KoolDuct Training Manual 2018-10 - US Units
KoolDuct Training Manual 2018-10 - US Units
1
The Kingspan System
Training Manual - Contents
Page Page
29 Double offset
87 Chapter 6 – Maintenance and external
30 Take off ductworks
2
The Kingspan System
Training Manual
Chapter 1
Introduction
3
The Kingspan System
Notice to User
Kingspan Insulation Ltd provide this publication to Kingspan Insulation’s Delivery
Partners and KoolDuct fabricators for information purposes as part of their Technical
Support Documentation that give broad directions and process recommendations for
the design and use of the Kingspan KoolDuct System.
This manual is not to be used as the sole reference material for the fabrication and
installation of Kingspan KoolDuct System ductwork; reference should also be made to
The Kingspan KoolDuct System Fabrication Manual (latest edition).
For specification details, reference should be made to The Kingspan KoolDuct System
Specifier’s Guide (latest edition).
All principles and techniques contained in this Training Manual were developed using
reliable engineering principles and research, plus consultation with manufacturers,
users, testing laboratories, and others having specialised experience.
This manual is subject to revision as further experience and investigation may show is
necessary or desirable.
Kingspan Insulation assume no responsibility and accept no liability for the application
of the principles or techniques contained in this publication. Authorities considering
adoption of any standard contained herein should review all state, local and contract
regulation applicable to specific installations.
The Delivery Partner and/or KoolDuct fabricators shall have full regard to Kingspan’s
Technical Support Documentation for the KoolDuct System and shall ensure that in any
design and any erection of using the Kingspan KoolDuct System, the guidelines in the
Technical Support Documentation are followed by it and any sub-contractors engaged
to design and/or assemble the ductwork.
In the event of any doubt please do not hesitate to contact us for further assistance.
4
The Kingspan System
Health and Safety
Kingspan KoolDuct panels are chemically inert and safe to use.
Wear gloves when handling and cutting the product: particles of the
glass fibre reinforced facings can be irritating to the skin.
Use suitable protective clothing (e.g. long-sleeved garments).
The reflective surface on this product will reflect light as well as heat,
including ultraviolet light. If this board is being installed during very
bright or sunny weather, wear UV protective sunglasses or goggles,
and if the skin is exposed for a significant period of time, protect the
bare skin with a UV block sun cream.
When hand tools with blades, saws or other cutting tools are used,
please handle the tools with caution.
Safety Data Sheet are available for the adhesive and silicone sealant
supplied by Kingspan Insulation
The application of adhesive and sealant shall be performed in a well
ventilated area, wearing protective gloves.
5
The Kingspan System
Storage and Handling
Please note that the factory applied packaging shall not be considered
weatherproof.
Any panels or sections which have been allowed to get wet shall not be
used.
INSIDE STORAGE
Wherever possible, both Kingspan KoolDuct panels and ductwork
sections shall be stored inside, under cover, and clear of the ground.
Once the duct sealant has fully cured, the open ends of the
ductwork sections shall be fully sealed with a weatherproof sheet to
prevent the ingress of foreign matter.
OUTSIDE STORAGE
Where storage inside a building is not possible, Kingspan KoolDuct
panels and ductwork sections shall be stored clear of the ground
protected and secured against all weather, including wind, rain, and
sunlight, by an opaque light coloured weatherproof material suitable for
the climate in which it is to be stored. As above, the open ends of the
ductwork shall be fully sealed with a weatherproof sheet to prevent the
ingress of foreign matter.
6
The Kingspan System
KoolDuct Panel
47 ¼” (3.94 ft)
Printed foil
facing shall
be kept inside
ductwork
Silver
Black
(NOTE: The black faced KoolDuct is NOT part of the
UL listed duct system)
7
The Kingspan System
KoolDuct System Operational Limits
Not Applicable
• Where fire dampers cannot be used and fire rated ductwork must be used:
• Kitchen extract systems
• Smoke extractions of products of combustion
• Enclosed car park extract systems
• Pressurisation systems for protected staircase, lobby, corridors
• Conveyance of solid particles
• Chemical or fume exhaust systems (please check compatibility with Kingspan)
• For use with extreme heat above 185°F (85°C)
• High Pressure systems above 4.in.w.g. (1000 Pascal) positive
• Outdoor use without additional protection
8
The Kingspan System
Information Required for Fabrication and Installation
Information to be provided by the designer for the fabrication and installation of
KoolDuct pre-insulated ductwork
STANDARDS
• Insulation panel thickness
• Special requirements (if any)
PARTICULAR REQUIREMENTS
• Air leakage testing: leakage classification required and testing pressure
• Protective finishes (i.e. indoor / outdoor installation, etc.)
• Special supports (if any)
• Attachment to building structure: specific requirements for the junction of
ductwork to building openings
• Air terminal units: location
• Other requirements
9
The Kingspan System
Basic KoolDuct Fabrication Procedure
1. TRACING
2. CUTTING
3. ASSEMBLY:
• with Tiger Clips (for pressure classes up to 1000 Pascal) or
• with Adhesive (for pressure classes up to 750 Pascal)
4. TAPING
5. REINFORCING
6. COUPLING/JOINING
7. SEALING: with KoolDuct Silicone sealant.
8. FABRICATION INSPECTION
UL 181 A-P
Generous and
Listed Aluminum
continuous bead of
Tape at corners
Kingspan approved
where KoolDuct
silicone placed in
foil has been
ALL FOUR interior
cut.
joints extending for
full length of duct.
Factory applied
aluminum facings
on air stream and
exterior surfaces.
NO YES
10
The Kingspan System
Machine Cutting
Specific training to be provided by the manufacturer of the machine
CNC machine
11
The Kingspan System
Cutting - Jack Planes for 7/8” (22 mm) Panels, R-6
# 511 - Jack Plane, two blades at 45°
1” 1” 1”
2 3/8”
12
The Kingspan System
Cutting - Jack Planes for 1 3/16” (30 mm) Panels, R-8
# 516 - Jack Plane, two blades
Ref.514U - Small Jack Plane Ref.513U - Small Jack Plane Ref.515U - Small Jack Plane
45 Degrees Left 90 Degrees 45 Degrees Right
1 ¼” 1 ¼” 1 ¼”
2 ¾”
13
The Kingspan System
Assembly option 1 - Tiger Clips # 364
ALL duct sections MUST be assembled with Tiger Clips or Adhesive
Example 1: Duct 18” x 12”, at 2 in.w.g. Example 2: Duct 18” x 12”, at 4 in.w.g.
T. Closures only on the open mitred joints T. Closures on ALL the mitred joints
Max spacing: 20” Max spacing: 10”
Tiger Clips on folded mitre joints ONLY required if the alum. facing has cut or tears
14
The Kingspan System
Assembly option 2 – Adhesive # 212 (or spray)
ALL duct sections MUST be assembled with adhesive or Tiger Clips
Training Manual
Chapter 2
17
The Kingspan System
Straight Duct - Cutting METHOD 1
Cutting along the panel length
7/ 1 3/4” or 1 3/4” or 1 3/4” or 7/
8” or 8” or
1 3/16” H 2 3/
8”
W 2 3/
8”
H 2 3/
8”
W 1 3/16”
• 7/
8” R-6: The sum of 4 internal sides less than 40 ¼” (2H + 2W)
• 1 3/16” R-8: The sum of 4 sides less than 37 ¾“ (2H + 2W)
SEQUENCE OF
ASSEMBLY
Aluminum Tape
18
The Kingspan System
Straight Duct - Cutting METHOD 2
Cutting along the panel length
7/ 1 3/4” or 1 3/4” or 7/ 7/
8” or
7/
8” or 8” or 8” or
1 3/16” H 2 3/
8”
W 2 3/
8” H 1 3/16” 1 3/16” W 1 3/16”
47 ¼ “
• 7/
8” R-6: The sum of 3 sides less than 42” (2H + W or 2W + H)
• 1 3/16” R-8: The sum of 3 sides less than 40 1/8 ” (2H + W or 2W + H)
SEQUENCE OF
ASSEMBLY
19
The Kingspan System
Straight Duct - Cutting METHOD 3
Cutting along the panel length
7/ 1 3/4” or 7/ 7/ 1 3/4” or 7/
8” or 8” or 8” or 8” or
1 3/16” H 2 3/
8”
W 1 3/16” 1 3/16” H 2 3/
8”
W 1 3/16”
47 ¼ “ 47 ¼ “
• 7/
8” R-6: The sum of 2 sides less than 43 ¾“ (W + H)
• 1 3/16” R-8: The sum of 2 sides less than 42 ½“ (W + H)
SEQUENCE OF
ASSEMBLY
20
The Kingspan System
Straight Duct - Cutting METHOD 4
Cutting along the panel length
7/ 7/ 7/ 7/
8” or 7/
8” or 8” or 7/
8” or 8” or 7/
8” or 8” or 7/
8” or
1 3/16” H 1 3/16” 1 3/16” W 1 3/16” 1 3/16” H 1 3/16” 1 3/16” W 1 3/16”
47 ¼ ” 47 ¼ ” 47 ¼ ” 47 ¼ ”
• 7/
8” R-6: Each side less than 45 ½ “
• 1 3/16” R-8: Each side less than 44 7/8 “
NOTE
• When assembling the four sides, the duct should be checked (with the
T square rule) and held in position
21
The Kingspan System
Straight Duct - Cutting METHODS 5-8
Cutting along the panel width
• 7/
8” R-6: Width or Height more than 45 ½ “
• 1 3/16” R-8: Width or Height more than 44 7/8 “
H W H W
H W H W
Panel length
H W H W
Panel length
H W H W
Panel
length
22
The Kingspan System
Panel joint
Tiger Clips on external side
Adhesive
Tape
250
23
The Kingspan System
Multiple Duct Design
joint
when
Grip
Flange
is used
24
The Kingspan System
End Cap
Option 1: Short Duct or Plenum Option 2: Long Duct > 40”
Adhesive # 212
TClip # 364
Silicone
# 231G
Seal with silicone inside duct and End Cap Apply UL tape around End-Cap
25
The Kingspan System
Transition
W
W1
W1
W
A
A
Offset
W1
Angled Offset
W1
θ max. 15°(D ≥ 4 x A)
W
W
W
W
W
W
W
A
A
Mitred Offset
θ max. 30°(D ≥ 2 x A) Radius Offset
(B = 0.27 x W) θ max. 30°
(200mm Radius minimum)
26
The Kingspan System
Eccentric Transition
Minimum Neck size: 100 mm
Crease Outside
Crease Inside
Min
4” Crease Outside
Crease D
D Lines
• Dimensions in inches
• D minimum = 2.5 x (18”-12”) = 2.5 x 6” = 15”
27
The Kingspan System
Concentric Transition
Minimum Neck size: 100 mm
Crease Outside
Crease Inside
Crease Inside
Crease Outside
Cover
TH TH
12” 22”
Min 4”
Crease Outside
D Crease D
Lines
18”
• Dimensions in inches
• D minimum = 2.5 x 3” = 7 ½ ”
28
The Kingspan System
Double Offset
Minimum Neck size: 4”
TH TH
TH TH
29
The Kingspan System
Take-Off
Boot Branch
6 ¾”
# 512, # 519
Jack Plane 22.5º
4”
2½“
4” 2”
TH Jack Plane 22.5º
45.0° 5¾“
4”
W1=16” *
*Note 45.0°
W=12” W1 = W+1/4 W, min. 4” UL tape
UL tape
TH
10” 30
The Kingspan System
Small Take-Off – Un-flanged Connection
Duct side up to 24”, and Low Pressure up to 2 in.w.g.
Mechanical fix:
• 75mm (3”) from corners
• 300mm (12”) maximum intervals
“F” Profile
Take-off inside dim. – 6 mm
Silicone bead
around exterior
circumference
Mechanical Fix
for diam. larger than 12”
and/or Pressure > 2 in.w.g.
U profile U profile
33
The Kingspan System
Round Fitting for Round Diffusers and Flexible Ducts
Mechanical Fix required for diam. larger than 12” and/or Pressure > 2 in.w.g.
Round metal
fitting
with folding Round take off
tabs spigot with
spiral tube
34
The Kingspan System
Grille / Register / Diffuser Installation
with Aluminum Profile
“U” Profile
Clip Clip
“U” Profile
Grille / Grille /
Diffuser Diffuser
35
The Kingspan System
Square Elbow With Turning Vanes
Turning Vanes required when either duct dimension greater than 8”
(3 ½”)
1) The elbow top and bottom sides are cut in a
90° “L” shape
Cut vane
6 to 8mm less
than duct height
Reinforcing Bar
(2 3/8”)
Splitter
24” = W 6
1/3 W
ER=32” SR=16” = 8”
8” = IR 5
NECK
1/3 W 4” Min
= 8” 4
TH 24” = W 8” = IR 4” Min
1 2 3
37
The Kingspan System
Asymmetric Radius Elbow
NECK
TH
Splitter
18” = W2 4
ER=32”
1/3 W2
SR=16” = 6”
8” = IR 5
2”
6” 6
NECK
1/3 W1 7
4” Min
= 8”
LEGEND
TH = Panel Thickness
ER = External Radius
IR = Internal Radius (minimum 8”)
SR = Splitter Radius
• Dimensions in inches
• Numbers in the hoop show NOTE: Minimum Bend Radius: 8”
suggested tracing procedure Minimum Neck: 4”
38
The Kingspan System
Symmetric/Asymmetric Radius Elbow
45°taper
edges
toward air
stream
Ends of panels cut
square (90°)
Splitter fasten in
place with adhesive
(or Tiger Clips) and
silicone
39
The Kingspan System
Elbow assembly with Tiger Clips – # 364
Can be used instead of the Adhesive for duct assembly
Max TC Spacing
2”
40
The Kingspan System
Symmetric Elbow with Templates
B l A
Use the Elbow Template with side l required
l1
C E C
B l A B l A
1 - Use the Elbow Template with smaller 2 - Use the Elbow Template with bigger side
side l to trace the lines AB and BC l1 to trace the lines AD and DE
Splitter
SPLITTER
Elbow side (inches) Splitters Position
0 – 20” 0 -
20” – 32” 1 W/3
32” – 64” 2 W/4 W/2
Over 64” 3 W/8 W/3 W/2
Splitter not required in angles less than 45°:
SMACNA vane selection is also acceptable
42
The Kingspan System
Elbow, 45 Deg Throat, Radius Heel
Alternative Elbow Design
# 512, 519 Jack Plane 22.5 degrees
Clamp
Blades set 1/32” less than Panel ing
thickness Rule
2 ½”
2 ¾”
3 1/8” 3 1/8”
Cut 1:
Setup tool
Neck size +2 ¾“
from panel end
Cut 2
Setup tool
Throat size +2 ¾“ from
cut 1 centre
43
The Kingspan System
Dynamic Branch – “Y” branch with radius elbow
10
20”
NECK
NECK
Min 4”
4
ER = 32”
D
24”
2xTH 1/3 = 8”
8” = IR
2
NECK
1/3 Min 4”
= 6” 2”
1
3 minus 5
• Dimensions in inches
• Numbers in the hoop show suggested tracing procedure
• D minimum = 2.5 x (20”-16”) = 10”
44
The Kingspan System
Assembly Procedure
2 1 4 6
3
6
45
NECK NECK
TH
12” ER1
ER2
8
20” 3
2xTH
IR
The Kingspan
IR
2
Min 100
10
Min 4”
1
14 13 12 11 4 5 6 7
8 minus 11 3 minus 4
• Dimensions in inches
Dynamic Branch – Tee Branch (external sides flushed)
46
• Numbers in the hoop show suggested tracing procedure NOTE: Minimum Bend Radius: 8”
Minimum Neck: 4”
TH
8”
ER2 = 32” NECK
24”
ER2 = 24”
3
16”
8
1/3 2xTH
The Kingspan
= 8”
8” = IR
8” = IR
2 9
1/3
1” = 7” N
N
10
1
System
7 6 5 4 11 12 13 14
3 minus 4 8 minus 11
• Dimensions in inches
Dynamic Branch – Tee Branch (internal sides flushed)
47
• Numbers in the hoop show suggested tracing procedure NOTE: Minimum Bend Radius: 8”
Minimum Neck: 4”
ASSEMBLY PROCEDURE
4 7 8 3 2
The Kingspan
7
1
8
48
The Kingspan System
Training Manual
Chapter 3
Coupling Systems
for joining ductwork sections
49
The Kingspan System
4-Bolt Flange – # 380-385
Assembly
1) Cut flange 20mm (¾ “) short of the duct 2) For any Duct size: Add Tiger Units,
internal dimensions: one each side of each corner,
i.e. h - 20 mm (h – ¾ “) Total no.8 Tiger Units
w - 20mm (w – ¾ “)
50
The Kingspan System
4-Bolt Flange – # 380-385
Assembly
Tiger Unit
4-Bolt flange
4-Bolt flange
Screw
Tape
8) Detail
51
The Kingspan System
4 Bolt Flange – # 380-385
Coupling
A
Seal here
B
C
D Clip (not supplied by Kingspan)
• Attach gasket to one flange face. Attach in G-Clamp (not supplied by Kingspan)
one piece working around the corners.
• The preferred gasket shall be # 242
polyurethane 5/8” wide and 5/8” thick (15mm)
• Apply silicone to exposed corner edges
• Fit Bolts into the corner holes (loose bolts)
• If necessary align the corner holes by use of
the Joggle holes
• Insert Clamps or Clips in sufficient numbers
to ensure that there are no gaps in the seam
• Tighten Clamps or Clips - Suggested: at max
12” centres (300mm) about 3” (75 mm) from
corners
• Finally tighten the bolts
Silicone
52
The Kingspan System
Aluminum Grip Flange System
7/ 1 3/16” R-8
8” R-6
Internal Grip
for 1 3/16”
External h Grip h “Chair” Grip Flange
LKDA 317
# 314
53
The Kingspan System
Grip Flange System – 7/8” (22mm), R-6
May be used with pressure up to 2 in.w.g. (or Tiger Clip when possible)
Must be used with static pressure > 2 in.w.g. (or 4-Bolt flange)
Gasket
# 242
SUGGESTED GASKET
PU 5/8” x 5/8”
54
The Kingspan System
Grip Flange System – 1 3/16” (30 mm), R-8
May be used with pressure up to 2 in.w.g. (or Tiger Clip when possible).
Must be used with static pressure > 2 in.w.g. (or 4-Bolt flange)
EXPOSED INSULATION
Prior to insertion of the
R-8 Grip flange, the ends of
the duct section (or just the
corners) should be covered
with UL tape to seal the
External Grip
exposed insulation.
Internal Grip Flange, ref 312
Flange for R8,
ref 317
55
The Kingspan System
Grip Flange Assembly
Features:
• Positive air-tight joint on panels of varying thickness (¾” to 1” and 1 3/16” to 1 5/16”)
• No need of adhesive or rivets.
• Strengthen the ends of the duct
• Aerodynamic
Each dimension mark represents the centre line of a “V” 90° cut.
Fold the external male flange section at each cut to form a rectangular shape.
Installation:
All internal Grip (female) pieces are applied with light pressure until the total flange
assembly is formed. Only when one piece is properly engaged and correctly
positioned, it should be forced into the final locking grip using a rubber mallet.
V cut V cut
Straight cut
External joint
about centre of duct
Grip Notcher
# 451
Silicone
57
The Kingspan System
Duct-to-Duct Coupling
Aluminum Grip with Bayonet Cleat
Grip
Flange
58
The Kingspan System
Tiger Clip Coupling – # 364
LIMITATIONS:
• Low Pressure applications only (below 2 in.w.g)
STEP 1
Both ends of the KoolDuct duct must
be flat and perfectly squared
Aluminum tape is applied on
both ends of the duct segments.
STEP 2
Apply a continuous bead of
Kingspan approved silicone to one
end of one segment.
STEP 3
The two duct segments are joined together.
Tiger Clips (# 364) are placed on all four corners
of the duct
Tiger Clips (# 364) are placed on all four sides of
the duct. # 364
bent
STEP 4
Apply aluminum tape around the connection
of the two duct segments
59
The Kingspan System
Aluminum Flange Profiles
for Connection To Duct System Components
Example: h flange
60
The Kingspan System
Structural Aluminum Profiles
(Alternative to Grip for 7/8” R-6 KoolDuct only)
Adhesive inside
each profile
EXAMPLE:
STRUCTURAL
FLANGE
Aluminum Tape
on corners
Prior to insertion of the
Structural flanges, the
ends of the duct
section (both inner and
outer surfaces) should
be gently tapered
with the black Rigid
Spatula
Structural F # 332
Internal dim. – 1/8”
Adhesive inside
each profile
EXAMPLE:
“F” STRUCTURAL Aluminum Tape
FLANGE on corners
61
The Kingspan System
Connection To Duct System Components
Gasket
Gasket
Gasket Gasket
Bolt
Rivet
Flanged Connection using Spigotted Connection using
The 4 Bolt flange The 4 Bolt flange
62
The Kingspan System
Connection To a Fire Damper
with break-away joint
NOTE: The installation of fire dampers and their connection to ductwork fabricated
from the Kingspan KoolDuct system should always be in accordance with the building
regulations
63
The Kingspan System
Alternative Connection With Tiger Unit # 363
Low Pressure only ≤1 in.w.g.
UL TAPE FIRST
VCD
TIGER UNIT
After connection :
• Apply UL tape over Tiger Units KoolDuct
• Seal with sealant
FAN KoolDuct
COI
L
UNI
T
UL TAPE FIRST
TIGE
After connection : R
• Apply UL tape over Tiger Units UNIT
For any dimension of FCU • Seal with sealant DETAILED VIEW
65
The Kingspan System
Training Manual
Chapter 4
Duct Reinforcement
66
The Kingspan System
Duct Reinforcement
It is required to ensure that the true rectangular cross section of the duct is maintained.
Reinforcement Requirements
The ductwork may require reinforcement, check the following:
• Duct Size (both width and height must be evaluated)
• System Pressure inside ductwork (static plus dynamic)
Refer to the following Schedule.
Large Ductwork
For ductworks larger than those covered by the Schedule of duct reinforcement in this
manual, the Multiple Duct method of construction can be used, in this case each one of
the multiple smaller ductworks shall be reinforced independently.
67
The Kingspan System
Reinforcement System
Always install reinforcement for both Positive and Negative Pressure
KoolDuct Panel
Outer tube
(Negative Pressure) Reinforcement Disc #353
= Internal duct dim.
Inner tube
(Positive Pressure)
= External duct dim. + ½ “
KoolDuct Panel
Threaded rod
(Positive Pressure)
KoolDuct Panel
Threaded insert
Reinforcement Disc #353
Outer tube
(Negative Pressure)
68
The Kingspan System
Reinforcement System
Always install reinforcement for both Positive and Negative Pressure
Max
O.D I.D. Thickness
Alu Tube Length
mm mm mm
mm
Max
Rigid O.D I.D. Thickness
Length
Conduit mm mm mm
mm
1/2" 21.3 16.1 2.65 1320
Note on Reinforcing Bars for Negative Pressure: Max Length (L) established to limit the
compression stress to that associated with a Max Ratio of 200 L/rg
rg = Radius of Gyration
69
The Kingspan System
Reinforcement Application
Reinforcing Bars
Add reinforcement for each duct segment, based on duct size and pressure. Both
straight ductwork and fittings (e.g. elbows, transitions, etc.) shall be included in the
reinforcement procedure.
Flanged Joint
when required
Reinforcements Reinforcements
on the sides required on elbows, transition, tee, etc.
70
The Kingspan System
KoolDuct 7/8” (R-6) - Schedule of Duct Reinforcement
Grip flange and Bayonet Coupling
Max Duct
Pos Pressure
Duct Dimension segment Static Pressure Positive and Negative
only
length
inches inches 1/2 in.w.g. 1 in.w.g. 2 in.w.g. 3 in.w.g. 4 in.w.g.
4-8 154 3/4"
9 - 12 154 3/4" NO REINFORCEMENT
13 - 16 154 3/4"
19 - 20 154 3/4"
21 - 24 154 3/4" 1@36" 1@36"
NOTES
1 BAR CENTERED One Reinforcing Bar centered equal distance between joints
2@24" Reinforcing Bars shall be placed as a pair at a maximum of 24" centers, and
Aluminium Grip: FIRST and LAST pairs at MAX 12" FROM JOINT
3@24" Reinforcing Bars shall be placed as a trio at a maximum of 24" centers, and
Aluminium Grip: FIRST and LAST trio at MAX 12" FROM JOINT
71
The Kingspan System
KoolDuct 7/8” (R-6) - Schedule of Duct Reinforcement
4-Bolt Coupling
Max Duct
Pos Pressure
Duct Dimension segment Static Pressure Positive and Negative
only
length
1/2 in.w.g. 1 in.w.g. 2 in.w.g. 3 in.w.g. 4 in.w.g.
4-8 154 3/4"
9 - 12 154 3/4" NO REINFORCEMENT
13 - 16 154 3/4"
19 - 20 154 3/4"
21 - 24 154 3/4" 1@36" 1@36"
NOTES
1 BAR CENTERED One Reinforcing Bar centered equal distance between joints
2 BARS CENTERED Two Reinforcing Bars centered equal distance between joints
2@24" Reinforcing Bars shall be placed as a pair at a maximum of 24" centers, and
4-Bolt Flange: FIRST and LAST pairs at MAX 12" FROM JOINT
3@24" Reinforcing Bars shall be placed as a trio at a maximum of 24" centers, and
4-Bolt Flange: FIRST and LAST trio at MAX 12" FROM JOINT 72
The Kingspan System
KoolDuct 7/8” (R-6) - Schedule of Duct Reinforcement
Tiger Clip Coupling
Max Duct
Pos Pressure
Duct Dimension segment Static Pressure Positive and Negative
only
length
1/2 in.w.g. 1 in.w.g. 2 in.w.g. 3 in.w.g. 4 in.w.g.
4-8 154 3/4"
9 - 12 154 3/4" NO REINFORCEMENT NOT APPLICABLE
13 - 16 154 3/4"
19 - 20 154 3/4"
21 - 24 154 3/4" 1@Joint
61 - 64 47 1/4"
65 - 68 47 1/4"
69 - 72 47 1/4" NOT APPLICABLE
73 - 76 47 1/4"
79 - 80 47 1/4"
Over 2000
NOTES
73
The Kingspan System
KoolDuct 1 3/16" (R-8) - Schedule of Duct Reinforcement
Grip flange and Bayonet Coupling
Max Duct
Pos Pressure
Duct Dimension segment Static Pressure Positive and Negative
only
length
1/2 in.w.g. 1 in.w.g. 2 in.w.g. 3 in.w.g. 4 in.w.g.
4-8 154 3/4"
9 - 12 154 3/4" NO REINFORCEMENT
13 - 16 154 3/4"
19 - 20 154 3/4"
21 - 24 154 3/4" 1@36" 1@36"
NOTES
1 BAR CENTERED One Reinforcing Bar centered equal distance between joints
2@24" Reinforcing Bars shall be placed as a pair at a maximum of 24" centers, and
Aluminium Grip: FIRST and LAST pairs at MAX 12" FROM JOINT
3@24" Reinforcing Bars shall be placed as a trio at a maximum of 24" centers, and
Aluminium Grip: FIRST and LAST trio at MAX 12" FROM JOINT
74
The Kingspan System
KoolDuct 1 3/16" (R-8) - Schedule of Duct Reinforcement
4-Bolt Coupling
Max Duct
Pos Pressure
Duct Dimension segment Static Pressure Positive and Negative
only
length
inches inches 1/2 in.w.g. 1 in.w.g. 2 in.w.g. 3 in.w.g. 4 in.w.g.
4-8 154 3/4"
9 - 12 154 3/4" NO REINFORCEMENT
13 - 16 154 3/4"
19 - 20 154 3/4"
21 - 24 154 3/4" 1@36" 1@36"
NOTES
1 BAR CENTERED One Reinforcing Bar centered equal distance between joints
2 BARS CENTERED Two Reinforcing Bars centered equal distance between joints
2@24" Reinforcing Bars shall be placed as a pair at a maximum of 24" centers, and
4-Bolt Flange: FIRST and LAST pairs at MAX 12" FROM JOINT
3@24" Reinforcing Bars shall be placed as a trio at a maximum of 24" centers, and
4-Bolt Flange: FIRST and LAST trio at MAX 12" FROM JOINT
75
The Kingspan System
KoolDuct 1 3/16" (R-8) - Schedule of Duct Reinforcement
Tiger Clip Coupling
Max Duct
Pos Pressure
Duct Dimension segment Static Pressure Positive and Negative
only
length
1/2 in.w.g. 1 in.w.g. 2 in.w.g. 3 in.w.g. 4 in.w.g.
4-8 154 3/4"
9 - 12 154 3/4" NO REINFORCEMENT NOT APPLICABLE
13 - 16 154 3/4"
19 - 20 154 3/4"
21 - 24 154 3/4"
25 - 28 154 3/4" 1@Joint
61 - 64 47 1/4"
65 - 68 47 1/4"
69 - 72 47 1/4" NOT APPLICABLE
73 - 76 47 1/4"
79 - 80 47 1/4"
Over 2000
NOTES
76
The Kingspan System
Duct Reinforcement
Examples
Reinforcements Reinforcements
R-6 with Grip flange and bayonet joint: R-6 with 4-Bolt flange :
Side 40”: 1@36”, bar max 18” from flange Side 40”: 1@36”, bar max 36” from flange
Side 20”: No reinforcement Side 20”: No reinforcement
R-8 with Grip flange and bayonet joint: R-8 with 4-Bolt flange
Side 68”: 2@24”, bar max 12” from flange Side 68”: 2 Centered
Side 48”: 1 Centered Side 48”: 1 Centered
77
The Kingspan System
Non-standard reinforcement
Where the standard reinforcing bars cannot be installed:
• top of a large square elbow
• where a large branch takes off from a large duct
• large end cap.
Reinforcing Disc
Reinforcing Channel
min 1 5/8” x 13/16 “ (40x20mm)
min 16 gage (1.5mm thick)
78
The Kingspan System
Training Manual
Chapter 5
79
The Kingspan System
Hangers and Supports - Ductwork
KoolDuct ductwork installed according to the principals of HVCA DW/144 Chapter
6 or SMACNA HVAC Duct Construction Standard Chapter 5
Tiger
Support
Washer
Nut
The selection of all supports and hangers shall be based on the weight of KoolDuct
ductwork, according to the recommendations of the support/hanger manufacturer.
See tables Weight of KoolDuct.
80
The Kingspan System
Horizontal Ductwork - Max Spacing Between Supports
Note: Closer spacing may be required due to limitations of the building structure or to
achieve the necessary duct rigidity
Note: When available, please follow the specific recommendations of the hanger
Manufacturer
81
The Kingspan System
Hangers and Supports – Hanging Duct Fittings
The KoolDuct System is light weight, so duct support and hangers do not have to
be as robust nor as numerous as with sheet metal ducts.
Max 600mm
24”
82
The Kingspan System
Hangers and Supports – Vertical Ductwork
KoolDuct
KoolDuct
Strut channel
Tiger Supports at every
corner of the duct
Threaded bar
Option 2
Note that the couplings of ductwork fabricated from the Kingspan KoolDuct system are
NOT designed to take the vertical load of ductwork.
83
The Kingspan System
Hangers and Supports – Vertical Ductwork
WEIGHT OF KOOLDUCT
The weight of the ductwork section shall always be independently determined by the
Trained Fabricator / Installer, and the appropriate gauge of supports and hanger
chosen in accordance with the relevant manufacturer's guidelines.
84
The Kingspan System
Hangers and Supports – Weight of KoolDuct 7/8” R-6
7/8" R-6 KoolDuct
Weight in [lbs per foot length] depending on width / height
Duct connecting joint : 4 BOLT FLANGE
Width (inch)
8" 12" 16" 20" 24" 28" 32" 36" 40" 44" 48" 52" 56" 60" 64" 68" 72" 76" 80"
8" 1.5 1.8 2.0 2.3 2.6 2.8 3.2 3.5 3.8 4.0 5.8 6.2 6.6 7.0 7.4 7.8 8.2 8.5 8.9 8"
12" 2.0 2.3 2.6 2.8 3.1 3.5 3.8 4.0 4.3 6.2 6.6 7.0 7.3 7.8 8.2 8.6 8.9 9.3 12"
16" 2.6 2.8 3.1 3.4 3.8 4.1 4.3 4.6 6.6 7.0 7.4 7.7 8.2 8.6 9.0 9.4 9.7 16"
Height (inch)
20" 3.1 3.4 3.7 4.1 4.4 4.6 4.9 7.0 7.4 7.8 8.1 8.6 9.0 9.4 9.8 10.1 20"
24" 3.7 3.9 4.4 4.6 4.9 5.2 7.4 7.8 8.2 8.5 9.0 9.4 9.8 10.2 10.5 24"
28" 4.2 4.7 4.9 5.2 5.5 7.8 8.2 8.5 8.9 9.5 9.8 10.2 10.6 10.9 28"
32" 5.2 5.5 5.7 6.0 8.2 8.6 8.9 9.3 9.9 10.2 10.6 11.0 11.4 32"
Height (inch)
36" 5.7 6.0 6.3 8.6 8.9 9.3 9.7 10.3 10.6 11.0 11.4 11.8 36"
40" 6.3 6.6 9.0 9.3 9.7 10.1 10.7 11.0 11.4 11.8 12.2 40"
44" 6.9 9.4 9.7 10.1 10.5 11.1 11.5 11.8 12.2 12.6 44"
10.0 10.4 10.8 11.2 11.8 12.2 12.6 13.0 13.4 48"
Weight based on 12.9 ft long ducts 10.8 11.2 11.6 12.2 12.6 13.0 13.4 13.8 52"
KoolDuct panel weight 0.34 lbs/ft2 11.6 11.9 12.6 13.0 13.4 13.8 14.2 56"
Reinforcement based on low pressure (2 in.w.g Pascal) 12.3 13.0 13.4 13.8 14.2 14.6 60"
13.7 14.1 14.6 15.0 15.4 64"
14.6 15.0 15.4 15.8 68"
15.4 15.8 16.2 72"
Weight based on 4 ft long ducts 16.2 16.6 76"
Reinforcement based on low pressure (2 in.w.g.) 17.0 80"
20" 3.0 3.2 3.5 4.0 4.2 4.5 4.7 6.5 6.8 7.2 7.5 8.1 8.5 8.8 9.2 9.5 20"
24" 3.5 3.8 4.3 4.5 4.8 5.0 6.9 7.2 7.6 7.9 8.5 8.9 9.2 9.6 9.9 24"
28" 4.0 4.5 4.8 5.1 5.3 7.3 7.6 8.0 8.3 9.0 9.3 9.6 10.0 10.3 28"
32" 5.0 5.3 5.5 5.8 7.7 8.0 8.4 8.7 9.4 9.8 10.1 10.4 10.8 32"
Height (inch)
36" 5.6 5.8 6.1 8.1 8.4 8.7 9.1 9.8 10.2 10.5 10.8 11.2 36"
40" 6.1 6.4 8.4 8.8 9.1 9.5 10.2 10.6 10.9 11.3 11.6 40"
44" 6.7 8.8 9.2 9.5 9.8 10.6 11.0 11.3 11.7 12.0 44"
9.2 9.6 9.9 10.3 11.1 11.4 11.8 12.1 12.5 48"
Weight based on 12.9 ft long ducts 9.9 10.3 10.6 11.5 11.8 12.2 12.5 12.9 52"
KoolDuct panel weight 0.34 lbs/ft2 10.7 11.0 11.9 12.3 12.6 12.9 13.3 56"
Reinforcement based on low pressure (2 in.w.g Pascal) 11.4 12.3 12.7 13.0 13.3 13.7 60"
12.8 13.2 13.5 13.8 14.2 64"
13.6 13.9 14.2 14.6 68"
14.3 14.7 15.0 72"
Weight based on 4 ft long ducts 15.1 15.4 76"
Reinforcement based on low pressure (2 in.w.g.) 15.8 80"
20" 2.6 2.9 3.1 3.5 3.7 4.0 4.2 4.5 4.8 5.0 5.2 n.a. n.a. n.a. n.a. n.a. 20"
24" 3.2 3.4 3.8 4.0 4.3 4.5 4.8 5.0 5.3 5.5 n.a. n.a. n.a. n.a. n.a. 24"
28" 3.6 4.1 4.3 4.5 4.8 5.1 5.3 5.5 5.8 n.a. n.a. n.a. n.a. n.a. 28"
32" 4.5 4.8 5.0 5.3 5.6 5.8 6.1 6.3 n.a. n.a. n.a. n.a. n.a. 32"
Height (inch)
36" 5.0 5.3 5.5 5.9 6.1 6.3 6.6 n.a. n.a. n.a. n.a. n.a. 36"
40" 5.5 5.8 6.1 6.4 6.6 6.9 n.a. n.a. n.a. n.a. n.a. 40"
44" 6.0 6.6 6.9 7.2 7.4 n.a. n.a. n.a. n.a. n.a. 44"
6.9 7.2 7.4 7.7 n.a. n.a. n.a. n.a. n.a. 48"
Weight based on 12.9 ft long ducts 7.4 7.7 8.0 n.a. n.a. n.a. n.a. n.a. 52"
KoolDuct panel weight 0.34 lbs/ft2 7.9 8.2 n.a. n.a. n.a. n.a. n.a. 56"
Reinforcement based on low pressure (2 in.w.g Pascal) 8.5 n.a. n.a. n.a. n.a. n.a. 60"
n.a. n.a. n.a. n.a. n.a. 64"
n.a. n.a. n.a. n.a. 68"
n.a. n.a. n.a. 72"
Weight based on 4 ft long ducts n.a. n.a. 76"
Reinforcement based on low pressure (1 in.w.g.) n.a. 80"
85
The Kingspan System
Hangers and Supports – Weight of KoolDuct 1 3/16” R-8
1 3/16" R-8 KoolDuct
Weight in [lbs per foot length] depending on width / height
Duct connecting joint : 4 BOLT FLANGE
Width (inch)
8" 12" 16" 20" 24" 28" 32" 36" 40" 44" 48" 52" 56" 60" 64" 68" 72" 76" 80"
8" 1.9 2.3 2.6 2.9 3.3 3.6 4.0 4.4 4.7 5.1 6.9 7.4 7.8 8.2 8.7 9.2 9.6 10.1 10.5 8"
12" 2.6 2.9 3.3 3.6 3.9 4.4 4.7 5.1 5.4 7.4 7.8 8.3 8.7 9.1 9.7 10.1 10.6 11.0 12"
16" 3.3 3.6 3.9 4.3 4.8 5.1 5.4 5.8 7.8 8.3 8.7 9.2 9.6 10.2 10.6 11.0 11.5 16"
Height (inch)
20" 3.9 4.3 4.6 5.1 5.4 5.8 6.1 8.3 8.7 9.2 9.6 10.1 10.6 11.1 11.5 11.9 20"
24" 4.6 5.0 5.5 5.8 6.1 6.5 8.8 9.2 9.6 10.1 10.5 11.1 11.5 12.0 12.4 24"
28" 5.3 5.8 6.2 6.5 6.8 9.2 9.6 10.1 10.5 11.0 11.6 12.0 12.4 12.9 28"
32" 6.4 6.7 7.1 7.5 9.7 10.1 10.5 11.0 11.4 12.0 12.5 12.9 13.3 32"
Height (inch)
36" 7.1 7.5 7.8 10.1 10.6 11.0 11.4 11.9 12.5 12.9 13.4 13.8 36"
40" 7.8 8.2 10.6 11.0 11.5 11.9 12.3 13.0 13.4 13.9 14.3 40"
44" 8.5 11.0 11.5 11.9 12.3 12.8 13.4 13.9 14.3 14.8 44"
11.7 12.2 12.6 13.1 13.5 14.3 14.7 15.2 15.6 48"
Weight based on 12.9 ft long ducts 12.6 13.1 13.5 14.0 14.7 15.2 15.6 16.1 52"
KoolDuct panel weight 0.44 lbs/ft2 13.5 14.0 14.5 15.2 15.6 16.1 16.6 56"
Reinforcement based on low pressure (2 in.w.g Pascal) 14.5 14.9 15.7 16.1 16.6 17.0 60"
15.4 16.1 16.6 17.0 17.5 64"
16.9 17.4 17.9 18.4 68"
17.9 18.4 18.8 72"
Weight based on 4 ft long ducts 18.8 19.3 76"
Reinforcement based on low pressure (2 in.w.g.) 19.8 80"
20" 3.9 4.2 4.5 5.0 5.4 5.7 6.0 7.7 8.1 8.5 9.0 9.5 10.1 10.5 10.9 11.3 20"
24" 4.5 4.9 5.4 5.7 6.1 6.4 8.1 8.5 8.9 9.5 9.9 10.6 11.0 11.4 11.8 24"
28" 5.2 5.8 6.1 6.4 6.7 8.5 8.9 9.4 9.9 10.3 11.1 11.5 11.9 12.3 28"
32" 6.3 6.6 7.0 7.3 9.0 9.4 9.8 10.4 10.8 11.6 12.0 12.4 12.8 32"
Height (inch)
36" 7.0 7.3 7.7 9.4 9.8 10.2 10.8 11.3 12.1 12.5 12.9 13.3 36"
40" 7.7 8.0 9.9 10.3 10.7 11.3 11.7 12.5 12.9 13.3 13.8 40"
44" 8.4 10.3 10.7 11.1 11.7 12.1 13.0 13.4 13.8 14.2 44"
10.7 11.1 11.5 12.2 12.6 13.5 13.9 14.3 14.7 48"
Weight based on 12.9 ft long ducts 11.5 11.9 12.6 13.0 14.0 14.4 14.8 15.2 52"
KoolDuct panel weight 0.44 lbs/ft2 12.4 13.1 13.5 14.4 14.8 15.2 15.6 56"
Reinforcement based on low pressure (2 in.w.g Pascal) 13.5 13.9 14.9 15.3 15.8 16.2 60"
14.4 15.4 15.8 16.2 16.6 64"
16.0 16.4 16.8 17.2 68"
16.9 17.3 17.7 72"
Weight based on 4 ft long ducts 17.7 18.2 76"
Reinforcement based on low pressure (2 in.w.g.) 18.6 80"
20" 3.5 3.8 4.1 4.5 4.8 5.1 5.4 5.8 6.1 6.4 6.7 n.a. n.a. n.a. n.a. n.a. 20"
24" 4.0 4.4 4.9 5.1 5.4 5.7 6.2 6.5 6.8 7.1 n.a. n.a. n.a. n.a. n.a. 24"
28" 4.7 5.2 5.5 5.8 6.1 6.5 6.8 7.1 7.4 n.a. n.a. n.a. n.a. n.a. 28"
32" 5.8 6.1 6.4 6.7 6.8 7.1 7.4 7.7 n.a. n.a. n.a. n.a. n.a. 32"
Height (inch)
36" 6.4 6.7 7.0 7.4 7.7 8.0 8.3 n.a. n.a. n.a. n.a. n.a. 36"
40" 7.0 7.3 7.7 8.0 8.3 8.7 n.a. n.a. n.a. n.a. n.a. 40"
44" 7.6 8.3 8.6 9.0 9.3 n.a. n.a. n.a. n.a. n.a. 44"
8.6 9.0 9.3 9.6 n.a. n.a. n.a. n.a. n.a. 48"
Weight based on 12.9 ft long ducts 9.3 9.6 10.0 n.a. n.a. n.a. n.a. n.a. 52"
KoolDuct panel weight 0.44 lbs/ft2 9.9 10.3 n.a. n.a. n.a. n.a. n.a. 56"
Reinforcement based on low pressure (2 in.w.g Pascal) 10.6 n.a. n.a. n.a. n.a. n.a. 60"
n.a. n.a. n.a. n.a. n.a. 64"
n.a. n.a. n.a. n.a. 68"
n.a. n.a. n.a. 72"
Weight based on 4 ft long ducts n.a. n.a. 76"
Reinforcement based on low pressure (1 in.w.g.) n.a. 80"
86
The Kingspan System
Training Manual
Chapter 6
87
The Kingspan System
Cleaning KoolDuct
KoolDuct ductwork shall be cleaned in accordance to the Guide of Good Practice
HVCA TR/19 or NADCA. Dry Cleaning and non-abrasive methods only :
Mechanical
Air Whip/Skipper Ball (A) Low volume Directional jet nozzle on the
- plastic ball only compressed air end of a flexible hose
Air Lance (A) Low volume Air gun with a trigger to direct
compressed air compressed air locally
Manual
Hand Wipe Manual Wiping of duct surface
Where Note (A) appears, particulates should be collected using an air movement and
containment machine with appropriate filtration for contaminants.
KoolDuct is unsuitable for Wet Cleaning methods and any technique considered to
be abrasive such as hard brushing, scraping or high pressure systems.
88
The Kingspan System
Building Management Systems
Building Management Systems include sensors / controllers that may need to be
installed inside/outside the ductwork to monitor temperature, pressure and other
parameter of the HVAC system.
These sensors / controllers typically have a mounting plate with mounting holes
and are fixed to steel ductwork using screws.
A hole is also drilled into the ductwork to allow the insertion of the measuring
probe.
With ductwork fabricated from the KoolDuct system, a protective metal plate
needs to be installed inside the ductwork using adhesive/sealant before the
sensor / controller is fixed to the outside KoolDuct ductwork wall, so that the
insulating panel is protected by the sandwich type of installation - mounting plate
outside KoolDuct, metal plate inside KoolDuct.
Once the protective metal plate is installed, standard fixing operation can follow
(e.g. drilling, fixing screws).
In case the sensor / controller needs to be installed after the duct is already in
place, an access door will be required on KoolDuct, to allow the above mentioned
installation.
89
The Kingspan System
Damage Repair
Superficial damage can be repaired with UL tape only
More substantial damage can be cut out and replaced.
Silicone # 231G
Aluminum Tape
90
The Kingspan System
Protective treatment and External ductwork
Internal Installation
No special treatment required for conventional internal installations
External Installation
Ductwork subjected to the elements must be weather proofed.
Kingspan preferred finishes should be applied in factory controlled conditions and shall
be either
The chosen finish shall be installed in accordance with the manufacturer’s instructions
Note that all external couplings must be fully sealed.
Painting
Kingspan KoolDuct System can be painted for decorative purposes with paint that it is
compatible with aluminum.
Please bear in mind the project specification with regards to fire performance
requirements of the duct when selecting the paint.
Note: that paint is not an acceptable weatherproof solution for external installations
91
The Kingspan System
Training Manual
Appendixes
92
The Kingspan System
Appendix 1
93
The Kingspan System
94
The Kingspan System
95
The Kingspan System
96
The Kingspan System
97
The Kingspan System
98
The Kingspan System
99
The Kingspan System
100
The Kingspan System
101
The Kingspan System
102
The Kingspan System
103
The Kingspan System
104
The Kingspan System
Appendix 2
105
The Kingspan System
106
The Kingspan System
107
The Kingspan System
108
The Kingspan System
Appendix 3
Commissioning
109
The Kingspan System
Appendix 3
110
The Kingspan System
Bibliografy
The Kingspan KoolDuct System
Kingspan Insulation, The Kingspan KoolDuct System - Fabrication Manual
Kingspan Insulation, The Kingspan KoolDuct System - A Specifier’s Guide
Kingspan Insulation, The Kingspan KoolDuct System – Technical Data Sheet
Kingspan Insulation,Technical Note, Ductwork Commissioning And Testing
HVAC Ductwork
ASHRAE Handbook, HVAC Systems, Chapter 18 “Duct Construction”, 2008
ASHRAE Handbook, Fundamentals, Chapter 21 “Duct Design”, 2009
BESA, DW /144 - Specification for Sheet Metal Ductwork, 2013
BESA, DW /143 - Specification for Ductwork Leakage Testing, 2000
BESA TR19 Internal Cleanliness of Ventilation Systems, 2013
BSRIA, Commissioning Air Systems, 2013
BSRIA, Structural Fixings for Ductwork Systems, 2010
CIBSE Guide B2-Ventilation and Ductwork, 2016
NADCA – Introduction to HVAC systems cleaning services, 2005
NADCA – Assessment cleaning and restoration of HVAC systems, 2006
SMACNA - HVAC Systems Duct Design, 2006
SMACNA - HVAC Duct Construction Standards, Metal and flexible, 2005
SMACNA - HVAC Air Duct Leakage Test Manual, 2012
SMACNA – Phenolic Duct Construction Standards, 2015
TIMSA TGN3 - Thermal Insulation of H & V Ductwork, 1998
Standards
ANSI/ASHRAE/IES Standard 90.1, Chapter 6 “Heating, Ventilating, and Air
Conditioning”, 2010
BS EN 13403 - Ventilation for Buildings - Non-metallic ducts - Ductwork made from
insulation ductboards
BS EN 12097 - Ventilation for buildings - Ductwork - Requirements to facilitate
maintenance (access panels and openings)
BS EN 15780 - Ventilation for buildings - Ductwork - Cleanliness of ventilation systems
BS 9999 - Fire precautions - Air-Conditioning Ductwork
IECC - International Energy Conservation Code, 2012
IMC - International Mechanical Code, Chapter 6 “Duct Systems”, 2012
NFPA 90A - Standard for the Installation of Air-Conditioning and Ventilating Systems
NFPA 90B - Standard for the Installation of Warm Air Heating and Air-Conditioning
Systems
UL 181 – Standard for Safety - Factory-Made Air Ducts and Air Connectors, 2013
111
Using unsuitable cleaning methods on Kingspan KoolDuct panels can result in severe damage to the integrity and performance of the ductwork. Improper cleaning can introduce moisture, leading to potential degradation of the panels, which are not designed to be used once they have become wet . There is also a risk of damage to the aluminum facings, adversely affecting the insulating properties of the panels . Adherence to recommended practices is critical as it ensures that the panels maintain their specified performance characteristics, such as thermal insulation and structural integrity, and prevents breaches that could result in air leakage or inefficiencies in HVAC systems . This adherence is crucial since the system requires specific materials and methods for installation, like silicone sealants and aluminum foil, which need to be maintained correctly to ensure long-term effectiveness .
When using the Kingspan System 72 KoolDuct, reinforcing bars must be installed for both positive and negative pressure applications. The requirements for reinforcing bars depend on the duct size, static pressure levels, and specific construction details. For ducts under 24 inches in any dimension, panels are used as reinforcement under negative pressure. For larger ductworks, reinforcement is essential to maintain the true rectangular section and prevent any compromise in duct integrity due to overpressure . Reinforcements are placed according to a schedule that considers static pressure and duct dimensions . For instance, at higher static pressures, reinforcing bars are placed at more frequent intervals, such as at 24 or 36-inch centers, depending on duct width and height . Reinforcement is also crucial in sections such as elbows and transitions and must accommodate system-specific requirements, like pressure levels of up to 4 in.w.g. for positive pressure and up to 3 in.w.g. for negative pressure ."}
Duct width significantly impacts the weight of KoolDuct panels, as it directly influences the amount of material used in fabrication. For instance, weight calculations for KoolDuct panels show that wider ducts result in heavier installations, requiring adaptations in support strategy . Specific support systems like metal channels or Tiger supports, depending on duct size, are necessary to properly manage and distribute the weight of the installed ductwork . Wider duct installations might also demand closer spacing between supports and additional reinforcement to maintain structural integrity while minimizing loading on the KoolDuct system . This affects the installation and support strategy by necessitating tailored support and hanger designs according to duct width and installation specifics . Moreover, KoolDuct's lightweight nature compared to conventional ductwork influences the need for less robust supports but requires careful planning to avoid overloading the system .
When installing sensors in the KoolDuct system, it's essential to protect the insulating panels. Installation requires a protective metal plate to be installed inside the ductwork to prevent damage. The sensors, which include temperature and pressure monitors, are mounted on the duct exterior using adhesives and sealants. Holes must be drilled into the duct for probe insertion, emphasizing minimal impact on the structural integrity and thermal efficiency of the KoolDuct panels .
KoolDuct panel weights vary based on the dimensions and pressure specifications. For different duct sizes and thicknesses, panels typically weigh 0.34 lbs/ft² for a 7/8" R-6 panel and 0.44 lbs/ft² for a 1 3/16" R-8 panel . The weight implications for installation are significant, as KoolDuct panels are lighter than traditional sheet metal ductwork, which means less robust supports are needed, reducing installation complexity and time . For instance, a duct size of 48 inches with a standard 7/8" R-6 panel weighs about 9.9 lbs per foot length for a 12.9-foot duct . Therefore, lighter ductwork facilitates easier handling and potentially lower labor costs . However, despite being lightweight, careful attention must be paid to ensure proper supports and hangers are in place, as specified by manufacturers, to maintain the integrity of the duct system .
For maintaining the Kingspan KoolDuct System, cleaning methods that focus on minimizing damage to the duct surface are recommended. Wet cleaning methods should generally be avoided, as the KoolDuct panels and ductwork sections should not be allowed to get wet due to potential deterioration of the panels' aluminum facings and because the factory-applied packaging is not weatherproof . Additionally, abrasive cleaning methods may damage the silver aluminum foil facings, and hence, these should also be avoided to maintain the structural integrity and surface finish of the KoolDuct panels . Thus, maintenance should focus on dry cleaning methods that are gentle on the ductwork surfaces while still effectively removing dust and other dry contaminants.
For ducts up to 36 inches in size, the reinforcement strategy involves placing reinforcing bars at specified intervals, typically 36 inches, with bars positioned at the joint and spaced at 24 inches for additional segments as necessary, depending on pressure requirements . In contrast, for ducts over 36 inches, the reinforcement is more rigorous, requiring reinforcing bars at 24 inches apart and sometimes in multiple configurations like pairs or trios depending on the pressure and specific installation needs . The methodology includes using aluminum tubes or threaded rods, considering both positive and negative pressure scenarios, with specific attention to placement at joints and particular duct designs like elbows .
Static pressure significantly influences the reinforcement strategy for duct systems using Kingspan products. For instance, at lower pressures like 1/2 in.w.g., smaller ducts such as those under 12 inches often do not require reinforcement . As the static pressure increases, more reinforcement becomes necessary. For example, at 4 in.w.g., ducts over 28 inches may require multiple reinforcing bars centered or placed at 36-inch intervals to ensure structural integrity and meet safety standards . The reinforcement patterns are designed to counteract the forces exerted by higher static pressures, thus securing the ductwork structure .
The Kingspan KoolDuct system adapts duct segment lengths to ensure proper reinforcement under varying static pressures through specific reinforcement techniques. For duct sizes and pressures, both positive and negative, reinforcement is required to maintain a stable rectangular cross-section of the duct . Reinforcement methods include aluminum tubes encased tubes with discs and bolts for both positive and negative pressures . The maximum duct segment lengths for either pressure condition are specified with reinforcement often required at the joint and then at intervals determined by the static pressure, such as 1@24" or 1@36" . Larger duct segments or those facing pressures beyond typical reinforcement schedules might require custom reinforcement designed to suit specific applications or pressures . For segments that exceed standard lengths, a multiple duct design may be implemented where each smaller segment is reinforced independently .
The Kingspan KoolDuct system recommends using adhesive or sealant for sensor installation to ensure a protective and secure setup. Adhesive or sealant is used to install a protective metal plate inside the ductwork. This setup protects the insulating panel by creating a sandwich-like installation with the mounting plate outside and the metal plate inside the ductwork, which allows for standard fixing operations such as drilling and screwing without damaging the insulation . Additionally, this method ensures the integrity and performance of the ductwork by preventing air and moisture infiltration, which is crucial for maintaining the duct's insulation properties .