PRODUCT INFORMATION
Kurita® F-5106
Biocide for Cooling and Process Water Systems
Principal Application Application
Biofouling is a typical problem in recirculating Dose KURITA® F-5106 as a shock dosage
cooling water systems. Besides fouling of heat preferably at or before a point of high
exchangers and cooling tower packings it may mixing intensity in the system or into the
also be the primary cause for micro-biological cooling tower basin directly.
induced corrosion (MIC). KURITA® F-5106 should be added
KURITA® F-5106 is effective against slime undiluted.
forming microorganism and showing excellent If possible, try to keep the blowdown line
biocidal effect in open recirculating cooling water closed for 3 to 4 hours after the dosage of
systems. KURITA® F-5106.
KURITA’s engineers will advice you about
the correct application of the product.
Effect
Excellent control effect on bacteria, algae Storage
and fungi growth at low dosages
Excellent prevention effect against slime Store KURITA® F-5106 indoors at 0 to
forming bacteria 40°C.
Effective in the control of Legionella Keep container tightly closed when not in
pneumophila bacteria, which causes use.
Legionnaire's disease (Legionellose) Do not use the empty containers for
Effective in a pH-range from 6 to 9 drinking water supply.
General Description Material compatibility
Characteristics Data The following acid resistant materials are
Colourless to light suitable for storage and dosage of KURITA® F-
Colour and appearance 5106: Polyethylene, polypropylene, PVC, PTFE
yellow liquid
Bulk density (20°C) 1,09 ± 0,02 g/cm3
pH (20°C) 2,5 ± 1,0
Freezing point Approx. – 1 °C Attention:
Use biocides safely. Always read the label and
Non-oxidizing type.
product information before use.
Non-corrosive for steel
Liquid product with easy handling. Approval:
KURITA® F-5106 is registered by the German
Dosage CA BAuA under No. N-28384 for PT 11.
In recirculated cooling water, the treatment
depends on degree of contamination, on existing Handling and safety precautions:
nutritive substances, type of microbiological
deposits, temperature, holding time index and For industrial use only.
should be selected with the help of an Kurita-
representative. Do not apply to potable water or domestic water
systems.
In general a dosage of 25 to 100 g/m³ of
KURITA® F-5106 against the holding water For information please see material safety data
volume of the system once per week to twice sheet.
per month is recommended.
1/2
PRODUCT INFORMATION – KURITA® F-5106
The expiry date of the product is given on the
packaging labels.
Certification:
Our quality management system (ISO
9001:2008), environmental management system
(ISO 14001:2005) and occupational health and
safety management system (BS HSAS18001)
are successful certified by DQS.
The information contained herein reflects our current level of technical knowledge and experience. It does not constitute a legal warranty of particular
characteristics or of fitness for a specific purpose and, due to the abundance of possible influences, does not exempt the user from making its own examinations
and taking appropriate precautionary measures. It shall be the responsibility of the recipient of our products to respect any intellectual property rights and
comply with any laws or other provisions