Form - 4
SECONDARY WIRE COMPUTATION
FOR T-1
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P-2 to P-3 : Total Load = 45.92442 kVA
I = Load KVA/ 230 = 45.92442 /230= 199.6714 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
45.92442 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 199.6714 = 43564.66
CM =
11 11
CM: 52635 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 1.22 Ω / mile Xa = 1.22 Ω / mile
Xsf = 0.134 Ω / mile
X = Xa + (-0.049) 1.22 -0.049
= = 0.9598
R R 1.22
Actual Voltage Drop = (24 x d x I)/CM
24x100x 199.6714
= = 9.104423
52635
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 9.104423 x94
x 100 = = 3.72%
230 230
Use 52635 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-2
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P-5 to P-6 : Total Load = 33.33488 kVA
I = Load KVA/ 230 = 33.33488 /230= 144.9343 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
33.33488 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 144.9343 = 31622.02
CM =
11 11
CM: 33102 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 1.92 Ω / mile Xa = 0.138 Ω / mile
Xsf = 0.622 Ω / mile
X = Xa + (-0.049) 0.138 -0.049
= = 0.0464
R R 1.92
Actual Voltage Drop = (24 x d x I)/CM
24x100x 144.9343
= = 10.50819
33102
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 10.50819 x94
x 100 = = 4.29%
230 230
Use 33102 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-3
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P-8 to P-9 : Total Load = 29.15312 kVA
I = Load KVA/ 230 = 29.15312 /230= 126.7527 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
29.15312 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 126.7527 = 27655.14
CM =
11 11
CM: 0.042947 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 0 Ω / mile Xa = 0 Ω / mile
Xsf = 0 Ω / mile
X = Xa + (-0.049) 0 -0.049
= = #DIV/0!
R R 0
Actual Voltage Drop = (24 x d x I)/CM
24x100x 126.7527
= = 7083378
0.04294653
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 7083378 x94
x 100 = = ########
230 230
Use 0.042947 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-4
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P - 11 to P - 12 : Total Load = 25.08511 kVA
I = Load KVA/ 230 = 25.08511 /230= 109.0657 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
25.08511 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 109.0657 = 23796.15
CM =
11 11
CM: 0.285 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 182 Ω / mile Xa = 0.131 Ω / mile
Xsf = 1.21 Ω / mile
X = Xa + (-0.049) 0.131 -0.049
= = 0.0005
R R 182
Actual Voltage Drop = (24 x d x I)/CM
24x100x 109.0657
= = 918448.1
0.285
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 918448.1 x94
x 100 = = ########
230 230
Use 0.285 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-5
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P - 14 to P - 15 : Total Load = 28.4186 kVA
I = Load KVA/ 230 = 28.4186 /230= 123.5591 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
28.4186 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 123.5591 = 26958.36
CM =
11 11
CM: 33102 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 1.89 Ω / mile Xa = 0.145 Ω / mile
Xsf = 0.628 Ω / mile
X = Xa + (-0.049) 0.145 -0.049
= = 0.0508
R R 1.89
Actual Voltage Drop = (24 x d x I)/CM
24x100x 123.5591
= = 8.958429
33102
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 8.958429 x94
x 100 = = 3.66%
230 230
Use 33102 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-6
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P - 17 to P - 18 : Total Load = 33.33488 kVA
I = Load KVA/ 230 = 33.33488 /230= 144.9343 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
33.33488 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 144.9343 = 31622.02
CM =
11 11
CM: 33102 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 1.92 Ω / mile Xa = 0.138 Ω / mile
Xsf = 0.622 Ω / mile
X = Xa + (-0.049) 0.138 -0.049
= = 0.0464
R R 1.92
Actual Voltage Drop = (24 x d x I)/CM
24x100x 144.9343
= = 10.50819
33102
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 10.50819 x94
x 100 = = 4.29%
230 230
Use 33102 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-7
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P - 20 to P - 21 : Total Load = 33.33488 kVA
I = Load KVA/ 230 = 33.33488 /230= 144.9343 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
33.33488 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 144.9343 = 31622.02
CM =
11 11
CM: 33102 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 1.92 Ω / mile Xa = 0.138 Ω / mile
Xsf = 0.622 Ω / mile
X = Xa + (-0.049) 0.138 -0.049
= = 0.0464
R R 1.92
Actual Voltage Drop = (24 x d x I)/CM
24x100x 144.9343
= = 10.50819
33102
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 10.50819 x94
x 100 = = 4.29%
230 230
Use 33102 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-8
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P - 23 to P - 24 : Total Load = 29.15312 kVA
I = Load KVA/ 230 = 29.15312 /230= 126.7527 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
29.15312 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 126.7527 = 27655.14
CM =
11 11
CM: 33102 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 1.89 Ω / mile Xa = 0.145 Ω / mile
Xsf = 0.628 Ω / mile
X = Xa + (-0.049) 0.145 -0.049
= = 0.0508
R R 1.89
Actual Voltage Drop = (24 x d x I)/CM
24x100x 126.7527
= = 9.189973
33102
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 9.189973 x94
x 100 = = 3.76%
230 230
Use 33102 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-9
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P - 26 to P - 27 : Total Load = 29.26687 kVA
I = Load KVA/ 230 = 29.26687 /230= 127.2473 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
29.26687 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 127.2473 = 27763.04
CM =
11 11
CM: 33102 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 1.89 Ω / mile Xa = 0.145 Ω / mile
Xsf = 0.628 Ω / mile
X = Xa + (-0.049) 0.145 -0.049
= = 0.0508
R R 1.89
Actual Voltage Drop = (24 x d x I)/CM
24x100x 127.2473
= = 9.22583
33102
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 9.22583 x94
x 100 = = 3.77%
230 230
Use 33102 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-10
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P - 29 to P - 30 : Total Load = 29.26687 kVA
I = Load KVA/ 230 = 29.26687 /230= 127.2473 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
29.26687 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 127.2473 = 27763.04
CM =
11 11
CM: 20820 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 3.01 Ω / mile Xa = 0.152 Ω / mile
Xsf = 0.654 Ω / mile
X = Xa + (-0.049) 0.152 -0.049
= = 0.0342
R R 3.01
Actual Voltage Drop = (24 x d x I)/CM
24x100x 127.2473
= = 14.66827
20820
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 14.66827 x94
x 100 = = 5.99%
230 230
Use 20820 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-11
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P - 32 to P - 33 : Total Load = 29.15312 kVA
I = Load KVA/ 230 = 29.15312 /230= 126.7527 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
29.15312 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 126.7527 = 27655.14
CM =
11 11
CM: 26251 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 2.39 Ω / mile Xa = 0.148 Ω / mile
Xsf = 0.637 Ω / mile
X = Xa + (-0.049) 0.148 -0.049
= = 0.0414
R R 2.39
Actual Voltage Drop = (24 x d x I)/CM
24x100x 126.7527
= = 11.58838
26251
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 11.58838 x94
x 100 = = 4.74%
230 230
Use 26251 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-12
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P - 35 to P - 36 : Total Load = 44.88219 kVA
I = Load KVA/ 230 = 44.88219 /230= 195.1399 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
44.88219 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 195.1399 = 42575.99
CM =
11 11
CM: 33102 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 1.92 Ω / mile Xa = 0.138 Ω / mile
Xsf = 0.622 Ω / mile
X = Xa + (-0.049) 0.138 -0.049
= = 0.0464
R R 1.92
Actual Voltage Drop = (24 x d x I)/CM
24x100x 195.1399
= = 14.14826
33102
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 14.14826 x94
x 100 = = 5.78%
230 230
Use 33102 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-13
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P - 38 to P - 39 : Total Load = 33.33488 kVA
I = Load KVA/ 230 = 33.33488 /230= 144.9343 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
33.33488 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 144.9343 = 31622.02
CM =
11 11
CM: 41741 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 1.52 Ω / mile Xa = 0.135 Ω / mile
Xsf = 0.609 Ω / mile
X = Xa + (-0.049) 0.135 -0.049
= = 0.0566
R R 1.52
Actual Voltage Drop = (24 x d x I)/CM
24x100x 144.9343
= = 8.333347
41741
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 8.333347 x94
x 100 = = 3.41%
230 230
Use 41741 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-14
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P - 41 to P - 42 : Total Load = 33.33488 kVA
I = Load KVA/ 230 = 33.33488 /230= 144.9343 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
33.33488 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 144.9343 = 31622.02
CM =
11 11
CM: 33102 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 1.92 Ω / mile Xa = 0.138 Ω / mile
Xsf = 0.622 Ω / mile
X = Xa + (-0.049) 0.138 -0.049
= = 0.0464
R R 1.92
Actual Voltage Drop = (24 x d x I)/CM
24x100x 144.9343
= = 10.50819
33102
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 10.50819 x94
x 100 = = 4.29%
230 230
Use 33102 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-15
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P - 44 to P - 45 : Total Load = 33.33488 kVA
I = Load KVA/ 230 = 33.33488 /230= 144.9343 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
33.33488 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 144.9343 = 31622.02
CM =
11 11
CM: 33102 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 1.92 Ω / mile Xa = 0.138 Ω / mile
Xsf = 0.622 Ω / mile
X = Xa + (-0.049) 0.138 -0.049
= = 0.0464
R R 1.92
Actual Voltage Drop = (24 x d x I)/CM
24x100x 144.9343
= = 10.50819
33102
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 10.50819 x94
x 100 = = 4.29%
230 230
Use 33102 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-16
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P - 47 to P - 48 : Total Load = 33.33488 kVA
I = Load KVA/ 230 = 33.33488 /230= 144.9343 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
33.33488 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 144.9343 = 31622.02
CM =
11 11
CM: 33102 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 1.92 Ω / mile Xa = 0.138 Ω / mile
Xsf = 0.622 Ω / mile
X = Xa + (-0.049) 0.138 -0.049
= = 0.0464
R R 1.92
Actual Voltage Drop = (24 x d x I)/CM
24x100x 144.9343
= = 10.50819
33102
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 10.50819 x94
x 100 = = 4.29%
230 230
Use 33102 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-17
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P - 50 to P - 51 : Total Load = 53.40371 kVA
I = Load KVA/ 230 = 53.40371 /230= 232.1901 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
53.40371 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 232.1901 = 50659.65
CM =
11 11
CM: 52635 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 1.22 Ω / mile Xa = 0.134 Ω / mile
Xsf = 0.585 Ω / mile
X = Xa + (-0.049) 0.134 -0.049
= = 0.0697
R R 1.22
Actual Voltage Drop = (24 x d x I)/CM
24x100x 232.1901
= = 10.58718
52635
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 10.58718 x94
x 100 = = 4.33%
230 230
Use 52635 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-18
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P - 53 to P - 54 : Total Load = 33.33488 kVA
I = Load KVA/ 230 = 33.33488 /230= 144.9343 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
33.33488 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 144.9343 = 31622.02
CM =
11 11
CM: 33102 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 1.92 Ω / mile Xa = 0.138 Ω / mile
Xsf = 0.622 Ω / mile
X = Xa + (-0.049) 0.138 -0.049
= = 0.0464
R R 1.92
Actual Voltage Drop = (24 x d x I)/CM
24x100x 144.9343
= = 10.50819
33102
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 10.50819 x94
x 100 = = 4.29%
230 230
Use 33102 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-19
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P - 56 to P - 57 : Total Load = 33.33488 kVA
I = Load KVA/ 230 = 33.33488 /230= 144.9343 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
33.33488 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 144.9343 = 31622.02
CM =
11 11
CM: 33102 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 1.92 Ω / mile Xa = 0.138 Ω / mile
Xsf = 0.622 Ω / mile
X = Xa + (-0.049) 0.138 -0.049
= = 0.0464
R R 1.92
Actual Voltage Drop = (24 x d x I)/CM
24x100x 144.9343
= = 10.50819
33102
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 10.50819 x94
x 100 = = 4.29%
230 230
Use 33102 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-20
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P - 59 to P - 60 : Total Load = 29.26687 kVA
I = Load KVA/ 230 = 29.26687 /230= 127.2473 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
29.26687 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 127.2473 = 27763.04
CM =
11 11
CM: 33102 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 0.145 Ω / mile Xa = 0.628 Ω / mile
Xsf = 0.628 Ω / mile
X = Xa + (-0.049) 0.628 -0.049
= = 3.9931
R R 0.145
Actual Voltage Drop = (24 x d x I)/CM
24x100x 127.2473
= = 9.22583
33102
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 9.22583 x94
x 100 = = 3.77%
230 230
Use 33102 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-21
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P - 62 to P - 63 : Total Load = 33.33488 kVA
I = Load KVA/ 230 = 33.33488 /230= 144.9343 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
33.33488 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 144.9343 = 31622.02
CM =
11 11
CM: 33102 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 1.92 Ω / mile Xa = 0.138 Ω / mile
Xsf = 0.622 Ω / mile
X = Xa + (-0.049) 0.138 -0.049
= = 0.0464
R R 1.92
Actual Voltage Drop = (24 x d x I)/CM
24x100x 144.9343
= = 10.50819
33102
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 10.50819 x94
x 100 = = 4.29%
230 230
Use 33102 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-22
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P - 65 to P - 66 : Total Load = 33.33488 kVA
I = Load KVA/ 230 = 33.33488 /230= 144.9343 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
33.33488 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 144.9343 = 31622.02
CM =
11 11
CM: 33102 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 1.92 Ω / mile Xa = 0.138 Ω / mile
Xsf = 0.622 Ω / mile
X = Xa + (-0.049) 0.138 -0.049
= = 0.0464
R R 1.92
Actual Voltage Drop = (24 x d x I)/CM
24x100x 144.9343
= = 10.50819
33102
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 10.50819 x94
x 100 = = 4.29%
230 230
Use 33102 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-23
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P - 68 to P - 69 : Total Load = 33.33488 kVA
I = Load KVA/ 230 = 33.33488 /230= 144.9343 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
33.33488 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 144.9343 = 31622.02
CM =
11 11
CM: 33102 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 1.92 Ω / mile Xa = 0.138 Ω / mile
Xsf = 0.622 Ω / mile
X = Xa + (-0.049) 0.138 -0.049
= = 0.0464
R R 1.92
Actual Voltage Drop = (24 x d x I)/CM
24x100x 144.9343
= = 10.50819
33102
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 10.50819 x94
x 100 = = 4.29%
230 230
Use 33102 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-24
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P - 71 to P - 72 : Total Load = 33.33488 kVA
I = Load KVA/ 230 = 33.33488 /230= 144.9343 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
33.33488 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 144.9343 = 31622.02
CM =
11 11
CM: 33102 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 1.92 Ω / mile Xa = 0.138 Ω / mile
Xsf = 0.622 Ω / mile
X = Xa + (-0.049) 0.138 -0.049
= = 0.0464
R R 1.92
Actual Voltage Drop = (24 x d x I)/CM
24x100x 144.9343
= = 10.50819
33102
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 10.50819 x94
x 100 = = 4.29%
230 230
Use 33102 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-25
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P - 74 to P - 75 : Total Load = 33.33488 kVA
I = Load KVA/ 230 = 33.33488 /230= 144.9343 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
33.33488 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 144.9343 = 31622.02
CM =
11 11
CM: 33102 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 1.92 Ω / mile Xa = 0.138 Ω / mile
Xsf = 0 Ω / mile
X = Xa + (-0.049) 0.138 -0.049
= = 0.0464
R R 1.92
Actual Voltage Drop = (24 x d x I)/CM
24x100x 144.9343
= = 10.50819
33102
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 10.50819 x94
x 100 = = 4.29%
230 230
Use 33102 CM, Hard Drawn Copper Conductor
Form - 4
SECONDARY WIRE COMPUTATION
FOR T-26
KVA SPAN LEFT SIDE
To determine the size of wire of the secondary lines, assume V drop =
5% of the operating voltage for the no. of span for 1Ø, 2 wire system.
From P - 77 to P - 78 : Total Load = 33.33488 kVA
I = Load KVA/ 230 = 33.33488 /230= 144.9343 A
Distance = No. Of Span x 100 = 1x 100 = 100 ft
Total Load KVA:
33.33488 span, 11 volts, assume voltage drop at 5%
Refer to table:
24 x d x I 24x100x 144.9343 = 31622.02
CM =
11 11
CM: 33102 CM
Refer to table:
Actual DC Voltage Drop, 50°C, 60 Hz, 8” spacing,
R= 1.92 Ω / mile Xa = 0.138 Ω / mile
Xsf = 0 Ω / mile
X = Xa + (-0.049) 0.138 -0.049
= = 0.0464
R R 1.92
Actual Voltage Drop = (24 x d x I)/CM
24x100x 144.9343
= = 10.50819
33102
Actual Voltage Drop factor at 0.85 p.f. = 0.94
Voltage Regulation = AVD x df 10.50819 x94
x 100 = = 4.29%
230 230
Use 33102 CM, Hard Drawn Copper Conductor