PLC User's Manual of Analog Module
PLC User's Manual of Analog Module
Analog Module
User Manual & Application Case
User Manual
Contents
Chapter 1 User Manual .............................................................................................................................................1
1.1 Products receiving ........................................................................................................................................1
1.2 Model description .........................................................................................................................................1
1.3 Product model list & dimensions ..................................................................................................................1
1.4 Front / side view ...........................................................................................................................................2
1.5 Indicator description .....................................................................................................................................2
1.6 Power supply specification ...........................................................................................................................3
1.7 Environmental specifications for product .....................................................................................................4
1.8 Analog Input (AI) specification .....................................................................................................................4
1.9 Analog output (AQ) specification..................................................................................................................5
1.10 Analog input (AI) wiring diagram ................................................................................................................5
1.11 Analog output (AQ) wiring diagram ............................................................................................................6
1.12 Terminal wiring diagram .............................................................................................................................6
1.13 Module parameter table .............................................................................................................................6
1.14 Mounting and installation .........................................................................................................................14
Chapter 2 Application Case .....................................................................................................................................15
2.1 Expand module through the host PLC parallel port ...................................................................................15
2.1.1 Module power supply .......................................................................................................................15
2.1.2 The analog need't be written any conversion program, read the analog register value directly. ....15
2.1.3 Temperature modules need't be written any conversion program, read the current temperature
value directly when access the sensor .....................................................................................................16
2.1.4 Programming skills...........................................................................................................................17
2.1.5 Display analog value/ temperature value on SCADA, HMI .............................................................17
2.1.6 When the engineering value is not used, the default code value is 0 ~ 32000...............................18
2.1.7 Module CR code application example: Read the module channel disconnection alarm ................18
2.2 Module used as remote IO .........................................................................................................................19
2.2.1 Module power supply .......................................................................................................................19
2.2.2 Communication port introduction .....................................................................................................19
2.2.3 Communication protocols and default parameters ..........................................................................19
2.2.4 Module parameter configuration method introduction, when the module is used as remote IO ....20
2.2.5 Parameter configuration example: The module is configured by programming software remote
module tool................................................................................................................................................20
2.2.6 Remote IO application example (RS485 mode): The PLC read the 4 communication temperature
values of SMC-AD04EN module ..............................................................................................................22
2.2.7 Remote IO application example (RS485 mode): The PLC writes the 8-channel output values of
SMC-DA08EN module ..............................................................................................................................23
2.2.8 Remote IO application example (Ethernet mode): PLC read and write each channel input and
output values of SMC-AN08EN-e .............................................................................................................24
2.2.9 SAVCH Cloud configuration communicates directly with SMC-AD08EN module example ............24
Chapter 1 User Manual
Model: SMC-AD04EN
Power: DC24V 0.07A
P/N:1605261053011810012
SAVCH ELECTRIC CO.,LTD.
S M C - AD 04 E N
Product name Output type
N(No digital I/O)
Module type
M (Main)
Product Series
E (Extension module)
AD (Analog expansion_AD input)
DA (Analog expansion_DA output) I/O point
AN (Analog expansion_AD/DA combination)
TR (Analog expansion_Thermal resistance input)
TC (Analog expansion_Thermocouple input)
1
Size A Size B
0 1 2 3 4 5 6 7
8 9 10 11
0 1 2 3 4 5 6 7 DI(X)
DI(X)
95.0
35.0
PWR PWR
SMC-C16ER SMC-C24ER
LINK LINK
ON DIP
DO(Y)
0 1 2 3 4 5 6 7 DO(Y)
1 2 3 4 0 1 22 33 44 55 6 6 7 7
8 9 10 11
61.5 84.5
3.0
84.0
70.0 93.0
1 8 9 10 11 12 13 14 15
2
AI0I AI0V AI0G GND A+ B- RS485
AI1I AI1V AI1G AI2I AI2V AI2G AI3I AI3V AI3G
0 1 2 3
3
AI
4 PWR
LINK
SMC-AD08EN
ON DIP
1 2 3 4 AI
4 5 6 7
6
7
2
Reference processing
Module bus state LINK indicator state
mode
No communication of module No light
MPU has identified the module
Constant light in green
Normal but no communication
Serial or parallel port in
Green jitter: indicator on 30ms and off 30ms
communication
Parallel power supply Without serial or parallel port in
Yellow flicker: indicator on 0.5s and off 0.5s
not enough, must communication
connect to external With serial or parallel port in Yellow is darkened and jitter alternately:
power supply communication indicator off 0.5s and jitter 0.5s
Without serial or parallel port in
Firmware upgrade Red flicker: indicator on 0.5s and off 0.5s
communication
failed, reupgrade the
With serial or parallel port in Red is darkened and jitter alternately:
module firmware
communication indicator off 0.5s and jitter 0.5s
Without serial or parallel port in
Constant light in red
Hardware failure and communication
maintenance With serial or parallel port in Red jitter quickly: indicator on 30ms and off
communication 30ms
(3) RJ45 Ethernet indicator: There are two Ethernet LEDs, green and yellow, as shown on the picture:
Color Status description
Green light is Physical connection of TCP module and external device is
long bright normal;
TCP module fails to connect with external device or the
Green light goes out
module itself is abnormal
TCP module is connected to an external device normally, and
blinking frequency indicates the data transmission speed.
Yellow light blinks
When speed is fast, human eye is not easy to distinguish, at
this time, yellow light is long bright.
No data transmission communication of TCP module and
Yellow light goes out
external device
3
1.7 Environmental specifications for product
Item Environment Specification
Operating temperature:0~+55℃
Temperature/Humidity Storage temperature:-25~+70℃
Humidity:5~95%RH, No condensation
10~57 HZ, amplitude=0.075mm, 57HZ~150HZ acceleration=1G, 10
Vibration Resistance
times each for X-axis, Y-axis and Z-axis
Impact Resistance 15G, duration=11ms, 6 times each for X-axis, Y-axis and Z-axis
Interference Immunity DC EFT:±2500V Surge:±1000V
1500VAC/1min between AC terminal and PE terminal, 500VAC/1min
Over Voltage Resistance
between DC terminal and PE terminal
Between AC terminal and PE terminal @500VDC,>=5MΩ ,all
Insulation Impedance
input/output points to PE terminal @500VDC
Operating environment Avoid dust, moisture, corrosion, electric shock and external shocks
4
Power consumption 24VDC ±20%,50mA(maximum)
5
1.11 Analog output (AQ) wiring diagram
6
Function description
CR code
SMC-AD04EN SMC-DA04EN SMC-AN04EN
09~0AH Reserve
High byte subnet mask (b3~b0,1 indicates 255, 0 indicates 0, for example subnet mask
0BH
255.255.255.0, b3~b0=1110), low byte reserved
0CH-0EH Reserve
Error code: 0-Normal, 1-Illegal firmware identity, 2-Incomplete firmware, 3-System data access
0FH
exception, 4-No external 24V power supply
10H channel 1 input value channel 1 output value input channel 1 input value
11H channel 2 input value channel 2 output value input channel 2 input value
input channel 1 signal type,
12H channel 3 input value channel 3 output value
note 2
input channel 2 signal type,
13H channel 4 input value channel 4 output value
note 2
Use the engineering value
14H channel 1 signal type, note 2 channel 1 signal type, note 2
mark, note 4
input channel 1 engineering
15H channel 2 signal type, note 2 channel 2 signal type, note 2
lower limiting value
input channel 2 engineering
16H channel 3 signal type, note 2 channel 3 signal type, note 2
lower limiting value
input channel 1 engineering
17H channel 4 signal type, note 2 channel 4 signal type, note 2
upper limiting value
Use the engineering value Use the engineering value input channel 2 engineering
18H
mark, note 4 mark, note 4 upper limiting value
channel 1 engineering lower channel 1 engineering lower input channel 1
19H
limiting value limiting value sampling frequency, note 1
channel 2 engineering lower channel 2 engineering lower input channel 2
1AH
limiting value limiting value sampling frequency, note 1
channel 3 engineering lower channel 3 engineering lower input channel 1 zero point
1BH
limiting value limiting value correction value
channel 4 engineering lower channel 4 engineering lower input channel 2 zero point
1CH
limiting value limiting value correction value
channel 1 engineering upper channel 1 engineering upper Channel 1~2 input
1DH
limiting value limiting value disconnection alarm, note 3
channel 2 engineering upper channel 2 engineering upper
1EH output channel 1 output value
limiting value limiting value
channel 3 engineering upper channel 3 engineering upper
1FH output channel 2 output value
limiting value limiting value
channel 4 engineering upper channel 4 engineering upper output channel 1 signal type,
20H
limiting value limiting value note 2
channel 1 output channel 2 signal type,
21H power-off output mark, note 6
sampling frequency, note 1 note 2
channel 2 channel 1 power-off output Use the engineering value
22H
sampling frequency, note 1 value mark, note 6
channel 3 channel 2 power-off output output channel 1 engineering
23H
sampling frequency, note 1 value lower limiting value
Channel 4 channel 3 power-off output output channel 2 engineering
24H
sampling frequency, note 1 value lower limiting value
7
Function description
CR code
SMC-AD04EN SMC-DA04EN SMC-AN04EN
channel 1 zero point channel 4 power-off output output channel 1 engineering
25H
correction value value upper limiting value
channel 2 zero point Channel indicator status, note output channel 2 engineering
26H
correction value 5 upper limiting value
channel 3 zero point
27H Reserve power-off output mark, note 6
correction value
channel 4 zero point output channel 1 power-off
28H
correction value output value
Channel 1~4 input output channel 2 power-off
29H
disconnection alarm, note 3 output value
output channel indicator, note
2AH Reserve
5
2BH~2FH Reserve
9
Function description
CR code
SMC-AD08EN SMC-DA08EN SMC-AN08EN
limiting value limiting value note 2
channel 8 engineering upper channel 8 engineering upper output channel 3 signal type,
30H
limiting value limiting value note 2
channel 1 output channel 4 signal type,
31H power-off output mark, note 8
sampling frequency, note 1 note 2
channel 2 channel 1 power-off output Use the engineering value
32H
sampling frequency, note 1 value mark, note 4
channel 3 channel 2 power-off output output channel 1 engineering
33H
sampling frequency, note 1 value lower limiting value
channel 4 channel 3 power-off output output channel 2 engineering
34H
sampling frequency, note 1 value lower limiting value
channel 5 channel 4 power-off output output channel 3 engineering
35H
sampling frequency, note 1 value lower limiting value
channel 6 channel 5 power-off output output channel 4 engineering
36H
sampling frequency, note 1 value lower limiting value
channel 7 channel 6 power-off output output channel 1 engineering
37H
sampling frequency, note 1 value upper limiting value
channel 8 channel 7 power-off output output channel 2 engineering
38H
sampling frequency, note 1 value upper limiting value
channel 1 zero point channel 8 power-off output output channel 3 engineering
39H
correction value value upper limiting value
channel 2 zero point Channel indicator status, note output channel 4 engineering
3AH
correction value 5 upper limiting value
channel 3 zero point
3BH Reserve power-off output mark, note 6
correction value
channel 4 zero point output channel 1 power-off
3CH
correction value output value
channel 5 zero point output channel 2 power-off
3DH
correction value output value
channel 6 zero point output channel 3 power-off
3EH
correction value output value
channel 7 zero point output channel 4 power-off
3FH
correction value output value
channel 8 zero point output channel indicator, note
40H
correction value 5
Channel 1~8 input
41H Reserve
disconnection alarm, note 3
42H~4FH Reserve
Note:
① Sampling frequency:0 - 2 times, 1 - 4 times, 2 - 8 times, 3 - 16 times, 4 - 32 times, 5 - 64 times, 6 - 128
times, 7 - 256 times
② Signal type: 0 - [4,20]mA, 1 - [0,20]mA, 2 - [1,5]V, 3 - [0,5]V, 4 - [0,10]V, 5 - [-10,10]V
③ Disconnection alarm:Each bit indicates 1 channel, 0-normal, 1-disconnection
④ Use the engineering value mark:Each bit indicates 1 channel, 0-No, 1-Yes
⑤ Channel indicator status:Each bit indicates 1 channel, 0-off, 1-on
⑥ Power-off output mark:Each bit indicates 1 channel, 0-No, 1-Yes
10
Parameter table for 4-channel thermal resistance and thermocouple modules
Note: CR code is corresponding to the Modbus register address, the gray parts are read-only ,the white parts
are readable and writable.
Function description
CR code
SMC-TR04EN SMC-TC04EN
00H Low byte for module code, and high byte for module version number
01H Communication address
Communication protocol: The low 4-bit of the low byte: 0 - N,8,2 For RTU,1 - E,8,1 For RTU,
2 - O,8,1 For RTU,3 - N,7,2 For ASCII,4 - E,7,1 For ASCII,5 - O,7,1 For ASCII,6 - N,8, 1 For
02H RTU
The high 4-bit of the low byte: 0 – 2400,1 – 4800,2 – 9600,3 – 19200,4 – 38400,5 – 57600,
6 - 115200
03H~06H Module name
07H~08H Default IP address: 192.168.1.111
09~0AH Reserve
High byte subnet mask(b3~b0,1 indicates 255, 0 indicates 0, for example, subnet mask
0BH
255.255.255.0, b3~b0=1110), low byte reserved
0CH-0EH Reserve
Error code: 0-Normal, 1-Illegal firmware identity, 2-Incomplete firmware, 3-System data access
0FH
exception, 4-No external 24V power supply
10H channel 1 input value channel 1 input value
11H channel 2 input value channel 2 input value
12H channel 3 input value channel 3 input value
13H channel 4 input value channel 4 input value
14H channel 1 signal type, note 2 channel 1 signal type, note 3
15H channel 2 signal type, note 2 channel 2 signal type, note 3
16H channel 3 signal type, note 2 channel 3 signal type, note 3
17H channel 4 signal type, note 2 channel 4 signal type, note 3
18H Use the engineering value mark, note 5 Use the engineering value mark, note 5
19H channel 1 engineering lower limiting value channel 1 engineering lower limiting value
1AH channel 2 engineering lower limiting value channel 2 engineering lower limiting value
1BH channel 3 engineering lower limiting value channel 3 engineering lower limiting value
1CH channel 4 engineering lower limiting value channel 4 engineering lower limiting value
1DH channel 1 engineering upper limiting value channel 1 engineering upper limiting value
1EH channel 2 engineering upper limiting value channel 2 engineering upper limiting value
1FH channel 3 engineering upper limiting value channel 3 engineering upper limiting value
20H channel 4 engineering upper limiting value channel 4 engineering upper limiting value
21H channel 1 sampling frequency, note 1 channel 1 sampling frequency, note 1
22H channel 2 sampling frequency, note 1 channel 2 sampling frequency, note 1
23H channel 3 sampling frequency, note 1 channel 3 sampling frequency, note 1
24H channel 4 sampling frequency, note 1 channel 4 sampling frequency, note 1
25H channel 1 zero point correction value channel 1 zero point correction value
26H channel 2 zero point correction value channel 2 zero point correction value
27H channel 3 zero point correction value channel 3 zero point correction value
28H channel 4 zero point correction value channel 4 zero point correction value
11
Function description
CR code
SMC-TR04EN SMC-TC04EN
Channel 1~4 input disconnection alarm, note Channel 1~4 input disconnection alarm, note
29H
4 4
2AH Reserve Reserve
2BH~2FH
Note:
① Sampling frequency: 0 - 2 times, 1 - 4 times, 2 - 8 times, 3 - 16 times, 4 - 32 times, 5 - 64 times, 6 - 128
times, 7 - 256 times
② RTD signal type: 0 - Pt100, 1 - Pt1000, 2 - Cu50, 3 - Cu100
③ Thermocouple signal type: 0 - S, 1 - K, 2 - T, 3 - E, 4 - J, 5 - B, 6 - N, 7 - R, 8 – Wre3/25, 9- Wre5/26, 10 -
[0,20]mV, 11 - [0,50]mV, 12 - [0,100]mV
④ Disconnection alarm:Each bit indicates 1 channel, 0-normal, 1-disconnection
⑤ Use the engineering value mark: Each bit indicates 1 channel, 0-No, 1-Yes
13
1.14 Mounting and installation
The PLC should be secured to an enclosed cabinet while mounting. For heat dissipation, make sure to provide a
minimum clearance of 50mm between the unit and all sides of the cabinet. (See the figure.)
Screw Mounting: Each MPU or expansion module has two positioning screw holes, the diameter of the hole is
4.5mm. Please refer to the dimension figure for the location of the positioning holes and their spacing.
To avoid over temperature and for a better heat dissipation, do not mount PLC to a position near to the bottom/top
of the cabinet. Do not mount PLC in vertical direction.
Expansion Module Wiring: Connections between expansion modules and connections between module and
MPU are achieved through bus. One expansion cable will be configured to every expansion module, for the
connection between two different modules.Connection methods: turn the right side of extended interface(the last
MPU or expansion module) over, plug the expansion cable in the extended interface, then press down the cover
of the extended interface to reset the interface, the extended interface at the right side of the module will be
reserved for expansion of the next module. Connect all expansion modules in turn in the same way.
14
Chapter 2 Application Case
2.1.2 The analog need't be written any conversion program, read the analog register value
directly.
For example, the host PLC SMC-S16MT, respectively, is expanded with three modules of SMC-AD04EN,
SMC-DA04EN and SMC-AN08EN through the parallel port from left to right, assuming the scene:
Analog module SMC-AD04EN input channel 1, signal type is 4-20mA, used to measure the pressure, the
pressure range of 0.0~3.0Mpa;
Analog module SMC-DA04EN input channel 1, signal type is 0-10V, used to control the inverter frequency of
0.0~50.0Hz;
First enter the PLC programming software menu bar - view - hardware configuration, in accordance with the
external order of actual modules to add the module models, after added, the analog address will be automatically
arranged, as shown below:
SAVCH analog module need't be written any conversion program, as for above pressure measurement, we
only need to check the use of engineering value, set the lower limit value of 0 corresponding 0.0Mpa, set the
upper limit value of 3000 indicating 3.000Mpa, the upper limit value 3000 hidden three decimal places can
achieve magnification times and improve accuracy. Then we read the value of the analog input register AI0, if AI0
= 1234, then the actual value is 1.234Mpa.
15
Similarly, for the analog output, check the use of engineering value, set the lower limit value of 0 indicating
0.0Hz, set the upper limit value of 500 indicating 50.0Hz, if you want the inverter frequency output is 25.6Hz, as
long as force the AQ0 value as 256 or through other logic instructions to output the AQ0 value of 256. As shown
below:
2.1.3 Temperature modules need't be written any conversion program, read the current
temperature value directly when access the sensor
For example, the host PLC SMC-S16MT, respectively, is expanded with three modules of SMC-TC04EN,
SMC-TR04EN and SMC-TC08EN through the parallel port from left to right, assuming the scene:
Thermocouple module SMC-TC04EN input channel 1, signal type is K, input channel 2, signal type is E;
Thermal resistance module SMC-TR04EN input channel 1, signal type is PT100, SMC-TR04EN input
channel 2, signal type is PT1000;
First enter the PLC programming software menu bar - view - hardware configuration, in accordance with the
external order of actual modules to add the module models, after added, the analog addresses will be
automatically arranged, as shown below:
SAVCH temperature and humidity module need't be written any conversion program, for the above
measuring temperature, we only need to select the corresponding channel signal type, check the use of
engineering value and full index number by default, for example, the above module SMC-TC04EN input channel
1, the signal type is K; the input channel 2, the signal type is E, as long as we set the hardware configuration:
16
In this way, after configuration, as long as connect the K-type thermocouple to channel 1, then directly read
AI0 register value, AI0 = 123, that is the actual value of 12.3 ℃. In the same way, connect E-type thermocouple
to channel 2, read AI2 value, such as AI2 = 3456, that is the actual value of 345.6 ℃.
As we know that SAVCH temperature and humidity modules can be set the signal type of each channel
arbitrarily, so for the SMC-TR04EN module, after configuration, we can read the temperature value directly when
connecting the corresponding sensor to the channel.
17
So that when the PLC read AI0 value, AI0=1234, that is the actual value of 1.234Mpa, there is no need to
have data processing in PLC and configuration, only set the 3 decimal places on the numerical display primitive,
then it will be automatically reduced by 1000 times, displaying value of 1.234, that is the actual value of
1.234Mpa.
Note: the temperature module only needs to set 1 decimal place. So that when the PLC read AI0 value,
AI0=123, that is the actual value of 12.3℃, there is no need to have data processing in PLC and configuration,
only set the 1 decimal places on the numerical display primitive, then it will be automatically reduced by 10 times,
displaying value of 12.3, that is the actual value of 12.3℃.
2.1.6 When the engineering value is not used, the default code value is 0 ~ 32000
When using the engineering value, the linear transformation is specified by the lower limit and the upper limit
value, and the program is automatically transformed. When the engineering value is not used, all types are
unified to correspond with 0 ~ 32000 code value.The same case of pressure measurement, this time can
according to the linear transformation formula: Out = (In - InDw) * (OutUp- OutDw) / (InUp- InDw) + OutDw to
write the conversion program, or use the SC linear transformation instructions to calculate directly.
SAVCH analog used easily, it is recommended to check the use of engineering value, so that the analog will
be very convenient without writing any program.
2.1.7 Module CR code application example: Read the module channel disconnection alarm
In this example, in order to read the external sensor disconnection information of SMC-AN08EN module, the
disconnection alarm data of SMC-AN08EN module input channel 1-4 is stored in CR29, that is, 29H
(hexadecimal), decimal 41. (More CR contents can be found in the software online help - hardware manual -
expansion module parameters within the corresponding model).
This program is as follows:
Slot: Position number, SMC-AN08EN is the third module, so fill in 3;
CR: Module disconnection alarm CR41, that is, 29H (hexadecimal) = 41 (decimal), it can be directly input 41
or 0x29 into the instruction CR terminal;
N: Number for readings, 1 register for 16 bits, low 4 bits corresponding channel 1-4, disconnection for 1 (ON),
normal for 0 (OFF).
18
2.2 Module used as remote IO
SAVCH PLC expansion module is built-in one RS485 communication port(Some models with Ethernet
communication port), which not only supports parallel bus(Use the expansion bus to connect with the parallel
interface of host PLC), but also supports serial bus(Use the RS485 communication port of module networking
with communication port of host PLC, and host PLC controls the remote module by communication instructions),
when using the serial bus to expand (that is, remote IO module), it doesn't have expansion limit of system points
and can be distributed installation.
Distributed installation is very important for the system which needs to collect and monitor a large number of
decentralized digital or analog signals(temperature, humidity, differential pressure, blowing rate, flow, fan speed,
valve opening, etc.), it can easily achieve distributed installation control and unlimited points of expansion, greatly
improving the control system configuration flexibility and future control expansion capabilities, reducing the
number of signal wiring, also reducing the interference problem of too long analog signal line, saving the project
investment costs.
The following will introduce the operation key points and techniques.
Baud rate: 2400, 4800, 9600, 19200, 38400, 57600, 115200 optional;
Data format : N, 8, 2 RTU, E, 8, 1 RTU, O, 8, 1 RTU, N, 8, 1 RTU, E, 7, 1 ASCII, O, 7, 1 ASCII, N, 7, 2
ASCII optional.
19
RS485 default parameter: 19200, N 8 2 RTU, station number is 1.
Ethernet +: Support the standard Modbus TCP protocol, it can communicate with the configuration, touch
screen, PLC and other third-party host computers, which must support Modbus TCP protocol.
Among them:
Ethernet default parameters:
IP: 192.168.1.111
Subnet mask: 255.255.255.0
Gateway: 192.168.1.1
2.2.4 Module parameter configuration method introduction, when the module is used as
remote IO
There are three ways to configure remote IO parameters:
① It can be configured via programming software - tools - remote modules (recommended);
② It can be configured via the hardware configuration and TO instructions, when the module is hung behind
the host PLC through the parallel port;
③ It can be configured via MODW instructions through the serial communication.
Click the button in the pop-up window to open the "Online" window. The module default address is
20
If there is only one machine connected with 485 line, then check "stand-alone search"; if there are more than
one, then remove the button of "stand-alone search", and set the start address and end address, so that all the
machines connected with 485 line can be found and achieve parameter configuration.
Click to exit, enter the configuration interface, as shown below:
We can change the module name, address, IP, subnet mask, baud rate, data format and other
communication parameters in the communication parameter area.
21
In the external analog input area, we can set the signal type of each channel, choose whether to use
engineering value or not, the upper and lower limits of engineering value(it can be set if you check the use of
engineering value), sampling times and zero correction.
After setting, select the "parameter download" to download the parameter into the module.
In addition, we can do the following operations through the remote module tool:
① Online monitoring the channel value of module, error code.
② Upload the module paramater, upgrade the module firmware, then make the module support new
features.
③ It can export the module configuration to save or import and restore the default value.
2.2.6 Remote IO application example (RS485 mode): The PLC read the 4 communication
temperature values of SMC-AD04EN module
① Hardware wiring: PLC connects to 485 port of module by shielded twisted pair, A + connects to A +, B-
connects to B-, if the PLC connects to multiple remote IO modules, it needs to use Hand in hand way to
connect.
② Modbus address: From the above 4-channel analog CR parameter table shows that, the channel 1 ~ 4
input values are stored in 10H ~ 13H of SMC-AD04EN module.
③ PLC program: Host PLC wants to read the 4-channel liquid level values of remote IO module
SMC-AD04EN, 0 ~ 1000 indicates that 0 ~ 1.0m. In this example, SMC-AD04EN communication is the
default parameter: Station number address is 1, baud rate is 19200, data format is N 8 2 RTU. The
program of PLC reads the 4-channel liquid level value is as follows:
22
The host PLC reads the 4-channel liquid level values of SMC-AD04EN by Modbus read instruction MODR,
the start address is 10H (hexadecimal), that is, the decimal value is 16. When the communication is successful,
M0 is ON, the liquid level values which are read back will be stored in V0-3, V0=235, indicating that the actual
temperature of the first channel is 0.235m, the same as V3=867, indicating that the actual temperature of the
fourth channel is 0.867m.
2.2.7 Remote IO application example (RS485 mode): The PLC writes the 8-channel output
values of SMC-DA08EN module
① Hardware wiring: PLC connects to 485 port of module by shielded twisted pair, A + connects to A +, B-
connects to B-, if the PLC connects to multiple remote IO modules, it needs to use Hand in hand way to
connect.
② Modbus address: From the above 8-channel analog CR parameter table shows that, the channel 1 ~ 8
output values of SMC-DA08EN module are stored in address 10H~17H .
③ PLC program: Host PLC wants to write the 8-channel analog output values of remote IO module
SMC-DA08EN. In this example, SMC-DA08EN communication parameters: Station number address is 2
(set by DIP switch), baud rate 19200, data format N 8 2 RTU. The program of writing 8-channel analog
output values is as follows:
Host PLC writes the 8-channel analog output values of SMC-DA08EN by Modbus write instruction MODW,
the start address is 10H (hexadecimal), that is, the decimal value is 16. When writing successfully, M1 is ON, the
8-channel values which will be written into are stored in V1000-1007.
In this example, for the channel 1 of analog output, check the use of engineering value, the lower limit value
is 0, the upper limit value is 3600, indicating that the valve opening is 0.0~360.0°, this case V1000=500, so the
first output channel value is 500, that is, the valve opening is 50.0°.
23
2.2.8 Remote IO application example (Ethernet mode): PLC read and write each channel
input and output values of SMC-AN08EN-e
① Hardware wiring: PLC and module Ethernet port connected with a shielded network cable, they can be
connected directly or through the switch.
② Modbus address: From the above SMC-AN08EN-e analog module CR parameter table shows that the
input values of module input channel 1 ~ 4 are stored in the address 10H ~ 13H. The output values of
module output channel 1-4 are stored in 2AH ~ 2DH.
③ PLC program: Read the 4-channel measurements of remote Ethernet module SMC-AN08EN-e and write
the 4-channel output values of SMC-AN08EN-e, if the module IP address is 192.168.1.112, station
number address is 1, the read results are stored in the V0 ~ V3, the values to be written are stored in the
register V10-V13. As follows:
24
Click OK, then we are prompted to start set up variables, the establishment of eight variables indicates 8
channels:
25
Then set up the screen, we can use the display primitives to bind the corresponding channel variable values.
If you need to display the decimal places, it can set the corresponding decimal places on the display primitive. As
shown below:
26
■ Innovate for more | win forever
■ Industry intelligence | Energy saving | Green power
Savch wechat
Service Number
Quanzhou Factory
Address:3# Zixin Road, Jiangnan Hi-Tech Industrial Park, Sales service contact address
Quanzhou, Fujian, China
Tel:0595-24678267 Fax:0595-24678203
Service Network
Website:www.savch.net
Qualification
Received ISO9001 and CE recognition