

Danfoss
8
2 2
11 16
9 3 3
10 15 13
4
3
13
14
12
2 5
13 14
6
7 5 1
14

148G237_02-2017
5 6

Danfoss
6 1
1

Table 3: Material specification


No. Part Material DIN/EN ISO ASTM
P285QH
1 Housing Steel LF2, A350
EN10222-4
P275NL1
2 Bonnet, Flange Steel
EN10028-3
3 Bonnet, Insert Steel
4 Spindle Stainless steel X 10CrNiS18-9 Type 17, 17440 AISI 303, 683/13
Steel
5 Cone
Teflon (PTFE)
6 O-ring Chloroprene (Neoprene)
7 Spindle extension Steel
Packing gland Stainless steel
8
O-rings Chloroprene (Neoprene)
9 Packing washer Aluminium
10 Spring loaded seal Teflon (PTFE)
11 O-ring Chloroprene (Neoprene)
12 Bolts Stainless steel A2-70 A2-70 Type 308
13 Gasket Fiber, non-asbestos
14 Spring Steel
15 Identification ring Stainless steel
16 Seal cap gasket Nylon
17 Spindle seal cap Aluminium

© Danfoss | Climate Solutions | 2022.12 AI250986497520en-001102 | 6


Stop/Check valve & and Check valve, type SCA-X and CHV-X

SCA-X 50 - 125 and CHV-X 50 - 125


Table 4: SCA-X 50 - 125 and CHV-X 50 - 125
SCA-X 50 - 125 CHV-X 50 - 125 CHV-X 50 - 125

18 4
18 3

17 4 2
17
1
3
8
2
10

8 1
7 9
5 5
7 10 12
12 6
6 11
11 9

148G243_01-2018

148G244_01-2018
Danfoss A/S

Danfoss A/S
No. Part Material DIN/EN ISO ASTM
P285 QH
LF2, A350
EN 10222-4
Housing DN 50-65 Steel
1 G20Mn5 QT
LCC, A352
SEW 685
Housing DN 80-125 Steel G20Mn5 QT SEW 685 LCC, A352
2 Gasket Fiber, Non-asbestos
SCA-X: Valve bonnet P285 QH
3 Steel LF2, A350
CHV-X: End cover EN 10222-4
4 Bolts Stainless steel A2-70 A2-70 A-276
5 Tube Steel
6 Seat Steel
7 Valve plate Steel
8 Guide sleeve Steel
9 Spring ring Steel
10 Spring Steel
Chloroprene
11 O-ring
(Neoprene)
12 Teflon ring Teflon (PTFE)
13 Soft back seal Teflon (PTFE)
X8CrNiS18-9 Type 17
Spindle DN 50-65 Stainless steel AISI 303
17440 R 683/13
14
X5CrNi1810 Type 11 AISI 304
Spindle DN 80-125 Stainless steel
17440 683/13 A-276
Type 2
15 Packing gland Stainless steel 9Mn28, 1651 1213, SAE J403
R 683/9
16 Spindle seal cap and gasket Aluminium
17 Marking label Stainless steel
18 Eye bolt DIN 580 Steel

Computation and selection


Introduction
When dimensioning SCA-X/CHV-X, it is important to select a valve that is best suited to all operating conditions.
Therefore, it is necessary to consider both the nominal and part load working conditions.

Please refer to Coolselector®2 for calculation and selection of the right SCA-X/CHV-X.

© Danfoss | Climate Solutions | 2022.12 AI250986497520en-001102 | 7


Stop/Check valve & and Check valve, type SCA-X and CHV-X

Connections
Available with the following connections:

• Butt-weld DIN (EN 10220)


◦ DN 15 - 125 (½ - 5 in.)
• Butt-weld ANSI (B 36.10 Schedule 80),
◦ DN 15 - 40 (½ - 1½ in.)
• Butt-weld ANSI (B 36.10 Schedule 40),
◦ DN 50 - 125 (2 - 5 in.)
• Butt-weld GOST, (8734-75 and 8732-78)
◦ DN 15 - 125 (½ - 5 in.)
• Socket-weld ANSI (B 16.11),
◦ DN 50 (2 in.)

Figure 3: DIN

Table 5: Butt-weld DIN (EN 10220)


kv Straight‐ Cv Straight‐
Size ØD T ØD T kv Angleway Cv Angleway
way way
mm in. mm mm in. in. m3/h USgal/min m3/h USgal/min
15 ½ 21.3 2.3 0.839 0.091 8 9.3 4 4.6
20 ¾ 26.9 2.3 1.059 0.091 10 11.6 7 8.1
25 1 33.7 2.6 1.327 0.102 24 27.8 16 18.6
32 1¼ 42.4 2.6 1.669 0.102 30 34.8 21 24.4
40 1½ 48.3 2.6 1.902 0.102 30 34.8 21 24.4
50 2 60.3 2.9 2.37 0.11 45 53 28 34
65 2½ 76.1 2.9 3.00 0.11 72 85 41 48
80 3 88.9 3.2 3.50 0.13 103 129 81 94
100 4 114.3 3.6 4.50 0.14 196 232 157 182
125 5 139.7 4.0 5.50 0.16 301 356 250 290

Figure 4: ANSI

Table 6: Butt-weld ANSI (B 36.10 Schedule 80)


kv Straight‐ Cv Straight‐
Size ØD T ØD T kv Angleway Cv Angleway
way way
mm in. mm mm in. in. m3/h USgal/min m3/h USgal/min
15 ½ 21.3 3.7 0.839 0.146 8 9.3 4 4.6
20 ¾ 26.9 4.0 1.059 0.158 10 11.6 7 8.1
25 1 33.7 4.6 1.327 0.181 24 27.8 16 18.6
32 1¼ 42.4 4.9 1.669 0.193 30 34.8 21 24.4
40 1½ 48.3 5.1 1.902 0.201 30 34.8 21 24.4

© Danfoss | Climate Solutions | 2022.12 AI250986497520en-001102 | 8


Stop/Check valve & and Check valve, type SCA-X and CHV-X

Table 7: Butt-weld ANSI (B 36.10 Schedule 40)


kv Straight‐ Cv Straight‐
Size ØD T ØD T kv Angleway Cv Angleway
way way
mm in. mm mm in. in. m3/h USgal/min m3/h USgal/min
50 2 60.3 3.9 2.37 0.15 45 53 28 34
65 2½ 76.1 5.2 2.87 0.20 72 85 41 48
80 3 88.9 5.5 3.50 0.22 103 129 81 94
100 4 114.3 6.0 4.50 0.24 196 232 157 182
125 5 141.3 6.6 5.56 0.26 301 356 250 290

Figure 5: GOST

Table 8: Butt-weld GOST (8734-75 and 8732-78)


kv Straight‐ Cv Straight‐
Size ØD T ØD T kv Angleway Cv Angleway
way way
mm in. mm mm in. in m3/h USgal/min m3/h USgal/min
15 ½ 18 2 0.709 0.079 8 9.3 4 4.6
20 ¾ 25 2.5 0.984 0.098 10 11.6 7 8.1
25 1 32 3 1.260 0.118 24 28.8 16 18.6
32 1¼ 38 3 1.496 0.118 30 49.4 21 24.4
40 1½ 45 3 1.772 0.118 30 52.4 21 24.4
50 2 57 3.5 2.244 0.138 45 53 28 34
65 2½ 76.1 2.9 3 0.11 72 85 41 48
80 3 88.9 3.2 3.50 0.13 103 129 81 94
100 4 108 4 4.252 0.157 196 232 157 182
125 5 133 4 5.236 0.157 301 356 250 290

Figure 6: SOC

Table 9: Socket welding ANSI (B 16.11)


Size ID T ID T L L
mm in. mm mm in. in mm in.
15 ½ 21.8 6 0.858 0.235 10 0.39
20 ¾ 27.2 4.6 1.071 0.181 13 0.51
25 1 33.9 7.2 1.335 0.284 13 0.51
32 1¼ 42.7 6.1 1.743 0.240 13 0.51
40 1½ 48.8 6.6 1.921 0.260 13 0.51
50 2 61.2 6.2 2.41 0.24 16 0.63

© Danfoss | Climate Solutions | 2022.12 AI250986497520en-001102 | 9


Stop/Check valve & and Check valve, type SCA-X and CHV-X

Dimensions and weights


SCA-X/CHV-X 15-40 (½-1½ in.)
Table 10: SCA-X /CHV-X 15-40 (½-1½ in.)
SCA-X 15-40 CHV-X 15-40

G
B

148G238_02-2017
E

DANFOSS
H

Table 11: SCA-X 15-40


C G ØD Fmin ØH Weight
Valve size
mm in. mm in. mm in. mm in. mm in. kg lb
SCA-X 15 (½ in.) 212 8.35 45 1.77 38 1.50 60 2.36 60 2.36 1.6 3.53
SCA-X 20 (¾ in.) 212 8.35 45 1.77 38 1.50 60 2.36 60 2.36 1.6 3.53
SCA-X 25 (1 in.) 295 11.61 55 2.17 50 1.97 85 3.35 70 2.76 3.2 7.05
SCA-X 32 (1¼ in.) 295 11.61 55 2.17 50 1.97 85 3.35 70 2.76 3.2 7.05
SCA-X 40 (1½ in.) 295 11.61 55 2.17 50 1.97 85 3.35 70 2.76 3.2 7.05

Table 12: CHV-X 15-40 Angleway


C G Fmin ØH Weight
Valve size
mm in. mm in. mm in. mm in. kg lb
CHV-X 15 (½ in.) 103 4.06 45 1.77 60 2.36 60 2.36 1.2 2.65
CHV-X 20 (¾ in.) 103 4.06 45 1.77 60 2.36 60 2.36 1.2 2.65
CHV-X 25 (1 in.) 143 5.63 55 2.17 85 3.35 70 2.76 2.3 5.07
CHV-X 32 (1¼ in.) 143 5.63 55 2.17 85 3.35 70 2.76 2.3 5.07
CHV-X 40 (1½ in.) 143 5.63 55 2.17 85 3.35 70 2.76 2.3 5.07

Table 13: CHV-X 15-40 Straightway


C B E G Fmin ØH Weight
Valve size
mm in. mm in. mm in. mm in. mm in. mm in. kg lb
CHV-X 15 (½ in.) 99 3.90 114 4.49 19 0.75 120 4.72 60 2.36 60 2.36 1.3 2.87
CHV-X 20 (¾ in.) 99 3.90 114 4.49 19 0.75 120 4.72 60 2.36 60 2.36 1.3 2.87
CHV-X 25 (1 in.) 141 5.55 157 6.18 26 1.02 155 6.10 85 3.35 70 2.76 2.6 5.73
CHV-X 32 (1¼ in.) 141 5.55 157 6.18 26 1.02 155 6.10 85 3.35 70 2.76 2.6 5.73
CHV-X 40 (1½ in.) 141 5.55 157 6.18 26 1.02 155 6.10 85 3.35 70 2.76 2.6 5.73

© Danfoss | Climate Solutions | 2022.12 AI250986497520en-001102 | 10


Stop/Check valve & and Check valve, type SCA-X and CHV-X

Table 14: CHV-X 32-40 Straightway, Socket weld


C B E G Fmin ØH Weight
Valve size
mm in. mm in. mm in. mm in. mm in. mm in. kg lb
CHV-X 32-40 (1¼ -
132 5.20 156 6.14 26 1.02 155 6.10 85 3.35 70 2.76 2.8 6.11
1½ in.)

 NOTE:
Specified weights are approximate values only.

SCA-X/CHV-X 50-65 (2-2½ in.)


Table 15: SCA-X/CHV-X 50-65 (½- 1½ in.)
SCA-X 50-65 CHV-X 50-65

Table 16: SCA-X


K C G ØD ØH Weight
Valve size
mm in. mm in. mm in. mm in. mm in. kg lb
SCA-X 50 70 2.76 315 12.40 60 2.36 50 1.97 77 3.03 3.8 8.40
SCA-X (2) 70 2.76 315 12.40 60 2.36 50 1.97 77 3.03 3.8 8.40
SCA-X 65 70 2.76 335 13.19 70 2.76 50 1.97 90 3.54 5.5 12.16
SCA-X (2½) 70 2.76 335 13.19 70 2.76 50 1.97 90 3.54 5.5 12.16

Table 17: CHV-X Angleway


C G Fmin ØH Weight
Valve size
mm in. mm in. mm in. mm in. kg lb
CHV-X 50 132 5.20 60 2.36 92 3.62 77 3.03 3.2 7.10
CHV-X (2) 132 5.20 60 2.36 92 3.62 77 3.03 3.2 7.10
CHV-X 65 152 5.98 70 2.76 107 4.21 90 3.54 4.5 9.95
CHV-X (2½) 152 5.98 70 2.76 107 4.21 90 3.54 4.5 9.95

© Danfoss | Climate Solutions | 2022.12 AI250986497520en-001102 | 11


Stop/Check valve & and Check valve, type SCA-X and CHV-X

Table 18: CHV-X Straightway


C B E G Fmin ØH Weight
Valve size
mm in. mm in. mm in. mm in. mm in. mm in. kg lb
CHV-X 50 139 5.47 140 5.51 32 1.26 148 5.83 92 3.62 77 3.03 3 6.72
CHV-X (2) 139 5.47 140 5.51 32 1.26 148 5.83 92 3.62 77 3.03 3 6.72
CHV-X 65 163 6.4 164 6.4 40 1.6 176 6.9 107 4.21 90 3.54 4.3 9.44
CHV-X (2½) 163 6.4 164 6.4 40 1.6 176 6.9 107 4.21 90 3.54 4.3 9.44

Table 19: CHV-X Straightway, Socket weld


C B E G Fmin ØH Weight
Valve size
mm in. mm in. mm in. mm in. mm in. mm in. kg lb
CHV-X 50 142 5.59 147 5.79 37 1.46 162 6.38 92 3.62 77 3.03 3.8 8.33
CHV-X (2) 142 5.59 147 5.79 37 1.46 162 6.38 92 3.62 77 3.03 3.8 8.33

 NOTE:
Specified weights are approximate values only.

SCA-X/CHV-X 80-125 (3-5 in.)


Table 20: SCA-X/CHV-X 80-125 (2 - 2½ in.)
SCA-X 80-125 CHV-X 80-125

148G246_01-2018
M148G0006_1

Danfoss A/S
Danfoss

Fmin.
.6
29
148G245_01-2018
Danfoss A/S

36
Fmin.

B
G
C
G

C
ØH

ØH

Table 21: SCA-X


K C G ØD ØH Weight
Valve size
mm in. mm in. mm in. mm in. mm in. kg lb
SCA-X 80 76 3.00 388 15.28 90 3.54 58 2.28 129 5.08 9.7 21.4
SCA-X (3) 76 3.00 388 15.28 90 3.54 58 2.28 129 5.08 9.7 21.4
SCA-X 100 90 3.54 437 17.20 106 4.17 58 2.28 156 6.14 15.3 33.7
SCA-X (4) 90 3.54 437 17.20 106 4.17 58 2.28 156 6.14 15.3 33.7
SCA-X 125 90 3.54 533 20.98 128 5.04 74 2.91 193 7.60 28.1 61.9
SCA-X (5) 90 3.54 533 20.98 128 5.04 74 2.91 193 7.60 28.1 61.9

© Danfoss | Climate Solutions | 2022.12 AI250986497520en-001102 | 12


Stop/Check valve & and Check valve, type SCA-X and CHV-X

Table 22: CHV-X Angleway


C G Fmin ØH Weight
Valve size
mm in. mm in. mm in. mm in. kg lb
CHV-X 80 218.6 8.61 90 3.54 103.4 4.07 129 5.08 8.7 19.23
CHV-X (3) 218.6 8.61 90 3.54 103.4 4.07 129 5.08 8.7 19.23
CHV-X 100 252.6 9.94 106 4.17 133.4 5.25 156 6.14 14.3 31.60
CHV-X (4) 252.6 9.94 106 4.17 133.4 5.25 156 6.14 14.3 31.60
CHV-X 125 297.6 11.72 128 5.04 160.4 6.31 193 7.60 25.6 56.58
CHV-X (5) 297.6 11.72 128 5.04 160.4 6.31 193 7.60 25.6 56.58

Table 23: CHV-X Straightway


C B E G Fmin ØH Weight
Valve size
mm in. mm in. mm in. mm in. mm in. mm in. kg lb
CHV-X 80 206 8.11 204 8.03 48 1.89 216 8.50 133 5.24 129 5.08 9.3 20.4
CHV-X (3) 206 8.11 204 8.03 48 1.89 216 8.50 133 5.24 129 5.08 9.3 20.4
CHV-X 100 256 10.08 248 9.76 62 2.44 264 10.39 163 6.43 156 6.14 14.6 32.29
CHV-X (4) 256 10.08 248 9.76 62 2.44 264 10.39 163 6.43 156 6.14 14.6 32.29
CHV-X 125 314 12.36 302 11.89 74 2.91 322 12.68 190 7.48 193 7.60 32.5 71.65
CHV-X (5) 314 12.36 302 11.89 74 2.91 322 12.68 190 7.48 193 7.60 32.5 71.65

 NOTE:
Specified weights are approximate values only.

© Danfoss | Climate Solutions | 2022.12 AI250986497520en-001102 | 13


Stop/Check valve & and Check valve, type SCA-X and CHV-X

Ordering

Ordering complete valves


How to order
The table below is used to identify the valve required.

Please note that the type codes only serve to identify the valves, some of wich may not form part of the standard
product range.

For further information please contact your local Danfoss Sales Company.

Table 24: Ordering complete valves

Check & Stop valve


SCA-X
Valve type Check Valve
CHV-X
A D G SOC
15 DN 15 X X X X
20 DN 20 X X X X
25 DN 25 X X X X
32 DN 32 X X X X
(valve size measured
40 DN 40 X X X X
on the connection di-
50 DN 50 X X X X
ameter)
65 DN 65 X X
80 DN 80 X X
100 DN 100 X X X
125 DN 125 X X X
A Welding branches: ANSI B 31.5 schedule 80 DN 15 - 40 (½ - 1½ in.)
Welding branches: ANSI B 31.5 schedule 40 DN 50 - 125 (2 - 5 in.)
Connections D Welding branches: EN 10220
G Butt-weld connection: GOST (8734-75 and 8732-78)
SOC Socket weld: ANSI B 16.11
Valve housing ANG Angle flow
STR Straight flow

 IMPORTANT:
Where products need to be certified according to specific certification societies the relevant information should be
included at the time of order.

Angleway
SCA-X
Table 25: SCA-X Butt-weld DIN (EN 10220)
Size
Type Code No.
mm in.
15 ½ SCA-X 15 D ANG 148B5208
20 ¾ SCA-X 20 D ANG 148B5308
25 1 SCA-X 25 D ANG 148B5408
32 1¼ SCA-X 32 D ANG 148B5508
40 1½ SCA-X 40 D ANG 148B5608
50 2 SCA-X 50 D ANG 148B5702
65 2½ SCA-X 65 D ANG 148B5803
80 3 SCA-X 80 D ANG 148B5902
100 4 SCA-X 100 D ANG 148B6002
125 5 SCA-X 125 D ANG 148B6102

© Danfoss | Climate Solutions | 2022.12 AI250986497520en-001102 | 14


Stop/Check valve & and Check valve, type SCA-X and CHV-X

Table 26: SCA-X Butt-weld ANSI (B 36.10 Schedule 80)


Size
Type Code No.
mm in.
15 ½ SCA-X 15 A ANG 148B5209
20 ¾ SCA-X 20 A ANG 148B5309
25 1 SCA-X 25 A ANG 148B5409
32 1¼ SCA-X 32 A ANG 148B5509
40 1½ SCA-X 40 A ANG 148B5609

Table 27: SCA-X Butt-weld ANSI (B 36.10 Schedule 40)


Size
Type Code No.
mm in.
50 2 SCA-X 50 A ANG 148B5703
65 2½ SCA-X 65 A ANG 148B5802
80 3 SCA-X 80 A ANG 148B5903
100 4 SCA-X 100 A ANG 148B6004
125 5 SCA-X 125 A ANG 148B6103

Table 28: SCA-X Socket welding ANSI (B 16.11)


Size
Type Code No.
mm in.
50 2 SCA-X 50 SOC ANG 148B5704

ANG = Angleway

CHV-X
Table 29: CHV-X Butt-weld DIN (EN 10220)
Size
Type Code No.
mm in.
15 ½ CHV-X 15 D ANG 148B5236
20 ¾ CHV-X 20 D ANG 148B5336
25 1 CHV-X 25 D ANG 148B5436
32 1¼ CHV-X 32 D ANG 148B5536
40 1½ CHV-X 40 D ANG 148B5636
50 2 CHV-X 50 D ANG 148B5736
65 2½ CHV-X 65 D ANG 148B5838
80 3 CHV-X 80 D ANG 148B5936
100 4 CHV-X 100 D ANG 148B6036
125 5 CHV-X 125 D ANG 148B6136

Table 30: CHV-X Butt-weld ANSI (B 36.10 Schedule 80)


Size
Type Code No.
mm in.
15 ½ CHV-X 15 A ANG 148B5237
20 ¾ CHV-X 20 A ANG 148B5337
25 1 CHV-X 25 A ANG 148B5437
32 1¼ CHV-X 32 A ANG 148B5537
40 1½ CHV-X 40 A ANG 148B5637

Table 31: CHV-X Butt-weld ANSI (B 36.10 Schedule 40)


Size
Type Code No.
mm in.
50 2 CHV-X 50 A ANG 148B5737
65 2½ CHV-X 65 A ANG 148B5837
80 3 CHV-X 80 A ANG 148B5937
100 4 CHV-X 100 A ANG 148B6037
125 5 CHV-X 125 A ANG 148B6137

© Danfoss | Climate Solutions | 2022.12 AI250986497520en-001102 | 15


Stop/Check valve & and Check valve, type SCA-X and CHV-X

Table 32: CHV-X Socket welding ANSI (B 16.11)


Size
Type Code No.
mm in.
32 1¼ CHV 32 SOC ANG 148B5539
50 2 CHV 50 SOC ANG 148B5740

Straightway
CHV-X
Table 33: CHV-X Butt-weld DIN (EN 10220)
Size
Type Code No.
mm in.
15 ½ CHV-X 15 D STR 148B6581
20 ¾ CHV-X 20 D STR 148B6583
25 1 CHV-X 25 D STR 148B6585
32 1¼ CHV-X 32 D STR 148B6587
40 1½ CHV-X 40 D STR 148B6589
50 2 CHV-X 50 D STR 148B6591
65 2½ CHV-X 65 D STR 148B6593
80 3 CHV-X 80 D STR 148B6595
100 4 CHV-X 100 D STR 148B6597
125 5 CHV-X 125 D STR 148B6599

Table 34: CHV-X Butt-weld ANSI (B 36.10 Schedule 80)


Size
Type Code No.
mm in.
15 ½ CHV-X 15 A STR 148B6582
20 ¾ CHV-X 20 A STR 148B6584
25 1 CHV-X 25 A STR 148B6586
32 1¼ CHV-X 32 A STR 148B6588
40 1½ CHV-X 40 A STR 148B6590

Table 35: CHV-X Butt-weld ANSI (B 36.10 Schedule 40)


Size
Type Code No.
mm in.
50 2 CHV-X 50 A STR 148B6592
65 2½ CHV-X 65 A STR 148B6594
80 3 CHV-X 80 A STR 148B6596
100 4 CHV-X 100 A STR 148B6598
125 5 CHV-X 125 A STR 148B6600

Table 36: CHV-X Socket welding ANSI (B 16.11)


Size
Type Code No.
mm in.
15 ½ CHV-X 15 SOC STR 148B6601
20 ¾ CHV-X 20 SOC STR 148B6602
25 1 CHV-X 25 SOC STR 148B6603
32 1¼ CHV-X 32 SOC STR 148B6604
40 1½ CHV-X 40 SOC STR 148B6605
50 2 CHV-X 50 SOC STR 148B6606

STR = Straightway

Ordering SCA-X from the parts programme


Example (select from table 37 and 38)
Example

© Danfoss | Climate Solutions | 2022.12 AI250986497520en-001102 | 16


Stop/Check valve & and Check valve, type SCA-X and CHV-X

Valve housing, size 25 (1 in.), Top part, SCA-X


DIN butt weld, angleway, size 25 (1 in.)
148B5452 148B5482
Table 37 Table 38

Valve Housing SVL


DN 15-65 mm (½ - 2½ in.) DN 80-125 mm (3 - 5 in.)

Table 37: SVL valve housings w/different connections


Valve Housing SVL
Sizes [DN]
DIN-Butt weld ANSI-Butt weld GOST-Butt-weld SOC FPT T
[mm] [in] ANG STR ANG STR ANG STR ANG STR ANG STR ANG
15 ½ 148B5252 148B5253 148B5254 148B5255 148B5391 148B5392 148B5256 148B5257 148B5258 148B5259 _
20 ¾ 148B5352 148B5353 148B5354 148B5355 148B5393 148B5394 148B5356 148B5357 148B5358 148B5359 _
25 1 148B5452 148B5453 148B5454 148B5455 148B5498 148B5499 148B5456 148B5457 148B5458 148B5459 _
32 1¼ 148B5576 148B5577 148B5578 148B5579 148B5593 148B5594 148B5580 148B5581 148B5582 148B5583 _
40 1½ 148B5652 148B5653 148B5654 148B5655 148B5681 148B5682 148B5656 148B5657 _ _ _
50 2 148B5741 148B5742 148B5743 148B5744 148B5759 148B5760 148B5745 148B5746 _ _ _
65 2½ 148B5816 148B5817 148B5818 148B5819 148B5816 148B5817 _ _ _ _ _
80 3 148B5912 148B5913 148B5914 148B5915 148B5912 148B5913 _ _ _ _ _
100 4 148B6014 148B6015 148B6016 148B6017 148B6033 148B6034 _ _ _ _ _
125 5 148B6112 148B6113 148B6114 148B6115 148B6133 148B6134 _ _ _ _ _

Complete top part SCA-X


SCA-X 15-50 SCA-X 80-125

© Danfoss | Climate Solutions | 2022.12 AI250986497520en-001102 | 17


Stop/Check valve & and Check valve, type SCA-X and CHV-X

Table 38: SCA-X complete top part including gaskets and bolts
Sizes [DN] Complete top part
[mm] [in] SCA-X
15 ½
148B5282
20 ¾
25 1
32 1¼ 148B5482
40 1½
50 2 148B5735
65 2½ 148B5825
80 3 148B5918
100 4 148B6019
125 5 148B6118

Ordering CHV-X from the parts programme


Example (select from table 40 and 41)
Example

Valve housing, size 25 (1 in.), Top part, CHV-X


DIN butt weld, angleway, size 25 (1 in.)
148B5452 148B5483
Table 40 Table 41

Valve Housing SVL


DN 15-65 mm (½ - 2½ in.) DN 80-125 mm (3 - 5 in.)

Table 39: SVL valve housings w/different connections


Valve Housing SVL
Sizes [DN]
DIN-Butt weld ANSI-Butt weld GOST-Butt-weld SOC FPT T
[mm] [in] ANG STR ANG STR ANG STR ANG STR ANG STR ANG
15 ½ 148B5252 148B5253 148B5254 148B5255 148B5391 148B5392 148B5256 148B5257 148B5258 148B5259 _
20 ¾ 148B5352 148B5353 148B5354 148B5355 148B5393 148B5394 148B5356 148B5357 148B5358 148B5359 _
25 1 148B5452 148B5453 148B5454 148B5455 148B5498 148B5499 148B5456 148B5457 148B5458 148B5459 _
32 1¼ 148B5576 148B5577 148B5578 148B5579 148B5593 148B5594 148B5580 148B5581 148B5582 148B5583 _
40 1½ 148B5652 148B5653 148B5654 148B5655 148B5681 148B5682 148B5656 148B5657 _ _ _
50 2 148B5741 148B5742 148B5743 148B5744 148B5759 148B5760 148B5745 148B5746 _ _ _
65 2½ 148B5816 148B5817 148B5818 148B5819 148B5816 148B5817 _ _ _ _ _

© Danfoss | Climate Solutions | 2022.12 AI250986497520en-001102 | 18


Stop/Check valve & and Check valve, type SCA-X and CHV-X

Valve Housing SVL


Sizes [DN]
DIN-Butt weld ANSI-Butt weld GOST-Butt-weld SOC FPT T
[mm] [in] ANG STR ANG STR ANG STR ANG STR ANG STR ANG
80 3 148B5912 148B5913 148B5914 148B5915 148B5912 148B5913 _ _ _ _ _
100 4 148B6014 148B6015 148B6016 148B6017 148B6033 148B6034 _ _ _ _ _
125 5 148B6112 148B6113 148B6114 148B6115 148B6133 148B6134 _ _ _ _ _

Complete top part CHV-X


CHV-X 15-50 CHV-X 80-125

Table 40: CHV-X complete top part including gaskets and bolts
Sizes [DN] Complete top part
[mm] [in] CHV-X
15 ½
148B5283
20 ¾
25 1
32 1¼ 148B5483
40 1½
50 2 148B5747
65 2½ 148B5827
80 3 148B5919
100 4 148B6022
125 5 148B6119

Table 41: Replacement kit (O-ring replacement) for R717 Ammonia Heat Pump* and Propylene applications (including ID
tag)
Size (DN) O-ring kit for
mm in. R717 Heat pump R1270 Propylene
15 ½
148B6070 148B6077
20 ¾
25 1
32 1¼ 148B6071 148B6078
40 1½
50 2 148B6072 148B6079
65 2½ 148B6073 148B6080
80 3 148B6074 148B6081
100 4 148B6075 148B6082
125 5 148B6076 148B6083

*Replacement kits for R717 Ammonia Heat Pump is applicable for continuous operating temperature between +100
°C to 150 °C (212 °F to 302 °F)

© Danfoss | Climate Solutions | 2022.12 AI250986497520en-001102 | 19


Stop/Check valve & and Check valve, type SCA-X and CHV-X

Certificates, declarations and approvals

The list contains all certificates, declarations, and approvals for this product type. Individual code number may have
some or all of these approvals, and certain local approvals may not appear on the list.

Some approvals may change over time. You can check the most current status at danfoss.com or contact your local
Danfoss representative if you have any questions.

Pressure Equipment Directive (PED)


REG valves are approved according to the European standard specified in the Pressure Equipment Directive and are
CE marked.

Table 42: Pressure Equipment Directive (PED)


REG-SA and REG-SB valves
Nominal bore DN = < 25 mm (1 in.) DN32 - 65 mm (1¼ - 2½ in.)
Classified for Fluid group I
Category Article 3, paragraph 3 II

© Danfoss | Climate Solutions | 2022.12 AI250986497520en-001102 | 20


Online support

Danfoss offers a wide range of support along with our products, including digital product information, software,
mobile apps, and expert guidance. See the possibilities below.

The Danfoss Product Store


The Danfoss Product Store is your one-stop shop for everything product related—no matter where
you are in the world or what area of the cooling industry you work in. Get quick access to essential
information like product specs, code numbers, technical documentation, certifications, accessories,
and more.
Start browsing at store.danfoss.com.

Find technical documentation


Find the technical documentation you need to get your project up and running. Get direct access to
our official collection of data sheets, certificates and declarations, manuals and guides, 3D models
and drawings, case stories, brochures, and much more.

Start searching now at www.danfoss.com/en/service-and-support/documentation.

Get local information and support


Local Danfoss websites are the main sources for help and information about our company and
products. Find product availability, get the latest regional news, or connect with a nearby expert—all
in your own language.

Find your local Danfoss website here: www.danfoss.com/en/choose-region.

Danfoss Learning
Danfoss Learning is a free online learning platform. It features courses and materials specifically
designed to help engineers, installers, service technicians, and wholesalers better understand the
products, applications, industry topics, and trends that will help you do your job better.

Create your Danfoss Learning account for free at www.danfoss.com/en/service-and-support/learning.

Spare Parts
Get access to the Danfoss spare parts and service kit catalog right from your smartphone. The app
contains a wide range of components for air conditioning and refrigeration applications, such as
valves, strainers, pressure switches, and sensors.

Download the Spare Parts app for free at www.danfoss.com/en/service-and-support/downloads.

Coolselector®2 - find the best components for you HVAC/R system


Coolselector®2 makes it easy for engineers, consultants, and designers to find and order the best
components for refrigeration and air conditioning systems. Run calculations based on your operating
conditions and then choose the best setup for your system design.

Download Coolselector®2 for free at coolselector.danfoss.com.

© Danfoss | Climate Solutions | 2022.12 AI250986497520en-001102 | 21