Data sheet 6EP3436-8SB00-0AY0
SITOP PSU8200/3AC/24VDC/20A
SITOP PSU8200 24 V/20 A stabilized power supply input: 400-500 V 3 AC
output: 24 V DC/20 A *Ex approval no longer available*
Input
type of the power supply network 3-phase AC
supply voltage at AC
● minimum rated value 400 V
● maximum rated value 500 V
● initial value 320 V
● full-scale value 575 V
design of input wide range input Yes
operating condition of the mains buffering at Vin = 400 V
buffering time for rated value of the output current in the 15 ms
event of power failure minimum
operating condition of the mains buffering at Vin = 400 V
line frequency
● 1 rated value 50 Hz
● 2 rated value 60 Hz
line frequency 47 ... 63 Hz
input current
● at rated input voltage 400 V 1.2 A
● at rated input voltage 500 V 1A
current limitation of inrush current at 25 °C maximum 16 A
I2t value maximum 0.8 A²·s
fuse protection type none
● in the feeder Required: 3-pole connected miniature circuit breaker 6 ... 16 A
characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or
3RV2711-1DD10 (UL 489)
Output
voltage curve at output Controlled, isolated DC voltage
output voltage at DC rated value 24 V
output voltage
● at output 1 at DC rated value 24 V
relative overall tolerance of the voltage 3%
relative control precision of the output voltage
● on slow fluctuation of input voltage 0.1 %
● on slow fluctuation of ohm loading 0.2 %
residual ripple
● maximum 100 mV
voltage peak
● maximum 200 mV
adjustable output voltage 24 ... 28 V
product function output voltage adjustable Yes
6EP34368SB000AY0 Subject to change without notice
4/4/2022
Page 1/3 © Copyright Siemens
type of output voltage setting via potentiometer; max. 480 W
display version for normal operation Green LED for 24 V OK
type of signal at output Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"
behavior of the output voltage when switching on No overshoot of Vout (soft start)
response delay maximum 2.5 s
voltage increase time of the output voltage
● maximum 500 ms
output current
● rated value 20 A
● rated range 0 ... 20 A; +60 ... +70 °C: Derating 2%/K
supplied active power typical 480 W
short-term overload current
● at short-circuit during operation typical 60 A
duration of overloading capability for excess current
● at short-circuit during operation 25 ms
constant overload current
● on short-circuiting during the start-up typical 22 A
product feature
● bridging of equipment Yes; switchable characteristic
number of parallel-switched equipment resources for 2
increasing the power
Efficiency
efficiency in percent 94 %
power loss [W]
● at rated output voltage for rated value of the output 31 W
current typical
Closed-loop control
relative control precision of the output voltage with rapid 0.1 %
fluctuation of the input voltage by +/- 15% typical
relative control precision of the output voltage load step of 1%
resistive load 50/100/50 % typical
setting time
● load step 50 to 100% typical 0.2 ms
● load step 100 to 50% typical 0.2 ms
relative control precision of the output voltage at load step 2%
of resistive load 10/90/10 % typical
setting time
● load step 10 to 90% typical 0.2 ms
● load step 90 to 10% typical 0.2 ms
● maximum 10 ms
Protection and monitoring
design of the overvoltage protection < 32 V
response value current limitation typical 22 A
property of the output short-circuit proof Yes
design of short-circuit protection Alternatively, constant current characteristic approx. 22 A or latching
shutdown
enduring short circuit current RMS value
● typical 22 A
overcurrent overload capability in normal operation overload capability 150 % Iout rated up to 5 s/min
display version for overload and short circuit LED yellow for "overload", LED red for "latching shutdown"
Safety
galvanic isolation between input and output Yes
galvanic isolation Safety extra low output voltage Vout according to EN 60950-1
operating resource protection class Class I
leakage current
● maximum 3.5 mA
● typical 0.9 mA
protection class IP IP20
Approvals
certificate of suitability
● CE marking Yes
6EP34368SB000AY0 Subject to change without notice
4/4/2022
Page 2/3 © Copyright Siemens
● UL approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259;
cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
● CSA approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259;
cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
● cCSAus, Class 1, Division 2 No
● ATEX No
certificate of suitability
● IECEx No
● NEC Class 2 No
● ULhazloc approval No
● FM registration No
type of certification CB-certificate Yes
certificate of suitability
● EAC approval Yes
● C-Tick Yes
certificate of suitability shipbuilding approval Yes
shipbuilding approval ABS, DNV GL
Marine classification association
● American Bureau of Shipping Europe Ltd. (ABS) Yes
● French marine classification society (BV) No
● DNV GL Yes
● Lloyds Register of Shipping (LRS) No
● Nippon Kaiji Kyokai (NK) No
EMC
standard
● for emitted interference EN 55022 Class B
● for mains harmonics limitation EN 61000-3-2
● for interference immunity EN 61000-6-2
environmental conditions
ambient temperature
● during operation -25 ... +70 °C; With natural convection; startup tested starting from -40
°C nominal voltage
● during transport -40 ... +85 °C
● during storage -40 ... +85 °C
environmental category acc. to IEC 60721 Climate class 3K3, 5 … 95% no condensation
Mechanics
type of electrical connection screw-type terminals
● at input L1, L2, L3, PE: 1 screw terminal each for 0.2 ... 4 mm² single-core/finely
stranded
● at output +, -: 2 screw terminals each for 0.2 ... 4 mm²
● for auxiliary contacts 13, 14 (alarm signal): 1 screw terminal each for 0.14 ... 1.5 mm²; 15, 16
(Remote): 1 screw terminal each for 0.14 ... 1.5 mm²
width of the enclosure 70 mm
height of the enclosure 125 mm
depth of the enclosure 125 mm
required spacing
● top 50 mm
● bottom 50 mm
● left 0 mm
● right 0 mm
net weight 1.2 kg
product feature of the enclosure housing can be lined up Yes
fastening method Snaps onto DIN rail EN 60715 35x7.5/15
electrical accessories Buffer module
mechanical accessories Device identification label 20 mm × 7 mm, TI-grey 3RT2900-1SB20
MTBF at 40 °C 590 573 h
other information Specifications at rated input voltage and ambient temperature +25 °C
(unless otherwise specified)
6EP34368SB000AY0 Subject to change without notice
4/4/2022
Page 3/3 © Copyright Siemens