70

70 Series - Line monitoring relay SERIES

Features 70.11 70.31


Electronic voltage monitoring relays for
single and three-phase applications
• Multifunctional types, providing the flexibility
of monitoring Undervoltage, Overvoltage,
Window Mode, Phase rotation, Phase loss
• Positive safety logic - Make output contact
opens if the relay detects an error
• All functions and values can be easily adjusted
by the selector and trimmer on front face
• “Blade + cross” – both flat blade and cross
Single-phase (220...240 V) Three-phase (380...415 V)
head screw drivers can be used to adjust the
voltage monitoring: voltage monitoring:
regulators and the function selector
• Colored LEDs for clear & immediate visual
• Undervoltage • Undervoltage
indication • Overvoltage • Overvoltage
• 1 CO relay output, 6 or 10 A • Window mode (overvoltage • Window mode (overvoltage
• Modular housing, 17.5 or 35 mm wide + undervoltage) + undervoltage)
• 35 mm rail (EN 60715) mount • Voltage fault memory • Voltage fault memory
• Cd-free contact material selectable selectable
• Phase loss
• Phase rotation
Screw terminal

For outline drawing see page 10


Contact specification
Contact configuration 1 CO (SPDT) 1 CO (SPDT)
Rated current/Maximum peak current A 10 / 30 6 / 10
Rated voltage/Max. switching voltage V AC 250 / 400 250 / 400
Rated load AC1 VA 2,500 1,500
Rated load AC15 VA 750 500
Single phase motor rating (230 V AC) kW 0.5 0.185
Breaking capacity DC1: 30/110/220 V A 10 / 0.3 / 0.12 6 / 0.2 / 0.12
Minimum switching load mW (V/mA) 300 (5 / 5) 500 (12 / 10)
Standard contact material AgNi AgNi
Supply specification
Nominal system voltage (UN) V AC (50/60 Hz) 220…240 380…415
Rated power VA (50 Hz) / W 2.6 / 0.8 11 / 0.9
Operating range V AC (50/60 Hz) 130…280 220…510
Technical data
Electrical life at rated load AC1 cycles 80 · 103 60 · 103
Voltage detection level range V 170…270 300…480
Asymmetry detection level range % — —
Switch-off delay time (T on function diagrams) s 0.5...60 0.5...60
Switch-on lock-out time s 0.5 1
Switch-on hysteresis (H on function diagrams) V 5 (L-N) 10 (L-L)
Power-on activation time s ≈1 ≈1
III-2015, www.findernet.com

Insulation between supply and contacts (1.2/50 μs)kV 4 4


Dielectric strength between open contacts V AC 1,000 1,000
Ambient temperature °C –20…+60 –20…+60
Protection category IP20 IP20
Approvals (according to type)

1
70
SERIES 70 Series - Line monitoring relay
Features 70.41 70.42
Electronic voltage monitoring relays for
three-phase applications
• Multifunctional types, providing the flexibility
of monitoring Undervoltage, Overvoltage,
Window Mode, Phase rotation, Phase loss,
Asymmetry and Neutral loss
• Positive safety logic - Make output contact
opens if the relay detects an error
• All functions and values can be easily adjusted
by the selector and trimmer on front face
Three-phase (380...415 V, Three-phase (380...415 V,
• “Blade + cross” – both flat blade and cross
with or without neutral) with neutral) voltage
head screw drivers can be used to adjust the
voltage monitoring: monitoring:
regulators and the function selector
• Colored LEDs for clear & immediate visual
• Window mode (overvoltage • Undervoltage
indication + undervoltage) • Overvoltage
• 1 or 2 CO relay output, 6 or 8 A • Phase loss • Window mode (overvoltage
• Modular housing, 35 mm wide • Phase rotation + undervoltage)
• 35 mm rail (EN 60715) mount • Asymmetry • Voltage fault memory
• Cd-free contact material • Neutral loss selectable selectable
• Phase loss
Screw terminal • Phase rotation
• Asymmetry
E • Neutral loss

For outline drawing see page 10


Contact specification
Contact configuration 1 CO (SPDT) 2 CO (DPDT)
Rated current/Maximum peak current A 6 / 10 8 / 15
Rated voltage/Max. switching voltage V AC 250 / 400 250 / 400
Rated load AC1 VA 1,500 2,000
Rated load AC15 VA 500 400
Single phase motor rating (230 V AC) kW 0.185 0.3
Breaking capacity DC1: 30/110/220 V A 6 / 0.2 / 0.12 8 / 0.3 / 0.12
Minimum switching load mW (V/mA) 500 (12 / 10) 300 (5 / 5)
Standard contact material AgNi AgNi
Supply specification
Nominal system voltage (UN) V AC (50/60 Hz) 380…415 380…415
Rated power VA (50 Hz) / W 11 / 0.9 12.5/1
Operating range V AC (50/60 Hz) 220…510 220…510
Technical data
Electrical life at rated load AC1 cycles 60 · 103 60 · 103
Voltage detection level range V 300…480 300…480
Asymmetry detection level range % 4...25 5...25
Switch-off delay time (T on function diagrams) s 0.5...60 0.5...60
Switch-on lock-out time s 1 1
Switch-on hysteresis (H on function diagrams) V 10 (L-L) 10 (L-L)
Power-on activation time s ≈1 ≈1
III-2015, www.findernet.com

Insulation between supply and contacts (1.2/50 μs)kV 4 4


Dielectric strength between open contacts V AC 1,000 1,000
Ambient temperature °C –20…+60 –20…+60
Protection category IP20 IP20
Approvals (according to type)

2
70
70 Series - Line monitoring relay SERIES

Features 70.61 70.62


Electronic phase loss and rotation monitoring
relays for three-phase applications
• Universal voltage monitoring (UN from 208 V
to 480 V, 50/60 Hz)
• Phase loss monitoring, even under phase
regeneration
• Positive safety logic - Make contact opens if
the relay detects an error
• 2 versions:
1 CO relay output, 6 A (17.5 mm wide), and
2 CO relay output, 8 A (22.5 mm wide) Three-phase (208...480 V) Three-phase (208...480 V)
• 35 mm rail (EN 60715) mount
voltage monitoring: voltage monitoring:
• European patent pending for the innovative
• Phase loss • Phase loss
principle at the root of the 3 phase monitoring
• Phase rotation • Phase rotation
and error survey system (70.61)

Screw terminal

For outline drawing see page 10


Contact specification
Contact configuration 1 CO (SPDT) 2 CO (DPDT)
Rated current/Maximum peak current A 6 / 15 8 / 15
Rated voltage/Max. switching voltage V AC 250 / 400 250 / 400
Rated load AC1 VA 1,500 2,000
Rated load AC15 VA 250 400
Single phase motor rating (230 V AC) kW 0.185 0.3
Breaking capacity DC1: 30/110/220 V A 3 / 0.35 / 0.2 8 / 0.3 / 0.12
Minimum switching load mW (V/mA) 500 (10 / 5) 300 (5 / 5)
Standard contact material AgCdO AgNi
Supply specification
Nominal system voltage (UN) V AC (50/60 Hz) 208…480 208...480
Rated power VA (50 Hz) / W 8/1 11 / 0.8
Operating range V AC (50/60 Hz) 170…500 170...520
Technical data
Electrical life at rated load AC1 cycles 100 · 103 60 · 103
Switch-off delay time s 0.5 0.5
Switch-on lock-out time s 0.5 0.5
Power-on activation time s <2 <2
III-2015, www.findernet.com

Insulation between supply and contacts (1.2/50 μs)kV 5 5


Dielectric strength between open contacts V AC 1,000 1,000
Ambient temperature °C –20…+60 –20...+60
Protection category IP20 IP20
Approvals (according to type)
3
70
SERIES 70 Series - Line monitoring relay
Ordering information
Example: 70 series, three-phase voltage monitoring relay, 1 output, supply voltage 380…415 V AC.
A B C D

7 0 . 3 1 . 8 . 4 0 0 . 2 0 2 2
Series D: Fault memory option
0 = No fault memory
Type
2 = Fault memory function selectable
1=1 phase AC line monitoring
3=3 phase AC line monitoring C: Time delay setting
4=3 phase + neutral AC line monitoring 0 = Fixed switch-off delay
6=3 phase loss and rotation monitoring 2 = Adjustable switch-off delay
3 = Adjustable switch-off
No. of poles
delay and asymmetry
1 = 1 pole
2 = 2 pole B: Contact circuit
0 = CO
Supply version
8 = AC (50/60 Hz) A: Detection values
0 = Non-adjustable detection values
Supply voltage
2 = 2 adjustable detection values
230 = 220…240 V (70.11)
400 = 380…415 V (70.31/41/42) Codes
400 = 208…480 V (70.61/62) 70.11.8.230.2022 70.42.8.400.2032
E 70.31.8.400.2022 70.61.8.400.0000
70.41.8.400.2030 70.62.8.400.0000

Monitoring and function overview


70.11 70.31 70.41 70.42 70.61/62
Supply system type Single phase system 3-phase systems 3-phase systems 3-phase systems 3-phase systems
Nominal voltage 50/60 Hz V 220...240 380...415 380...415 380...415 208...480
Undervoltage with/without memory (selectable) • • — • —
Overvoltage with/without memory (selectable) • • — • —
Window Mode with/without memory (selectable) • • — • —
Window Mode without memory — — • — —
Phase loss — • • • •
Phase rotation — • • • •
Phase asymmetry — — • • —
Neutral loss (selectable) — — • • (fixed) —

Technical data
Insulation 70.11/31/41/42 70.61/62
Between supply and contacts dielectric strength V AC 2,500 3,000
impulse (1.2/50 μs) kV 4 5
Between open contacts dielectric strength V AC 1,000 1,000
impulse (1.2/50 μs) kV 1.5 1.5
EMC specifications
Type of test Reference standard
Electrostatic discharge contact discharge EN 61000-4-2 4 kV
air discharge EN 61000-4-2 8 kV
Radiated electromagnetic field 80 … 1,000 MHz EN 61000-4-3 10 V/m
1 … 2.8 GHz EN 61000-4-3 5 V/m
Fast transients on supply terminals EN 61000-4-4 4 kV
(burst 5/50 ns, 5 and 100 kHz)
Voltage pulses on supply common mode EN 61000-4-5 4 kV
terminals (surge 1.2/50 μs) differential mode EN 61000-4-5 4 kV
Radiofrequency common mode on supply terminals EN 61000-4-6 10 V
voltage (0.15…230 MHz)
Voltage dips 70 % UN EN 61000-4-11 25 cycles
Short interruptions EN 61000-4-11 1 cycle
Radiofrequency conducted emissions 0.15…30 MHz CISPR 11 class B
Radiated emissions 30…1,000 MHz CISPR 11 class B
Terminals solid cable stranded cable
Max. wire size mm2 1x6/2x4 1 x 4 / 2 x 2.5
III-2015, www.findernet.com

AWG 1 x 10 / 2 x 12 1 x 12 / 2 x 14
Screw torque Nm 0.8
Wire strip length mm 9
Other data 70.11 70.31/41 70.42/61/62
Power lost to the environment without output current W 0.8 0.9 1
with rated output current W 2 1.2 1.4
4
70
70 Series - Line monitoring relay SERIES

Functions
Output relay On (NO closed) when all OK: positive logic.

Type Overvoltage (OV and OVm functions) Functions


70.11 = Output contact
70.31 (11-14, 21-24 for 70.42 only)
70.42 OV = Overvoltage
OVm = Overvoltage with memory
UV = Undervoltage
UVm = Undervoltage with memory
W = Window mode (OV + UV)
Wm = Window mode (OV + UV)
with memory
Without Memory

H = Hysteresis

If the voltage moves out of limits, following


delay T the output relay turns Off.

When the voltage is again within limits


With memory

(± the Switch-on hysteresis H):


- if set in the “without memory” position, the
output relay “recovers”, i.e. it turns On
(after the Switch-on lock-out time) without
any memory of the previous event.
Type
70.11
Undervoltage (UV and UVm functions)
- if set in the “with memory” position E
(70.11, 70.42 and 70.31 only), the output
70.31
relay remains open. To reset, it is necessary
70.42
to switch the supply Off and then On again,
or to rotate the selector first to an adjacent
position and then to the original position.
Without Memory
With memory

Type Window mode (overvoltage + undervoltage, W and Wm functions)


70.11
70.31
70.41
(70.41
without
memory)
70.42
Without Memory
With memory
III-2015, www.findernet.com

5
70
SERIES 70 Series - Line monitoring relay
Functions
Output relay On (NO closed) when all OK: positive logic.

Type Phase loss and phase rotation If the sequence (L1, L2, L3) is incorrect at power-on, the output
70.31 relay will not turn-on.
70.41
70.42 If a phase is lost, the output relay turns off immediately.
70.61 When the phase is again active, the output relay turns on
70.62 immediately.

For types 70.61 and 70.62:


Phase loss monitoring possible even under regeneration up to
80% of the average of the other 2 phases.

(for 70.42 and 70.62 only)

E Type
70.41
Neutral loss and asymmetry If the neutral is lost (and the Neutral control function is set), the
output relay turns off immediately.
Asymmetry
70.42 When the neutral is again present, the output relay turns on
immediately

If the asymmetry (Umax - Umin)/UN is above the % set value, the


output relay turns off after the set delay T.
When the asymmetry is again below the % set value (with a fixed
hysteresis of approximately 2%), the output relay turns on after
the Switch-on lock-out time.

Neutral Loss

III-2015, www.findernet.com

6
70
70 Series - Line monitoring relay SERIES

Front view: function selector and regulators


70.11 70.31 70.41
Functions: Functions: N = With N-line
OV, OVm, UV, OV, OVm, UV, monitoring
UVm, W, Wm UVm, W, Wm N = Without N-line
monitoring
Toff delay: UMax: UMax:
(0.5...60) sec (380...480) V (380...480) V

UMax: UMin:
(220...270) V (300...400) V
(4...25) % UN

UMin: Toff delay: UMin:


(170...230) V (0.5...60) sec (300...400) V

Toff delay:
(0.5...60) sec

70.42
Functions:
OV, OVm, UV,
E
UVm, W, Wm

UMax:
(380...480) V

(5...25) % UN

UMin:
(300...400) V

Toff delay:
(0.5...60) sec
III-2015, www.findernet.com

7
70
SERIES 70 Series - Line monitoring relay
LED indication
Monitoring relay LED Supply system normal Supply system abnormal Supply system abnormal
Type (Voltage out of limits, (Reason for switch-off,
switch-off delay RESET necessary when ”with Memory”* is selected)
time T running)
Contact 11 - 14 closed Contact 11 - 14 closed Contact 11-14 open

• Overvoltage OV and OVm

70.11.8.230.2022 • Undervoltage UV and UVm

With Memory, following a


failure a manual “RESET”
** is necessary

• Overvoltage OV and OVm

70.31.8.400.2022 • Undervoltage UV and UVm

• Phase loss

Phase rotation

With Memory, following a


E failure a manual “RESET”
** is necessary

• Overvoltage OV

70.41.8.400.2030 • Undervoltage UV

• Asymmetry

Phase loss

Neutral loss

Phase rotation

• Overvoltage OV and OVm

70.42.8.400.2032 • Undervoltage UV and UVm

• Asymmetry

Phase loss

Neutral loss

Phase rotation

With Memory, following a


failure a manual “RESET”
** is necessary

70.61.8.400.0000 • Phase rotation or


Phase loss

70.62.8.400.0000 • Phase loss

Phase rotation

* The function “with Memory” is only available for type 70.11, 70.42 and 70.31.
**It is necessary to switch the supply OFF and then On again (U off U on) or to rotate the function selector first to an adjacent position and then
to the original position.
III-2015, www.findernet.com

8
70
70 Series - Line monitoring relay SERIES

Wiring diagrams
L L1 L1
N L2 L2
L3 L3
N

Type 70.11 Type 70.31 Type 70.41

L1 E
L1 L1
L2
L2 L2
L3
L3 L3
N

Type 70.42 Type 70.61 Type 70.62

Application example
The output contact switches the coil of the line contactor.

L1
L2
L3
N
III-2015, www.findernet.com

9
70
SERIES 70 Series - Line monitoring relay
Outline drawings
70.11 70.31
Screw terminal Screw terminal

E 70.41
Screw terminal
70.42
Screw terminal

70.61 70.62
Screw terminal Screw terminal III-2015, www.findernet.com

10
70
70 Series - Line monitoring relay SERIES

Accessories
Adaptor for panel mounting, plastic, 17.5 mm wide for 70.11 and 70.61 020.01

020.01

Adaptor for panel mounting, plastic, 35 mm wide for 70.31, 70.42 and 70.41 011.01

011.01

Sheet of marker tags, plastic, 72 tags, 6x12 mm for 70.11, 70.31, 70.41, 70.42 and 70.62 060.72 E

060.72

Sheet of marker tags, plastic, 24 tags, 9x17 mm for 70.61 020.24

020.24

Identification tag, plastic, 1 tag, 17x25.5 mm for 70.11, 70.31, 70.42 and 70.41 019.01

019.01

Separator for rail mounting, plastic, 9 mm wide 022.09

022.09