SIST EN 12259-14:2020+A1:2022
01-julij-2022
Fixed firefighting systems - Components for sprinkler and water spray systems - Part 14:
Sprinklers for residential applications
iTeh STANDARD PREVIEW
(standards.iteh.ai)
Ortsfeste Brandbekämpfungsanlagen - Bauteile für Sprinkler- und Sprühwasseranlagen -
Teil 14: Sprinkler für die Anwendung im Wohnbereich
SIST l'incendie
Installations fixes de lutte contre EN 12259-14:2020+A1:2022
- Composants des systèmes d'extinction du
https://standards.iteh.ai/catalog/standards/sist/018cb862-9752-4ba6-b12c-
type sprinkleur et à pulvérisation d'eau - Partie 14: Sprinkleurs pour applications
résidentielles 18f6d3262872/sist-en-12259-14-2020a1-2022
ICS:
13.220.10 Gašenje požara Fire-fighting
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
SIST EN 12259-14:2020+A1:2022
English Version
This European Standard was approved by CEN on 4 November 2019 and includes Amendment 1 approved by CEN on 13 March
2022.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
© 2022 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 12259-14:2020+A1:2022 E
worldwide for CEN national Members.
SIST EN 12259-14:2020+A1:2022
EN 12259-14:2020+A1:2022 (E)
Contents Page
European foreword....................................................................................................................................................... 4
1 Scope .................................................................................................................................................................... 5
2 Normative references .................................................................................................................................... 5
3 Terms and definitions ................................................................................................................................... 5
4 Construction and performance .................................................................................................................. 8
4.1 General ................................................................................................................................................................ 8
4.2 Dimensions and pressure rating ............................................................................................................... 8
4.3 Nominal operating temperature ............................................................................................................... 8
4.4 Operating temperatures ............................................................................................................................... 9
4.5 Water flow and distribution ........................................................................................................................ 9
4.6 Function ........................................................................................................................................................... 10
4.7 Fire Test ........................................................................................................................................................... 10
4.8 Strength of sprinkler body and deflector ............................................................................................ 11
4.9 Strength of release element...................................................................................................................... 11
4.10 Leak resistance and hydrostatic strength ........................................................................................... 12
4.11
4.12 iTeh STANDARD PREVIEW
Heat exposure................................................................................................................................................ 12
Corrosion......................................................................................................................................................... 13
4.13 Water hammer .............................................................................................................................................. 13
4.14 (standards.iteh.ai)
Thermal response ........................................................................................................................................ 14
4.15 Resistance to vibration .............................................................................................................................. 14
4.16 Resistance to impact ...................................................................................................................................
SIST EN 12259-14:2020+A1:2022 14
4.17 Resistance to low temperature ...............................................................................................................
https://standards.iteh.ai/catalog/standards/sist/018cb862-9752-4ba6-b12c- 14
4.18 Resistance to heat ........................................................................................................................................
18f6d3262872/sist-en-12259-14-2020a1-2022 14
4.19 Test conditions.............................................................................................................................................. 14
5 Marking ............................................................................................................................................................ 14
5.1 General ............................................................................................................................................................. 14
5.2 Identification number ................................................................................................................................ 14
5.3 Nominal operating temperature and year of manufacture .......................................................... 15
5.4 Manufacturing location .............................................................................................................................. 15
5.5 Heat sensitive element supplier ............................................................................................................. 15
5.6 Protective covers .......................................................................................................................................... 15
5.7 Sidewall sprinklers ...................................................................................................................................... 15
5.8 Concealed sprinklers .................................................................................................................................. 15
5.9 Removable recessed housing................................................................................................................... 16
6 Instruction charts......................................................................................................................................... 16
6.1 General ............................................................................................................................................................. 16
6.2 Installation Instructions ............................................................................................................................ 16
Annex A (normative) Conditions for tests ........................................................................................................ 18
Annex B (normative) Water flow test ................................................................................................................ 19
Annex C (normative) Water distribution test ................................................................................................. 21
Annex D (normative) Fire test .............................................................................................................................. 27
Annex E (normative) Function test ..................................................................................................................... 37
2
SIST EN 12259-14:2020+A1:2022
EN 12259-14:2020+A1:2022 (E)
3
SIST EN 12259-14:2020+A1:2022
EN 12259-14:2020+A1:2022 (E)
European foreword
This document (EN 12259-14:2020+A1:2022) has been prepared by Technical Committee CEN/TC 191
“Fixed firefighting systems”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by November 2022, and conflicting national standards
shall be withdrawn at the latest by November 2022.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
The start and finish of text introduced or altered by amendment is indicated in the text by tags !".
!In comparison with EN 12259-14:2020, technical modifications have been made to clarify the types
of sprinkler seal that are covered by this document."
Any feedback and questions on this document should be directed to the users’ national standards body.
A complete listing of these bodies can be found on the CEN website.
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria,
Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland,
Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic of
North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the
United Kingdom.
4
SIST EN 12259-14:2020+A1:2022
EN 12259-14:2020+A1:2022 (E)
1 Scope
!This document specifies requirements for the construction and performance of residential
sprinklers as well as test methods for their type approval, which are operated by a change of state of an
element or bursting of a glass bulb under the influence of heat and incorporating the following types of
water seals:
— conical metal spring with a PTFE gasket or coating;
— metal cap or disc with PTFE gasket or coating;
— copper gasket, with or without a PTFE coating.
Sprinklers in accordance with this document are only used in automatic sprinkler systems for domestic
and residential applications as defined in EN 16925."
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
!EN 12259-1:1999+A1:2001 1", Fixed firefighting systems — Components for sprinkler and water
spray systems — Part 1: Sprinklers
ISO 65, Carbon steel tubes suitable for screwing in accordance with ISO 7-1
ISO 5658-2:2006, Reaction to fire tests — Spread of flame — Part 2: Lateral spread on building and
transport products in vertical configuration
ISO 5660-1:2015, Reaction-to-fire tests — Heat release, smoke production and mass loss rate — Part 1:
Heat release rate (cone calorimeter method) and smoke production rate (dynamic measurement)
UL 723, Standard for test for surface burning characteristics of building materials
5
SIST EN 12259-14:2020+A1:2022
EN 12259-14:2020+A1:2022 (E)
3.1
concealed sprinkler
unit (pre-assembled or assembled on site) consisting of a nozzle with a thermally sensitive sealing
device, a housing and a cover plate, that ensures that the sprinkler will be installed with all or part of
the thermally sensitive element behind the plane of the ceiling
3.2
recessed sprinkler
unit (pre-assembled or assembled on site) consisting of a nozzle with a thermally sensitive sealing
device and a housing, that ensures that the sprinkler will be installed with all or part of the thermally
sensitive element above the plane of the ceiling
3.3
discharge coefficient
known as K-factor
Q=K√p (1)
where
3.6
heat responsive element
portion of a sprinkler that breaks, melts, or otherwise functions to initiate the automatic operation of
the sprinkler when exposed to sufficient heat
3.7
heptane
commercial grade heptane having the following characteristics:
6
SIST EN 12259-14:2020+A1:2022
EN 12259-14:2020+A1:2022 (E)
3.8
orifice
opening that controls the amount of water discharged from a sprinkler at a given pressure
3.9
pendent sprinkler
nozzle with a thermally sensitive sealing device intended to be installed so that its deflector is located
below the orifice and the water flows downward through the orifice
3.10
residential sprinkler
nozzle with a thermally sensitive sealing device intended to be installed only in residential occupancies
as defined in EN 16925
3.11
sidewall sprinkler
nozzle with a thermally sensitive sealing device intended for installation on or near the wall
3.12
upright sprinkler
nozzle with a thermally sensitive sealing device intended to be installed so that its deflector is located
above the orifice
3.13
response time index
iTeh STANDARD PREVIEW
RTI (standards.iteh.ai)
measure of the thermal sensitivity of the sprinkler expressed in (meters.seconds)½ (m×s)½
3.15
design upper tolerance limit
DUTL
sprinkler supplier’s specified and assured highest upper tolerance limit
3.16
fusible link sprinkler
nozzle with a thermally sensitive sealing device which opens when an element provided for that
purpose melts
3.17
glass bulb sprinkler
nozzle with a thermally sensitive sealing device which opens when a liquid-filled glass bulb bursts
3.18
mean design service load
sprinkler supplier’s specified and assured highest mean service load for any batch of 10 or more
sprinklers
7
SIST EN 12259-14:2020+A1:2022
EN 12259-14:2020+A1:2022 (E)
3.19
mean design strength
glass bulb supplier’s specified and assured lowest mean bulb strength for any batch of 55 or more bulbs
3.20
horizontal sprinkler
nozzle with a thermally sensitive sealing device in which the nozzle directs the water horizontally
3.21
lower tolerance limit
LTL
glass bulb lowest strength determined by test and statistical analysis of a batch of 55 or more bulbs
3.22
supplier
company responsible for the design, manufacture and quality assurance of a product
3.23
upper tolerance limit
UTL
highest service load determined by test and statistical analysis of a batch of 20 or more sprinklers
3.24
frame arms iTeh STANDARD PREVIEW
part of a sprinkler that maintains the thermally sensitive element in load bearing contact with the
sprinkler head valve (standards.iteh.ai)
4 Construction and performance
SIST EN 12259-14:2020+A1:2022
4.1 General https://standards.iteh.ai/catalog/standards/sist/018cb862-9752-4ba6-b12c-
18f6d3262872/sist-en-12259-14-2020a1-2022
Sprinklers shall only be assembled in such a way that adjustment or dismantling will result in
destruction of an element of construction.
It shall be possible to remove the cover of a concealed sprinkler without having to use special tools, e.g.
for visual inspections.
4.2 Dimensions and pressure rating
4.2.1 Dimensions
Nominal thread sizes shall be suitable for fittings threaded in accordance with ISO 7-1.
It shall be possible for a sphere of (5,0 +0,01/-0) mm diameter to pass through the orifice of the
sprinkler.
4.2.2 Pressure ratings
When tested in accordance with “Test to determine operating temperatures of fusible link sprinklers
and glass bulb sprinklers” of !EN 12259-1:1999+A1:2001", sprinklers shall operate at a
temperature within the range:
8
SIST EN 12259-14:2020+A1:2022
EN 12259-14:2020+A1:2022 (E)
where
t is the nominal operating temperature.
When cover plates are tested in accordance with the “Test to determine operating temperatures of
fusible link sprinklers and glass bulb sprinklers” of !EN 12259-1:1999+A1:2001", cover plates
shall operate at a temperature within the range:
Ttest = [tcover ± (0,035 t +0,62)] o C
where
tcover is the nominal operating temperature of the cover.
This temperature tcover shall be 8 °C to 20 °C lower than the nominal operating temperature of its
sprinkler head.
4.4 Operating temperatures
The temperature classification, temperature rating, and colour coding of a residential sprinkler shall be
as specified in Table 1.
The nominal K-factor shall be specified by the supplier. The K-factor of the sprinklers shall be within the
nominal value ± 5 % for other than dry sprinklers and ± 8 % for dry sprinklers, when determined in
accordance with Annex B.
4.5.2 Water distribution
When installed in accordance with the installation instructions and tested as described in C.1 a
residential sprinkler shall distribute water over a horizontal surface so that the discharge density for
any pan within the design area (the maximum area the sprinkler is intended to protect) shall be at least
0,8 mm/min except that:
9
SIST EN 12259-14:2020+A1:2022
EN 12259-14:2020+A1:2022 (E)
a) no more than 2 pans (0,5 m × 0,5 m) or not more than 4 pans (0,3m × 0,3m) for each quadrant shall
be allowed to be at least 0,6 mm/min for upright and pendant sprinklers; and
b) no more than 8 pans (0,3 m × 0,3 m) or 3 pans (0,5 m × 0,5 m) shall be allowed to be at least
0,6 mm/min for each half (split along the sprinkler centreline) of the maximum area a sidewall
sprinkler is intended to protect
When installed in accordance with the installation instructions and tested as described in C.2, a
residential sprinkler shall distribute water in a uniform manner over vertical surfaces as follows:
a) walls within the coverage area shall be completely wetted to at least within 711 mm of the ceiling
with one sprinkler discharging water at the specified design flow rate;
b) for square coverage areas, each wall within the coverage area shall be wetted with at least 5 % of
the sprinkler flow; for rectangular coverage areas, each wall within the coverage area shall be
wetted with a proportional water amount based on 20 % of the total sprinkler discharge in
accordance with the following formula
WW – 20 % (D / P) (2)
where
WW
iTeh STANDARD PREVIEW
is required amount of water collected on a wall, in %;
D is wall length, in m; (standards.iteh.ai)
P is total perimeter of coverage area, in m.
SIST EN 12259-14:2020+A1:2022
4.5.3 Water Impingement Test
https://standards.iteh.ai/catalog/standards/sist/018cb862-9752-4ba6-b12c-
18f6d3262872/sist-en-12259-14-2020a1-2022
When tested in accordance with Annex C and while discharging water at a service pressure of 5,2 bar
less than the maximum operating pressure, a residential sprinkler shall not prevent the operation of an
adjacent residential sprinkler.
4.6 Function
When tested in accordance with Annex E each of the residential sprinklers shall operate at service
pressures of 0,5 bar to the maximum operating pressure. The sprinkler shall open and within 5 s of
release of the thermally sensitive element shall operate satisfactorily. Any lodgement of released parts
shall be cleared within 60 s of the release of the thermally sensitive element. After testing in accordance
with Annex E the sprinkler shall conform to the requirements of 4.5.2.
NOTE In most instances visual examination of the equipment will be sufficient to establish conformity with the
requirements of 4.5.2.
When fire tested as described in Annex D a residential sprinkler shall limit temperatures as specified
below when tested at each spacing referenced in the installation instructions. Additionally, a maximum
of two residential sprinklers shall operate and the third sprinkler, located near the 1 000 mm wide
doorway, shall not operate. The sprinklers shall limit temperatures as follows:
a) The maximum temperature measured 76 mm below the ceiling at locations 4 and 5 as illustrated in
Figure D.1, Figure D.2 and Figure D.3 shall not exceed 316 °C.
10
SIST EN 12259-14:2020+A1:2022
EN 12259-14:2020+A1:2022 (E)
b) The maximum temperature measured 1,6 m above the floor at location 4 shall not exceed 93 °C.
c) The temperature at the location described in (b) shall not exceed 54 °C for more than any
continuous 2 min period.
d) The maximum ceiling material temperature measured 6 mm behind the finished ceiling surface
shall not exceed 260 °C.
NOTE The thermocouple 76 mm below the ceiling, located above the fire source, is for reference purposes
only.
See Figure D.1, (pendant, upright, flush, recessed pendant, and concealed sprinklers) or Figure D.2 and
Figure D.3 (sidewall sprinklers) for temperature measuring locations.
4.8 Strength of sprinkler body and deflector
4.8.1 Strength of frame
The sprinkler body shall not show permanent elongation of more than 0,2 % between the load-bearing
parts when subjected to twice the average service load when tested in accordance with F.1.
4.8.2 Flow endurance
A residential sprinkler shall withstand for 30 min, without evidence of cracking, deformation, or
iTeh STANDARD PREVIEW
separation of any part when tested in accordance with F.2.
4.8.3 Strength of deflector
(standards.iteh.ai)
The sprinkler deflector and its supporting parts shall withstand an applied force of 70 N without
permanent deformation when tested in accordance with F.3.
4.9 Strength of release elementSIST EN 12259-14:2020+A1:2022
https://standards.iteh.ai/catalog/standards/sist/018cb862-9752-4ba6-b12c-
18f6d3262872/sist-en-12259-14-2020a1-2022
4.9.1 Glass bulb sprinklers
When evaluated and tested in accordance with Annex G, glass bulb sprinklers shall have:
a) a mean design bulb strength of at least six times the mean design service load;
b) a mean bulb strength not less than the mean design bulb strength;
c) a mean service load not more than the mean design service load;
d) a design lower tolerance limit (DLTL) on the distribution curve of at least two times the design
upper tolerance limit (DUTL) of the service load distribution curve;
e) an upper tolerance limit (UTL) less than or equal to the design upper tolerance limit (DUTL);
f) a lower tolerance limit (LTL) greater than or equal to the design lower tolerance limit (DLTL) see
Figure 1.
11
SIST EN 12259-14:2020+A1:2022
EN 12259-14:2020+A1:2022 (E)
Key
1 service load distribution curve
2 bulb strength distribution curve
3 mean service load
4 mean bulb strength
5 upper tolerance limit (UTL)
6 lower tolerance limit (LTL)
A number of samples
B strength (N)
Twenty residential sprinklers shall be tested and not leak when tested in accordance with H.1 and,
subsequently, shall not rupture, operate or release, when tested in accordance with H.2.
4.11 Heat exposure
4.11.1 General
A residential sprinkler shall withstand for 90 days, without evidence of weakness or malfunction, an
exposure to the high-ambient temperature in accordance with I.1.
After the exposure period four sprinklers shall be tested in accordance with E.2; the sprinklers shall
operate such that the waterway is cleared. Any lodgements shall be disregarded. Four sprinklers shall
be leak tested in accordance with H.1. Four sprinklers shall be tested in accordance with “Test to
determine operating temperatures of fusible link sprinklers and glass bulb sprinklers” of
!EN 12259-1:1999+A1:2001".
Additionally, after the exposure period four recessed, concealed and flush sprinklers shall be tested in
accordance with M.2. Their mean operating time shall be equal to or less than a 1,30 multiple of the
mean operating time of the sprinkler tested in accordance with M.2 for compliance with 4.14.2.
12
SIST EN 12259-14:2020+A1:2022
EN 12259-14:2020+A1:2022 (E)
There shall be no damage to the glass bulb when sprinklers are tested in accordance with I.2.
!deleted text"
4.11.3 Thermal shock
When glass bulb sprinklers are tested in accordance with Annex J, the glass bulbs shall either:
— break correctly on cooling such that the waterway is cleared; or
— remain intact. After immersion when subjected to a function test in accordance with E.2, the
sprinkler shall operate in such way that the waterway is cleared; any lodgements shall be
disregarded.
4.12 Corrosion
4.12.1 Stress corrosion
After being subjected for 10 days to a moist ammonia exposure as described in K.1 a residential
sprinkler having copper alloy parts shall:
a) show no evidence of cracking, delamination, or degradation; and
If the application of a 12 bar water pressure to the inlet of the sprinkler increases the assembly load by
more than 10 %, the additional(standards.iteh.ai)
load is to be applied during the moist ammonia-air mixture exposure
specified in K.1.
4.12.2 Sulphur dioxide corrosion
SIST EN 12259-14:2020+A1:2022
https://standards.iteh.ai/catalog/standards/sist/018cb862-9752-4ba6-b12c-
Residential sprinklers shall be subjected to a sulphur dioxide corrosion test in accordance with K.2.
18f6d3262872/sist-en-12259-14-2020a1-2022
After exposure, when subjected to a function test in accordance with E.2 the sprinkler shall operate
such that the waterway is cleared; any lodgements shall be disregarded.
4.12.3 Salt mist corrosion
Residential sprinklers shall be subjected to a salt mist corrosion test in accordance with K.3. After
exposure, when subjected to a function test in accordance with E.2, the sprinkler shall operate such that
the waterway is cleared; any lodgements shall be disregarded.
4.12.4 Moist air
Residential sprinklers shall withstand an exposure to moist air atmospheres when tested in accordance
with K.4.
4.13 Water hammer
Sprinklers shall not leak when subjected to pressure surges in accordance with Annex L. After the test,
when subjected to a function test in accordance with E.2, the sprinkler shall operate such that the
waterway is cleared; any lodgements shall be disregarded.
13