RAA30 RAA30.16/GR RAA30.26/GR

Room Thermostat RAA30…


Adjustable room thermostat for heating only or cooling only systems

Room thermostat with manual ON/OFF switch


Two-position control
Switching voltage AC 24…250 V

Use

The RAA30... room thermostat is used in heating only or cooling only systems to main-
tain the selected room temperature.

Typical use:
• Residential buildings
• Light industrial buildings
In conjunction with
• zone valves, thermal valves
• gas or oil burners
• fans
• pumps

Functions

The front of the unit carries an ON/OFF switch.


OFF In the OFF position, the input voltage is physically separated from the output voltage.
ON The RAA30... room thermostat has separate ouputs for heating only and cooling only. If
the room temperature falls below the selected setpoint, the heating contact will close. If
the room temperature exceeds the selected setpoint, the cooling contact will close.

CE1N3003E
03.10.2008 Building Technologies
Y1 Y2

3001D01

3001D02
Function diagrams T Room temperature
SD Switching differential
ON ON W Room temperature set-
point
Y1 Output signal "Heating"
W
OFF OFF
Y2 Output signal "Cooling"
T[°C] T[°C]
SD SD

Type summary

Functionality Order number (ASN)


Thermostat for heating or cooling application with RAA30
ON/OFF switch
Operating voltage AC 24...250 V
Thermostat for heating or cooling application with RAA30.16/GR
ON/OFF switch and operation mode indication (LED)
Operating voltage AC 230 V + 10/-15 %.
Thermostat for heating or cooling application with RAA30.26/GR
ON/OFF switch and operation mode indication (LED) and
independent ON/OFF switch
Operating voltage AC 230 V + 10/-15 %.

Equipment combinations

Type of unit Type reference Data sheet


Motoric on/off actuator SFA21... 4863
Electric actuator (for small valves) SFP21… 4865
Thermal actuator (for radiator valve) STA21... 4877
Thermal actuator (for small valve 2,5 mm) STP21... 4878
Accessories

Description Type reference


Adapter plate 120 x 120 mm for 4“ x 4“ conduit boxes ARG70
Adapter plate 96 x 120 mm for 2“ x 4“ conduit boxes ARG70.1
Adapter plate for surface wiring 112x130 mm ARG70.2

Technical design

Key features of the RAA30... room thermostat:


• Two-position control
• Manual ON/OFF switch
• Gas-filled diaphragm

Adjustments

The required temperature is selected by a setpoint adjuster on the front of the thermo-
stat.
The setpoint setting range can be mechanically limited by means of setpoint limiter
under the cover.

2/5

Siemens Room Thermostat RAA30... CE1N3003E


Building Technologies 03.10.2008
Notes

Mounting, installation The room thermostat should be located where the air temperature can be sensed as
and commissioning accurately as possible, without getting adversely affected by direct solar radiation or
other heat or refrigeration sources.
Mounting height is about 1.5 m above the floor.

The unit can be fitted to most commercially available recessed conduit boxes or directly
on the wall.
Only authorised personnel may open the unit to perform service
(Caution: AC 24…250 V).
The unit must be isolated from the mains supply before opening.
When installing the unit, fix the baseplate first then hook on the thermostat body and
make the electrical connections. Then fit the cover and secure it (also refer to separate
mounting instructions).
The thermostat must be mounted on a flat wall.
The local electrical regulations must be complied with.
If there are thermostatic radiator valves in the reference room, set them to their fully
open position.
Maintenance The room thermostat is maintenance-free.
Mechanical design The diaphragm is filled with environmentally friendly gas.
The thermostat housing is made of plastic.

Technical Data

Switching capacity
Voltage
• RAA30... AC 24...250 V
• RAA30.16/GR / 30.26/GR AC 230 V +10/-15 %
Power consumption of each LED 0.5 VA (Only RAA30.16/30.26)
Current 0.2…6 (2) A
Frequency 50 or 60 Hz
Operational data Switching differential SD ≤1K
Setpoint setting range 8…30 °C
Environmental conditions Operation to IEC 60721-3-3
Climatic conditions class 3K5
Temperature 0…+50 °C
Humidity <95 % r.h.
Pollution degree Normal, to EN 60730
Transport / storage to IEC 60721-3-2
Climatic conditions class 2K3/1K3
Temperature -20…+50 °C
Humidity <95 % r.h.
Mechanical conditions class 2M2

3/5

Siemens Room Thermostat RAA30... CE1N3003E


Building Technologies 03.10.2008
Norms and standards conformity
Low voltage directive 2006/95/EEC
Product standard EN 60730
N474
C-Tick conformity to
EMC emission standard AS/NSZ 4251.1:1994
Safety standard II to EN 60730
Degree of protection IP30 to EN 60529
Screw terminals for 2 x 1.5 mm2 or 1 x 2.5 mm2, min. ( 0.5 mm2 )
Weight 0.14 kg
Colour of top cover white, NCS 50502-G (RAL 9003)

Connection diagrams

L L D1 Zone valve or thermal valve for


L L
heating
S S
D2 Zone valve or thermal valve for
T T
cooling
Y1 Y2 N1 Y1 Y2 N1 L Switching voltage
AC 24…250 V (RAA30 only)
AC 230 V
(RAA30.16/GR / 26/GR only)
N1 Room thermostat
3003A01

D1

3003A02
D2
N N S ON/OFF switch
Y1 Control output "Heating",
RAA30 – Heating mode RAA30 – Cooling mode
AC 24…250 V (RAA30 only)
AC230V
(RAA30.16/GR / 26/GR only)
Y2 Control output "Cooling",
AC 24…250 V (RAA30 only)
AC230V
(RAA30.16/GR / 26/GR only)
N Neutral
T Thermostat element
(gas-filled diaphragm)
L L

L4, L5 Input AC 230 V


L L4 L L4 L5
S S SA
L50 Output
T T SA Auxiliary switch
Y1 Y2 N N1 Y1 Y2 N L50 N1
3003A04
3003A04

D1 D1
N N

RAA30.16/GR – Heating mode RAA30.26/GR – Heating mode

4/5

Siemens Room Thermostat RAA30... CE1N3003E


Building Technologies 03.10.2008
Dimensions

Unit

3003M01
RAA30 and
RAA30.16/GR

99,6
96,4 42,8

Baseplate 86
30 30

30
28
86
28
30

3,6
3001M02

28 28 3010M01

Unit :
RAA30.26/GR
113,1

96,4 42,8
Baseplate
Ø 6,4
65 Ø 3,6
50
13

35
99
30

65
11,8

13
16,9
25,5 30
3011M02

86

5/5

Siemens Room Thermostat RAA30... CE1N3003E