ADVANCE JOB SPECIFICATION 

Drawing No: Status:


The information contained in
1YEM037911A0000 APPROVAL this document has to be kept
strictly confidential.
Shop Order No.: Line Item No.: Serial No.: Any unauthorized use,
SLPB0379 A01 1YEC212457A10 reproduction, distribution or
disclosure to third parties is
Engineer: Approved: Cust P.O.: strictly forbidden. ABB reserves
GGM JTL 1161 all rights regarding Intellectual
Date: Date: Rev: Property Rights.
© Copyright 2024 ABB.
9/12/24 9/12/24 0 All rights reserved.

Rev. GENERAL INFORMATION

Sold To: POTENCIA TOTAL For: POTENCIA TOTAL


S.A. DE C.V. S.A. DE C.V.
Modernización Celdas PROLEC Project
TMT-01

UL Label: CSA Label: IBC Cert: Nuclear Cert:

Product Type: ADVANCE

Rated Voltage: 15kV

System Voltage: 13.8kV

Main Bus Rating: 1200 A

kA Rating: 31.5kA

System Source Type: 3 Phase Wye - Solid Ground

Freq: 60 Hz

Construction: Indoor

Environmental: Standard

Seismic Reinforced: None

Paint Finish: ANSI 61-light gray exterior galvalum interior

Special Color: No

Undercoating:

Mimic Bus: None

Swgr Breakers CT's PT's

Cert Prod Test Reports: X X X X

Cert of Conformance:

Customer Visit: Inspection Test

Sheet 1 of 4
ADVANCE JOB SPECIFICATION 
Drawing No: Status:
The information contained in
1YEM037911A0000 APPROVAL this document has to be kept
strictly confidential.
Shop Order No.: Line Item No.: Serial No.: Any unauthorized use,
SLPB0379 A01 1YEC212457A10 reproduction, distribution or
disclosure to third parties is
Engineer: Approved: Cust P.O.: strictly forbidden. ABB reserves
GGM JTL 1161 all rights regarding Intellectual
Date: Date: Rev: Property Rights.
© Copyright 2024 ABB.
9/12/24 9/12/24 0 All rights reserved.

Rev. MECHANICAL INFORMATION

Frame Construction

Match & Line:

Ref. S.O. Item:

Frame Depth: Special (See Floor Plan)

10" Front Extension: X

Enclosure Vent:

Rear Access: Two Split Bolted Panels w/ Handles

Frame Hrdwr: Grade 5 (Zinc Chromate) Steel

Channel Sills:

Floor Plates: X

Breaker Compartment Cable Compartment

Bkr Pri Bushing: Epoxy Cable Entry: Bottom

Bkr Sec. Plug: Dual Ground Sensors: X

TOC Switch: 8 Pole Surge Arrestors: X

Bkr Shutters: Grounded Metal Cable Lug Boots: X

Bkr Kirk Lock: None Cable Supports: X

Gnd Studs:

Front Door Construction Heater Guards: X

Front Door Hrdwr: MPL-Turn Handle Bus Compartment


All Doors
Front Door Padlck: X Bus Plating: Silver

Front Door Gasket: Bus Hardware: Grade 5 (Zinc Chromate) Steel

Front Door Stop: X Main Bus Sup'ts: Epoxy

RH Hinged Cub 1: Riser Sup'ts: Polyester

SmartRack: None Neutral Bus: None X Grounded

Sheet 2 of 4
ADVANCE JOB SPECIFICATION 
Drawing No: Status:
The information contained in
1YEM037911A0000 APPROVAL this document has to be kept
strictly confidential.
Shop Order No.: Line Item No.: Serial No.: Any unauthorized use,
SLPB0379 A01 1YEC212457A10 reproduction, distribution or
disclosure to third parties is
Engineer: Approved: Cust P.O.: strictly forbidden. ABB reserves
GGM JTL 1161 all rights regarding Intellectual
Date: Date: Rev: Property Rights.
© Copyright 2024 ABB.
9/12/24 9/12/24 0 All rights reserved.

Rev. ELECTRICAL INFORMATION

Wire Markers: Standard - Destination

C.T. Wire Size: #12 AWG SIS

P.T. Wire Size: #14 AWG SIS

Chg/Close Wire Size: #14 AWG SIS

Trip Wire Size: #14 AWG SIS

AC/DC Ctrl Bus Size: #8 AWG SIS

Control Lugs: Insulated Ring Tongue

Terminal Blocks: Phoenix Contact (ABB Standard)

Interior Dev. NP: Typed Mylar Adhesive

Wire Spare Cont: No

Spare Term Pt's: 20%

Wire Duct Required: Yes

Arc Flash Fiber Optic Cable:

Rev. PROJECT NOTES

1. THE CONTROL WIRING TO BE SIS GRAY.


ALL CONTROL WIRING THAT ARE NOT INDICATED ON THE SCHEMATIC DIAGRAMS
WILL BE #14 AWG GAUGE.
THE COLOR OF CONTROL WIRING THAT ARE NOT INDICATED ON THE SCHEMATIC
DIAGRAMS WILL BE GRAY.

2. LOCKING FORKS ARE NOT RECOMMENDED, ESPECIALLY IN DOUBLE-WIRE


CONNECTION POINTS BECAUSE THEY ARE PRONE TO COME LOOSE. ABB
STANDARD PRACTICE IS TO USE RING TONGUE LUGS OR FERRULE, AS REQUIRED.

3. FOR WIRE SIZE UP TO #10AWG: SCREW TERMINAL BLOCKS PHOENIX CONTACT


OTTA6.
FOR WIRE SIZE #8AWG: SCREW TERMINAL BLOCKS PHOENIX CONTACT OTTA 25-
M5.
FOR CT CIRCUITS: SHORTCIRCUITING TERMINAL BLOCKS PHOENIX CONTACT RSC
5.

4. THE CONTROL WIRING CONNECTED DIRECTLY TO THE SPACE HEATERS WILL BE


CABLE TYPE UL 3284, 125°C, BLACK COLOR.

Sheet 3 of 4
ADVANCE JOB SPECIFICATION 
Drawing No: Status:
The information contained in
1YEM037911A0000 APPROVAL this document has to be kept
strictly confidential.
Shop Order No.: Line Item No.: Serial No.: Any unauthorized use,
SLPB0379 A01 1YEC212457A10 reproduction, distribution or
disclosure to third parties is
Engineer: Approved: Cust P.O.: strictly forbidden. ABB reserves
GGM JTL 1161 all rights regarding Intellectual
Date: Date: Rev: Property Rights.
© Copyright 2024 ABB.
9/12/24 9/12/24 0 All rights reserved.

Rev. PROJECT NOTES

5. DRAWOUT CIRCUIT BREAKERS ARE CAPABLE OF BEING LOCKED WITH ONE


PADLOCK IN EITHER THE TEST OR THE DISCONNECT POSITIONS. PADLOCKING
PREVENTS RACKING UNTIL THE LOCK ARE REMOVED. THERE IS ALSO A LOCATION
FOR A LOCK ON THE OUTSIDE OF THE SWITCHGEAR DOOR TO PREVENT RACKING
IN THE SAME MANNER.

6. GROUND BUS EXTENSIONS ARE REQUIRED IN THE REAR CABLE COMPARTMENTS.

7. ADVAC CKT BKR ACCESSORIES INCLUDE: RACKING HANDLE ASSEMBLY, LIFTING


HOOK ASSEMBLY, MANUAL CHARGING HANDLE

8. SHUTTERS SHALL BE CLEARLY MARKED WITH AN INSCRIPTION INDICATING "MAIN


BUS" OR "OUTGOING LOAD" FOR FEEDER CUBICLES, "INCOMING LINE" OR "MAIN
BUS" FOR MAIN CUBICLES. THIS INSCRIPTION SHALL BE MINIMUN 1/2-INCH (13 mm)
HIGH WHITE LETTERING ON A RED BACKGROUND.

9. ADD PHASE BUS MARKING LABELS, 2" LETTERS (A-B-C)

Sheet 4 of 4