Siemens Thermostat
Siemens Thermostat
Use
The RAA30... room thermostat is used in heating only or cooling only systems to main-
tain the selected room temperature.
Typical use:
• Residential buildings
• Light industrial buildings
In conjunction with
• zone valves, thermal valves
• gas or oil burners
• fans
• pumps
Functions
CE1N3003E
03.10.2008 Building Technologies
Y1 Y2
3001D01
3001D02
Function diagrams T Room temperature
SD Switching differential
ON ON W Room temperature set-
point
Y1 Output signal "Heating"
W
OFF OFF
Y2 Output signal "Cooling"
T[°C] T[°C]
SD SD
Type summary
Equipment combinations
Technical design
Adjustments
The required temperature is selected by a setpoint adjuster on the front of the thermo-
stat.
The setpoint setting range can be mechanically limited by means of setpoint limiter
under the cover.
2/5
Mounting, installation The room thermostat should be located where the air temperature can be sensed as
and commissioning accurately as possible, without getting adversely affected by direct solar radiation or
other heat or refrigeration sources.
Mounting height is about 1.5 m above the floor.
The unit can be fitted to most commercially available recessed conduit boxes or directly
on the wall.
Only authorised personnel may open the unit to perform service
(Caution: AC 24…250 V).
The unit must be isolated from the mains supply before opening.
When installing the unit, fix the baseplate first then hook on the thermostat body and
make the electrical connections. Then fit the cover and secure it (also refer to separate
mounting instructions).
The thermostat must be mounted on a flat wall.
The local electrical regulations must be complied with.
If there are thermostatic radiator valves in the reference room, set them to their fully
open position.
Maintenance The room thermostat is maintenance-free.
Mechanical design The diaphragm is filled with environmentally friendly gas.
The thermostat housing is made of plastic.
Technical Data
Switching capacity
Voltage
• RAA30... AC 24...250 V
• RAA30.16/GR / 30.26/GR AC 230 V +10/-15 %
Power consumption of each LED 0.5 VA (Only RAA30.16/30.26)
Current 0.2…6 (2) A
Frequency 50 or 60 Hz
Operational data Switching differential SD ≤1K
Setpoint setting range 8…30 °C
Environmental conditions Operation to IEC 60721-3-3
Climatic conditions class 3K5
Temperature 0…+50 °C
Humidity <95 % r.h.
Pollution degree Normal, to EN 60730
Transport / storage to IEC 60721-3-2
Climatic conditions class 2K3/1K3
Temperature -20…+50 °C
Humidity <95 % r.h.
Mechanical conditions class 2M2
3/5
Connection diagrams
D1
3003A02
D2
N N S ON/OFF switch
Y1 Control output "Heating",
RAA30 – Heating mode RAA30 – Cooling mode
AC 24…250 V (RAA30 only)
AC230V
(RAA30.16/GR / 26/GR only)
Y2 Control output "Cooling",
AC 24…250 V (RAA30 only)
AC230V
(RAA30.16/GR / 26/GR only)
N Neutral
T Thermostat element
(gas-filled diaphragm)
L L
D1 D1
N N
4/5
Unit
3003M01
RAA30 and
RAA30.16/GR
99,6
96,4 42,8
Baseplate 86
30 30
30
28
86
28
30
3,6
3001M02
28 28 3010M01
Unit :
RAA30.26/GR
113,1
96,4 42,8
Baseplate
Ø 6,4
65 Ø 3,6
50
13
35
99
30
65
11,8
13
16,9
25,5 30
3011M02
86
5/5