Drawing Panel Jockey
Drawing Panel Jockey
1
0 1 2 3 4 5 6 7 8
PER QUOTE DRAWING No.
Jockey Pump Controller
Across the Line / 3 Phase REV. DESCRIPTION DD/MM/YY
A Model:JP3 0 As Built 18/07/23
DRAWING
NUMBER A
Wiring schematic Built to the latest edition of the UL 508A D 1308061-S1
380V/3Ø/50Hz
L1 L2 L3 PT1
Pressure Sensor
Type 0.5 - 4.5V
Field Connections
DS1
G
G
Normal Power Connections
B B
White
Terminals Wire Size:
Black
Red
Y
R DS1 C1
B W G R S 5 14 AWG-6 AWG 14 AWG-10 AWG
J5 2 Nm 1.8 Nm
RESET
HAND G G AUTO Incoming Power
OL1 Ground
34 33 7
9 IN1 J9
J21
G
C IN2 14-2 AWG C
OUTPUT ON J8 L1 L2 L3
DS1
J19 "IPD+"
C1
T1 T2 T3
14-2 AWG
F5
D J2 J3 J1 D
FU1 XTR1
1L3 2L3 3 24Vac 24Vac
H2 X1 A2 A1
M
3 1 22 8
1L1 2L1 H1 X2 1
E A1 A2 E
C1
F F
G G
OL1
H H
C1
G
T1 T2 T3
I I
P1
4KW
0 1 2 3 4 5 6 7 8
Copyright © 2023 Tornatech Inc. All rights reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
P.2
0 1 2 3 4 5 6 7 8
PER QUOTE DRAWING No.
Jockey Pump Controller
Across the Line / 3 Phase REV. DESCRIPTION DD/MM/YY
A Model:JP3 0 As Built 18/07/23
DRAWING
NUMBER A
Dimensions Built to the latest edition of the UL 508A D 1308061-S1
FU1 DS1
B B
IPD+
XTR1
10-5/8" [270]
6-1/4" [159]
8" [203]
C Main C
Disconnect
G
Y
ON
R
OL1
OFF
HAND G G AUTO
C1
PT1
Underwriters
Laboratories Inc.
######
R R
LISTED
ENCLOSED INDUSTRIAL CONTROL PANEL
No. AC-XXX
Rating
E Label E
Internal Layout
Ø3/8" [9] x4
Designation Description Tornatech ID
C1 Contactor CONLOV0001
G 3-3/8" [86] G
2-1/4" [58]
10" [254]
H H
Notes:
- Enclosure TYPE 2 (NEMA 2)
- All Dimensions are in Inches (Millimeters).
- Paint: Textured Red RAL 3002
- Use Watertight Conduit and Connector Only.
- Protect Equipment Against Drilling Chips.
I - Door Swing Equal to Door Width I
Projection
- Panel shall be protected by an inverse time circuit breaker rated no more than 25A
- Branch Circuit Protection to be Provided by the Installer: SCCR @ 5 kA, 600VAC
when provided with the following fuses: class RK5 30A
0 1 2 3 4 5 6 7 8
Copyright © 2023 Tornatech Inc. All rights reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.