X-DCS2000 Digital Integrated System Manager

(abbr.DCS) is the basic unit of X-618 Public Address and


Voice Alarm System. DCS integrates plentiful functions
such as zone expansion, multiple audio sources support,
audio file storage, net audio,broadcasting, zone control,
monitoring, fault diagnosis etc. With powerful audio matrix
structure, X-DCS2000 is capable of bringing value to big
infrastructures in terms of saving extension and cabling.

X-ND100
Honeywell

BROADCASTING Specifications
DCS supports a variable range of audio sources, such Parameters Values
as audio files from external devices
Main power supply voltage AC 100-240V, 50/60Hz
(CD/DVD, cassette, FM tuner and etc.), remote paging
Backup power supply voltage DC 21.5V-28.5V
announcement or broadcasting from X-NPMS, etc.
DC power output DC24V/1A
Main power supply fuse T2AL250V
DCS can broadcast 4 audio message or internet audio
Rated power sow
simultaneously. Timer broadcast setting can be config­
Auxiliary input
ured via software to allow system to play specific
Channels 3
programs at a specific time even when it is not super­
Auxiliary input AUX1: 0dBV ( 1V)
vised. With the software, user can also handle up to 255
AUX2, 3: -40dBV-0dBV
priorities to meet complex public address requirements.
Input impedance 10KO
Frequency response 60Hz-16KHz (local input signal)

COMPONENTS SNR >85dB


Audio output
Buttons for special operations: select all, reset, error Channels 8 channels main power amplifier,
confirm and etc. 2 channels standby power amplifier,
Zone selection buttons 2 channels auxiliary output
Audio source selection buttons Output signal 1.2V(<1.6dBV)
Emergency mode button Record output 1V(0dBV)
THO <0.06%
DCL Inputs
INDICATORS
Channels 8

Device status indicator lights can show whether the Module Number 5 modules per channel

device is powered, malfunctioned, disabled, running or Module Type Noise Detector, EOLmodule

delayed Loudspeaker circuit

Zone status indicator lights Output Voltage 100V

Audio source status indicator lights Channels 8 (with circuit fault detection)
Max. Output load power 500W
Contact Input /Output
INTERFACES Contact input B(with circuit fault detection)
Contact output 8 outputs (NO, NC and COM)
8 dry-contact outputs
Maximum voltage of the outputs 250V AC / 30V DC
8 loudspeaker line outputs
Maximum current of the outputs 2.5A
8 dry-contact inputs
Other
8 DCL inputs
Monitoring loudspeaker 10W/8O
8 amplifier interfaces
Ethernet interface 10M/100M
RS - 485 port for fire alarm
Ethernet switching 4 ports
Main power port
Memory capacity 1GB (606MB for audio files)
Backup power port (DC 24V)
Working conditions
4 10/1 QOM adaptable Ethernet interfaces
Working temperature -1o0c to +55°C
Storage temperature
Certification and Standard
Humidity <95%, without condensing
Category Region Certification
Specification
Safety Europe CE Complied
Dimension (WxHxD) 482 mmxBB mm x420mm
Packing dimension (WxHxD) 580mmx235mm x552mm
Net weight 9.3Kg
Gross weight 12.5Kg

X-618 Digital Public Address/ Voice Alarm System I X-DCS2000Digital Integrated System Manager -- Page 2/ 3