Pressure regulators

Pressure range
from 0.3 to 5 bars
Summary

30 Pressure regulators NATURAL GAS/PROPANE and accessories

30.1 REGULATORS TYPE GAZ DE FRANCE page 4

Following the technical specifications « B and C » in « elevation » and « underground » versions


Use, installation, operation, security and protection functions

30.2 PRESSURE REGULATORS TYPE B page 8


2 3
30-2-1/ PRESSURE REGULATORS TYPE « B6N - B10N » page 8

30-2-2/ PRESSURE REGULATORS TYPE « B25N - B40N - BCH30N » page 12

30-2-3/ PRESSURE REGULATORS TYPE « B50N - B75N - B100N - BCH60N - BCH90N » page 16

30.3 PRESSURE REGULATORS TYPE « BATTERY » page 20

BATTERY « 2xB25N - 2xBCH30N - 3xB25N - 3xBCH30N - 4xB25N - 4xBCH30N »

30.4 PRESSURE REGULATORS TYPE « C » page 23

PRESSURE REGULATORS TYPE «C40 – C65 – C100 – CCH50 – CCH80 – CCH130»


30.1 REGULATORS TYPE GAZ DE FRANCE
B50N, B75N, B100N, BCH60N, BCH90N

> Following the technical specifications « B and C »

Use and installation


BRIFFAULT’s regulators are designed to be installed on distribution networks supplied with “Medium Pressure” MP from 0.3
to 5 bars. They guarantee flow rate and regulation in “Low Pressure” LP from 9 to 50 mbars (for B and C types) and in “Me-
dium Pressure “A-MPA from 50 to 400 mbar (for BCH and CCH types). This equipment combines cutting functions (only B6N
and B10N), flow rate/regulation and security functions. To be installed in rooms, cubicles, shelters ventilated or airy, in rising C40, C65, C100, CCH50, CCH80 et CCH130
4 5
ducts or in boiler rooms. In this case, the air vent MUST BE PUT IN ATMOSPHERE. In its underground version, this equipment
must be installed in « plastic modules surmounted by a peep hole/ buffer » to assure their protection. The installation of this
equipment must comply with « Gaz de France Supply Guidebook ».

B6N and B10N square

Description and operation Security functions


The « B » and « C » regulators, in elevation or underground, is The « B » and « C » regulators are also used for security, for installations located downstream, in the following cases:
an equipment with a two-stage reduction device functioning in «
direct action », allowing to maintain a constant downstream pres- > Unusual drops of incoming and outgoing pressures and flow rate excess:
sure whatever incoming pressure variations are. At the first stage, Closure of the second stage and then of the first stage,
the «Network gas» in MP-B is reduced of PE pressure in E (in red
on the diagrams) to an intermediate pressure IP (in green). At the > Outgoing pressure excess:
second stage, the gas with an IP pressure is reduced and regulated B25N, B40N and BCH30N Closure of the second stage and then of the first stage, opening of the discharge valve DS, driving off of gas to the air
in LP or in MP-A (in yellow). “Outgoing pressure PS is caught on the square vent duct EV and closure of the safety valve SV for regulators type « C and CCH » if pressure excess lasts or increases
output S by the pressure tapping O in the « venturi tube » ; this one despite discharge valve operation.
will be affected by flow variation and will act on the second stage
membrane. This system allows our regulators to guarantee an out- > Membrane puncture:
going pressure stabilized at + or – 5% around nominal pressure (set In this case, out of normal operation of the equipment, closure of the second stage because of missing pressure
point) whatever incoming pressure and gas flow rates are. under its membrane. In cubicle of very low leakage « type : pinhole », opening of the discharge valve DS ,

> Zero flow :


Closure of the first and second stages following the « direct action » principle.
30.1 REGULATORS TYPES GAZ DE FRANCE
Filters F
To protect the equipment inside the regulators, a strainer filter retains, in the inlet connection of B6N B10N, B25N,
B40N, BCH30N and batteries, impurity such as PE or metal chips coming from the drilling in charge of connections and
of grains of sand coming from the embankment. For regulators, B50N, B75N, B100N, BCH60N, BCH90N, C40, C65,
C100, CCH50, CCH80 and CCH130 filtering elements are not in the inlet connection. They are accessible, on all models,
without having to dismantle the inlet connection having a sphero-conic joint.

Systems specific to regulators B50N, B75N, B100N, BCH60N, BCH90N, C40, C65, C100, CCH50, CCH80
and CCH130:
To suppress the impact of the incoming pressure variation PE, the first stage is « compound in pressure » by the CP
Air Vent EV (setup : « in elevation ») and Discharge valve DS system. Regulators ill-timed vibrations are eliminated by the AV system hitched to the first stage.
It is through the air vent that regulators sense the atmospheric pressure called « reference pressure ». If the discharge valve
is opened or in cubicle of membrane puncture, gas is sent « out to the air » by the air vent EV. If the regulator is placed
6 inside the houses, the air vent must be connected to the atmosphere by a manifold of a diameter determined according The «underground systems» 7
to its length (elimination of pumping phenomena). The trimming of temporary overpressures (dilatation of natural gas -their protections against corrosion:
downstream – discharge instantaneous stop) is the function of the discharge valve. The regulators designed for the equipping of underground gas cases, receive appropriate protections to work in «hostile
environment ». Reliability, INDISPENSABLE IN TIME, led BRIFFAULT to prepare its equipment with protections against
fast corrosion of internal and external components in contact with atmosphere. Engaged in fulfilling the future prohi-
Cutting and resetting system : B6N and B10N bition of using chromating with chromium VI, Briffault had GDF homologating a new chromium III based surface treat-
This system allows to stop the gas supply of the downstream installation; the operation is ensured by pressing and turning ment with application of a coating varnish. The technique of “underground” gas cubicles allows to fulfill environmental
the pushbutton P located on the foreside of the equipment. The commissioning of regulators, with the pushbutton P in constraints. That is why Briffault is continually researching processes which are best appropriate to operate, in hostile
« opening » position, is assured by pressing it until obtaining a “downstream” pressure equal to the set point. The ope- environment, their pressure regulators ; the reliability of such regulators along the time depends on them.
ration is identical after a safe operation is established. This system design prohibits the resetting of equipment in cutting - their protections against water penetration and frost:
position. In order to offset water penetration and frost risks inside regulators, BRIFFAULT designed and patented an anti-flooding
system with cover. Regulators air vents are extended by a manifold of a diameter compatible with equipment perfor-
mances. Their extremities are surmounted by BRIFFAULT’s anti-flooding system. The systems cubic capacity allows the
Resetting system of B25N, B40N, BCH30N, B50N, B75N, B100N, BCH60N, BCH90N and Batteries operation of regulators for floods high up to 1m. When water goes out, the inside of the regulator is free from water
Regulators commissioning is assured by turning the lever L until obtaining a “downstream” pressure equal to the set point; and the filter preserves its initial state.
the operation is identical after a safe operation is established. For the batteries, the resetting is executed by action on only
one resetting lever (any choice can be made).
The B6NE and B10NE «elevation for areas undergoing flooding»
In order to answer to problems caused by floods in areas at risk, BRIFFAULT created a variant version to underground
Resetting system of C40, C65, C100, CCH50, CCH80 and CCH130 regulators by adapting the ANTI-FLOODING system of those ones to allow their assembly in elevation cubicles S2300
Resetting of the SV by turning the lever LVS (mechanical interlocking) and turning the lever L until obtaining a “downstre- and S300.
am” pressure equal to the set point; the operation is identical after a safe operation is established.
30.2 PRESSURE REGULATORS TYPE «B»
Underground model

30.2.1 PRESSURE REGULATORS TYPE «B6N - B10N»


REG-GAZ

Aerial Model
High cover for cubicles equipped in plant

8 9

Inlet and outlet connections are usable in all versions


Low cover for old cubicles renewal

Possible installation in S2300 and S22 cubicles for B6N regulators and in cubicle S300, S22, multicount case for B10N
regulators, in underground circular cubicle.

Input Also available: Model in U


Nipple at JSC cal 15
to braze on Cu Ø 18 mm
925 1490 10

Output

B6N B6N
Nipple at JPC cal 20 Nipple at JPC cal 20
to braze on Cu Ø 22 mm to weld on Ac Ø 26.9 mm
925 1500 10 925 1510 10
Nipple at JSC cal 15 JPC 925 3420 10 JPC 925 3420 10
to weld on Ac Ø 21.3 mm
925 1520 10 B10N B10N
Nipple at JPC cal 32 Nipple at JPC cal 32
to braze on Cu Ø 35 mm to weld on Ac Ø 42.4 mm
925 5160 10 925 1830 10
JPC 925 2610 10 JPC 925 2610 10
30.2 PRESSURE REGULATORS TYPE «B»
Outgoing pressure curves for incoming pressures ranging between 0.5 and 5 bars

30.2.1 PRESSURE REGULATORS TYPE «B6N - B10N» Propane Setting: 37 mbar Safety
keeping
area

GN-L Setting: 27 mbars

CHARACTERISTICS B6N B10N


GN-H Setting : 27 mbars

Incoming pressure 0.3 to 5 bars

Outgoing pressure
Manufactured gas-(butane -propane) 11 ± 0.6 mbar
10 Natural gas « H »-(Lacq type) 21 ± 1 mbar 11
Natural gas « L »-(Groningue type) 27 ± 1.5 mbar
Propane 37 ± 2 mbar

Operating temperature -20°C à + 60°C Flow curves guaranteed according to the upstream pressure
At upstream pressure of: 300 Nominal 500 mbar and + 300 Nominal 500 mbar and +
Flow rates are mbar Guaranteed mbar Guaranteed
Manufactured gas-(butane-propane) 4.3 m3/h(n) 5.2 m3/h(n) 7.1 m3/h(n) 8.5 m3/h(n)
Natural gas « H »-(Lacq type) 6 m3/h(n) 7.2 m3/h(n) 10 m3/h(n) 12 m3/h(n)
Natural gas « L »-(Groningue type) 5.9 m3/h(n) 7.08 m3/h(n) 9.8 m3/h(n) 11.76 m3/h(n)
3.8 m3/h(n) 4.56 m3/h(n) 6.3 m3/h(n) 7.56 m3/h(n)
Propane or or or or
7.6 kg/h 9.12 kg/h 12.6 kg/h 15.12 kg/h

Gas flow in m3/h (n)


Safe keeping flow Between 110 and 150% of the nominal flow rate

Minimal outgoing pressure of


safe keeping
Manufactured gas-(butane-propane) 4 mbar
Natural gas « H »-(Lacq type) 10 mbar
Natural gas « L »-(Groningue type) 14 mbar
Propane 19 mbar Upstream pressure in bars

Safety valve calibration


Manufactured gas-(butane-propane) Between 30 and 40 mbar
Natural gas « H »-(Lacq type) Between 40 and 50 mbar B6N and B10N regulators assure their respective flow rate from an upstream pressure of 0.3 bars.
Natural gas « L »-(Groningue type) Between 45 and 55 mbar
Propane Between 50 and 60 mbar

Connection input: nut JSC cal.15 input: nut JSC cal.15


output: nut JPC cal.32 output: nut JPC cal.32
Weight about 1100 g
aerial underground aerial underground
Briffault’s Coding REG-GAZ REG-GAZ REG-GAZ REG-GAZ

0.3 to 5 bar 0.5 to 5 bar 0.5 to 5 bars type 0.3 to 5 bar 0.5 to 5 bars type 0.5 to 5 bars type
type GDF GDF low cover GDF low cover GDF low cover
Manufactured gas-(butane-propane) - 005411090-84.50.121 - - 005431090-84.50.136 -
Natural gas « H »-(Lacq type) 005415190 005410090-84.50.123 005410190-84.50.801 005435190 005430090-84.50.138 005436190-84.50.811
Natural gas « L »-(Groningue type) 005415290 005412090-84.50.132 005412290-84.50.802 005435290 005432090-84.50.140 005436290-84.50.812
Propane 005415390 005414090-84.50.128 - 005435390 005434090-84.50.141 -

For any other setting: please contact us


30.2 PRESSURE REGULATORS TYPE «B»
Underground model

30.2.2 PRESSURE REGULATORS TYPE «B25N - B40N - BCH30N»

Aerial Model

12 13

Inlet and outlet connections are usable in all versions

Low cover for old cubicles renewal

Input

Nipple at JSC cal 15


to weld on Cu Ø 18 mm
925 1490 10
Output

B25N / B40N B25N / B40N


Nipple at JPC cal 32 Nipple at JPC cal 32
to braze on Cu Ø 35 mm to weld on Ac Ø 42.4 mm
925 5160 10 925 1830 10 High cover for cubicles equipped at the premises
JPC 925 2610 10 JPC 925 2610 10
Installation is possible in cubicle S2300, S22, industrial station, multi-count case (only for B25)
B-CH30N B-CH30N
Nipple at JSC cal 15
Nipple at JPG cal 25 Nipple at JPG cal 25 underground circular cubicle.
to weld on Ac Ø 21.3 mm
to braze on Cu Ø 28 mm to weld on Ac Ø 33.7 mm
925 1520 10
925 1970 10 925 1960 10
JPG 925 1940 10 JPG 925 1940 10
30.2 PRESSURE REGULATORS TYPE «B»
Flow curves guaranteed according to the upstream pressure

30.2.2 PRESSURE REGULATORS TYPE «B25N - B40N - BCH30N»

CHARACTERISTICS B25N B40N BCH30N

Incoming pressure 0.3 to 5 bars 0.8 to 5 bars

Outgoing pressure
Manufactured gas-(butane-propane) 11± 0.6 mbar 300 mbar ± 15 mbar
14 Natural gas « H »-(Lacq type) 21 ± 1 mbar 15
Natural gas « L »-(Groningue type) 27 ± 1.5 mbar
Propane 37 ± 2 mbar
B25N and B40N regulators assure the flow rate from an upstream pressure of 0.3 bars.
Operating temperature -20°C à + 60°C

At upstream pressure of: 300 Nominal 500 mbar and + 500 Nominal 800 mbar and + 650 Nominal 800 mbar and +
Flow rates are mbar Guaranteed mbar Guaranteed mbar Guaranteed
Manufactured gas-(butane-propane) 17.8 m3/h(n) 21.4 m3/h(n) - - Outgoing pressure curves for incoming pressures ranging between 0.5 and 5 bars
Natural gas « H »-(Lacq type) 25 m3/h(n) 30 m3/h(n) 40 m3/h(n) 44 m3/h(n) 30 m3/h(n) 36 m3/h(n)
Natural gas « L »-(Groningue type) 24.4 m3/h(n) 29 m3/h(n) 39 m3/h(n) 43 m3/h(n)
15.6 m3/h(n) 18.7 m3/h(n) 25 m3/h(n) 27.5 m3/h(n) 18.7m 3/h(n) 22.5m 3/h(n)
Propane or or or or or or Safety
31.2 kg/h 37.4 kg/h 50 kg/h 55 kg/h 37.4 kg/h 45 kg/h
Propane Setting : 37 mbars keeping
area
Safe keeping flow rate Between 110 and 150 % of the nominal flow rate

Minimal outgoing pressure of GN-L Setting : 27 mbars


safe keeping
Manufactured gas-(butane-propane) 4 mbar 240 mbar
Natural gas « H »-(Lacq type) 15 mbar
Natural gas « L »-(Groningue type) 18 mbar GN-H Setting : 21 mbars
Propane 25 mbar

Safety valve calibration


Manufactured gas-(butane-propane) Between 25 and 40 mbar Between 350 and 400 mbar
Natural gas « H »-(Lacq type) Between 35 and 50 mbar
Natural gas « L »-(Groningue type) Between 37 and 50 mbar
Propane Between 47 and 60 mbar

Connection input: nut JSC cal.15 - output: nut JPC cal. 32 input: nut JSC cal.15
output: nut JPC cal. 25
Weight about 1400 g

Briffault’s Coding aerial underground aerial underground


0.3 to 5 bar 0.5 à 5 bartype GDF 0.5 to 5 bartype GDF 0.8 to 5 bar 0.8 to 5 bar 0.8 to 5 bar 0.8 to 5 low barcover
Manufactured gas-(butane-propane) - 00550039084.51.056 low cover - - 005500590 005436190
Natural gas « H »-(Lacq type) 005515190in square 00550009084.51.055 00550209084.51.151 005511090in square 005511890 300 mbar 84.51.305

005503490in line - - 005512090in line - in square


Natural gas « L »-(Groningue type) 005515290in square 00550019084.51.058 00550219084.51.152 005511190in square 005511990 84.51.302

005503590in line - - 005512190in line - 005503790in line


Propane 005515390in square 00550029084.51.061 - 005511290in square - 005501090150 mbar
005503690in line - - 005512290in line -

For any other setting: please contact us


30.2 PRESSURE REGULATORS TYPE «B»
Modèle enterré

30.2.3 PRESSURE REGULATORS TYPE


«B50N - B75N - B100N - BCH60N - BCH90N»

Aerial Model

16 17

Nipple at JSC cal 25 Nipple at JSC cal 25


to braze on Cu Ø 28 mm to weld on Ac Ø 33.7 mm
925 2140 10 925 1890 10

Input

Nipple at JSC cal 25


to braze on Cu Ø 28 mm
925 2140 10

Input
Nipple at JPG cal 50
to braze on Cu Ø 54 mm
925 2010 10
JPG 925 2090 10

Output
Nipple at JSC cal 25
to weld on Ac Ø 33.7 mm
925 1890 10

Cross-head for
assembly in Output Nipple at JPG cal 50
cubicle
to weld on Ac Ø 60.3 mm
S2300
925 2000 10
JPG 925 2090 10
Long cross-head
for input PE
954 5001 77

short cross- Possible installation in S2300 cubicle, industrial station, in underground circular cubicle.
head for input 2 pieces connection cal.50 2 pieces connection cal.50
Cu or Ac to braze on Cu Ø 54 mm to weld on Ac Ø 60.3 mm
925 2740 10 925 1860 10 925.1850.10
JPG 925 2090 10 JPG 925 2090 10
30.2 PRESSURE REGULATORS TYPE «B»
Flow curves guaranteed according to the upstream flow

30.2.3 PRESSURE REGULATORS TYPE


«B50N B75N B100N BCH60N BCH90N»

Gas flow rate in m3/h (n)


CARACTERISTIQUES B50N B75N B100N BCH60N BCH90N

Incoming pressure 0.3 to 5 bars 0.4 to 5 bars 0.5 to 5 bars 0.8 to 5 bars

Outgoing pressure
Natural gas « H »-(Lacq type) 21 ± 1 mbar 300 mbar ± 15 mbar
18 Natural gas « L »-(Groningue type) 27 ± 1.5 mbar
19
Propane 37 ± 2 mbar

Operating temperature -20°C à + 60°C

At upstream pressure of: 300 Nominal 500 mbars and 400 Nominal 700 mbars and 550 Nominal 800 mbars and 520 Nominal 700 mbars 650 Nominal 800 mbars and
Flow rates are mbars + Guaranteed mbars + Guaranteed mbars + Guaranteed mbars and + Gua- mbars + Guaranteed
Natural gas « H »-(Lacq type) 50 m3/h(n) 60 m3/h(n) 75 m3/h(n) 97 m3/h(n) 100 m3/h(n) 115m3/h(n) ranteed
Natural gas « L »-(Groningue type) 48.8 m3/h(n) 58 m3/h(n) 73.2 m3/h(n) 94.7m3/h(n) 97.6m3/h(n) 112m3/h(n) 60 m3/h(n) 72 m3/h(n) 80 m3/h(n) 96 m3/h(n)
31.2 m3/h(n) 37 m3/h(n) 47 m3/h(n) 77.5m3/h(n) 62.5m3/h(n) 72 m3/h(n) 37.5 m3/h(n) 45 m3/h(n) 50 m3/h(n) 60 m3/h(n)
Propane or or or or or or or or or or
Upstream pressure in bars
62.4 kg/h 74.8 kg/h 94 kg/h 155 kg/h 125 kg/h 144 kg/h 75 kg/h 90 kg/h 100 kg/h 120 kg/h

Safe keeping flow rate Between 110 and 150% of the nominal flow rate

Minimal outgoing pressure of


safe keeping
Natural gas « H »-(Lacq type) 15 mbar 10 mbar 180 mbar
Natural gas « L »-(Groningue type) 18 mbar 14 mbar
Propane 25 mbar 19 mbar

Safety valve calibration


Natural gas « H »-(Lacq type) between 35 and 50 mbars between 40 and 50 mbars between 360 between 350
Natural gas « L »-(Groningue type) between 37 and 50 mbars Between 45 and 55 mbars and 400 mbars and 370 mbars
Propane between 47 and 60 mbars Between 50 and 60 mbars
input: nut JSC cal.25 – output: male JPG cal.50 (aerial model)
Connection input: nut JSC cal.25 – output: nut JPG cal.50 (underground model)
Weight about 8 kg

Briffault’s Coding aerial underground aerial aerial aerial underground aerial underground

Natural gas « H »-(Lacq type) 005499090 005498590 005494090 005486090 005499390 005498790 005484590 005484890
84.51.020 84.52.025 84.51.302 300mbar 84.52.033 only

Natural gas « L »-(Groningue type) 005499190 005498690 005494190 005486190 005499890 for rectangular

84.52.021 84.52.026 150mbar cubicle

Propane 005499290 - 005494290 005486290


84.52.022

For any other setting: please contact us


30.3 PRESSURE REGULATORS TYPE «BATTERY» Batteries are composed by 2 to 4 regulators type B25N or BCH30N. B25N regulators have a specific setting point to be uses
in battery. They are also fitted with a pulse plug with internal diameter 6 mm allowing to take the outgoing pressure of the
downstream manifold, at the opposite of BCH30N that have neither specific setting nor pulse plug. Regulators are assem-
bled on an outlet manifold (brass) and an inlet manifold (copper). Because of their distinct positions, every regulator has
its own setting, in order to obtain a stable pressure and a steady flow rate. Thus we do not recommend to interchange the
regulators. Description and characteristics of the regulator alone: please see previous paragraph.

Possible installation in S2300 cubicle and industrial station.

Batteries 2 x regulators

2 pieces connection cal.50


to braze on Cu Ø 54 mm
925 1860 10
20 JPG 925 2090 10 21

Nipple at JSC cal 25 Output


Input
to braze on Cu Ø 28 mm
925 2140 10
Batteries 3 x regulators
2 pieces connection cal.50
to weld on Ac Ø 60.3 mm
925 1850 10
JPG 925 2090 10

Output manifold
cal 50
to braze on Cu
Output Ø 54 mm
04 0000 922
JPG 925 2090 10
Input

Batteries 4 x regulators
Output manifold
Nipple at JSC cal 25 cal 50
to weld on Ac Ø 33.7 mm to weld on Ac
925 1890 10 Ø 60.3 mm
925.198.010
JPG 925 2090 10
Output

Input
30.3 PRESSURE REGULATORS TYPE «BATTERY» 30.4 PRESSURE REGULATORS TYPE «C»

Aerial model Square version

CHARACTERISTICS 2 x B25N 3 x B25N 4 x B25N 2 x BCH30N 3 x BCH30N 4 x BCH30N

Incoming pressure 0.5 to 5 bars 0.8 to 5 bars

Outgoing pressure
Natural gas « H »-(Lacq type) 21 ± 1 mbar 300 mbar ± 15 mbar
22 Natural gas « L »-(Groningue type) 27 ± 1.5 mbar
23
Propane 37 ± 2 mbar

Operating temperature 20°C to 60°C

At upstream pressure of: 300 Nom. 500 mbars 300 Nom. 500 mbars 300 Nom. 500 mbars 520 Nom. 700 mbars 520 Nom. 700 mbars 520 Nom. 700 mbars
Flow rates are mbars and+ Guaran. mbars and+ Guaran. mbars and+ Guaran. mbars and+ Guaran. mbars and+ Guaran. mbars and+ Guaran.
Natural gas « H »-(Lacq type) 41 m3/h 52 m3/h 67 m3/h 83 m3/h 90 m3/h 110 m3/h
Natural gas « L »-(Groningue type) 40 m3/h 50 m3/h 65 m3/h 80 m3/h 87 m3/h 107 m3/h 55 m3/h 65 m3/h 90 m3/h 100 m3/h 120 m3/h 130 m3/h
Propane 25 m3/h 32 m3/h 41 m3/h 52 m3/h 56 m3/h 69 m3/h 35 m3/h 41 m3/h 56 m3/h 62 m3/h 75 m3/h 81 m3/h
or or or or or or or or or or or or
51 kg/h 65 kg/h 83 kg/h 104 kg/h 112 kg/h 138 kg/h 70 kg/h 82 kg/h 112 kg/h 125 kg/h 150 kg/h 162 kg/h

Safe keeping flow rate between 110 and 150% of the nominal flow Input
Nipple at JSC cal 25
Minimal outgoing pressure of to braze on Cu Ø 28 mm
safe keeping 925 2140 10
Natural gas « H »-(Lacq type) 15 mbar 240 mbar
Natural gas « L »-(Groningue type) 18 mbar
Propane 25 mbar Cross-head for square version
Long cross-head for input PE 954 5001 77
Safety valve calibration Short cross-head for
Natural gas « H »-(Lacq type) between 35 and 50 mbar between 350 mbar and 400 mbar input Cu or Ac 925 2740 10
Natural gas « L »-(Groningue type) between 37 and 50 mbar
Propane between 47 and 60 mbar

Connection input: nut JSC cal.25 – output: male JPG cal.50 Output
Weight approximately 10 kg approximately 12 kg approximately 14 kg approximately 10 kg approximately 12 kg approximately 14 kg

Nipple at JSC cal 25


Briffault’s Coding to weld on Ac Ø 33.7 mm
925 1890 10
Natural gas « H »-(Lacq type) 005452190 005453190 005454190 005452390 005453390 005454390
Natural gas « L »-(Groningue type) 005452290 005453290 005454290
Propane 005452990 005453990 005454990

For any other setting: please contact us 2 pieces connection 2 pieces connection Output manifold Output manifold
cal.50 to braze on cal.50 to weld on cal 50 to braze on cal 50 to weld
Cross-head for Cu Ø 54 mm Ac Ø 60.3 mm Cu Ø 54 mm on Ac Ø 60.3 mm
battery version 925 1860 10 925 1850 10 04 0000 922 925 198 010
954 6201 77 JPG 925 2090 10 JPG 925 2090 10 JPG 925 2090 10 JPG 925 2090 10
30.4 PRESSURE REGULATORS TYPE «C» Other possible model: model in line

Aerial model Battery version

24 GDF Version Versions type C GDF are equipped with inlet cross-head and with mounting kit: 25

2 pieces connection 2 pieces connection Output manifold Output manifold


cal.50 to braze on cal.50 toweld on cal 50 to braze on cal 50 to weld
Cu Ø 54 mm Ac Ø 60.3 mm Cu Ø 54 mm on Ac Ø 60.3 mm
925 1860 10 925 1850 10 04 0000 922 925 198 010
JPG 925 2090 10 JPG 925 2090 10 JPG 925 2090 10 JPG 925 2090 10

Output

Nipple at JSC cal 25


to braze on Cu Ø 28 mm
925 2140 10
« U » Version (GDF designation)
Cross-head for square version Input
long cross-head for input PE 954 5001 77
short cross-head for
input Cu or Ac 925 2740 10

Nipple at JSC cal 25 Cross-head for


to weld on Ac Ø 33.7 mm battery version
925 1890 10 954 6201 77

« Square » Version (GDF designation)


CHARACTERISTICS C40 C65 C100 CCH50 CCH80 CCH130

Incoming pressure 0.8 to 5 bars

Outgoing pressure
Natural gas « H »-(Lacq type) 21 ± 1 mbar 300 mbar ± 15 mbar
Natural gas « L »-(Groningue type) 27 ± 1.5 mbar
Propane 37 ± 2 mbar

Operating temperature 20°C to 60°C

At upstream pressure of: 300 Nom. 700 mbars 550 Nom. 700 mbars 550 Nom. 800 mbars 650 Nom. 800 mbars 650 Nom. 800 mbars 850 Nom. 1000 mbars
Flow rates are mbars and+ Guaran. mbars and+ Guaran. mbars and+ Guaran. mbars and+ Guaran. mbars and+ Guaran. mbars and+ Guaran.
Natural gas « H »-(Lacq type) 40 m3/h 48 m3/h 65 m3/h 78 m3/h 100m3/h 115m3/h

30.4 PRESSURE REGULATORS TYPE «C» Natural gas « L »-(Groningue type) 39 m3/h 47 m3/h 63 m3/h 76 m3/h 97m3/h 112m3/h 50 m3/h 60 m3/h 80 m3/h 96 m3/h 130 m3/h 146 m3/h
Propane 25 m3/h 30 m3/h 40 m3/h 48 m3/h 62m3/h 72m3/h 31 m3/h 37 m3/h 50 m3/h 60 m3/h 81 m3/h 91 m3/h
or or or or or or or or or or or or
50 kg/h 60 kg/h 81 kg/h 97 kg/h 125kg/h 144kg/h 63 kg/h 75 kg/h 100 kg/h 120 kg/h 162 kg/h 182 kg/h

Safe keeping flow between 110 and 150% of the nominal flow rate

Minimal outgoing pressure of


safe keeping
Natural gas « H »-(Lacq type) 10 mbar 180 mbar
Natural gas « L »-(Groningue type) 14 mbar
Propane 19 mbar

Safety valve calibration


Natural gas « H »-(Lacq type) between 40 and 50 mbar between 350 mbar and 370 mbar
Square » Version (GDF designation) Natural gas « L »-(Groningue type) between 45 and 55 mbar
Propane between 50 and 60 mbar

Maximal pressure of
safe keeping
Natural gas « H »-(Lacq type) 65 mbar 390 mbar
26 Natural gas « L »-(Groningue type) 27
Propane

Connection input: nut JSC cal.25 – output: male JPG cal.50 (aerial model)
input: nut JSC cal.25 – output: male JPG cal.50 (underground model)
Weight about 9 kg

Briffault’s Coding
aerial square aerial square aerial square aerial square aerial square aerial square
Natural gas « H »-(Lacq type) 00545009084.51.320 00547009084.52.160 005487090
Natural gas « L »-(Groningue type) 00546309084.51.321 00547309084.52.161 005487190 00548009084.52.190 00548309084.52.195 005487390
Propane 00546609084.51.322 00547609084.52.162 005487290
aerial battery aerial battery aerial battery aerial battery aerial battery aerial battery
Natural gas « H »-(Lacq type) 00546209084.51.330 00547209084.52.170 005487590
Natural gas « L »-(Groningue type) 00546509084.51.331 00547509084.52.171 005487690 00548209084.52.191 00548509084.52.196 005487890
Propane 00546809084.51.332 00547809084.52.169 005487790
Model for circular underground module (EV-BA) underground EV-BA underground EV-BA - underground EV-BA
Natural gas « H »-(Lacq type) 00546909084.51.345 00547909084.51.371
Natural gas « L »-(Groningue type) 00546919084.51.346 00547919084.51.372 00548909084.52.189
underground EH-EQ underground EH-EQ underground EH-EQ underground EH-EQ underground EH-EQ underground EH-EQ
Natural gas « H »-(Lacq type) 005450990 005470990 005487990 00548099084.52.194 00548399084.52.199 005488690
Natural gas « L »-(Groningue type) 005463990 005473990 005488590

For any other setting: please contact us Flow curves guaranteed according to the upstream flow rate

Possible installation in S2300, S300


cubicle, industrial station, in underground
circular and rectangular cubicle.

Model for rectangular underground module (EH-EQ)


28