Iec 60076-1 2011 (Id 45225)
Iec 60076-1 2011 (Id 45225)
INTERNATIONAL
STANDARD
WffireTffiffi
$ruYffiffiru&Y*ffiilq&tffi
Power transformers -
Part 1: General
Transformateurs de puissance -
Partie 1: G6n6ralit6s
.",r;tt1r'rh
*;""
i;':'
''i :::i
V*'t"t"
THIS PUBLICATION IS COPYRIGHT PROTECTED
Copyright @ 2011 lEC, Geneva, Switzerland
publication may be reproduced or utilized in any form or by
All rights reserved. Unless otheMise specified, no part of thls
;nd microfilm, without permission in wriling from either IEC
or
any means, etectronrc or mechanical, including photoc;pting
lE6's member National Commitlee in the country of the requester'
obtaining additional rights to this publica-
lf you have any questrons about IEC copyright or have an enquiry about
or you, to.tt iiCmember'National Committee for further information'
tion, please contact the address below
partie de cette p.ublication n:-p-.":-t ctre reproduite
Droits de reproduction r6serv6s. Sauf indicatlon contraire, aucune
que ce soit et p.t .r.rn pibcede €lectronique ou m6canique' y compris la photocople
ni utilis6e sous quelque forme
de la CEI du pays du demandeur
et les microfilms, sans I'accord bcrit de la CEI ou du Comite national
questions sur le copyright de la cEl ou si vous d6sirez obtenir des droits supplementaires sur cette
si vous avez des la CEI de votre pays residence'
de
publication, utilisez les coordonnees ci-apres ou contactez le Comite national de
A propos de la CEI
La Commission Electrolechnique Internationale (CEl) est la premiere organisation mondiale qui elabore el publie
des normes internationales pour tout ce qui a trait e l'electricite, e I'electronique et aux iechnologies apparenlees.
A propos des publications GEI
Le conlenu technique des publications de la CEI est constamment revu. Veuillez vous assurer que vous
possddez l'edition la plus r6cente, un corrigendum ou amendement peut avoir 6t€ publi€.
r Catalogue des publications de la CEI:www.iec.ch/searchpub/cur fut-f.htm
Le Catalogue en-ligne de la CEI vous perrnet d'efieCtuer des recherches en utilisant differents criteres (numero cle
reference, texte, comite d'etudes,...). ll donne aussi des informations sur les projets el les publications retirees ou remplacees.
r Just Published CEI: www.iec.chlonline news/iusipub
Restez informe sur les nouvelles puUiications de la CEl. Just Published d6taille deux fois par mois les
nouvelles publications parues. Disponible en-ligne et aussi par email.
. Electropedia: www.electropedia.orq
Le premier OictifrialreEn-iQ-i6Tf monde de termes electroniques et €lectriques. ll contient plus de 20 000 termes et
d6finitions en anglais et en frangais, ainsi gue les termes 6quivaients dans les langues additionnelles. Egalement appel€
Vocabulaire Electrotechnique International en ligne.
r Service Clients: www.iec.ch/webstore/custserv/custserv entrY-f.htm
Sivousdesireznousousivousavezdesquestions,visi1ez|eFAQ
du Service clients ou contactez-nous:
Email. [email protected]
+41 22 919 02 11
T61..
Fax +41 22 919 03 00
INTERNATIONAL
STANDARD
w&ffimww
XTfTYKT&TTQNAUW
Power transformers -
Part 1: General
Transformateurs de puissance -
Partie 1: G6n6ralit6s
lr'i"
.. .=,,$i
..., i l,i t'"I'
-'. 'ti'i;l-1'"'
INTERNATIONAL
t'*jt'
ELECTROTECHNiCAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
":5""'ff: Kry
rcs 29.180 lSBtl 978-2-88 912438-1
60076-1 @ IEC:2011
-2-
FOREWORD
rQ
2 Normative references ..........'. """"'v
R
3 Terms and definitions........'... .R
3.1 General q
3.2 Terminals and neutral Point
' ,ln
3.3 Windings """-"" 'v
3.4 Ratlng """""""11
3.5 TaPPings """""' 13
3.6 Losses and no-load current """"""""'15
3.7 Short-circuit impedance and voltage drop. ...'..." """"""""""16
3.8 Temperature rise """"""""17
3.9 Insulation """""17
3.10 Connections . ............... """"'"""""""""'17
3.11 Test classification. """""""'18
3'12Meteorologica|datawithrespecttocoo|ing
3.13 Other definitions """"""""19
Service conditions
4.1 General """"""'20
4.2 Normal service conditions ...'.....'."..""'20
Rating and general requirements............. ..,"22
5.1 Rated power. .. .,... .."..'..'."'22
'...'..'.."'."""22
5.1 .1 Generat
5.1.2 Preferred values of rated power. ......-...-"..22
5.1.3 Minimum power under alternative cooling modes '.....:...'......-.-.-..'22
5.1.4 Loading beyond rated power. ................ .........-....--.--...23
5.2 Cooling mode .------.----.--.......23
5.3 Load rejection on transformers directly connected to a generator............. -..-'......--...23
5.4 Rated voltage and rated frequency .."'23
5.4.1 Rated voltage ..".....23
5.4.2 Rated frequency ..".....'..'..'..'.'..23
5.4.3 Operation at higher than rated voltage and/or at other than rated
frequency ......'.'......24
5.5 Provision for unusual service conditions '............'.)......'....'.--.'.24
5.6 Highest voltage for equipment U,n and dielectric tests |eve|s......... .-....'.'25
5.7 Additional information required for enquiry ...........,*..a-1!-r........--25
5.7.1Transformerc|assification..,......'.,.
5.7.2 Winding connection and number of phases ..............:i',.:-'.i.''....:. . .....'.....'."..".25
5.7.3 Sound level .......... ............i';,"f .'...................,..................26
5.7.4 Transport. '.,.......'..'.26
5.8 Components and materials ."...".'..'.'....,..'......--.'.'..'26
6 Requirements for transformers having a tapped winding .'........'.-.-..27
6.1 General - Notation of tapping range ....,.......'....--."27
6.2 Tapping voltage - tapping current. Standard categories of tapping voltage variation.
Maximum voltage tapping. ..-...-.--.....-....27
6.3 Tapping power. Full-power tappings - reduced-power tappings .......-.....30
test)"""""'51
11.g Leak testing with pressure for liquid immersed transformers (tightness
11.9 Vacuum deflection test for liquid immersed transformers ' """"""" """"'51
"""""""
11.10 Pressure deflection test for liquid immersed transformers'
""""52
,11.11 Vacuum tightneSs test on site for liquid immersed transformers' """"""53
11.12Check of core and frame insulation """""""""""53
12 Electromagnetic compatibility (EMC) """"""53
13 High frequency switching transients...'...."""" """"""\""" """"""""'54
with enquiry and order """55
Annex A (informative) check list of information to be provided
with tappings """""""""'59
Annex B (informative) Examples of specifications for transformers
Annex C (informative) Specification of short-circuit impedance by boundaries "',"""""""""63
Annex D (informative) Examples of three-phase transformer connections """""" """"""""""64
Annex E (normative) Temperature correction of load loss """"""""""67
to transform-
Annex F (informative) Facilitres for future fitting of condition monitoring systems
.".'',....'.'
\;
POWER TRANSFORMERS .
Part 1: General
FOREWORD
International Standard IEC 60076-1 has been prepared by IEC technical committee 14:
Power transformers.
This third edition cancels and replaces the second edition published in 1993, and
its Amendment 1(1999). lt is a technical revision.
This edition includes the following significant technical changes with respect to the previ-
ous edition:
addition of a definition of harmonic content;
addition of a subclause on transport;
addition of functional method of specification;
addition of connection symbols for single phase transformers;
addition of safety and environmental requirements,
addition of requirements for liquid preservation systems;
Orrier No.. WS-201 1-AA231 - lt'JPORTANT: This iiie is copyrighi of lEC. Geneva. Swiuerland. All rignls reservec
-iiis iile is subjeot ro a licefice aljreerrieni. Errquines to Enrail: [email protected] - lei.: +41 22819 {i2 11
60076-,1 @ IEC:
-6- 2011
ts
now an. informative checklist;
informative annexes have been added on facilities for condition monitoring
and environmental and safety considerations'
The text of this stand is based on the follow rg documents:
FDIS
Full information on the voting for the approval of this standard can be found in the report
on voiing indicated in the above table. i
This publication has been drafted in accordance with the ISO/IEC Directives, Part2-
A list of all parts of the IEC 60076 series can be found, under the general title Pow-
er transformers, on the IEC website.
The committee has decided that the contents of this publication will remain unchanged until
the stability date indicated on the IEC web site under "http://webstore.iec.ch" in the data
related to the specific publication. At this date, the publication will be
. reconfirmed,
. withdrawn,
. replaced by a revised edition, or
. amendeci.
$$\sso$${oq\h
1 Scope
(including
This part of IEC 60076 applies to three-phase and single-phase power transformers
of small and special transformers
auto-transformers) with th'e exception oi certain categories
such as:
single-phase transformers with rated power less than 1 kvA and three-phase
transform-
ers less than 5 kVA,
transformers, which have no windings wlth rated voltage higher than 1 000
V; -instrument transformers;
traction transformers mounted on rolling stock;
startin g transformers,
testing transformers;
welding transformers;
explosion-proof and mining transformers,
transformers for deep water (submerged) applications.
When IEC standards do not exist for such categories of transformers (in particular transformer
having no winding exceeding 1OO0 V for industrial applications), this part of IEC 60076 may
still be applicable either as a whole or in part.
This standard does not address the requirements that would make a transformer suitable
for mounting in a position accessible to the general public.
For those categories of power transformers and reactors which have their own IEC standards,
this part is applicable only to the extent in which it is specifically called up by cross-reference
in the other standard. Such standards exist for:
2 Normative references ,
of this document'
The following referenced documents are indispensable for the application the latest edition
references,
For dated references, only the edition cited applies, For undated
of the referenced document (including any amendments) applies'
transformers
lEc 60076- 2, Power transformers - Part 2: Temperature rise for liquid-immersed
fesfs and exter'
lEc 60076-3:2000, Power transformers - Part 3: lnsulation tevels, dielectric
nal clearances in air
IEC 60076- 10'.2001 , Power transformers - Part 10: Determination of sound levels
IEC 601 37.2008, lnsulated bushings for alternating vottages above 1 000 V
IEC 6021 4-1:2003, Tap-changers - Part 1: Performance requirements and test m,ethods
IEC 60296:2003, Ftuids for electrotechnical apptications - lJnused mineral insulating oils
for transformers and switchgear
3.1 General
3.1.1
power transformer
a static piece of apparatus with two or more windings which, by electromagnetic
induction, transforms a system of alternating voltage and current into another system of
voltage and current usually of different values and at the same frequency for the purpose
of transmitting electrical power
3.1.4
liqu id-immersed type transformer
a transformer in which the magnetic circuit and windings are immersed in
lio u id
3.1.5
dry-type transformer
a transformer in which the magnetic circuit and windings are not immersed in an insulat-
ing liquid
3.1.6
liquid preservation system
system in a liquid-filled transformer by which the thermal expanslon of the liquid
is accommodated.
NOTE Contact between the liquid and external air may sometimes be diminished or prevented
3.',r,7
specified value
the value specified by the purchaser at the time of or-
der
3.'t.8
design value
the expected value given by the number of turns in the design in the case of turns ratio
or calculated from the design in the case of impedance, no-load current or other Parameters
3.1.9
highest voltage for equipment U, applicable to a transformer winding
the highest r.m.s. phase-to-phase voltage in a three-phase system for which a trans-
former winding is designed in respect of its insulation
3.2.1
terminal
a conducting element intended for connecting a winding to external conduc-
tors
3.2.2
line terminal
a terminal intended for connection to a line conductor of a net-
work
3.2.3
neutral termi-
nal
a) for three-phase transformers and three-phase banks of single-phase transforniers:
the terminal or terminals connected to the common point (the neutral point) of a
star-connected or zigzag connected winding
-
4n
tv - 60076-1 o IEC:2011
3.2.4
neutral point
the poini of a symmetrical system of voltages which is normally alzero poten-
tial
3.2.5
corresponding terminals
terminals of different windings of a transformer, marked with the same letter or correspond-
ing symbol
3.3 Windings
3.3.1
winding
the assembly of turns forming an electrical circuit associated with one of ,the volt;
ages assigned to the transformer
[lEC 60050 -421'.1990, 421-03-01, modified]
phase windlngs (see '3'3'3)'
N6TE For a three-phase transformer, the 'winding' is the combination of the
3.3.2
tapped winding
a winding in which the effective number of turns can be changed in
steps
3.3.3
phase winding
ihe assembly of turns forming one phase of a three-phase wind-
ing
3.3.4
high-voltage wind-
ing
HV winding*
the winding having the highest rated volt-
age
ing
LV winding* '
'primary
The winding which receives active power from the supply source in service is referred to as a
power to a foab is a'secondary winding'. These terms.fave no signif-
winding,, and that which detivers active
in the context
icance'as to which of the windings has ine higher rated voltage and should not be used except
in the
of direction of active power flow-(see IEC OObSO-aZt:1990, 421-03-06 and 07). A further winding
60076-1 o IEC:2011 - 11 -
NOTE For a series transformer, the winding having the lower rated voltage may be that having the
higher insulation level.
3.3.6
intermediate-voltage winding*
a winding of a multi-winding transformer having a rated voltage intermediate between
the highest and lowest winding rated voltages
Il EC 60050 -421 :1990, 421-03-05]
3.3.7
auxiliary winding
a winding intended only for a small load compared with the rated power of the trqns-
former
3.3.8
stabilizing winding
a supplementary delta-connected winding provided in a star-star-connected or star-
zigzag-connected transformer to decrease its zero-sequence impedance, see 3.7.3
3.3.9
common winding
the common part of the windings of an auto-trans-
former ,
3.3.10
series winding
the part of the winding of an auto-transformer or the winding of a series transformer which
is intended to be connected in series with a circuit
3.3.12
auto-connected windings !.1
the series and common windings of an auto-trans- ,..','. ,r!
1'"
former ..:.
"t
"
.
3.4 Rating
3.4.1
rating
those numerical values assigned to the quantities which define the operation of the
transformer in the conditions specified in this part of IEC 60076 and on which the manufac-
turer's guarantees and the tests are based
3.4.2
rated quantities
quantities (voltage, current, etc.), the nunterical values of which define the
rau ng
- 12 - 60076-1 e IEC:
2011
NOTE 1 For transformers having tappings, rated quantities are related to the principal tapping (see 3'5.2),
unless otherwise specified. Corresponding quantiiies with analogous meaning, related to othef specific
tappings, are called tapping guantities (see 3.5.9).
NOTE 2 Voltages and currents are atways expressed by their r.m.s. values, unless otherwise spebified.
3.4.3
rated voltage of a wind-
ing
ul
the voltage assigned to be applied, or developed at no-load, between the terminals of
an untapped winding, or of a tabped winding connected on the principal tapping (see 3.5.2)'
for a three-phase winding it is the voltage between line terminals
NOTE 2 For single-phase transformers intended to be connected in star to form a three-phase bank or to
be connected between 1,fi-e
line and the neu|,rXrt-q{g three phase system, the rated voltage is indicated as the
NOTE 3 For single phase transformers intended to be connected between phases of a netwotk, the rated
voltage is indicated as the phase-to'phase voltage.
NOTE 4 For the series winding of a three-phase series transformer, which is designed as an open winding
(see
r.ro.s), the rated voltage is indicated as if the windings were connected in star.
3.4.4
rated voltage ratio
the ratio of the rated voltage of a winding to the rated voltage of another winding associat-
ed with a lower or equal rated voltag
3.4.5
rated frequencY
fl
the frequency at which the transformer is designed to oper-
ate
3.4.7
rated current
Ir
the current flowing through a lrne terminal of a winding which is derived from rated power
S, and rated voltage Urfor the winding
/. = =S'
"!3xU,
' 'line
t^
'
vJ
NOTE 3 For a single phase transformer not intended to be connected to form a three phase bank, the
rated current is
,s'l
I Llr
NOTE 4 For open windings (see 3.10.5) of a transformer, the rated current of the open windings is the rated
power divided by the numbe r of phases and by th'e rated voltage of the open winding:
r, =---jL *
No. of phases x U
3.5 Tappings
3.5.'t
tapping
in-a transformer having a tapped winding, a specific connection of that winding, represent-
ing a definite effective number of turns in the tapped winding and, consequently, a definite
tuins ratio between this winding and any other winding with a fixed number of turns
NOTE One of the tappings is the principal tapping, and other tappings are described in relation'to the
principal tapping by their respective tapping factors. See definitions of these terms below.
3.5.2
principal taPPing
ine tapping iowhich the rated quantities are relat- i
edi
fl EC 60050 -421 :1990, 421 -05-021
3.5.3
tapping factor (corresponding to a given tapping)
11. It
- factor)
$ltapping or 100 #(tapping factor expressed as a percentage)
U,- UI
where
tJ, is the rated voltage of the winding (see 3.4.3);
ud is the voltage which would be developed at no-load at the terminals of the winding,
" at the tapping concerned, by applying rated voltage to an untapped windin$
NOTE For series transformers, the tapping factor is the ratio of the voltage of the series winding cprresponding
to a given tapping to Ur.
3.5.4
plus tapping
a tapping whose tapping factor is higher than
I
3.5.5
minus tapping
a tapping whose tapping factor is lower than
1
3.5.6
tapping step
the difierence between the tapping factors, expressed as a percentage, of two adja-
cent tappings
[l Ec 60050 -421 I s90, 421-05-061
"
3.5.7
tapping range
the variation range of the tapping factor, expressed as a percentage, compared with the
value'100'
NOTE lf this factor ranges from 1OO + a to 100 - b, the tapping range is said to be: +a o/o,
-b o/o o! la o/o, it a =
b.
Il Ec 60050 -421 1990, 421-05-07]
"
3.5.8
tapping voltage ratio (of a pair of windings)
the ratio which is equal to the rated voltage ra-
tio:
muttiplied by the tapping factor of the tapped winding if this is the high-voltage winding;
divided by the tapping factor of the tapped winding if this is the low-voltage winding
il EC 60050 -421'. 1990, 421-05-08l
NOTE While the rated voltage ratio is, by definition, at least equal to 1, the tapping voltage ratio can be
lower than 1 for certain tappings when the iated voltage ratio is close to 1.
3.5.9
tapping quantities
tnirie q-"uantities the numerical values of which define the duty of a particular tapping
(other than the princlpal tapping)
NOTE Tapping quantities exist for any winding in the transformer, not only for the tapped wincting (see
6.2 and 6.3).
3.5.13
de-energized taP-chang-
er
DETC
a device for changing the tapping connections of a winding, suitable for operation only
while the transformer is de-energized (isolated from the system)
3.5.14
maximum allowable tapping service voltage
the voltage at rated frequency a transformer is designed to withstand continuously
without damage at any particular tap position at the relevant tapping power
NOTE 1 This voltage is limited by Ur. I
NOTE 2 This voltage will normally be limited to 105 % of the rated tapping voltage unless a higher voltage is
required by the purchaser's specifiiation of the tapping (see 6.4) either explicitly or as a result of a specification
according io 6.a.2.
I
3.6.1
no-load loss
the active power absorbed when a rated voltage (tapping voltage) at a rated frequency
is apptied to the terminals of one of the windings, the other winding or windings being
open-circuited
3.6.2
no-load current
the r.m.s. vatue of the current flowing through a line terminal of a winding when rated
voltage (tapping voltage) is applied at a ratel frequency to that winding, the other winding or
windings being oPen-circuited
NOTE 1 For a three-phase transformer, the value is the arithmetic mean of the values of current in the three
lines.
NOTE 2 The no-toad current of a winding is often expressed as a percentage of the tated current of that
power'
winding. For a multi-winding transformer, Ihis percentage is referred to the winding with the highestrraled
3.6.3
load loss
the absorbed active power at a rated frequency and reference temperature (see
1l 1), associated with a pair of windings when rated current (tapping current) is flowing
through the line terminals of one of the windings, and the terminals of the other wind-
ing aie short-circuited. Further windings, if existing, are open-circuited
NOTE For a two-winding transformer, there is only one winding combination and one value of lpad loss' For a
i
multi-winding transformer, there are several valuei of load loss corresponding to the different two-winding
combinationi (see Clause 7 of IEC 60076-8:1997). A combined load loss figure for the complete transformer is
referred to a specified winding load combination. In general, it is usually not accessible for direct measurement
in
testi ng.
NOTE 2 When the windings of the pair have difierent rated power values, the load loss is referred to rated
current in the winding with the lower rated power and the reference power should be mentioned.
3.6.4
total losses
the sum of the no-load loss and the load
loss
NOTE The power consumption of the auxiliary plant is not included in the total losses and is staied separately.
NOTE 2 This quantity can be expressed in relative, dimensionless form, as a fraction z of the refer-
ence impedance Ztet, of the same winding of the pair. In percentage notat,0n:
z
z=i00]
" tel
where
tt2
Z,* = (formula valid for both three-phase and single-phase transformers);
?
U is the voltage (rated voltage or tapping voltage) of the winding to which Zand 2,", belong;
The relative value is also equal to the ratio between the applied voltage during a short-circuit measurement which
causes the relevant rated current (or tapping current) to flow, and rated voltage (or tapping voltage). This applied
voltage is referred to as the short-circuit voltage (lEC 60050-421:1990,421-07-01) ol the \ai oI windings. lt is
normally expressed as a percentage.
3.7.2
voltage drop or rise for a specified load condition
the arithmetic difference between the no'load voltage of a winding and the voltage devel-
oped at the terminals of the same winding at a specified load and power factor, the voltage
supplied to (one of) the other winding(s) being equal to:
its rated value if the transformer is connected on the principal tapping (the no-load
voltage of the winding is then equal to its rated value);
the tapping voltage if the transformer is connected on another tapping.
This difference is generally expressed as a percentage of the no-load voltage of the winding
NOTE For multi-winding transformers, the voltage drop or rise depends not only on the load and power faclor
of the winding itself, but also on the load and power factor of the other windings (see IEC 60076-8)- ,
NOTE 2 The zero-sequence impedance may be dependent on the value of the current and the temper-
ature, particularly in transformers without any delta-connected winding.
NOTE 3 The zero-sequence impedance may also be expressect as a relative value in lhe same way as
the (positive sequence) short-circuit impedance (see 3.7.1).
3.9 Insulation
For terms and definitions relating to insulation, see IEC 60076-3.
3.10 Connections
3.10.1
star connection
the winding connection so arranged that each of the phase windings of a,,three-
phase transformer, or of each of the windings for the same rated voltage of sin-
gle-phase transformers associated in a three-phase bank, is connected to a common point
(the neutral point) and the other end to its appropriate line terminal
3.10.2
delta connection
the winding connection so arranged that the phase windings of a three-phase transformer,
or the windings for the same rated voltage of single-phase transformers associated in a
three-phase bank, are connected in series to form a closed circuit
3.10.3
open-delta connection
the winding connection in which the phase windings of a three-phase transformer, or
the windings for the same rated voltage of single-phase transformers associated in a three-
phase bank, are connected in series without closing one corner of the delta
3.10.4
zigzag connec-
tion
Z-connection
a winding connection consisting of two winding secttons, the first section connected in
star, the second connected in series between the first section and the line terminals:
the two sections are arranged so that each phase of the second section is wound on a
different limb of the transformer to the part of the first section to which it is connected
NOTE See Annex D for cases where the winding sections have equal voltages.
3.10.s
open windings
the phase windings of a three-phase transformer which are not interconnectpd within
the transformer
[lEC 60050-421 1990, 421-1 0-05, modified]
3.10.6
phase displacement (of a three-phase winding)
ifre angular difference between the phasors iepresenting the voltages between the neutral
point (ieal or imaginary) and the corresponding terminals of two windings, a positive-
sequence voltage system being applied to the high-voltage terminals, following each other
in alphabetical sequence if they are lettered, or in numerical sequence if they are numbered;
the phasors are assumed to rotate in a counter-clockwise sense
NOTE 2 The high-voltage winding phasor is taken as reference, and the displacement tor any other winding is
conventionally eipressed'by the 'c-lock notation', that is, the hour indicated by the winding phasor when the H.V.
winding phasor is at 12 o'clock (rising numbers indicate increasing phase lag).
3ia^7
connection symbol ,
3.11.2
type test
a test made on a transformer which is representative of other transformers, to demon-
strate that these transformers comply with the specified requirements not covered by the
routine tests: a transformer is considered to be representative of others if it is built to
the same drawings using the same techniques and materials in the same factory
NOTE 1 Design variations that are clearly irrelevanl to a particular type test would not require that type test to
be reoeated.
NOITE 2 Design variatrons that cause a reduction in values and stresses relevant to a parrrcular type test do
not require a new type test if accepted by ihe purchaser and the manufacturer.
NOTE 3 For transformers below 20 MVA and tJn < 72,5 kV significant design variations may bp acceptable
if supported by demonstration of compliance with type test requirements.
3.12.2
monthly average temPerature
half the sum of the average of the daily maxima and the average of the daily minima during
a particular month over many Years
3.12.3
yearly average temPerature
one-twelfth of the sum of the monthly average tempera-
tures
3.13.2
total harmonic content
the ratio of the effective value of all the harmonics to the effective value of the fundamen-
tal (E1, /1)
li =n
,,/EE,i
J (for voltage)
-
El
I i=n
/S r?
\li4''
total harmonic content (for current)
ll
3.13.3
even harmonic content
the ratio of the effective value of all the even harmonics to the effective value of
the fundamental (E.', /.')
r:^
even harmonic content = ,lzr:, (for vottage)
-r- L
4 Service conditions
4.1 General
The service conditions set out in 4.2 represent the normal scope of operation of a transformer
specified to this standard. For any unusual service conditions which require special
consideration in the design of a transformer see 5.5. Such conditions include high altitude,
extreme high or low external cooling medium temperature, tropical humidity, sei'smic activity,
severe contamination, unusual voltage or load current wave shapes, high solar radiation and
intermittent loading. They may also Concern conditions for shipment, storage and installation,
such as weight or space limitations (see Annex A).
Supplementary rules for rating and testing are given in the following publications:
NOTE 5 Transformers can operate at rated current without excessive loss of life with a
qurrent harmonic
content of less lhan 5 eh, however it should be noted that the temperature rise will increase for any harmonrc
loading and may exceed rated rise.
e) Symmetry of three-phase supply voltage
For three-phase transformers, a set of three-phase supply voltages which are
approximately symmetrical. Approximately symmetrical shall be taken to mean that the
highest phase to phase voltage is no more than 1 % higher than the lowest phase to
phlse vottage conlinuorsty oiZ % higher for short periods (approximately 30 min) under
exceptional conditions.
f) Installationenvironment
An environment with a pollution rate (see IEC 60137 and IEC/TS 60815) that does not
require special consideration regarding the external insulation of transformer bushings or
of the transformer itself.
An environment not exposed to seismic disturbance which would require special
consideration in the design. (This is assumed to be the case when the ground acceleration
level an is below 2 ms-2 or approximately 0,2 g') See IEC 60068-3-3
The transformer shall have an assigned rated power for each winding which shall be marked
on the rating plate. The rated power refers to continuous loading, This is a reference value for
guarantees and tests concerning load losses and temperature rises.
lf differeni values of apparent power are assigned under different circumstances, for exarn-
pte, with different methods of cooling, the highest of these values is the rated power.
A two-winding transformer has only one value of rated power, identical for both windings.
For multi-winding transformers, the purchaser shall specify the required power-
loading combinations, stating, when necessary, the active and reactive outputs separately.
When the transformer has rated voltage applied to a primary winding, and rated current flows
through the terminals of a secondary winding, the transformer receives the relevant rated
power for that pair of windings.
The transformer shall be capable of carrying, in continuous service, the rated power (for a
multi-winding transformer: the specified combination(s) of winding rated power(s)) under
conditions tisteO in Clause 4 and without exceeding the temperature-rise limitations specified
in IEC 60076-2 for liquid immersed transformers.
NOTE 1 The interpretation of rated power according to this subclause implies that it is a value of apparent
power input to the transformer - including its own absorption of active and reactive power. The apparent power
that the transformer delivers to the circuit connected to the terminals of the secondary winding under rated
loading differs from the rated power. The voltage across the secondary terminals differs from rated voltage by the
voltag- drop (or rise) in the transformer. Allowance for voltage drop, with regard to lo€d power factor, is made in
the specification of the rated voltage and the tapping range (see Clause 7 ol IEC 60076-8:1997).
NOTE 2 For a multi-winding transformer, half the arithmetic sum of the rated power values of all windings
(separate windings, not auto-connected) gives a rough estimate of its physical size as compared with a two-
winding transformer. r
Any specific requirements for loading beyond rated power, operation at higher external
cooling medium temperatures or reduced temperature rise limits shall be spdcified by the
purchaser in the enquiry and the contract. Any additional tests or calculations required to
verify compliance with these specific requirements shall also be specified,
NOTE 1 This option is intended to be used in particular to give a basis for design and gua.antees concern-
ing temporary emergency loading of power transformers.
The bushings, tap-changers, current transformers and other auxiliary equiprnent shall
be selected so as not to restrict the loading capabiiity of the transformer.
NOTE 2 The relevant component standards IEC 60137 for bushings and IEC 60214-1 for tap-chEngers should
be consulted for the loading capability of those components.
NOTE 3 These requirements do not apply to transformers for special applications, which do not need a load-
ing capability beyond rated power. For these transformers, if such a capability is reguired, it should be specified.
lf the user has particular requirements for the cooling method(s) or cooling equipment,
this shall be stated rn the enquiry.
For additional information see IEC 60076-2.
The transformer shall have an assigned rated voltage for each winding which shall be
marked on the rating plate.
The rated frequency is the basis for the guaranteed values such as losses, impedance,
and sound level.
5.4.3 Operation at higher than rated voltage andlor at other than rated f requency
Methods for the specification of suitable rated voltage values and tapping range to cope with
a set of loading cases (loading power and power factor, corresponding line-to-line service
voltages) are described in IEC 60076-8.
Within the prescribed values of U., for the transformer windings, a transfofmer shall be
capable of continuous operation at rated power without damage under conditions of
'overfluxing' where the value of voltage divided by frequency (Vl4z),exceeds the
corresponding value at rated voltage and rated frequency by no more than 5 %, unless
otherwise speclfied by the purchaser.
At a current K times the transformer rated current (0 < K < 1), the overfluxing shall be
limited in accordance with the following formula:
uf, (%)
"'?"'oo<110-5K
f f the transformer is to be operated at YlHz in excess of those stated above, this shall
be identified by the purchaser in the enquiry.
5.5 Provision for unusual service conditions
The purchaser shall identify in his enquiry any service conditions not covered by the
normal service conditions. Examples of such conditions are.
external cooling medium temperature outside the limits prescribed in 4.2;l
restricted ventilation;
altitude in excess of the limit prescribed in 4.2;
damaging fumes and vapours;
steam:
humidity in excess of the limit prescrlbed in 4.2',
dripping water;
salt spray;
excessive and abrasive dust;
high harmonic content of the load current exceeding the requirements of4.2,
distortion of the supply voltage waveform exceeding the limits of 4.2,
unusual high frequency switching transients, see Clausel3;
superimposed DC current;
seismic qualification which would otherwise require special considerations in
the design, see 4.2,
extreme mechanical shock and vibrations;
solar radiation,
regular frequent energisation in excess of 24 times per year;
reg lar frequent short-circu its;
u
Transformer specification for operation under such abnormal conditions shall be subject
to agreement between the supplier and purchaser.
Supplementary requirements, within defined limits, for the rating and testing of transformers
designed for other than nornral service conditions listed in Clause 4, such as high temperature
of cooling air or altitude above 1 000 m are given in IEC 60076-2.
For transformer windings with a highest voltage for equipment greater than (>) 72,5 kY the
purchaser shall specify whether any neutral terminals for that winding are to be directly
earthed in service or not, and if not, the U^for the neutral terminals shall be specified by the
0urcnaser.
Unless otherwise specified by the purchaser, dielectric test levels shall be taken to be
the lowest applicable value corresponding to U*, given in IEC 60076-3.
5.7 Additional information required for enquiry
5.7.1 Transformerclassification
The kind of transformer, for example, separate winding transformer, auto-transformer
or series transformer shall be specified by the user.
lf there are requirements for high and low limits for the zero sequence impedance, this shall
be stated by the purchaser and may influence the core configuration and the requirement for
a delta winding. lf the zero sequence requirements dictated the use of a delta connected
winding that was not directly specified by the purchaser, then this shall be cleqrly stated by
the manufacturer in the tender documents.
The transformer manufacturer shall not use a delta connected test winding if no delta
winding has been specified, unless specifically agreed by the purchaser.
lf there is a particular requirement for either a bank of single phase transforrner or a three
phase unit, then this shall be specified by the user; otherwise the manufacturer shall make it
clear in the tender document what type of transformer is being offered.
Unless otherwise specified, the sound level shall be taken as the no load sound level with all
cooling equipment required to achieve rated power in operation. lf an alternative cooling mode
is specified (see 5.1.3) the sound level for each alternative mode may be specified by the
purchaser and if specified shall be guaranteed by the manufacturer and measured on test.
The sound level in service is influenced by the load current (see IEC 60076-10). lf the
purchaser requires a load current sound level measurement test or a guarantee of the total
noise level of the transformers, including load noise, this shall be stated in the enquiry.
The sound level measured in the test according to IEC 60076-10 shall not exceed the
guaranteed maximum sound level. The guaranteed maximum sound level is a limit without
tolerance.
5.7.4 Transport
5.7.4.1 Transportlimitation
lf transport size orweight limits apply,'they shall be stated in the enquiry.
lf any other special conditions apply during transportation, they shall be stated in the enquiry.
This might include a restriction on the transportation with insulating liquid or different
environmental conditions expected to be experienced during transportation than those
expected in service.
5.7.4.2 Transportacceleration
The transformer shall be designed and manufactured to withstand a constant acceleration of
at least 1 g in all directions (in addition to the acceleration due to gravity in the vertical
direction) without any damage, demonstrated by static force calculations based on a constant
value of acceleration.
lf the transport is not the responsibility of the manufacturer and an acceleration, in excess of
1g is expected during transport, the accelerations and frequencies shall be defined in the
enquiry. lf higher accelerations are specified by the customer, the manufacturer shall
demonstrate compliance by means of calculation.
For transformers specified in accordance wrth 6.4.2, the notation shall be as specified by
the purchaser in item 3 of that subclause.
In auto-connected transformers, tappings are sometimes arranged at the neutral which means
that the effective number of turns is changed simultaneously in both windin'gs. For such
transformers, unless they are specified in accordance with 6.4.2, the tapping particulars are
sublect to agreement. The requirements of this subclause should be used as far as
applicable.
Unless otherwise specified, the principal tapping is located in the middle of the tapping range-
Other tappings are identified by their tapping factors. The number of tappings dnd the range
of variation of the transformer ratio may be expressed in short notation by the deviations of
the tapping factor percentages from the value 100 (fordefinitions of terms, see 3.5).
EXAMPLE A transformer with a tapped 160 kV winding with a tapping range of +15 ok
having 21 tappings, symmetrically arranged around the rated voltage, is designated:
(160 110x1,5%)t66kV
lf the tapping range is specified asymmetrically around the rated voltage, this is designat-
ed as:
haol.,{;lfi:)/oo rv
Regarding the full presentation on the nameplate of data related to individual tappings,
see Clause 8.
Some tappings may be 'reduced-power tappings' due to restrictions in either tapping voltage
or tapping current. The boundary tappings where such limitations appear are called 'maximum
voltage tapping'and'maxlmum current tapping'(see Figures 1a, 1b and 1c). i
The tapping voltage in any untapped winding is constant from tapping to tapping. The
tapping voltages in the tapped winding are proportional to the tapping factors. See Figure 1a.
The tapping voltage in the tapped winding is constant from tapping to tapping: The tapping
voltages in any untapped winding are inversely proportional to the tbpping factor. See Figur6
1b.
In many applications and particularly with transformers having a large tapping range, a
combination is specified using both principles applied to different parts of tne r-nge:
combined voltage variation (CbVV). The change-over point is called 'maximum voltage
tapping'. For this system the following applies: ,
CFVV applies for tappings with tapping factors below the maximum voltage tapping factor.
VFVV applies for tappings with tapping factors above the maximum voltage tapping factor.
See Figure 1c.
100
100 1
100 1 10
Tapping factor
tr i
100
Us
1,
tB
lz'
l/t- 2
- -
,".
a'L
.l
,t tt
2
Sne
100 1 10
Tapping factor
"";lu
100
100
90 100 110
Tapping factor
tEC 681/11
Where variable flux voltage variation VFVV is used, it is normally only possible for
the design
ratio to match the specified ratio at two positions over the regutation'range. The purchas-er
shall specify where the design ratio shall match the speciied ratio, e*trere taps,
principal and maximum tap or principal and mininimum tap. lf not otherwlse"lg.
Jpeciried, the two
extreme taps shall be the ratios to match.
NoTE Subclause 6'4.2 requires the user to specify which winding is to be tapped and particutar tapptng powers"
subclause 6 4 3 defines.overatl voitage and current requirements and reguires the manufacturer'to
winding or windings will be-tapped. Such a specification may resull in a variety of possible setect whjch
lEc 60076-8 gives detairs of tapping arrangements and voltage drop calculations, transformer des;gns.
c) which voltage shail vary for the purpose of defining rated tapping
vortage.
NorE 2 The rated tapping voltage is needed to determine the impedance base for each tap. whqre the func-
of specification is aiopted, the rated tapping vottags cannot
be used to determine the rated tapping
f:*:'rt"'noo
d) Any requirements for fixing the ratio of turns between two particular
windinEs on a
more than two winding transformer.
e) Minimurn full load power factor (this affects the voltage drop of the transformer).
f) whether any tapping or range of tappings can be reduced power tappings.
The manufacturer will choose the arrangement of windings, the winding or windings
tapped. The transformer shall be able to supply the rated current on the
that are
-*inding
seconda,rv on
all tapping positions consistent with the operating conditions, without exceeding the
loove
temperature rise requirements defined by IEC 600i6_2.
The transformer shall be designed to withstand without damage the vottages and fluxes
arising from the above specified loading conditions (includiig any specified overload
conditions). A calculation showing that this condition is satisfied snalt oe supplied
purcnaser on request to the
Alternatively, the user may submit a set of loading cases with values of actrve
power (clearly indicating the direction of power flow), and corresponding and reactive
on-load voltages.
These cases should indicate the extreme values of voltage ratio under full and
rgduced power
(see "the six-parameter method" of IEC 60076-8). Based on this rnformation,
the manufacturer
will then select the tapped winding and specify rated quantities and tapping quantities in
his
tender proposal. An agreement shall be reached between the manufacturer and the purchaser
on the design tapping quantities.
6.5Specificationofshort.circuitimpedance
For transformers with no tappings exceeding a voltage variation of +5 o/o from
the principal
tapping, the short-circuit impedance of a pa-r of winJings shall be specifieo at
the principal
tapprng only, either in terms of ohms per phase Z or in percentage terms z re,ferred
to ine
rated power and rated voltage of the transformer (see 3.7.1). Altlernatively, the impedance
may be specified in accordance with one of the methods below.
For transformers with tappings exceeding a voltage variation of +5 o/o lrom the principal
tapping, impedance values expressed in terms of Z or z shall be specifiecj for the
principal
Lrisroni€,"r
lglroll.{o:.--ryg.oi.y.s^el(:):,1 -]!gnpany: Ozctj'\JEy El-EKTR'K
60076-1 @ IEC:2011
-33-
tapping and the. extreme tapping(s) exceeding S %. on such
transformers, these values of
impedance shall also be measured during thi short-circuit
impedance and road tosses test
(see 11'4) and shall be subject to the tolerances given in
Clause ,10. lf the impedance is
expressed in percentage terms z, this shall be refeired to
the rated tapprng vottage (at that
tapping) and the rated power of the transformer (at the principar
tappingj '
NoTE 1 The selection of an impedance value by the user is
drop versus limitation of overcurrenl under system fault
subject to conflicting demands. ljmitation of vottaqe
conditions. Economic optim-izaiion of the design, bearing-in
mind loss' leads tow-ards a certain range of impedance parallel opii"iior-*ith an existing
requires matching impedance (see Ctausi 6 of lEb "irr"t. translormer
oooio_s,i99zi.
NorE 2 lf an enguiry contains a specification of not only the impedance at
varration across the tapping range, this can impose the principai tapping but atso its
an irp6rtant reslriction on the design of the transformer
arrangement of the windings in relation to each other {the
€nd $,eiileometry).
also need to take into account that large changes ;n ;mpeoancEGt*""n The transtorme-r specitigation and design
of the tappings. taps can reduce or exaggerare the etfect
NorE 4 Basing the lmpedance on the rated tapping voltage and the rated power
principal tapping means that the relationship oetw6en'onm.i"ipn"t" of the transformer at the
be different for each tap and will also depend on which winding z and percentage impectan ce z wirl
care is therefore needed to ensure thal the s_pecified impedance ls the voltage variation is specified. Great
transformers specified with tapping po\ryers oiffbrent to r.t'"0 po*"|. correct. This is particutarly important tal
r t plncigal tapping.
6.6 Load loss and temperature rise
a) lf the tapping range is within +So/o, and the rated power not above 2 500 kVA, load loss
guarantees and temperature rise refer to the principal
tapping only, and the temperature
rise test is run on that tapping.
b) lf the tapping range exceeds t5 oh or the rated power is above 2
so} kVA, the guaranteed
losses shall be stated on the princ'tpal tapping position, untess
purchaser at the enquiry stage. lf such'a re!uirement otherwise specified by the
exists, it shall be stated for which
tappings, in addition to the principal tapping, ine toao tosses are
to be guaranteed by the
manufacturer' These load losses are referrid to the relevant
tapping current values. The
temperature-rise limits are valid for all tappings, at the appropriate
tJpprng power, tapping
voltage and tapping current.
The temperature-rise type test shall be carried out on one tapping
onty,
specified' lt will, unless otherwise agreed, be the 'maximum culrent- untJss otherwise
tapping, (which is
usually the tapping with the highest loss) The maximum totat loss on any tapping ls
foad
the test power for determination of liquid temperature rise
durlng the temperature rise test,
and the tapping current for the selecied tapping is the reference
current
of winding temperature rise above liquid. For iiformation about rules for determination
the temperature rise of liquid-immersed transformers, see IEC
and tests regarding
60076-2.
ln principle, the temperature-rise type test shall demonstrate that the
cootrng equipment is
sufficient for dissipation of maximum total loss on any tapping, and
rrse over externa-l cooling medium temperature of any winbing,
that the temperature
at any tapplng, does not
exceed the specified maximum value.
NorE 1 For an autotransformer, the maximum current in
different tap positions' Therefore an intermediate taf the series and common wind,ngs are usuaily at two
po"itt" may be selected for test to allorn
requrrements of rEC 60076-2 to be met on both windings the
cuiinlinu same test.
NOTE 2 For some tapping arrangements, the tapp,ng winding
is not carry,ng current in the maximum currenl
tapp'ng position Therefore, if the temperature rise o1 tne
tapptng may be selected or an extra test may be agreed.
taiping winding needs to be determrned, another
NorE 1ym!e-rlng is arbitrary. Terminal marking on the transformer follows national practice. Guidance
may be fhis
found in IEC/TR 60616.
open windings do not have a clock number notation because the phase relationship
of
these windings with other windings depends on the externar connection
lf HV can be 220 kV or 110 kV (dual voltage) but star-connection is required for both
voltages and the transformer is deliveredin22o kV configuration and LV is t0,5 kV delta
connected:
lf the LV vector grgup is reconfigurable without changing the rated voltages (11 kV in
this example) and the transformer is delivered in d11 anO tne HV is '110 kV star eonnected.
7.1.5 Examples
Examples are shown below and their graphical representations are shown in Figures 2 and 3.
12
,{--f,\
tfi %t
rit ill
al1
t{
12
A/{-f,l'\I
ill
\D/ 12
/<1>.
Dynl 1
ffiYNyn0d5
ffi,)
K'V
YNaOd1 1
ll ll't: delta winding is. not brought out to three tine terminats but onty prouioeo as a
stabilizing winding, the symodt wourd indicate this o}, a prus sign.
displacement notation wourd then appry for the staoiLiiing No phase
;rnding.
400 lt30
Symbol: YNa0+d -/ I l22kv
43 "13
The symbol would be the same for a three-phase auto-transformer
same connection, internally with the exception of the voltage notation. with the
below.
See exampte
ilil|
tilill
iltffi
-;; \-),
|l|lll
ffi
ffi iti
v-l-)'/ l'l'l
ili Diii
;EC 68y1t
|
Figure 3 - lllustration of .clock number' notation for
transformers with open windings
A three-phase transformer designed for a 20 kV detta
connected HV and with a 10
kV open winding.
7.2.1 Connectionsymbol
The connection of a set of phase windings of single-phase
transformers is indicated by the
capital letter I for the high-voltage (HV) winOing ani
smalt letter i for the intermediate and low-
voltage (LV) windings.
Symbol: li0+i.
7.2.4 Reconnectablewindings
lf a transformer is specified with a reconfigurable winding connection, the alternative coupling
voltage and connection is noted in brackets after the delivered configuration aq indicated by
the following examples
lf HV can be220 kV or 110 kV (dual voltage) butwith the same connection required
for both voltages ,
Symbol: li0
220 (110) | 27,5
KV
lf the LV vector group is reconfigurable without changing the rated voltages (11 kV
in this example) and the transformer is delivered in i0 and the HV is 110 kV:
Symbol: li0 (i6) 110/11kV
Examples
Examples are shown below and some of their graphical representations are on Figure 4
1a
XT>'..
ft1
t-- 1
i Kot/
I I
12 lz 12'
/(-il^ /<1tl}'.
r'1-\
tt1 Fr1
I
r-1
vv
\{-]_y
lz
I I
Kot/ I kjt 12t
\/
/<T>\
Dt1
\-v
z<-D\
r.-1t-l r'T\
r--
{Ly |l] Kd9. I K+t/
ti0i6 la0i0
lf the third winding is not intended to be loaded, the symbol would indicate this by
a plus sign. No phase displacement notation would then apply for the thirQ winding.
SYmbol: li0+i 400 t 130 | 22 kv '.' i;
"
Rating plates
8.1 General
The transformer shall be provided with a rating plate of weatherproof material, fitted in a
visible position, showing the appropriate items indicated below. The entries on the plate shall
be indelibly marked.
The Information listed below shall be included on the rating plate when it is applicable to
a particular transformer.
a) For transformers having one or more windings with 'highest voltage for equipment'
U* equal to or above 3,6 kV:
short notation of insulation levels (withstand voltages) as described in IEC 60076-3.
b) Tapping designations
For transformers with highest rated voltage less than or equal to 72,5 kV and
with rated power less than or equal to 20 MVA (three phase) or 6,7 MVA (singie
phase)
having a tapping range not exceeding t5 %, tapping voltages on the tapped wind
ing for all tappings.
For all other transformers
o a table stating tapping voltage and maximum allowable tapping service volt-
age, tapping current, tapping power, and internal connection for all tappings,
r a table showing the short-circuit impedance values for the principal tapping and
at least the extreme tappings in % with the reference power.
c) Guaranteed maximum temperature rises of top liquid and windrngs (if not normal values).
When a transformer is intended for installation at high altitude, the altitude, power rating
Plates with identification and characteristics of auxiliary equipment according to standards for
such components (bushings, tap-changers, current transformers, special cooling equipment)
shall be provided either on the components themselves or on the transformer.
9.1.2 Safetyconsiderations
The manufacturer shall consider the safety of operators and maintenance staff in the
design of the transformer in particular the following aspects:
Cusromer. Serkan Kog - No. of User"is): 1 - Conrpany: OZGUNEY ELE(TRIK
Or<ler No.: WS-201 1-010231 - IMPORTANT; This file is copyright ol 1EC, Geneva, Switzerland. Aii rights reterved.
l-his iiie is subject to a lir:errce ?greenref)t. €nquiries to Enraitr: [email protected] - Tel.: +41 22 919 02 1i
-42- 60076j1 O IEC:2011
Where installation may affect any of the above, suitable installation instructions shall
be provided with the transformer.
NOTE ISO 14122 series, Safety of machinery - Permanent means of access to machinery, should be consult-
ed where ladders, platforms and similar means of access are provided with the transfolmer.
The neutral conductor and terminal of transformers not intended to carry load between phase
and neutral shall be designed to carry earth-fault current as if the transformer was directly
earthed
The size of the conservator or expansion system shall be sufficient to accommodate the
change in liquid volume from the coldest ambient when the transformer is de-energized to the
highest mean liquid temperature experienced when the transformer is loaded tb the highest
level allowed by the provisions of the loading guide in IEC 60076-7 for mineral oil or as
specified for an alternative cooling liquid.
NOTE Allowance should be made for the variation ot the coefficieni of thermal expansion that may
be experienced for different iiquids of the same type.
i., L,,1 iir-i riL:I Serkan Kcq - l"Jo. i - Cornl.rar'ry. OZGUhIEY ELEh'iRiK
ui Useris):
t|c€r i'd(]. \rv'S-201 1-010231 - iMPORTANT: This file is copyrigfrt rtl tEC. Geneva, Srrilzerland. All righis re*ertr:C
3li- I
60076-1 o IEC:2011 -43-
9.4 DC currents in neutral circuits
flowing through
A transformer wrth a grounded neutral can be influenced by DC currents
the neutral. For example, the DC current can be generated by'
DC traction systems;
cathodic Protection systems;
rectifier systems;
geomagnetically induced currents (GlC).
The phenomenon depends on the ability of the DC current to magnetize the core and on the
core design. The resulting effects are a function of the magnitude and duration of the DC
current, core type and general iransformer design features.
lf a transformer may be subject to DC currents, then the levels of these currents shall be
stated by the purchaser in the enquiry together with any required limits on the consequences
of these current levels. See also 4.11 of IEC 60076-8:1997.
10 Tolerances
It is not always possible, particularly in large, multi-winding transformers with relatively low
rated voltages, to accommodate turns ratios which correspond to specified tated voltage
ratios with high accuracy. There are also other quantities which may not be accurately
explored at the time of tender, or are subject to manufacturing and measuring uncertainty.
A transformer is considered as complying with this part when the quantities subject to
tolerances are not outside the tolerances given in Table 1. Where a tolerance in one direction
is omitted, there is no restriction on the value in that direction.
This clause is for the purposes of acceptance or rejection only and does not replace the
purchasers' prescribed guarantees for economic evaluation purposes (for example penalties
on losses). lt does not take precedence over any limits specified in the enquiry.
Table 1 - Tolerances
b) Measured component losses See Note 1 +15 s/o ol each component loss, provicled thal the
tolerance tor total losses is not exceeddd
2. Measured voltage ratio at no load on princlpal The lower of the following values:
tapping for a specified first pair of windings or the a) 4.5 oh of the sPecified ratio
extreme tapPings, if sPecified
b) +1110 of the actual percenlage impedance on
the princiPal taPPing
Measured voltage ratio on other tappings, same pair +0,5 o/o of the design value of turns ratiq
b) any other tapping of the pair When the impedance value is >10 o/o
NOTE 1 The loss tolerances of multi-winding transformers apply to every pair of windings unless the guarantee
states that they apply to a given load condition.
NOTE 2 For certain auto-transformers and series transformers the low value of their impeOanle may justify a
more liberal tolerance. Transformers having large tapping ranges, particularly if the range is asymmetrical, may
also require special consideration. On the other hand. for example, when a transformer is to be combined with
previously existing units, it may be justified to specify and agree on narrower impedance tolerances. Any special
tolerances should be indicated in the enquiry, and any revised tolerances agreed upon between manufacturer and
pu rch a ser.
'|.1 Tests
11.1 General requarements for routine, type and special tests
11.1.1 General
Transformers shall be subjected to tests as specified below.
Tests other than temperature rise tests shall be made at an external cooling medi-
um temoerature between 10'C and 40'C. See IEC 60076-2 for temperature rise tests.
Tapped windings shall be connected on their principal tapping, unless the relevant test
clause requires otherwise or unless the manufacturer and the purchaser agree otherwise.
The test basis for all characteristrcs other than insulation is the rated condition, unless
the test clause states otherwise.
All measuring systems used for the tests shall have certified, traceable accuracy and
be subjected to periodic calibration, according to the rules given in ISO 9001.
Specific requirements on the accuracy and verification of the measurtng systems
are described in IEC 60060 series and IEC 60076-8.
Where it is required that test results are to be corrected to a reference temperature, this
shall be:
a) for dry-type transformers, the reference temperature shall be according to the gener-
al requirements for tests in IEC 60076-11;
b) for liquid-immersed transformers with rated average winding temperature rise less than
or equal to 65 K for OF or ON, or 70 K for OD;
1) reference temperature is 75 "C; I
Any inability of the manufacturer to perform the test or measurement at the rated freguency
shall be stated by the manufacturer at the tender stage and appropriate convdrsion factors
agreed.
The following list of tests is not in any specific order. lf the purchaser requires the
tests performed in a particular order, this shall be included in the enquiry.
11.1.2 Routine tests
11.1.2.1 Routine test for all transformers
a) Measurement of winding resistance (11.2).
b) Measurement of voltage ratio and check of phase displacement (11.3).
c) Measurement of short-circuit impedance and load loss(11.4).
d) Measurement of no-load loss and current (11.5).
e) Dielectric routine tests (lEC 60076-3).
f) Tests on on-load tap-changers, where appropriate (11.7).
g) Leak testing with pressure for liquid-immersed transformers (tightness test) (11.8).
h) Tightness tests and pressure tests for tanks for gas-filled transformers (refer to
60076-
15)
i) Check of the ratio and polarity of built-in current transformers.
j) Check of core and frame insulation for liquid immersed transformers with core or
rame insulation (11 .12\.
f
d)Measurementofthepowertakenbythefanandliquidpumpmotors'l
e) Measurement of no-load loss and current at 90 % and 110 o/o ol rated voltage'
Other tests for transformers may be defined in the specific documents for special-
ized transformers such as dry-type, self-protected and other groups.
tf test methods are not prescribed in this standard, or if tests other than those listed above
are specified in the contract, such test methods are subject to agreement.
In all resistance measurements, care shall be taken that the effects of setf-induction
are minimized
11.2.2 Dry-typetransformers
Before measurement the external cooling medium tcmperature shall not have changed by morc than J 'C'
fbr at leasr 3 h and all winding temperatures of the transformer measured by the internal
temperature
temperature sensors shall not differ from the external cooling medium
Dy
windlng resrstance and winding temperature shall be measured at the same positions'
time-- The
winding temperature shall be measured by sensors placed at representative
and low-
preferabty inside the set of windings, for example, in a duct between the high-voltage
voltage windings.
ln measuring the cold resistance for the purpose of temperature-rise determination, special
efforts shall be made to determine the average winding temperature accurately. Thus, the
difference in temperature between the top and bottom liquid shall not exceed 5 K. To obtain
this result more rapidly, the liquid may be circulated by a pump'
The measured value of load loss shall be multiplied with the square of the ratio of rated
current (tapping current) to test current. The resulting figure shall then be corrected to
reference temperatu.re (11.1). The /2R loss (R being d.c. resistance) is takeh as varying
directly with the temperature and all other losses inversely with the temperature. The
measurement of winding resistance shall be made according to 11.2. The temperature
correction procedure is detailed in Annex E.
The short-circuit impedance is represented as reactance and a.c. resistance in series. The
impedance is corrected to reference temperature assuming that the reactance istconstant and
that the a.c. resistance derived from the load loss varies as described above.
On transformers having a tapped winding with tapping range not exceeding t5 %, tne
short-circuit impedance shall be measured on the principal tapping.
For transformers with tappings exceeding a voltage variation of 5 % from the principal
tapping, impedance values shall be measured for the principal tapping and the extreme
tapping(s) exceeding 5 %. Measurements at other tap positions may be specified in the
enq u rry.
For a three-phase transformer, the selection of the winding and the connection to the test
power source shall be made to provide, as far as possible, symmetrical and sinusoidal
voltages across the three phases.
The test voltage shall be adjusted according to a voltmeter responsive to the mean value of
voltage but scaled to read the r.m.s. voltage of a sinusoidal wave having the same mean
value. The reading of this voltmeter is Ul
At the same time, a voltmeter responsive to the r.m.s. value of voltage shall be connected
in parallel with the mean-value voltmeter and its indicated voltage U shall be recorded.
When a three-phase transformer is tested, the voltages shall be measured between line
terminals, if a delta-connected winding is energized, and between phase and neuiral terminals
if a YN or ZN connected winding is energized.
Phase to phase voltages may be derived from phase to ground measurements,,but phase
to neutral voltages shall not be derived from phase to phase measurements.
The test voltage wave shape is satisfactory if the readings U'and U are equal within 3 o/o. lf
the difference between voltmeter readings is larger than 3 %, the validity of the test is subject
to agreement. A larger difference may be acceptable at higher than rated voltage unless this
measurement is subject to guarantee.
NOTE 1 lt as recognlzed that the most severe loading conditions for test voltage source accuracy are
usually imposed by large single-phase transformers.
The measured no-load loss is Pn",, and the corrected no load loss is taken as:
Po= P^ (1 + d)
.l
Custorrer. Serkan Koe - No. ol User(s;: - Company: OZGUNEY ELEKTR|K
Or-der rr-o.: !!S-2011-010231 - lI\4PORTANT: Tt.ris {ile is copyriqht of lEC, Geneva. S.rt'itzerland. Ail r;ghts reserved.
Thjs file is sub.iecl to a licence agreement. Enquir:es to Ernbit: ;[email protected] - Te;.: +41 22918A2-11
-50- 60076-1 C IEC:2011
ul' ..-..r"
I II
(usuallY negative)
d=
U'
For
The r.m.s. value of no-load current is measured at the same time as the loss'
a
phases is taken'
three-phase transformer, the mean value of readings in the three
The no load losses shall not be corrected for any effect of temperature'
in mind that
NOTE 2 In deciding the place of the no-load test in the complete tesl sequence, it shguld be borne
are, in general,
no-load toss measurements performed before impulse tests andlor resistance measurements
representative of the average loss level over long iime in service, assuming, that lhe core is notrpre-magnetized'
tests, th€ core
That means, if no-load testJare carried out after resistance measurements and/oI lightning impulse
out'
of the transformer should be demagnetized by overexcitation before the no-load test is carried
The zero-sequence rmpedance is measured at rated frequency between the line terminals of a
star-connected or zigzag-connected winding connected together, and its neutral terminal- lt
'iu
expressed in ohms per phase and is given by
'" , vv5gls U is the test voltage and / is the test
current.
In the case of a transformer with an additional delta-connected winding, the value of the test
current shall be such that the current in the delta-connected winding is not excessive, taking
into account the duration of application.
lf winding balancing ampere-turns are missing in the zero-sequence system, for example, in a
star-star-connected transformer without delta winding, the applied voltage shall not exceed
the phase-to-neutral voltage at normal operation. The current in the neutral and the duration
of application should be limited to avoid excessive temperatures of metallic constructional
parts.
In the case of transformers having more than one star-connected winding with neutral
terminal, the zero-sequence impedance is dependent upon the connection (see 3 7 3) and the
tests to be made shall be subject to agreement between the manufacturer and thb purchaser.
For YD transformers, the zero sequenoe impedance is measured from the Y slde only.
a) with the transformer de-energized, eight complete cycles of operation (a cycle of oper-
ation goes from one end of the tapping range to the other, and back again).
b) with the transformer de-energized, and with the auxiliary voltage reduced to 85 % of
its rated value, one complete cycle of operation.
c) with the transformer energized at rated voltage and frequency at no load, one com-
plete cycle of operation.
d) with one winding short-circuited and, as far as practicable, rated current in the tapped
winding, '10 cycles of tap-change operations across the range of two steps on each side
from where a coarse or reversing changeover selector operates, or otherwise from the
middle tapping (the tapchanger will pass 20 times through the changeover position).
11.8 Leak testing with pressure for liquid immersed transformers (tightness test)
The transformer manufacturer shall perform an agreed test to prove the transformer tank will
not leak in service. lf there is no agreement, a pressure of at least 30 kPa over the normal
liquid pressure shall be applied and maintained for 24 h for transformers greater'than 20 MVA
or 72,5 kV, and 8 h for transformers of lower rating and voltage. Typically, this is applied
either using a liquid column or gas pressure in the conservator. Thereafter, the entire
transformer shall be visually inspected for leaks. For tanks that are specifically designed to be
flexible for liquid expansion (corrugated), leak and lifetime tests need to be agreed.
Where specified the deflection of the tank when vacuum is applied and the perma-
nent deflection of the tank when the vacuum is released shall be measured"
The test shall be carried out on the transformer when it is complete in all relevant
respects and on all compartments that require vacuum to be applied on-site"
Before vacuum is applied, a suitable measuring reference point, attached rigidly to the test
room structure or floor, independent of the transformer shall be established as close as
possible to the point on the tank where the maximum deflection under vacuum is expected.
The distance from the reference point to the tank wall in a direction approximately normal to
the tank wall shall be measured and noted. l
i
L!srom€r. Serkan l(r:q - No. of Use(sj' - Company: OZGUNFY E.EKTRIK
Order Nc.: \rVS-201 1-010231 - IMPORTANT: This file is copyright oi lEC. Geneva. S'criueriand. A!i !-ignts !-eserleii.
T;'rrs fiie is srbject ts a iicence agreement. Enquiries ic Ernail: ci:[email protected] - Tei.. +41 22 919 C2 11
- 52 - 60076-1 I IEC:
201 1
Following the application of the vacuum to the level required for the
site. operation ' the
a approximately normal to the
distance from the reference point to the tank wall in direction
between
under vacuum is the difference
tank wall shall be measured again. The deflection
this measurement and the first measurement.
The vacuum shall then be released and a third measurement of the distance frorn the
reference point to the tank wall in a direction approximately normal to the tank wall shall be
taken The permanent deflection is the difference between this measurement' and the first
measurement.
Normally the expected deflection under vacuum and the permanent dellection shall be
catculated and declared by the manufacturer before the test. Alternatively the following typical
values shall be used:
The test shall be carried out on the transformer when it is complete in all relevant re-
spects and filled with liquid lt shall be carried out on all separate compartments that contain
liq u id.
Unless otherwise specified, the test pressure in the tank shall be 35 kPa over the normal
operating pressure. lf the transformer is fitted with pressure relief devices, the pressure,
applied during this test shall exceed the pressure required to operate the pressure relief
device by at least 10 kPa. Pressure relief devices will therefore need to be blanked off during
this test.
NOTE The specified overpressure may conveniently be applied by adjusting the heighl of a liquid column
(for example by lifting a separate conservator attached to a crane).
Before pressure is applied, whilst the tank is at its normal working liquid levdl, a suitable
measuring reference point, attached rigidly to the test room structure or floor, independent of
the transformer shall be established as close as possible to the point on the tank where the
maximum deflection under pressure is expected, taking into account the expected deflection.
The distance from the reference point to the tank wall in a direction approximately normal to
the tank wall shall be measured and noted.
Following the application of the additional pressure, the distance from the reference point to
the tank wall in a direction approximately normal to the tank wall shall be mea,sured again.
The deflection under oressure is the difference between this measurement and the first
measurement.
The pressure shal then be reduced back to the originally established level and a third
measurement of the distance from the reference point to the tank wall
in a direction
approximately normal to the tank wall shall be taken. The permanent deflectton is the
difference between this measurement and the first rneasurement
Normally the expected deflection under pressure and the permanent deflection shall be
calculated and declared by the manufacturer before the test' Alternatively the following
typical
values shall be used:
lf the expected values are exceeded, the test shall be repeated to see if the tank dimensions
have stabilized. lf not, remedial actions, for example adding additional stiffening to the tank,
shall be carried out.
A vacuum to the highest level required by the site operation shall be applied fdr a period of
two hours or until a stable vacuum level is obtained. The vacuum pump shall then be stopped
and the transformer sealed.
The vacuum inside the transformer shall then be monitored, using a suitabie vacuurn gauge
until a steady rate of change of vacuum is observed. The increase in pressure shall be less
than 0,2 kPa per hour measured over a period of at least 30 min.
For transformers where the core and frame earth connections are not accessible when the
transformer is liquid filled, the insulation shall be tested at 500 V d.c. for 1'min without
breakdown before the active oart is installed in the tank.
For transformers where the core and frame earth connectrons are accessibie when the
transformer is liquid filled, the insulation shall be tested at 2 500 V d.c. for 1 min without
breakdown after the transformer is filled with liquid.
NoTE 2 passive etsments are not lieble to cause electromagnetic disturbances and their p"ko't"n"" i"
Switching tighily toaded andlor low power factor (inductively loaded) trangformers with
-""0-SF.
;;;il; 'fvlHzthe
interrupters may subject transformer to potentially damaging voltage
transients with f-requencies up to the -notand
range voltages exceeding the transformer
impulse withstand. Mitigation measures, while part of the transformer, might include
means to increase damp-ing through resistor-capacitor snubbers, pre-insertion resistors within
the switches, or switching-under load. lf speciiied by the purchaser, the mandfacturer shall
ptouide details of natural iesonant frequencies andlor high frequency model parameters of the
transformer. '
NOTE MorE information is ayaileble in IEEE C57.142 Guide to describe the occurrence and mitigation
of switching transients induced by transformer, switching device, and system inleraclion
w-sssttns'*?{h
e) Frequency.
f) Dry-type or liquid-immersed type. lf liquid-immersed type, whether mineral oil, natural
insulating liquid or synthetic insulating liquid. lf dry-type, degree of protection (see
rEc 60s29).
g) lndoor or outdoor type.
h) Type of cooling.
i) Rated power for each winding and, for tapping range exceeding !5 %, the spec-
ified maxrmum current tapping, if applicable
lf the transformer is specified with alternative methods of cooling, the respective lower
power values are to be stated together with the rated power (which refers to the rnost
efficient cooling).
j) Rated voltage for each winding.
k) For a transformer with tappings (see 6.4):
whether'de-energized' or'on-load' tap-changing is required;
- any requirements for fixing the ratio of turns between two particular windings on
a more than two winding transformer,
- whether any tapping or range of tappings can be reduced power tappings,
- the number of tapping steps and the size of the tapping step or the tapping range;
and either:
which winding is tapped;
if the tapping range is more than t5 %, the type of voltage variation, and
the location of the maximum current tapping, if applicable,
nl
.*us$u***
lf this transformer shall have reduced power tappings, say, from tapping -O %, adO:
maximum current tapping: tapping -G %
The tapping current of the HV winding is then limited to 372 A from the tapping -6 % to
the extreme tapping -1Oo/o where tapping power is reduced to 38,3 MVA.
6 = 6.32 kV to 6 = 5.22 kY
0,95 1,15
lf this transformer shall have reduced power tappings, add for example:
maximum current tapping taPPing +$ o7o
The 'tapping current' of the untapped winding (LV) is then limited to 2 020 A from the tapping
+5 % to the extreme tapping +15 o/o where the tapping power is reduced to 18,3 MVA.
tl\
KV KV A A s
18,43 't25,6 1 155 36,46
1 (+15 %) 9.20 169,6
136,2 1 155 40
7 (+6 o/o) 8,48 169.6
144 .4 1 155 40
11 (0 %) 160
20
.FQ A 'l 155 40
17 \-9 %) 145,6
158.7 'r 080 37 ,4
21 (-15 %) 6.80 20
The difference is that the HV tapping vottage, according to the example, does not.exceed
the'system highest
value). The quantity'highest voltage for equipment'
voltage,of the HV system, which'is llOxV lieb stanOarOized
which characterizes the insulation of the winding, is also 170 kV (see IEC 60076-3)'
Unless otherwise specified, the maximum operating voltage is to be taken as being on any
tapping and is an upper limit on the voltage on all windings simultaneously, for example a
step d6wn transformer with a +15 o/o LV tapping and a specified maximum operating voltage of
+10 oh of rated voltage will not be used at no load on that tapping at HV voltages exceeding
-5 % of rated voltage, but on load, the tapping may be used at higher HV voltages to
compensate for voltige drop in the transformer Short periods of operation at higher LV
voltage may be required under load rejection situaiions'
The current on the load side is given by the rated power divided by the rated voltage (at the
principal tapping). A transformeispecified according to 6.4.3 will be capable of dupplying this
load current at all tapping positions. Alternatively, the load current capability may be specified
for each tapping.
particular care needs to be given to the specification of impedance in percentaEe terms an0
the basis in terms of voltage and power shall either be explicit or follow the conventton
that
B.4.1Example4.1-TransformerspecifiedwithHVvo|tagevariation
Transformer to be surtable for step down operation i
rated power s': 70 MVA at principal tapping
rated voltages: 220 kV / 90 kV
maximum oPerating voltage: +10 ok
number of taPPing stePs: 26
o/o
variation on HV voltage: +10 o/o
-15
impedance.. 10 % on all tappings on 70 MVA base
minimum full load Power factor: 0'8
'7d 76 4,28
7 (+5 o/o) 2,57 231 YU z.1z 9V 175 449
a referred to 7 MVA
NOTE 1 The shori circuit current available at the LV terminals with 220 kV applied to the HV terminals rs
calculated as follows assuming no system network impedance.
220 100 s
/sc -lx/tu x'-- x r
uHv t St"o
NOTE 2 The impedance z in the example is constant with tap position for simplicity. This is not necessar,ly a
realistic situation.
NOTE 3 The impedance of the transformer in terms of ohms per phase is calculated as follows
)
zU HV
Lu.' A-
100
-
s-
e
Rated tapPing Max 1l o/o oara[ taq )ir{pn0 0tSVAircuit sc
voltage continuoqgi gg taPPing povvet impedance current
voltage (on current available
loadI on LV at
220 kv
a referred to 70 /lVA,
Specification of short-circuit
impedance bY boundaries
30
28
26
t
(,
24
22
o
c(s
!t0t 20
CL
.E 18
16
14
EC Aav'r1
The upper boundary is a constant value of short-circuit impedance as a percentage, which is detErmined by the
permissible voltage drop at a specified loading and at a specified power factor.
The lower boundary is determined by permissible overcurrent on the secondary sicte during a throulh-fault'
The dashed line is an example of a transformer short-circuit impedance curve which would satisfy this
specification.
q.sss$re$'sq\h
Examplesofthree.phasetransformerconnections
Common connections are shown in Figure D'1 below
rlllll al)? I
???
A
IQ? +
ill
lll
y0
tf
ltJul
Dd0
I tl ,/'\ lfIt-Jllu tl
Dz9
I
iiiiii ???
??? EQ? + ltl
/--
lll
lll
ltIUUI[ [ /\/\
lffi
|l || tl
\
lll
lll
lr#
n
l"-l
|| tt
tt? ??? I
??? t
lH
+
lll
lrl
I
I
[
lllu"l[ /'\ ttl
I
Yd5 Dv5
??? tt'1 ??? _1_1_1
lilHttl (
[l""ll [ lt \
-n-l
I
I[[|
r..l--r--1_t
U
L-.] LJ
I
|| ff-rr
Iil
l-"-l
-"^\
il ill
#l+ffi
I
ofe { aot
??? I
Yy6
t_]J
I
Dd6
fl|l ,/'\
Oz6
[l"-l [ tl
???
??? ??? \----7
Iutl Yt
ffifrm
lffi t---
iil il f
tl--t
t
Vi lt nt till
lffill
ll-al--'tl
IJ IJ IJ
{
??? t ?l)? ???
lll
lll -\ Il-"1tf I /'\ tll
lll
d11 Dyl 1 11
e?e \ ??? \
il il ti L.' lll
lrl
)-
tEc 686/11
Conventions of drawing are the same as in Figure 2 (Clause 7) of the main documenl
ot? I .la
ililil
l--l
od2
A 1ilil
Dz2
l'JlJl
e??
ott .t ttl
I lt I ---
f--7 lffi
l| lt tt
a|'? + .?e I
lt I ll
Dd4
A tfItl
Dz4
/\
_L1-1 ???
fiil| /\
D\
||llil
I 'frTr ||l
-lnl-l
||l ft ill
| -F
le-t
-f ---l
I
)*,
fl|l A
oQl + EQ?
ill--l il tl A
/\ l--l
Dd8 Dz8
???
L\
t---
ililtl
lt-"r
eQt afa
A
+
fiil1
Dd10
A [l--l [
DzlO
tl
e??
ef? ttt
l|iltl
IUUI
r-;--;l
ililil
tEC 687/11
Conventions of drawing are the same as in Figure 2 (clause 7) of the main document
l{l
tEc 689t11
List of sYmbols
(11'2)''
lndex 1 refers to measurement of 'cold winding resistance'
loss (1 1'4);
lndex 2 indicates conditions during measurement of load
indicates conditions at'reference temperature' 1'1 );
(1
r
R resistance;
e winding temPerature in 'C;
P load loss;
tapping
I specified toad current for loss determination (rated current,
loading case);
.uirlnt, other specified value related to a particular
a
'additional loss'.
The measured value is R''
The winding resistance measurement is made at a temperature 01'
The measured loss
The load loss is measured with the winding at an average temperatule e2
is of 'onhic loss': /2R, and
referred to specified current I. is P2. Ttnis loss composed
'additional loss': P"t
P^z = Pz -2,'n,
T
L/
ItR" is sum of the d.c. resistive losses in all windings'
At reference temperature 9,, the winding resistance is R,, the additional loss P"r' lhe
whole load loss P..
I
o,
22? + (aluminium)
R, = (copper) R. = R,
R1
#H+ 225+\
For liquid-immersed transformers with reference temperature 75 "C, the formulae become
as follows: I
Rr : Rr R. = R. ,,100, (aluminium)
225+\
"#*(copper)
235 + 02 n 225+02
Par = Pa2 tsar = ra7 300
310
Tap-position Sensor
Active power consumption of motor drive Facility to fit transducer
Diverter switch compartment oil temperature Facility to fit sensor
.i
Cl:sio!-ner. Serxan Kog - No. oi Userisi: - Cornpany. OZGUh]EY Ej-EKTRIK
5r<ier No.: trVS-201 t,CtOZ:t - IMPORTAI'.iT: This iil-e is ccpyrlght of lEC. Genera, Sw;izeriand. All :"ignts {?'srrrel
lnlsfileis*rriliecttoaiicenceaoreemenl Fncr;irlestnFrnaii'r:rrst:;prvl?}ier:r:h-Tei -41 22919i)2i1
60076-1 O IEC:2011
69-
Annex G
(informative)
BibliograPhY
Chapter 421: Pow-
IEc60050-421.'1ggo,InternationalE!ectrotechnicalVocabuIary
er transformers and reactors
I
lEc 60076- 12, power transformers - Part 12: Loading guide for dry-type power transform'
ers IEC 60076-1 3, power transformers - Part 13: Self-protected liquid-filled transformers I
IEC 60076-'15: 2008, Power transformers - Part 15: Gas-fitled power transformers
IEC 60076- i6, power transformers - Part 16 : Transformers for wind turbines applicationt
IEC 6031 O, Railway apptications - Traction transformers and inductors on board rolling stock
IEC/TR 60616: 1978, Terminal and tapping markings for power transformers
IEC/TS 608i5 (alt parts), Selection and dimensioning of high-voltage insulators intended
for use in polluted conditions
1 To be published.
lso .141 22 (all parts), safety of machinery- Permanent means of access to machinery
power
ANSt/tEEE C57.12.90, IEEE standard test code for tiquid-immersed distribution'
and regulating transformers
iEEE C57.142, Guide to describe the occurrence and mitigation of switching tran-
sienfs induced by transformer, switching device, and system interaction
CIGRE Brochure 156, Guide for customers specifications for transformers 100 MVA
and 123 kV and above
Cf GRE Brochure 204, Guide for transformer design review
CIGRE Brochure 343, Recommendations for Condition Monitoring and Condition Assess-
ment Facilities for Transformers