unit 1-5
unit 1-5
PROTECTION AND
SWITCHGEAR
SYLLABUS
TEXT AND REFERENCE BOOKS
INTRODUCTION
• Switching device: opening/closing and protective device: over-
current protection
• What is “Switchgear”?
• For all types of faults the sequence network equations will be the
same but the 3 equations describing the boundary conditions will
be different for different types of faults
• Sequence Networks of Transmission lines
• Sequence Networks of Loads
• Sequence Networks of Transformers
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
• Single Line to Ground Fault
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
• A 25 MVA, 13.2 KV alternator with solidly grounded neutral
has a sub-transient reactance of 0.25 p.u. The negative and
zero sequence reactances are 0.35 and 0.1 p.u. respectively. A
SLG/LL/LLG fault occurs at the terminals of an unloaded
alternator; determine the fault current and line-to-line
voltages. Neglect resistance.
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
• Line to Line Fault
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
• Double Line to Ground Fault
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
• Three Phase Fault (Symmetrical Fault)
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
• Conclusion:
1. Positive sequence currents are present in ALL types of faults
2. Negative sequence currents are present in ALL
Unsymmetrical faults
3. Zero sequence currents are present when the neutral of the
system is grounded and the fault also involves ground, the
magnitude of neutral current is 3Ia0
POWER SYSTEM GROUNDING OR
EARTHING
• The process of connecting the metallic frame (non-current carrying
part) of electrical equipment or some electrical part of the system
(neutral point) to earth (soil) is called “Grounding” or “Earthing”
• Connection to earth may be through a conductor or some other
circuit elements (resistor, CB) depending upon the situation.
• Advantages :
1. Protection to power systems
2. Ensures the safety of the persons handling the equipment
• Grounding or earthing may be classified as
(i) Equipment grounding
(ii) System (Neutral) grounding
UNGROUNDED NEUTRAL SYSTEM
• It can be seen that 3 phase faults have a more effect on the system
and they must be cleared faster than the SLG fault
• Relays should not be made extremely fast (<10 msec), because
when there is any lightning surge on the line, surge diverters must
have sufficient time to discharge the lightning to ground, otherwise
the relay will operate unnecessarily for transient conditions
ESSENTIAL QUALITIES OF PROTECTION
6. Discrimination: A relay should be able to distinguish
between a fault and an overload. In case of transformers
inrush of magnetizing current (5 to 7 times full load current)
may be comparable to fault current. The relay should not
operate for inrush currents.
• In interconnected systems, there will be power swings,
which should also be ignored by the relay. The discrimination
may either be an inherent characteristic of relay or may be
achieved by connecting auxiliary devices (minimum voltage
relay). It may be noted that the word ‘discrimination’ is
sometimes used to include ‘selectivity’
PROTECTION SCHEMES
• Protective scheme comprises set of ‘protective
systems’ and the protection schemes are named
according to the protected equipment. For example,
– Generator protection (scheme)
– Transformer protection (scheme)
– Motor protection (scheme)
– Bus bar protection (scheme)
• The term ‘protective system’ or simply ‘protection’ is
also named according to the principle of operation
or abnormal condition
PROTECTION SCHEMES
• Names based on abnormal condition:
– Over-current protection
– Earth-fault protection
– Reverse-power protection
– Under-voltage protection
– Under-frequency protection
• Names based on principle of operation:
– Differential protection
– Distance protection
– Power line carrier protection
PROTECTION SCHEMES
• A protective scheme includes one or more relays of the same
or different types. The following are the most common
schemes.
1. Over current protection: An O/C relay may operate when the
current increases above a certain magnitude. It is used for
protection of distribution lines, motors, equipments, etc.
2. Distance protection: A distance relay measures the distance
between the relay location and point of fault in terms of
impedance, reactance, etc. and operates if the point of fault
lies within the protected section of the line. It is used for the
protection of transmission or sub-transmission lines; usually
33 KV, 66 KV and 132 KV lines. The important types are:
— Impedance, Reactance and Mho type relays
PROTECTION SCHEMES
3. Carrier-current protection: Relay operates depending on the
information available in generated carrier signal (50-500 kHz).
• A transmitter and receiver are installed at each end of a
transmission line to be protected. Information regarding the
direction of fault current is transmitted from one end of the line
section to the other.
• Depending on the information, relays placed at each end trip if the
fault lies within their protected section. Relays do not trip in case
of external faults.
• Relays are of distance type and their tripping operation is
controlled by ‘carrier signal’.
• Used for protection of EHV and UHV lines (132 KV and above)
PROTECTION SCHEMES
4. Differential protection: Relay operates by comparing the current
entering and leaving a machine.
• Used for protection of generators, transformers, motors of very
large size, bus zones, etc.
• CTs are placed on both sides of each winding of a machine. The
outputs of their secondaries are applied to the relay coils
(compares current entering and leaving the machine winding )
• Under normal conditions or during external fault, the current
entering the winding is equal to the current leaving the winding.
• In case of an internal fault on the winding, these are not equal.
This difference in the current actuates the relay