TEST REPORT

No. GZIN2007034267SC
Date Jul 24 , 2022
Page: 1 of 4

CUSTO MER NAME: DANUBE BUILDING MATERIALS


ADDRESS: Jabel Ali Free Zone, Gate No 4 - Dubai

Sample Name MILANO M88 FIRE RETARDANT PU FOAM


Manufacturer
Above information and sample(s) was/were submitted and confirmed by the client. SGS,however,
assumes no responsibility to verify the accuracy,adequacy and completeness of the sample
information provided by client.

Date of Receipt Jun 28,2022


Testing Start Date Jun 28,2022
Testing End Date Jul 24, 2022
Test result(s) For further details, please refer to the following page(s)
(Unless otherwise stated the results shown in this test report refer only to
the sample(s) tested)

Signed for
SGS-CSTC Standards Technical
Services Co., Ltd. GZ Branch Testing
Center

Quincey lee
Authorized signatory

Unless otherwise agreed In writing, this document Is is.s.ued by the Company subject to ks General Conditions of Service printed
\�fill£' 1
1:T��-.�� rt��:;rJ�•�•M::�1�n&:cii�n:2�fhm1!JYJ!w�S-:.�'!:!'r!a���s!o:o=�:•;:

,�:=�.:��
���1���
Attention Is drawn to the !Imitation or liability, indemnification a uns ictioo issues e n rmn. y er o •• ment a
:�:srr�= '1! �: tt'!gi,�;r:r::. �� �=i"d':'s':!r ::!.':'�l; ;!!.-J.�1:,°!
u $ d m
C1, : ��: :�::����:. :"a����::'e:n"/:�� ny

:;�:������, ::���lJ����.����.�r��� :�.�-�::�:�


transaction from exercising all their �hts and obngatlons un'ler the lransactlon documents. This document cannot be reproduced
r.t$1r.t,\H m ,�
mpectioft !losing -
���.��f:: :��tt�1::::n��"::=1rh°!
re.suit$ $hown In this test report ,efar only to the s:arnpae(a) test:fand such umpla(a) are retained fot 30 dayaon.ty.
Atten tion To c:h■ck th• authenticity of t■sling f inspection report & cert1f,c:ate, pleas. contact us at telephon■:(H•7S5) 8307
1443, o, ■mall [email protected]
si:; l.��rJQ�?' Lid_ 1!111"'1!ulbllSdndiPal�EmmUfamq�llslli�On 510663 t (86-3))8215fi661 f (86-3))82075(8) www.sgsgroup.<Xll1l.ai
ij,liil •iltt •&gflf::,jt:1flltl&M!ltlllM!lJ&198� iHI: 510663 t (86-3))8215fi661 f (86-3))82075(8) • [email protected]

Member of the SGS Group (SGS SA)


TEST REPORT
No. GZIN2007034267SC
Date Jul 24, 2022
Page: 2 of 4

Test Requested:
To determine the flammability (building materials class B2) in accordance with DIN 4102-1 (May 1998)
Fire behaviour of building materials and elements Part 1: Classification of building materials,
Requirements and testing
Conclusion: The tested sample meets the Normal flammability requirements of class B1 of building
materials under DIN 4102-1 (May 1998).

Unless otherwise agreed In writing, this document Is is.s.ued by the Company subject to ks General Conditions of Service printed
\�fill£' 1
1:T��-.�� rt��:;rJ�•�•M::�1�n&:cii�n:2�fhm1!JYJ!w�S-:.�'!:!'r!a���s!o:o=�:•;:
::!.':'�l; 1
:;�:������, ::���lJ����.����.�r��� :�.�-�::�:� ���.��f::,�:=�.:�� :��tt�1::::n��"::=
���1���
Attention Is drawn to the !Imitation or liability, indemnification a uns ictioo issues e n rmn. y er o •• ment a
:�::����:. :"a����::'e:n"/:�� :�:srr�= '1! �: tt'!gi,�;r:r::. �� �=i"d':'s':!r °!
d m
C1, : ��: u $ ny
;!!.-J.�1:,
transaction from exercising all their �hts and obngatlons un'ler the lransactlon documents. This document cannot be reproduced
r.t$1r.t,\H m ,� rh°!
mpectioft !losing - re.suits shown In this test report refer only to the s:arnpae(a) test:fand such umple(a) are retained fot 30 dayaon.ty.
Atten tion To c:h■ck th• authenticity of t■sling f inspection report & cert1f,c:ate, pt.as. contact us at t■lephon■:(H•7S5) 8307
1443, o, ■mall [email protected]
si:; l.��rJQ�?' Lid_ 1!111"'1!ulbllSdndiPal�EmmUfamq�llslli�On 510663 t (86-3))8215fi661 f (86-3))82075(8) www.sgsgroup.<Xll1l.ai
ij,liil •iltt •&gflf::,jt:1flltl&M!ltlllM!lJ&198� iHI: 510663 t (86-3))8215fi661 f (86-3))82075(8) • [email protected]

Member of the SGS Group (SGS SA)


TEST REPORT
No.
GZIN2007034267SC
Date : Jul 24, 2022
Page: 3 of 4
I. Test conducted
This test was conducted as per DIN 4102-1 :1998 Clause 6.2. Classification in according to DIN 4102-
1 (May 1998) Clause 6.2. Class B2 materials.

II. Sample details

Sample description PU foam

Color Yellow

Area density About 647 g/m2


Size of sample 190mmx90mmx(26.2~31.0)mm

Conditioning
Prior to testing, the sample was conditioned at least 14 days to constant mass at a temperature of 23
± 2 °C, and a relative humidity of 50 ± 5 %.
Ill. Test results
Normal Flammability Test according to DIN 4102-1 Clause 6.2.1
Edge ignition
Fire application time: 15s

Parameter 1 2 3 4 5
Whether or not flaming extinguished before reach the
Yes Yes Yes Yes Yes
gauge mark (Yes/No)
Whether or not flaming reach the measuring mark
No No No No No
within 20 seconds ( Yes/No)
Time for the flame tip to reach the gauge mark (s) NA NA NA NA NA
Afterflame time (s) 0 0 0 0 0

Max. flame height (cm) 7 6 7 6 8

Molten dripping (Yes/No) No No No No No

Smoke developments (visual impression) Medium

Note: NA---Not applicable

To be continued...

Unless otherwise agreed In writing, this document Is is.s.ued by the Company subject to ks General Conditions of Service printed
1 n m1

,�:=�.:��
\�fill£' ���1��� 1:T��-.�� rt��:;rJ�•�•M::�1� &:cii�n:2�fh !JYJ!w�S-:.�'!:!'r!a���s!o:o=�:•;:
Attention Is drawn to the !Imitation or liability, indemnification a uns ictioo issues e n rmn. y er o •• ment a
C1,:��: :�::����:. :"a����::'e:n"/:�� :�:srr�= �: tt'!gi,�;r:r::. �� �=i"':'':!r ::!.':'�l; ;!!.-J.�1:,°!
u $ ny d m
'1! d s

:;�:������, ::���lJ����.����.�r��� :�.�-�::�:� ���.��f::


transaction from exercising all their �hts and obngatlons un'ler the lransactlon documents. This document cannot be reproduced
:��tt�1::::n��"::=
1
r.t$1r.t,\H m ,� rh°!
mpectioft !losing - re.suit$ $hown In this test report ,efar only to the s:arnpae(a) test:fand such umpla(a) are retained fot 30 dayaon.ty.
Atten tion To c:h■ck th• authenticity of t■sling f inspection report & cert1f,c:ate, pleas. contact us at telephon■:(H•7S5) 8307
1443, o, ■mall [email protected]
si:; l.��rJQ�?' Lid_ 1!111"'1!ulbllSdndiPal�EmmUfamq�llslli�On 510663 t (86-3))8215fi661 f (86-3))82075(8) www_sgsgroup.<Xllll.ai
ij,liil •iltt •&gflf::,jt:1flltl&M!ltlllM!lJ&198� iHI: 510663 t (86-3))8215fi661 f (86-3))82075(8) • [email protected]

Member of the SGS Group (SGS SA)


TEST REPORT
No. GZIN2007034267SC
Date : Jul 24, 2022
Page: 4 of 4

DIN 4102-1:1998 Criteria for B2/B3 classification


1) Materials may be classed as B2 materials if they pass the ignitibility test specified in DIN 4102-1:
1998 subclause 6.2.
For each specimen, flaming doesn't reach the gage mark within 20s after flame application.
2) Combustible materials which cannot be classed as B1 or B2 materials shall be classed as B3
materials

STATEMENTS:
This declaration of conformity is only based on the result of this laboratory activity, the impact of the
uncertainty of the results was not included.
This test report does not replace any mandatory certification of the product that may be required.
The test results relate to the behaviour of the test specimens of a product under the particular
conditions of the test; they are not intended to be the sole criterion for assessing the potential fire and
smoke hazard of the product in use.

Photo Appendix:

Appendix Information:
The above test was carried out by SGS-CSTC Co., Ltd. Anji Branch.
******** End of report********

Unless otherwise agreed In writin g, this document Is is.s.ued by the Company subject to ks General Conditions of Service printed
1 n m1

,�:=�.:��
\�fill£' ���1��� 1:T��-.�� rt��:;rJ�•�•M::�1� &:cii�n:2�fh !JYJ!w�S-:.�'!:!'r!a���s!o:o=�:•;:
Attention Is drawn to the !Imitation or liability, indemnification a uns ictioo issues e n rmn. y er o •• ment a
C1,:��: :�::����:. :"a����::'e:n"/:�� :�:srr�= �: tt'!gi,�;r:r::. �� �=i"':'':!r ::!.':'�l; ;!!.-J.�1:,°!
u $ ny d m
'1! d s

:;�:������, ::���lJ����.����.�r��� :�.�-�::�:� ���.��f::


transaction from exercising all their �hts and obngatlons un'ler the lransactlon documents. This document cannot be reproduced
:��tt�1::::n�� "::=
1
r.t$1r.t,\H m ,� rh°!
mpectioft !losing - re.suit$ $hown In this test report ,efar only to the s:arnpae(a) test:fand such umpla(a) are retained fot 30 dayaon.ty.
Attantion To c:hack th• authanticity of tasling f inspection report & cert1f,c:ate, pleas. contact us at talephon■:(H•7S5) 8307
1443, o, •mall [email protected]
si:; l.��rJQ�?' Lid_ 1!111"'1!ulbllSdndiPal�EmmUfamq�llslli�On 510663 t (86-3))8215fi661 f (86-3))82075(8) www.sgsgroup.<Xll1l.ai
ij,liil •iltt •&gflf::,jt:1flltl&M!ltlllM!lJ&198� iHI: 510663 t (86-3))8215fi661 f (86-3))82075(8) • [email protected]

Member of the SGS Group (SGS SA)