SG3300UD/SG4400UD

Outdoor Inverter for 1500 Vdc System

HIGH YIELD SMART O&M


Advanced three-level technology, max. inverter Integrated zone monitoring function for online analysis and
efficiency 99 % trouble shooting
Effective cooling, full power operation at 45 ℃ Modular design, easy for maintenance

SAVED INVESTMENT GRID SUPPORT


Low transportation and installation cost Compliance with standards: IEC 61727, IEC 62116
due to outdoor design Low / High voltage ride through (L/HVRT)
DC 1500 V system, low system cost Active & reactive power control and power ramp rate
Q at night function optional control

EFFICIENCY CURVE

100%
98%
96%
94%
Vdc=800V
92% Vdc=1100V
Vdc=1300V
90%
88%
5% 10% 20% 30% 50% 75% 100%

SA © 2023 Sungrow Power Supply Co., Ltd. All rights reserved. Subject to change without notice. Version 16
Type designation SG3300UD SG4400UD
Input (DC)
Max. PV input voltage 1500 V
Min. PV input voltage / Startup input voltage 895 V / 905 V
MPP voltage range 895 – 1500 V
No. of independent MPP inputs 3 4
15(optional: 18/21 inputs 20(optional: 24/28 inputs negative
No. of DC inputs
negative grounding) grounding)
Max. PV input current 3 * 1435 A 4 * 1435 A
Max. DC short-circuit current 3 * 3528 A 4 * 3528 A
PV array configuration Negative grounding or floating
Output (AC)
3300 kVA @ 45 ℃ 4400 kVA @ 45 ℃
AC output power 3399 kVA @ 40 ℃ 4532 kVA @ 40 ℃
3795 kVA @ 20 ℃ 5060 kVA @ 20 ℃
Max. AC output current 3 * 1160 A 4 * 1160 A
Nominal AC voltage 630 V
AC voltage range 536 – 693 V
Nominal grid frequency / Grid f requency range 50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz
Harmonic (THD) < 3 % (at nominal power)
Power factor at nominal power / Adjustable power factor > 0.99 / 0.8 leading – 0.8 lagging
Feed-in phases / AC connection 3/3
Efficiency
Max. efficiency / European efficiency 99.0 % / 98.7 %
Protection & Function
DC input protection Load break switch + fuse
AC output protection Circuit breaker
Overvoltage protection DC Type II / AC Type II
Grid monitoring / Ground fault monitoring Yes / Yes
Insulation monitoring Yes
Surge protection Yes
Q at night function Optional
General Data
Dimensions (W*H*D) 2130 mm * 2235 mm * 1690 mm 2845 mm * 2235 mm * 1690 mm
Weight ≤ 2.5 T ≤ 3.3 T
Topology Transformerless
Degree of protection IP65
Night power consumption < 200 W
Operating ambient temperature range -35 to 60 ℃ (> 40 ℃ derating)
Allowable relative humidity range 0 – 100 %
Cooling method Temperature controlled forced air cooling
Max. operating altitude 4000 m (> 3000 m derating)
Display LED indicators, WLAN+WebHMI
Communication Standard: RS485, Ethernet; Optional: optical fiber; MPLC
CE, IEC 62109, IEC 61727, IEC 62116, IEC 62109, IEC 61727, IEC 62116, IEC
Compliance 60068, IEC 61683, VDE-AR-N 4110:2018, VDE-AR-N 4120:2018, EN 50549-1/2,
UNE 206007-1:2013, P.O.12.3, UTE C15-712-1:2013
Q at night function (optional), L/HVRT, active & reactive power control
Grid support
and power ramp rate control, Q-U control, P-f control

© 2023 Sungrow Power Supply Co., Ltd. All rights reserved. Subject to change without notice. Version 16 SA