Maithan-Turbine O&m Manual
Maithan-Turbine O&m Manual
NO.STE-
NO.STE-TF-
TF-277-
77-MS
MAITHAN-MPL, 2X525 MW
½ãõ©ãã¶ã-†½ã.¹ããè.†Êã., 2x525 ½ãñØããÌãã›
This manual contains information on the turbine. Bharat Heavy Electricals Limited
operation and maintenance of steam turbine. can not be responsible for any malfunction
The information has been prepared with the occurring as a result of operation beyond
assumption that the O&M personnel have rated limits and such operation, if
basic knowledge of power plant engineering undertaken by utilities, must be at their own
and operation. risk.
KJ SM VS SRP PCK
Prepared Approved
Checked
by by
by
5.0-0002-77/2
Subject Document No Subject Document No
□ Monitoring devices 5.2-0027-01/1 ■ Automatic turbine tester 5.2-0455-00/9
□ Operating parameters 5.2-0028-01/1 ■ Oil system 5.2-0460-00/6
Start-up ■ Control fluid system 5.2-0470-00/3
■ Starting the turbine 5.2-0110-01/1 ■ Gland steam system 5.2-0480-01/1
■ Startup & shutdown 5.2-0111-00/1 ■ Bypass System 5.2-0490-00/3
diagrams, symbols MAINTENANCE
■ Startup diagram ■ Introduction 5.3-0001-01/1
□ General 5.2-0112-00/2 ■ Inspection schedule 5.3-0010-04/3
□ Preparation for startup 5.2-0113-00/1 ■ Maintenance schedule
□ Operating position of 5.2-0120-00/1 □ Turbine 5.3-0021-02/1
manually operated valves □ Oil system, seal steam 5.3-0022-01/3
□ Oil System & Turning Gear 5.2-0130-02/5 system, drains
□ Control fluid system 5.2-0135-02/4 □ FRF system 5.3-0023-01/2
start-up diagram ■ Testing during start-up 5.3-0030-02/7
□ Condensing Plant 5.2-0140-02/4 ■ Testing during power 5.3-0035-02/5
□ Bypass System 5.2-0150-00/3 operation
□ Warm-up & startup of turbine 5.2-0160-02/6 ■ Acquisition & archiving of 5.3-0037-03/3
□ Temperature criteria 5.2-0170-01/4 operating data
□ Controllers 5.2-0180-00/4 ■ Remedial actions for off- 5.3-0040-01/6
On-load Running normal operating conditions
■ Load operation, Introduction 5.2-0200-00/1 ■ Measurement of internal 5.3-0050-02/3
■ Synchronization and loading 5.2-0210-00/5 efficiency
■ Power operation, controllers 5.2-0220-00/9 ■ Testing during shut down 5.3-0060-01/5
■ Actions to prevent 5.2-0230-00/4 ■ Testing during standstill 5.3-0061-02/6
unallowable heat-up ■ Testing of safety valves 5.3-0062-01/1
through blade wind age ■ Testing of signaling devices 5.3-0063-00/2
Shut-down ■ Testing of TSC 5.3-0064-01/4
■ Introduction 5.2-0300-00/1 ■ Steam washing of turbine 5.3-0070-02/3
■ Shutdown diagram ■ Turbine Oil care 5.3-0080-03/11
□ General 5.2-0310-01/1 ■ Grease and Oil lubrication 5.3-0081-00/1
□ Turbine-generator 5.2-0320-02/5 ■ Care of control fluid 5.3-0082-02/9
□ Condensing plant 5.2-0330-01/2 ■ Determination of FRF purity 5.3-0083-01/2
□ Oil system 5.2-0340-01/2 ■ Vibration dampers 5.3-0100-00/2
■ Fast cooling down of turbine 5.2-0350-01/1 ■ Instructions for overhaul 5.3-0200-05/8
■ Preventing corrosion in 5.2-0360-00/2 ■ Turbine restart after boiler 5.3-0210-00/1
idle turbine repairs
Fault Tracing ■ Turbine restart after major 5.3-0220-00/3
■ Introduction 5.2-0400-00/1 inspections or repairs
■ Serious faults 5.2-0410-00/8 ■ Environmental protection 5.3-0250-00/1
■ Vibration 5.2-0420-00/5 □ Fluorelastomer products 5.3-0251-00/1
■ Bearing temperature 5.2-0421-01/1 safety notice
■ Casing temperatures 5.2-0423-02/2 □ Safe disposal of turbine oil 5.3-0252-00/1
■ Turbine stress controller: 5.2-0430-01/5 ■ Ordering of spares 5.3-0300-00/1
measures to avoid
impermissible operation
■ Stop & control valves 5.2-0440-01/2
■ Protective devices 5.2-0450-01/7
5.0-0002-77/3
Steam Turbine Preface
General
This manual contains information on the turbine. Bharat Heavy Electricals Limited
operation and maintenance of steam turbine. can not be responsible for any malfunction
The information has been prepared with the occurring as a result of operation beyond
assumption that the O&M personnel have rated limits and such operation, if
basic knowledge of power plant engineering undertaken by utilities, must be at their own
and operation. risk.
SM VS SRP PCK SB
Prepared Approved
Checked
by by
by
5.0-0002-77/2
Subject Document No Subject Document No
□ Monitoring devices 5.2-0027-01/1 ■ Automatic turbine tester 5.2-0455-00/9
□ Operating parameters 5.2-0028-01/1 ■ Oil system 5.2-0460-00/6
Start-up ■ Control fluid system 5.2-0470-00/3
■ Starting the turbine 5.2-0110-01/1 ■ Gland steam system 5.2-0480-01/1
■ Startup & shutdown 5.2-0111-00/1 ■ Bypass System 5.2-0490-00/3
diagrams, symbols MAINTENANCE
■ Startup diagram ■ Introduction 5.3-0001-01/1
□ General 5.2-0112-00/2 ■ Inspection schedule 5.3-0010-04/3
□ Preparation for startup 5.2-0113-00/1 ■ Maintenance schedule
□ Operating position of 5.2-0120-00/1 □ Turbine 5.3-0021-02/1
manually operated valves □ Oil system, seal steam 5.3-0022-01/3
□ Oil System & Turning Gear 5.2-0130-02/5 system, drains
□ Control fluid system 5.2-0135-02/4 □ FRF system 5.3-0023-01/2
start-up diagram ■ Testing during start-up 5.3-0030-02/7
□ Condensing Plant 5.2-0140-02/4 ■ Testing during power 5.3-0035-02/5
□ Bypass System 5.2-0150-00/3 operation
□ Warm-up & startup of turbine 5.2-0160-02/6 ■ Acquisition & archiving of 5.3-0037-03/3
□ Temperature criteria 5.2-0170-01/4 operating data
□ Controllers 5.2-0180-00/4 ■ Remedial actions for off- 5.3-0040-01/6
On-load Running normal operating conditions
■ Load operation, Introduction 5.2-0200-00/1 ■ Measurement of internal 5.3-0050-02/3
■ Synchronization and loading 5.2-0210-00/5 efficiency
■ Power operation, controllers 5.2-0220-00/9 ■ Testing during shut down 5.3-0060-01/5
■ Actions to prevent 5.2-0230-00/4 ■ Testing during standstill 5.3-0061-02/6
unallowable heat-up ■ Testing of safety valves 5.3-0062-01/1
through blade wind age ■ Testing of signaling devices 5.3-0063-00/2
Shut-down ■ Testing of TSC 5.3-0064-01/4
■ Introduction 5.2-0300-00/1 ■ Steam washing of turbine 5.3-0070-02/3
■ Shutdown diagram ■ Turbine Oil care 5.3-0080-03/11
□ General 5.2-0310-01/1 ■ Grease and Oil lubrication 5.3-0081-00/1
□ Turbine-generator 5.2-0320-02/5 ■ Care of control fluid 5.3-0082-02/9
□ Condensing plant 5.2-0330-01/2 ■ Determination of FRF purity 5.3-0083-01/2
□ Oil system 5.2-0340-01/2 ■ Vibration dampers 5.3-0100-00/2
■ Fast cooling down of turbine 5.2-0350-01/1 ■ Instructions for overhaul 5.3-0200-05/8
■ Preventing corrosion in 5.2-0360-00/2 ■ Turbine restart after boiler 5.3-0210-00/1
idle turbine repairs
Fault Tracing ■ Turbine restart after major 5.3-0220-00/3
■ Introduction 5.2-0400-00/1 inspections or repairs
■ Serious faults 5.2-0410-00/8 ■ Environmental protection 5.3-0250-00/1
■ Vibration 5.2-0420-00/5 □ Fluorelastomer products 5.3-0251-00/1
■ Bearing temperature 5.2-0421-01/1 safety notice
■ Casing temperatures 5.2-0423-02/2 □ Safe disposal of turbine oil 5.3-0252-00/1
■ Turbine stress controller: 5.2-0430-01/5 ■ Ordering of spares 5.3-0300-00/1
measures to avoid
impermissible operation
■ Stop & control valves 5.2-0440-01/2
■ Protective devices 5.2-0450-01/7
5.0-0002-77/3
BHEL Haridwar 5.1-0001-04
Steam turbine General Description
Description
The IP turbine has two reheat stop and control A common oil supply system lubricates and
valves. The reheat stop valves are spring-action cools the bearings . The main oil pump is driven
single-seat valves. The control valves, also by the turbine shaft and draws oil from the main
spring-loaded, have diffusers. The control valves oil tank. Auxiliary oil pumps maintain the oil
operate in parallel and are fully open in the supply on start-up and shutdown, during turning
upper load range. In the lower load range, they gear operation and when the main oil pump is
control the steam flow to the IP turbine and faulted. DC Emergency oil pump supplies oil to
ensure stable operation even when the turbine- the bearings during AC power failures.
generator unit is supplying only the station load.
A Jacking oil pump forces high-pressure oil
The reheat stop and control valves are under the shaft journals to prevent boundary
supported free to move in response to thermal lubrication during turning gear operation. The
expansion on the foundation cover plate below Jacking oil pump also supplies the high pressure
the operating floor and in front of the turbine- oil to the Hydraulic Turning gear motor. The
generator unit. All valves are actuated by lubricating and cooling oil is passed through oil
individual hydraulic servomotors. coolers before entering the bearings.
5.1-0002-04/2
Steam Turbine
Description Fixed Points
Design of the supports for the turbine has to Centering of LP outer casing is provided by
allow for the expansion of the turbine during guides which run in recesses in the foundation
thermal cycling. Constrained thermal expansion cross beam. Axial movement of the casings is
would cause overstressing of the components. unrestrained.
The method of attachment of the turbine Hence, when there is a temperature rise, the
components is also critical to the magnitude of outer casings of the HP turbine expand from
the differential expansion between the rotor and their fixed points towards Front pedestal. Casing
turbine casings which is given careful attention of IP Turbine expand from its fixed point towards
in the determination of internal clearances. the generator.
LP Casing expands from its fixed point at front
end, towards the generator.
Rotor Expansion
The following components form the fixed The thrust bearing is housed in the rear bearing
points for the turbine: pedestal of the HP turbine. The HP turbine rotor
expands from the thrust bearing
The HP, IP and LP turbine bearing pedestals
towards the front bearing pedestal of the HP
The horn supports of the HP and IP
turbine and the IP turbine rotor from the thrust
turbine at
bearing towards the generator.
HP- IP Pedestal
The LP turbine rotor is displaced towards the
At turbine end of longitudinal girder of the
generator by the expansion of the shaft
LP Turbine
assembly, originating from the thrust bearing.
The thrust bearing in the HP turbine rear
bearing pedestal Differential Expansion
Differential expansion between the rotors and
Casing Expansion
casings results from the difference between the
The bearing pedestals are anchored to the
expansion of rotor and casing originating from
foundation by means of anchor bolts and are
the HP-IP pedestal. The largest differential
fixed in position. The HP and IP turbines rest
expansions of the HP and IP turbines thus occur
with their lateral support horns on the bearing
at the ends farthest from the thrust bearing.
pedestals at the turbine centerline level. The HP
Differential expansion between the rotor and
and IP casings are connected with the bearing
casing of the LP turbine results from the
pedestals by casing guides which establish the
difference between the expansion of the shaft
centerline alignment of the turbine casings. The
assembly, originating from the thrust bearing
axial position of HP and IP casings is fixed at the
and the casing expansion, which originates from
HP-IP pedestal. Thermal expansion of the
the fixed points on the LP turbine longitudinal
casings originates from the fixed points. The LP
beams.
Turbine outer casing is held in place axially, at
turbine end of longitudinal girder by means of
fitted keys. Free lateral expansion is allowed.
Load
Construction
Double flow IP Turbine with 12 reaction stages per flow Type : M30-63
Double flow LP Turbine with 6 reaction stages per flow Type : N30-2x10-2
2 Main Stop and Control valves (HP casing mounted) Type : EV 320-1
2 LP Bypass Stop and Control Valves with actuators & HPSU To be Ordered
(High pressure EHA Based)
Extraction 1 : No valve
Extraction 6 : No valve
* This speed range should be passed through in one smooth operation to avoid endangering the
blades due to resonance
Steam Pressures
♦ ♣ ♥ Unit
Rated Long time operation Short time operation
5.1-0100-77/2
Low vacuum trip, standard setting
Axial shift
Alarm ± 0.5 mm
Trip ± 1.0 mm
Direction of rotation
Anti clock wise when viewed from Front Pedestal towards the Generator
5.1-0100-77/3
Steam Turbine Technical Data
Description Steam & Casing Temperatures
Steam Temperatures
Steam Temperatures
Rated value Long term 80 hrs. per year, In special
♦ operation Max. 15 min. in cases at no
Unit
individual case load
No time limitation 17 °C
Short time period (15 min) 28 °C
In the hottest line the limitations indicated for main and reheat steam temperature must not be exceeded
Operation with feedwater heaters out of service Main steam flow, Kg/s Load,
(indicative) MW
Motoring
Motoring is the condition in which the turbine is driven by the generator at rated speed with the
stop and control valves closed. In this operating mode, certain turbine components are heated up
by windage power of the blading.
To prevent heat-up beyond permissible temperatures, motoring must not be allowed to continue
for longer than one minute. If the condenser low vacuum limit of 0.3 bar is exceeded, motoring
must not be allowed to continue for more than 4 seconds.
5.1-0101-77/2
Steam Turbine Technical Data
Description Bearing Metal Temperatures
Vibration, Weights
Vibration
Absolute bearing housing vibration Absolute shaft vibration
The normal level is the reproducible vibrational behaviour typical for the machine &
dependent on the operating conditions.
Vibration readings indicated in control room are peak to peak. The above values are also
given in peak to peak.
Weights
HP turbine, completely assembled 95 T
LP turbine, top half inner outer casing, complete with blading, guide blade carriers & 37 T
diffusers
HP turbine rotor, complete with blading 16 T
Reheat stop and control valve, complete with servo motors, without bend & pipe 32 T
section
All weights have been calculated with safety allowances. Slings chosen must provide sufficient
security.
OIL supply
3
Main oil tank, rated capacity 25/40 M
3
First oil filling (estimated) 53 M
3
Flushing oil quantity (estimated) 32 M
Min. 38 °C
Oil temperature at cooler outlet, unit in operation Normal 45
Max. 47
Duplex oil filter- full flow, Type: 2.68.2, size 355/750, Nb 150 1 No.
5.1-0103-77/2
Jacking oil pump, cut-in and cut-out speeds
Jacking oil pump must be in operation at turbine speeds below approx. 510 rpm to avoid
damage to bearings.
Jacking oil pump should be cut-out at speeds above approx. 540 rpm.
Oil pumps
5.1-0103-77/2
Steam Turbine Technical Data
Description Control Fluid System &
Control Fluid Pumps
Enclosure IP 55
Voltage 415 V
Frequency 50 Hz
Low pressure leakage fluid & low pressure control fluid 20.60 10.8
High pressure leakage fluid & high pressure control fluid 16.16 31.0
5.1-0104-77-2
Steam Turbine Technical Data
Operation Limit Curves
140
120 ∆θ = f(θm )
Heating up
100
F
80
N
60
40 S
∆θ[K] OPERATION MODE
F=Fast
20 N=Normal
S=Slow
-20
-40
Cooling down
-60
-80
0 100 200 300 400 500 600
θm [°C]
140
120 ∆θ = f(θm)
100 Heating up
80 F
60
N
40
OPERATION MODE
∆θ[K] F=Fast S
N=Normal
20 S=Slow
-20
-40
Cooling down
-60
-80
0 100 200 300 400 500 600
θm [°C]
∆θ = (θi - θm) on the wall temperature sensor
θi = temperature of inner layer
θm = temperature of middle layer
140
120 ∆θ = f( θm )
100
Heating up
80 F
60
N
40
OPERATION MODE
S
F=Fast
20 N=Normal
S=Slow
∆θ[K]
0
-20
-40
Cooling down
-60
-80
0 100 200 300 400 500 600
θm [°C]
5.1-0111-01/2
Steam Turbine Technical Data
Operation Limit Curves
220
200
180
160
∆θ[K]
140
120
100
80
60
θax [° C]
0 20 40 60 80 100 120
180
160
∆θ = f (θm)
140
Heating up
120
100 F
80
60 N
∆θ[K]
40
S
20 OPERATION MODE
0 F = Fast
N = Normal
-20 S = Slow
-40
-60
Cooling down
-80
-100
θm [°C]
0 100 200 300 400 500 600
200
180
160
140
120
∆θ[K]
100
80
60
40
θax [° C]
0 20 40 60 80 100 120
5.1-0112-01/2
Steam Turbine Technical Data
Operation Limit Curves
220
200
180
160
140
∆θ[K] 120
100
80
60
θax [°C]
0 20 40 60 80 100 120
The deposits which occur in turbines due to achieve the values in the normal operation
impurities in the steam can lead to column.
thermodynamic and mechanical inefficiencies
and, with the presence of salts, especially A recording instrument may be used to
chlorides, and sodium hydroxide also cause continuously monitor the electrical
damage to turbine parts. The corrosion conductivity of the main steam and turbine
stressing caused by active deposits, for condensate following a strongly acid cation
example, has an adverse effect on the fatigue exchange unit. In order to determine slight
strength of the blade material when the steam impurities, the sodium concentration should
is in the transition zone between the be measured in addition to this. Should
superheated and the saturated state. saline contamination occur, the turbine is to
be immediately washed with saturated
Compliance with the target values is steam to remove salt deposits.
mandatory in continuous operation, with the
values in the normal operation column Whether an alkaline, neutral or combined
preferable. With the commissioning of a new method is used for conditioning, the water
plant and starting-up operation, however, steam circulation is for the customer to
these values cannot be attained with an decide. If an alkaline method is used, the
economical outlay. The values listed in the oxygen content in the main steam
column “starting-up operation “are then valid. condensate can be max. 0.02 mg/kg and the
pH value in the turbine condensate max.9.3
It should be pointed out that adherence to the with brass condenser piping. When the
target values does not rule out deposition in condenser piping is of copper-nickel alloys,
the turbine with absolute certainty. Wherever the pH value must not exceed 9.5. There is
possible every effort should be made to no limitation for the pH value with non-
corroding steel or titanium.
Introduction Compatibility
This standard specifies the turbine oil For topping up of the oil system, it is
recommended for use in governing and preferable if the oil used is of the same
lubrication systems of BHEL make steam brand and quality as that already in the
turboset. system. However, if the same brand of oil is
not available and where it is intended to mix
Description in different products that individually conform
Oil of viscosity class ISO VG 46 shall be to this standard, a compatibility test should
used. The oil shall be a petroleum product be conducted before actually mixing the oils.
with or without additives to meet the Samples of both the oils in equal volume
requirement of this standard. The finished oil should be mixed and centrifuged for about
shall be clear and free from water, 40 hrs. and then mixture must comply fully
suspended matter, dust, sediment and other with the requirements of this standard.
impurities.
Properties
The turbine oil shall not contain additives The oil should comply with the
having any negative effect on the materials requirements given in table below when
of the oil system. The turbine oil must be tested according to the test methods given
capable of withstanding bearing temperature in the respective standards mentioned
of max. 130°C and oil tank temperature of against each property. For obvious
max. 80°C without physical and chemical reasons, we do not give any special
degradation. recommendation to a particular brand of oil
to be used in the oil system of our turbo
The properties of the oil shall not be affected sets. Any brand of the oil complying with
by centrifuging, water washing or filtering. the above standards may be used.
11. Total acidity after 2500 ≤ 0.2 mg DIN: 51587 ASTM D943
hrs oxidation KOH/g
12. Foaming characteristics at ----- ASTM: D892
25°C
3
- Foaming tendency ≤ 400 cm
- Foaming stability ≤ 450 s s
13. Deaeration capacity at 50°C ≤4 minutes DIN: 51381 ASTM: D3427
5.1-0130-04/2
Steam Turbine Fire Resistant Fluid (FRF)
Description for Turbine Control System
This specification is valid for Fire Resistant should be no deterioration of the FRF in
Fluids (FRF) recommended for BHEL presence of such trace quantities.
make steam turbine control system. The air release of the FRF should not
According to ISO 6743/4, FRF is a fluid deteriorate in presence of fluoroelastomer
based on triarylphosphate ester marked seals and packing used in the FRF system.
ISO-L-HFDR.
The FRF must be free of ortho-cresol
compounds.
General Requirements
The FRF must not pose a safety or health
The FRF shall not cause corrosion to Steel, hazard to the persons working with it,
Copper and its alloys, Zinc, Tin or provided that the requisite hygiene
Aluminum. regulations are observed.
The FRF must provide sufficient corrosion
protection to the materials used in the FRF
system. Limit values
The FRF shall be continuously regenerated The following limit values are not to be
with Fuller’s earth or an equivalent exceeded during the life time :
regeneration agent. Kinematic viscosity - maximum variation
Note: Before using regeneration agents ± 5% with reference to delivery condition.
other than Fuller’s earth (e.g. ion Neutralisation number - maximum increase
exchangers) BHEL and FRF manufacturer 0.20 mg KOH/g with reference to delivery
or supplier shall be contacted. condition.
The FRF must not cause any erosion or Air release -maximum 12 minutes.
corrosion on the edges of the control
elements. Foaming at 25 °C -Tendency maximum 200
ml, Stability maximum 450 sec.
The FRF must be shear-stable. It should not
contain any viscosity index improver.
Disposal
FRF leaking from the system, if any, must
not ignite or burn in contact with hot Supplier to be contacted for ‘Buy Back’ of
surfaces (up to 550 ºC). used fire resistant fluid.
The FRF must be capable of withstanding In consultation with supplier, liquid material
continuous operating temperatures of 75 °C should be incinerated and material absorbed
without physical or chemical degradation. on sand should be disposed off as
hazardous solid waste.
The FRF must be miscible with traces (max.
3 % by vol.) of TXP of another brand. There
5.1-0140-04/2
Steam Turbine HP Turbine
Description Valve Arrangement
General Arrangement
The short length of the admission section
The HP turbine has 2 main stop valves and 2 between the control valves and the casing
control valves located symmetrically to the right results in a very low steam volume in this
and left of the casing. The valves are arranged section, which has a beneficial effect on the
in pairs with one main stop valve and one shutdown characteristics of the turbine-
control valve in a common body. generator unit.
Valve Actuation
Steam flow
Each main stop valve and control valve has a
The main steam is admitted through the main dedicated hydraulic servomotor(3;5). The
steam inlet passing first the main stop valves servomotors are mounted above floor level so
and then the control valves. From the control that they are accessible and can be easily
valves the steam passes to the turbine maintained.
casing(1).
5.1-0205-00
BHEL Haridwar
Steam Turbine
Description HP Turbine
Casing
Fig. 1 HP Turbine
BHEL Haridwar 5.1-0210-01/1
Fig.2 Inlet Connection
3 Outer casing
4 Inner casing
valves are connected to the inlet connections
6 U seal ring of the outer casing by Breech Nuts(8) (Fig.2)
7 Cylindrical pin through buttress threading. Sealing is achieved
8 Breech nut by U-seal rings(6) which is forced against the
9 Inlet pipe from main stop and control valve outer sealing surface by inlet steam pressure.
The annular space around the sealing ring is
connected to the condenser through a steam
Connection to Main Stop and Control Valves leak-off line. Cylindrical pins(7) located at the
joint flange prevent rotation of the inlet pipe with
The steam lines from the main stop and control respect to the outer casing.
5.1-0210-01/2
Attachment of Inner Casing
Outlet Connections
The exhaust end of HPT has single outlet
Fig. 5 I-Ring seal (Detail A from Fig. 1)
connection from bottom. At the flange
connection a U-seal ring (19) is provided to
prevent any leakage (Fig.1)
Fig. 6 Axial Retention ofInner casing and Centering in vertical plane (Detail E from Fig.1)
5.1-0210-01/3
HP Turbine
Steam Turbine Blading
Description
A 2
3
B .
Gap sealing
Fig. 1 Drum Stages
Sealing strips(6) are caulked into the inner
casing(1) and the shaft (4) to reduce leakage
1 Inner casing 4 Turbine shaft losses at the blade tips. Cylindrically
2 Guide blade 5 Caulking piece machined surface on the blade shrouds are
3 Moving blade
opposite the sealing strips. The surfaces have
stepped diameters in order to increase the
also determine the distance between the
turbulence of the steam and thus the sealing
blades. The shrouds are machined integral with
effect. Should an operational disturbance
the blades and forms a continuous shrouding
cause the sealing strips to come into contact
after insertion.
st th with opposite surfaces, they are rubbed away
From 1 . to 8 . stages are provided with ‘3DS’
th th without any considerable amount of heat
blades, 9 . to 13 . stages with ‘TX’ blades and
th being generated. They can easily be renewed
14 . to 17 th. stages with ‘F’ blades.
at a later date to provide the specified
clearance.
5.1-0230-01/2
Steam Turbine HP Turbine
Description Front Bearing Pedestal
Arrangement
The bearing pedestal is located between the
HP and IP turbines. Its function is to support the
turbine casing and bear the HP and IP turbine
rotors.
BHEL Haridwar
5.1-0250-02/1
2 Combined journal and thrust bearing 9 8
8 Foundation
9 Hex head screw
5.1-0250-02/2
Steam turbine Combined Journal and Thrust
Description Bearing
12 Bearing shell,lower
1 Bearing pedestal, upper 7 Bearing liner
13 Shim
2 Cap 8 Turbine shaft 14 Spherical block
3 Key 9 Brg. pedestal 15 Shim
4 Bearing shell upper lower 16 Spherical support
5 Cowling with all baffle 10 Key 25 Key
6 Thrust pad 11 Oil line “a” Shaft jacking oil
JackingOil
5.1-0270-01/2
Steam Turbine HP Turbine
Description Casing Supports and Guides
5.1-0310-01/2
In the horizontal plane, as shown in details E and casing (4) and together with the fitted keys (14)
F (Fig. 4 & 5) the four support horns of the top half provide a centering system for the inner casing (3, 4)
inner casing (3) rest on plates (13) which are in the transverse plane This arrangement allows axial
supported by the joint surface of the bottom half outer and radial expansion of the inner casing relative to
casing (5). The shoulder screws (12) are provided the outer casing while the fitted keys (14) maintain
with sufficient clearance to permit the inner casing to transverse alignment.
expand freely in all directions in the horizontal plane.
Thermal expansion in the vertical direction originates
from the point of support at the joint. This ensures
concentricity of the inner casing relative to the rotor
(1) in this plane.
The support horns provided at the bottom half
inner casing (4), project into the recesses in bottom
half outer casing (5) with clearance on all sides.
Located on top of each support horn is a spacer disc
(11) whose upper surface has a clearance ’s’ to the
flange face of the top half outer casing (2). This
clearance thus determines the lift of the inner casing.
As shown in details E, the inner casing is located
axially by the fitted keys (10) arranged on both sides
of the support horns of the bottom half inner casing
(4). Thermal expansion in the axial direction
originates from these points. Radial expansion is not
prevented by these fitted keys, as they are free to
slide in the recesses of the bottom half outer casing.
Shoulders on the bottom half outer casing (5)
project into corresponding recesses in the bottom
half inner
5.1-0310-01/3
Steam Turbine IP Turbine
Description Blading
Gap SealIng
Moving and Stationary Blades Sealing strips (7) are caulked into the inner
casing (1) and the rotor (4) to reduce leakage
The IP turbine with advance blading consists of losses at the blade tips. Cylindrically machined
2x12 (double flow) drum stages. All stages are surfaces on the blade shrouds are opposite the
reaction stages with 50% reaction. The stationary sealing strips. These surfaces have stepped
and moving blades of all stages are provided with diameters in order to increase the turbulence of
inverted T -roots in moving blade and hook type the steam and thus the sealing effect. In case of
roots in Guide blade which also determine the an operation disturbance, causing the sealing
distance between the blades. All these blades are strips to come into contact with opposite surfaces,
provided with integral shrouds, which after they are rubbed away without any considerable
installation form a continuous shroud. The moving amount of heat being generated. They can then
and stationary blades are inserted into easily be renewed at a later date to provide the
appropriately shaped grooves in the rotor (4) and specified clearances.
in the inner casing (1) and are bottom caulked
with caulking material (5). The insertion slot in the
rotor is closed by a locking blade which is fixed by
grub screws. End blades, which lock with the
horizontal joint are used at the horizontal joint of
the inner casing (1).
1 Inner Casing
2 Guide Blade 5
3 Moving Blade
4 Turbine Shaft
5 Caulking piece 2
6 Sealing strip
7 Caulking wire
7
5
Function
The function of the shaft seals is to seal the caulked into the shaft and into seal rings
interior of the turbine casing against the centered in the outer casing.
atmosphere at the front (thrust bearing end) and The outer seal rings can be removed for
rear shaft penetrations of the IP turbine. inspection and if necessary seal strips can be
The shaft seals are axial-steam-flow non- replaced during a short turbine shut down
contacting seals. keeping module in place.
In the region subject to low relative
expansion in the vicinity of the combined journal Gap Sealing
and thrust bearing, the seal strips are caulked Sealing between the rotating and stationary
alternatively into the shaft and into spring- elements of the turbine is achieved by means of
supported segmented rings in the casing, seal strip (9) ,caulked into seal rings (3;5) and
forming a labyrinth to impede the outflow of into the rotor (4) (details A and C). The pressure
steam. gradient across the seal is reduced by
In the region subject to greater relative conversion of pressure energy into velocity
expansion at the exhaust end, see-through seals energy which is then dissipated as turbulence as
are used, in which the seal strips are located the steam passes through the numerous
opposite each other, compartments according to the labyrinth
principle.
5.1-0330-01/2
Steam Turbine IP Turbine
RearBearing Pedestal
Description
Arrangement
• Journal bearing
• Shaft vibration pick-up
• Bearing pedestal vibration pick-up
• Hand barring arrangement
5.1-0345-01/2
Steam Turbine
Description IP Turbine
Casing Supports and Guides
The turbine casing is supported on the support It is essential for the casing to retain
horns such as to make allowance for the thermal concentric alignment with the rotor which is
expansion. supported independently
1 HP Turbine rear bearing pedestal Fig.1 Connection between turbine casing and
2 IP turbine bearing pedestal
3 IP turbine rear bearing pedestal
5.1-0350-01/2
Steam Turbine LP Turbine
Description Casing
Construction
Inlet Connections
The LP turbine casing consists of a double- Steam admitted to the LP turbine from the IP
flow unit and has a triple shell welded casing. turbine flows into the inner casing (4,5) from
The outer casing consists of the front and rear both sides through steam inlet nozzles before
walls, the two lateral longitudinal support the LP blading Expansion bellows are
beams and the upper part. The front and rear provided in the steam piping to prevent any
walls as well as the connection areas of the undesirable deformation of the casings due to
upper part are reinforced by means of circular thermal expansion of the steam piping.
box beams. The outer casing is supported by
the ends of the longitudinal beams on the base
plates of the foundation.
5.1-0410-00/2
Fig.3 Guiding of the Outer Casing
5.1-0410-00/3
3 Outer shell, upper half
4 Inner shell, upper half
5 Inner shell, lower half
6 Outer shell, lower half
Fig. 7 Inner Casing, Longitudinal Section
5.1-0410-00/4
Steam Turbine Atmospheric Relief Diaphragm
Description
Atmospheric relief diaphragms are provided in consists of a thin rolled lead plate. To insure
the upper half of each LP exhaust end section that the remnants of the diaphragm and
to protect the turbine against excessive rupturing disc are not carried along by the
pressure. In the event of failure of the low blow-off steam a cage with brackets (5) is
vacuum trips the pressure in the LP turbine provided. As long as there is a vacuum in the
exhaust rises to an excessively high level until condenser the atmospheric pressure forces
the force acting on the rupturing disc (1) the breakable diaphragm and the rupturing
ruptures the breakable diaphragm (2) thus disc against the supporting flange (3).
providing a discharge path for the steam. The
diaphragm
Arrangement
The stationary blade rows (2, 5, 7) are made twisted and have integral shrouds with T -root.
by welding inner ring, blades and outer ring The last two stages of moving blades (6,8)
together to form Guide Blade Carriers in two have curved fir-tree roots (View-X) which are
halves, that are bolted to inner outer casing inserted in axial grooves in the turbine shaft
(1). The blades of rows 2 & 5 are of precision (4) and secured by means of clamping pieces
cast steels and the blades of row 7 are made (11). Axial movement of the blades
5.1-0440-01/1
BHEL Haridwar
is prevented by segments of locking plate Inter stage sealing
segments (12) and the end segments are spot In order to reduce blade tip
welded at joint. The difference in losses at the stationary blade rows
circumferential speed at the root and tip of the (2,5,7). sealing strips (9) are caulked
moving blades is taken into consideration by into turbine shaft. Opposite to this,
the twisted design of the blades. sealing strips are also caulked on the
inner ring of stationary blade rows as
shown in Detail A. This arrangement
permits favourable radial clearances
to be attained. In case of rubbing, the
thin seal strips are worn away without
generating much heat. They can be
easily replaced at a later date to
restore the required clearances.
5.1-0440-01/2
Steam Turbine LP Turbine
Description Shaft Seals
Function
Gap Sealing
Steam Spaces
Steam spaces are provided within the shaft
seal. When the plant is started up and in
operation, sealing steam enters space “Q” to
prevent air penetrating the space, which is
under a vacuum. The slight amount of steam
that passes the center seal ring is drawn off
from space “R” into the seal steam condenser.
Sealing Rings
Arrangement
5.1-0470-00/1
BHEL Haridwar
shell (6) through which high pressure oil is
supplied during start-up. This high pressure oil
relieves the bearing to overcome breakaway
torque and prevent dry friction, thus reducing
the torque requirements of the hydraulic
turning gear.
The lift oil flows into the above mentioned
threaded nozzles (17) through passages in the
lower bearing shell (6). A seal (18) prevents
high pressure oil from penetrating the space
between threaded nozzle and ring (16) and
thus from lifting the babbit. Any leakage oil can
drain through passages in the bearing shell
below the ring.
15 Termocouple
16 Ring
17 Threaded nozzle
18 Sealing ring
5.1-0470-00/2
Steam Turbine
Description Hydraulic Turing Gear
Arrangement
Function
The hydraulic turning gear is situated The function of the hydraulic turning gear is
between the main oil pump and the journal to rotate the shaft system at sufficient speed
bearing in the HP turbine front bearing pedestal. before start-up and after shut-down in order to
avoid irregular heating up or cooling down and
thus avoid any distortion of the turbine rotors.
The air flow set up by the blades along the inner
wall of the casing during turning operation
provides good heat transfer conducive to
temperature equalization between upper and
lower casing halves.
Operation
During turning gear operation, the shaft
system is rotated by a blade wheel which is
driven by oil supplied by the auxiliary oil pump.
This oil passes via a check valve into the nozzle
box (1) and from there into the nozzles (2) which
direct the oil jet in front of the blading.
Lifting of Shaft
To overcome the initial break-away torque on
start-up and to prevent dry friction, the bearings
are relieved during turning gear operation by
lifting oil supplied from below i.e. the shafts are
lifted slightly.
Function Operation
Take the following steps to make the
The turbine generator is equipped with a barring gear ready for operation: Remove
mechanical barring gear, which enables the cover (2) unlatches at (7) and attach a bar to
combined shaft system to be rotated manually lever (1).
in the event of a failure of the normal hydraulic Barring of lever (1) will rotate the
turning gear. combined turbine generator shaft system.
It is located at IP - LP pedestal
After barring has been completed, return
lever (1) and pawl (6) to the position shown in
figure and secure lever (1) by means of latch
Construction (7) Replace cover (2).
The barring gear consists of a gear
machined on the rim of the turning gear wheel The barring gear may only be operated
(10) and pawl (6). This pawl engages the ring after the shaft system has been lifted with
gear and turns the shaft system when high-pressure lift oil. If it is hard to start turning
operated by means of a bar attached to laver by means of the mechanical barring gear, this
(1). The pawl (6) is shown disengaged and the may be due to incorrect adjustment of the
lever (1) resting against a stop. The lever (1) is jacking oil system or due to a rubbing shaft.
held in position by latch (7). Before steam is admitted to the turbine.
corrective action must be taken
Function
When the turbine is started up or shut to protect the jacking oil system from damage
down, the hydraulic jacking device is used to due to improper switching ON of the jacking oil
maintain the oil film between rotor and pump when the check valve (12) is closed, a
bearings. The high-pressure oil is forced under spring-loaded safety valve (11) is situated in
the individual bearing, thus raising the rotor. the piping between the jacking oil pump (13)
The necessary torque from the hydraulic and the check valve (12). The necessary
turning device or from the manual turning pressure in the system is kept constant by
device is reduced in this way. The high- means of the pressure-limiting valve (8). The
pressure oil also provides motive force to pressure-limiting valve can be relieved by the
hydraulic turning gear motor installed in front bypass valve (9). The superfluous flow from
bearing pedestal. the pump is conducted into the main oil tank.
The turbine control system description for The special operating conditions existing in
500 MW steam turbine comprises the reheat condensing turbines necessitate
following: additional control elements. On start-up of
General Description the high-pressure boiler it is necessary to
Start-up Procedure start up the turbine straight away with a
Speed Control considerable steam rate and, due to the high
Electrical Speed Measuring temperature in the reheater to admit steam
Protective Devices to the reheater immediately.
Overspeed Trip Test As long as the HP section of the turbine is
Testing of Stop Valves unable to accommodate all the steam
Bypass Control System (General) supplied by the boiler, the rejected steam is
Electro-hydraulic Bypass Control (Electrical routed directly to the reheater via HP bypass
System) valve. The steam from the reheater which
Electro-hydraulic Bypass Control (Hydraulic cannot be accommodated by the IP section
System) with its control valves MAB10+20AA002 and
Extraction Check Valve reheat stop valves MAB10+20AA001 is
Swing Check Valve in CRH line routed into condenser MAG10BC001 by way
Testing of Swing Check Valves in the Cold of LP bypass stop & control valves
Reheat Line MAN11+12AA001 and MAN11+12AA002.
Automatic Turbine Tester, General
Automatic Turbine Tester, Protective The IP turbine must be fitted with its own
Devices control valves to prevent steam remaining in
Automatic Turbine Tester, Stop Valves the reheater from entering the turbine via the
HP Actuator IP and LP section and causing further
Electro-hydraulic Gland Steam Pressure acceleration of the turbine after the main
Control steam control valves have been closed in
Control System Diagram the event of load rejection or trip. In addition,
List of Parts the steam pressure in the main steam line
Lubrication Chart would increase after sudden closure of the
Lubrication Chart, Index main steam control valves, thus causing the
HP by pass valve to open, with the result
Turbine generator unit MAA50HA001 that even more steam would flow into the IP
MAB50HA001and MAC10HA001 comprises section of the turbine.
three-cylinder reheat condensing turbine
with condenser MAG10BC001 and a direct- It is the function of main oil pump MAV21
driven three-phase a.c. generator. AP001, driven directly by the turbine shaft,
to supply oil for bearing lubrication, for the
The turbine has a hydraulic speed governor oil circuit for the overspeed trip test, and for
MAX46BY001 and an electric turbine the primary oil circuit, pressure in which is
controller. The hydraulic speed governor generated by hydraulic speed transmitter
adjusts control valves MAA10+20AA002 and MAX44AP001.Two Electrically driven
MAB10+20AA002 by way of hydraulic auxiliary oil pumps are provided for auxiliary
amplifier MAX45BY011 whilst the electric oil supply. The LP control fluid circuit (8 bar)
turbine controller acts on these control and the HP actuators of the main steam
valves by way of electro-hydraulic converter control valves, reheat control valves, LP
MAX45BY001. bypass stop & control valves (32bar) are
Hydraulic amplifier MAX45BY011 and supplied by two full-load control fluid pumps
electro-hydraulic converter MAX45BY001 installed in the control fluid tank.
are switched in parallel to form a minimum The turbine is equipped with an electro-
gate. The system not exercising control is in hydraulic seal steam control system, an
its maximum position. electro-hydraulic bypass control system, an
5.1-0600-01/2
Steam Turbine Start-up Procedure
Description
5.1-0610-01/2
Steam Turbine Speed Control
Description
Speed control may be exercised either secondary medium pressures in the follow-up
hydraulically or electro-hydraulically. pistons of the hydraulic amplifier.
The secondary medium circuits and the
Hydraulic Control auxiliary secondary medium circuits are
Main oil pump MAV21AP001 supplies the supplied from the trip medium circuit by way
bearing and primary oil circuits with control of orifices.
oil whilst hydraulic speed transmitter The varying secondary medium pressure in
MAX44AP001 acts as a pulse generator for the follow-up pistons of the hydraulic amplifier
the control circuit, providing a primary oil in turn effects changes in the positions of
pressure proportional to the speed. This oil their associated control valves or other
pressure can also be read directly from control devices.
speed indicator pressure gauge
MAX44CP501. This primary oil pressure
acts on diaphragm KA09 of hydraulic speed Electro-hydraulic Control
governor MAX46BY001 against the force of The speed of the turbine is measured
speed setting spring KA02 which is digitally. For this purpose electrical speed
tensioned by reference speed setter transducers MYA01CS011 to 013 are
MAX46BY001.The travel of diaphragm mounted on the high-pressure end of the
KA09, which can be limited by starting and turbine shaft.
load limit device MAX47BY001, is
transmitted by linkage KA03 to sleeves The electro-hydraulic converter constitutes
the link between the electrical and hydraulic
KA04 of auxiliary follow-up pistons KA08,
parts of the governing system. The electro-
the pistons KA05 of which are held against
hydraulic converter consists of the speed
the medium pressure by spring KA06.
control converter MAX45BY001 and a
Medium drains off according to the amount
of port overlap between piston and sleeve plunger coil system CG001T. The signal from
and a medium pressure corresponding to the electro-hydraulic controller actuates the
control sleeve via the plunger coil system.
the tension of spring KA06 is built up. This
The control sleeve determines the position of
auxiliary secondary medium pressure acts
pilot valve KA07 in the manner of a follow-up
as a pulse signal via pilot valve KA07 of
hydraulic amplifier MAX45 BY011. piston. The further mode of action is the
same as that of the hydraulic speed
Piston KA08 of this hydraulic amplifier governor. Two differential transmitters
assumes a position corresponding to the CG001A and CG001K are located at piston
auxiliary secondary medium pressure and KA08 of electro-hydraulic converter MAX45
operates the sleeves of follow-up piston BY001 as feedback transmitters to the
KA01and KA02 via a linkage system. A electro-hydraulic controller. This stabilizes the
feedback system stabilizes the position of control process.
pilot valve KA07 and piston KA08 of
hydraulic amplifier MAX45BY011. As
Change-over from Hydraulic to Electro-
already described for auxiliary follow-up
hydraulic Control
piston KA08, a secondary medium
pressure corresponding to the position of As already mentioned, Change-over from one
the sleeves and to the related spring control system to the other is possible even
tension builds up in the follow up pistons of during operation as the two controllers are
hydraulic amplifier MAX45BY011. Any connected in parallel downstream of the
change in the position of linkage KA03 associated follow up piston batteries, which
results in a proportional change of the form a minimum value gate. This means that
5.1-0620-01/2
Steam Turbine Control System
Description Electrical Speed Measuring
The electrical speed signals originate from remaining speed probes. The output is then
the electrical speed transducers which fed to the speed measuring unit, electro-
consist of four ferromagnetic type speed hydraulic controller and speed target unit.
probes, MAY01CS011 to 014 (one as spare)
The speed-measuring unit incorporates two
and a toothed wheel with 60 teeth made
speed ranges. The lower range covers 0-
around its circumference located on the
360 rpm and the upper range 0-3600 rpm.
main oil pump shaft.
The changeover from one range to the other
The teeth of the wheel act upon the four is completely automatic.
stationary speed probes. When turbine
A speed indicator mounted on the hydraulic
rotates, square wave signals are generated
control equipment rack provides local
in the probes. The frequency of these
speed-readings. Indicating lights located
voltages is proportional to the rotational
near the speed indicator show which range
speed of the turbine. The output of these
is engaged.
speed probes are fed to the input modules
which provide digital output signals. From the speed-measuring unit, speed
signals are also provided to the turbine
The three values for the rotational speed
stress evaluator/controller, automatic turbine
obtained by this process are continuously
tester and recorders. Output signals are
monitored for failures. If one of the speed
available for purchaser’s remote speed
probes fail, the control circuit continues to
indicators and functional group automatic
operate without interruption, using two
(FGA).
5.1-0630-01/2
Steam Turbine Overspeed Trip Test
Description
Testing with Turbine under Load When this happened, pilot valve KA02 must
Condition be pushed downwards to admit control
Overspeed trips MAY10 AA001 and 002 can medium into the auxiliary start-up medium
be tested using test device MAX62AA001 circuit to the differential pilot valve of the
with the turbine running under load or no- overspeed trip device. The pilot valve moves
load conditions. To operate the test device, towards the right and latches the overspeed
pilot valve KA03 is first pushed downwards trip device in again.
and held in this position. This isolates the The buildup of pressure in the auxiliary start-
auxiliary trip medium circuit from the up medium circuit between the overseed trip
overspeed trips and prevents the main trip test device and the overspeed trip release
being initiated by the overspeed trips. device can be followed at pressure gauge
Subsequent operation of hand-wheel KA01 MAX48CP501. When pilot valve KA02 is
moves the center pilot valve downwards. then released, the auxiliary start-up medium
This action blocks the drain and allows the pressure returns to 0 pressure. The auxiliary
control oil to flow through the center bore of trip medium pressure must then remain at its
the pump shaft into overspeed trips. The full value (readable at pressure gauge
control oil pressure thus builds up and MAX52CP501). If this is the case, pilot valve
moves the eccentric bolts/strikers outwards KA03 may be released. The test is
against the spring force, releasing the pawls completed. If, when valve KA02 is released,
of the overspeed trip releasing device, as a the auxiliary trip medium pressure collapses,
results of which the pilot valve moves rapidly pilot valve KA02 must be pushed
inwards. The pressure in the auxiliary rip downwards again and must be held in this
medium circuit, up to the over speed trip test position a little longer. It is essential that the
device, then collapses. Operation is followed auxiliary trip medium pressure must remain
by observing the reading at pressure gauge steady before valve KA03 is released.
MAX52CP501.
The trip pressure is read off at pressure Testing with Turbine under No-Load
gauge MAX62CP501. If during operation at Condition
rated speed, this pressure should deviate
Overspeed trips MAY10AA001 and 002
from the baseline value as recorded in the
must be tested at regular intervals by
test report, a defect in the overspeed trip
running the unloaded turbine up to trip
may be assumed. If the trip pressure is too
speed. This is done by operating lever KA07
high, the bolt may be made to move freely
of hydraulic speed governor MAX46BY001,
by rapidly operating the pilot valve by means
which presses linkage KA03 downwards,
of hand-wheel KA01 several times in
thus increasing the secondary medium
succession. If this measure does not have
pressures. This causes the control valves to
the desired result, the turbine must be shut
open and the turbine starts to overspeed.
down and the emergency governor to be
The actual speed at which trip occurs can be
inspected.
read off at pressure gauge MAX44CP501.
As soon as the auxiliary trip medium
Limit switches MAY10CG001&002C of
pressure drops to 0 at pressure gauge
overspeed trip release device MAY10
MAX52CP501, the center pilot valve must
AA001 and 002 indicate in the control room
be returned to its original position using
that main trip valves MAX51AA005 and
hand-wheel KA01. The pressure in the test
MAX51AA006 have been actuated by
line should then return to 0, as can be read
overspeed protective device.
off at pressure gauge MAX62CP501. The
bolts/strikers of the overspeed trips should
return to their original position.
The function of extraction check valves there is a danger that the contents of the
LBQ50, LBS21, LBS31, LBS41 and LBS42 feed water heaters will flash into steam. In
AA001and 002 is to prevent the backflow of this case, closure of the swing check valves
steam into the turbine from the extraction is assisted for a short time by means of
lines and the feed water heaters. pistons KA01 of auxiliary slide valve MAX51
AA011. In normal operation pilot valve KA01
Two free-swinging check valves are
passes trip oil to pilot valve KA02. In the
installed in each extraction lines A2, A3, A4
event of an abrupt output drop, the pressure
and A5. In the event of flow reversal in the
on the top side of pilot valve KA01 drops,
extraction lines, the valves close
where as depressurization beneath the
automatically, whereby actuator KA01
piston is delayed by a check valve and the
assists the closing movement of the disc.
pressure in fluid accumulator MAX45BB001.
The mechanical design of the swing check The resulting differential pressure moves the
valves is such that they are brought into the piston upward to interrupt the trip fluid supply
free -swinging position by means of trip fluid to the swing check valves, whose closing
pressure via actuator KA01 and the disc is movement is assisted by the spring force of
moved into the steam flow by means of actuator via a flow restrictor. The pilot valve
spring force acting via the lever, shaft and moves back into its original position to open
disc lever and closes if differential pressure the way for the trip fluid to release the swing
is either lowered or reversed. check valves.
The trip supply to actuator KA01 is Turning the handwheel on the changeover
controlled by extraction valve relay MAX51 valves MAX51AA048, MAX51AA051 etc.
AA011, changeover valves MAX51AA028, close the associated swing check valves
MAX51AA031 etc. within the bounds of the effectiveness of the
spring.
Extraction valve relay MAX51 AA011
actuates the swing check valves in The swing check valve in extraction lines A4
accordance with the secondary fluid can also be triggered by differential pressure
pressure, suitable adjustment of the spring switch LBS42CP002. This differential
in relation to piston KA02 sets the turbine pressure switches energizes solenoid valves
load at which the swing check valves are MAX51AA028 and MAX51AA031 if the
released for opening or assisted in closing. steam flow drops below a preset rate
The release setting for opening cannot be (differential pressure), thereby further
arbitrarily adjusted towards higher turbine assisting the closing action of the swing
output, as the swing check valve will open check valve.
even without the release action if the steam
The position of all swing check valves is
pressure difference exerts a greater force
indicated via position transmitters-CG001A
than the closing spring.
and CG002A.
In the event of major output drops above
the opening point of the swing check valves,
In order that the turbine may be completely check valve is closed by the actuator KA01
separated from the steam when it is and prevent the steam in the cold reheat line
stationary, an additional check valve from returning to the turbine. By removing the
LBC10 AA001 is fitted in the line between valve from the steam flow during operation
the HP cylinder and the reheater and above 5 to 10% of maximum power,
operating through pilot valve MAX42AA001 additional pressure losses during normal
+002 and the rotary actuator KA01 operation are avoided. If, during start-up, the
depending on the pressure in the steam pressure on the inlet side of the valve
associated secondary medium circuit. The and at the same time the secondary medium
swing check valve opens fully when the pressure is not yet sufficient to open the
control valves reached approx. 5 to 10% of valve, the steam pressure will open the swing
their full-power travel. Only when the check valve against the medium pressure in
control valves reach this point again as the manner of a safety valve.
they are being closed, the swing check The Open and Control position of the swing
valve brought into steam flow again by the check valve are indicated in the control room
hydraulic actuator. Thus when the steam via the limit switches.
flow in the normal direction ceases, the
Function
Healthiness of the protective devices and the 1. Protective devices
stop and control valves is vitally important for
Description: “Automatic Turbine
the operational reliability and availability of
Tester, Protective device”.
the turbine. Hence, it is essential that these
equipments are always kept in a fully 2. Main stop and control valves
serviceable condition. Economy has dictated Description: “Automatic Turbine tester,
longer intervals between turbine overhauls, stop and control valves”.
with the result that testing of the equipments The complete testing of all components
and devices is now necessary at regular which must operate when an automatic trip
intervals during normal operation. becomes necessary is assured, despite the
There are manually operated devices for subdivision into two testing groups
testing the free operation of the stop and (protective devices, stop and control
control valves. However, these tests do not valves), because the main trip valves which
cover all components involved in an store the trip signal by mechanical hydraulic
automatic trip with the result that the means are operated together with each
conditions only party corresponds to those protective device and subsequent
prevailing during a real trip. satisfactory reduction of the trip oil pressure
after the valves are monitored.
The system
Nature of the description
Any possible mal-operation associated with
manually operated devices are avoided with The descriptions mentioned above contain
fully automatic tests by means of the the practical sequence of the tests on the
automatic turbine tester. Full protection for individual devices and gives details of
the turbine during testing is also assured by possible irregularities. The description of
suitable circuit arrangements. This increases equipment contained in the automatic
the operational reliability and availability of control cubicle (stepping switches, interlock
the plant. modules, etc), the control panel in the
control room and schematic circuit diagrams
The automatic turbine tester is realised in are contained in the separate electrical
digital technology. section of the “Operating Manual” for the
automatic turbine tester.
System adaptation For the understanding of the automatic
The system is subdivided into functional turbine tester from these descriptions it is
groups for each device. Each group contains assumed that the reader is fully conversant
the device itself and all necessary with the functioning of the individual
transmission elements for initiation of a protective devices and valves within the
normal trip. overall turbine governing and protection
system.
The automatic turbine tester is divided into
the following 2 subgroups:
Scope of Testing
The Automatic turbine tester (ATT) Trip Initiation during Testing
subgroup for the protective devices is To provide normal protection for the turbine
divided into a preliminary test and the during testing, any trip initiation signals from
following four individual testing systems. the protective devices will de-energize the
Remote trip solenoid MAX52AA001 solenoid valves for remote trip during testing
and the same time initiate the reset
Remote trip solenoid MAX52AA002 program. This also applies to all normal
Over speed trips MAY10AA001/MAY10 electrical remote trips such as generator
AA002 protection, etc. For the duration of testing,
two electrical speed signals are formed to
Low vacuum trip MAG01AA011 provide protection against turbine
One or more systems can be selected for overspend.
testing at the control panel and the selection During all electrical testing of the protective
is stored. The start of the test program devices, the electric trip action is prevented
automatically causes a preliminary test to be however, all annunciations are activated as
carried out on the protective channels which for actual trip. The appropriate section of the
are to be effective during actual testing and alarm annunciation system is thus also
then establishes the test circuit. Once the tested.
first test selected has been completed and
the protective device has latched in again,
the test circuit is restored to its normal Features of the Automatic Turbine Tester
operational configuration. Further selected The automatic turbine tester is distinguished
tests must be started individually by by the following features:
pressing the Test push-button to start the
Individual testing of each turbine
program.
protective device.
Automatic testing, upon selection of a
General
test, of the devices that protect the
During normal operation, the protective turbine during that test.
devices act via main trip valves MAX51
Testing of the protective devices for
AA005 and MAX 51AA006 on the stop and
normal turbine operation can only be
control valves and extraction swing check
performed if the preliminary test has run
valves. The remote trip solenoids MAX52
without fault and the protection of the
AA001 and MAX52 AA002, over speed trips
turbine during testing is assured.
MAY10AA001/MAY10AA002 and low
vacuum trip MAG01AA011 actuate main trip Monitoring of all program steps for
valves MAX51AA005 and MAX51AA006 by execution within a certain time.
opening the auxiliary trip fluid circuit.
Interruption if the running time of any
For the duration of testing of the protective program step is exceeded or if trip is
devices, a test circuit is established .In order initiated.
to keep the trip fluid circuit effective, it is
Automatic reset of the test program after
isolated from main trip valves MAX51 AA005
a fault.
and MAX51AA006 by means of change-over
valve MAX51AA211 and supplied with fluid Protection of the turbine during testing
via solenoid valves MAX51AA201 and provided by special test protective
MAX51AA202 (remote trip during testing). devices.
5.1-0661-00/2
fluid up stream of changeover valve MAX51 actuating limit switch MAX51CG211C which
AA211 is drained. Successful completion of annunciates this status.
testing is annunciated by pressure switch
MAX51CP207 between solenoid valve MAX De-activating the Test Circuit
51AA201 and changeover valve MAX51AA
211. Subsequently, solenoid valve MAX51 The test circuit is deactivated in the reverse
AA202 is de-energized via the second order on completion of the selected test and
channel of its Schmitt trigger, thereby after automatic latching of the protective
depressurizing the control fluid still present device concerned in its normal operating
between solenoid valves MAX51AA201 and position.
MAX51AA202. This process is monitored by Hydraulic Test Signal Transmitters
pressure switch MAX51CP205. On
successful completion of the preliminary The function of the hydraulic test signal
test, the test circuit is automatically transmitters is to activate the related
established, which permits realistic testing of protective device (with the exception of the
the protective devices without initiating remote trip solenoids). Each protective
turbine trip. device has an associated test signal
transmitter. For testing the over speed trip
Solenoid valves MAX51AA201 and MAX51 device, the associated test signal transmitter
AA202 (for remote trip during testing) are builds up a test pressure relatively slowly
again energized whereupon control fluid is and passes it to the overspeed trips, for
supplied to change over valve MAX51 testing the low vacuum trip, an air pressure
AA211. Then solenoid valve MAX61AA201 signal is introduced to the device via an
is energized, effecting changeover from trip orifice. The testing signals to remote trip
fluid to control fluid. The control fluid in this solenoids MAX52AA001 and MAX52AA002
line drains off, and the pressure difference
drives changeover valve MAX51AA211 into
its test position (lower end position), thereby
5.1-0661-00/3
Main Trip Valves Pressure switches MAX48CP201 and
MAX48CP202 monitor the orderly pressure
MAX 51 AA005 and MAX 51 AA006 collapse of auxiliary start-up fluid circuit after
Only one of the two main trip valves is latching-in of main trip valves.
described in the following, as they are Attention: The lever for manual actuation of
constructional and functionally identical. the main trip valve must not be test operated
during turbine automatic testing operation,
as the electrical trip action is always initiated
Function via the manual trip-out limit switch.
The function of the main trip valve is to Remote Trip Solenoids
amplify and store the hydraulic or
mechanical (manually initiated local) trip MAX52 AA001 and MAX52 AA002
signal. It must respond in the course of The twin electrical remote trip feature
every successful protective device test. consists of the two remote trip solenoid
valves MAX52AA001 and MAX52AA002.
Operation
0ne trip channel is described here, as the
Each main trip valve is kept in its position by test procedure is the same for both.
auxiliary trip fluid pressure. If a protective
device is actuated, the auxiliary trip fluid
circuit is depressurized and the main trip Function
valve is activated. This connects the trip fluid The function of the remote trip solenoids is
and auxiliary trip circuits to drain and shuts to depressurize the auxiliary trip fluid circuit
in the shortest possible time, thereby
bringing main trip valves MAX51AA005 and
MAX51AA006 into their trip positions, in the
Auxiliary start-up fluid pressure forces During normal operation, the remote trip
differential piston (3) into its normal solenoid isolates the auxiliary trip fluid circuit
operating position. Control fluid IV is then from the drain. For testing, the automatic
free to pass through to buildup the pressure turbine tester switches over the
in the trip fluid and auxiliary trip fluid circuits.
5.1-0661-00/4
solenoid valve so that the auxiliary trip fluid drain, thereby depressurizing it. The loss of
circuit is connected to drain. Trip initiation is auxiliary trip fluid pressure causes the main
monitored downstream of the main trip trip valve to drop which in turn causes the
valves by pressure switches MAX51CP209 trip fluid pressure to collapse.
and MAX52CP211 in the auxiliary trip fluid To activate the over speed trip at rated
circuit. In addition, the limit switch of each speed, as the test routine performed by the
main trip valve must annunciate successful automatic turbine tester requires, a specific
completion of the test. force, equivalent to the increase in
centrifugal force between rated speed and
Latching -in preset trip over speed, is needed .For
testing, this force is exerted by the test oil
On successful completion of testing, remote
pressure, acting on the flybolt /striker (2) .On
trip solenoids MAX52AA001 and MAX52
the basic of the existing defined geometry,
AA002 are de-energized. The reset program
the test oil is reproducible measure for the
is then started.
trip speed, and can therefore be used to
check whether the over speed trip responds
at the desired setting.
Overspeed Trips Test Sequence
MAY10AA001/MAY10AA002 The test oil pressure is produced using the
Function hydraulic test signal transmitter, which is
also used for manual testing. First the
The two over speed trips are provided to
command is given to the actuator motor to
protect the turbine against over speeding in
go into the trip position (down). After a
the event of load rejection coincident with
certain idling time, the test oil pressure
failure of the speed controller. As they are
builds up to act on the two over speed trip
particularly important to the protection of the flybolts/strikers (2).
turbine, they can also be locally tested by
manually with the aid of the over speed trip If the two bolts are functioning correctly, they
test device MAX62AA001 (hydraulic test will fly outwards into the trip position when
signal transmitter) during turbine operation the defined pressure is reached, thereby
at rated speed. (For description see Over activating the main trip valve via pawl (4),
Speed Trip Test). piston (5) and the auxiliary trip fluid circuit.
The two over speed trips are monitored for
activation at the given test oil pressure by
5.1-0661-00/5
pressure respectively. This test oil reference operation, the pressure in the turbine
pressure is determined during condenser exceed a preset valve.
commissioning and entered in the
commissioning test record. Limit switch (6) Operation
must respond within the pressure range
When the condenser pressure exceeds the
between the settings of pressure switches
adjusted limit, the piston (6) is moved
MAX62CP211 and MAX62CP212. A slow
downwards by this pressure, which acts
buildup of pressure is required for this
against diaphragm {4), and the spring force
operation, that is why a relatively long
(3). Thereby pressure below piston (7) drops
monitoring period equivalent to the running
and this piston moves in its lower end
time of the actuator, has to be selected.
position by spring force connecting the
Premature response of the over speed trips
auxiliary trip fluid circuit to the drain. The
is annunciated.
resultant depressurization of the auxiliary
trip fluid circuit actuates main trip valves
Latching-in MAX51AA005 and MAX51AA006, thereby
closing all turbine valves.
Once the trip has been initiated, the actuator
of the hydraulic test signal transmitter is
driven back until the limit switch annunciates
that normal position has been reached.
Monitoring must be continued until the test
oil pressure at pressure switch MAX62
CP213 is less than 0.1 bar.
This double check-back of the hydraulic test
signal transmitter having returned to normal
position ensures that, after completion of
testing, the over speed at which the turbine
will trip is not reduced due to test oil
pressure remaining effective and that the
over speed trip will not be set off
prematurely in the event of load reduction.
While test oil pressure is decreased, the two
over speed flybolts/strikers spring back into
their normal positions at a pressure well
above 0.5 bar.
Subsequently, piston (5) is brought back into
its normal position by the pressure of
auxiliary start-up fluid II and latched-in with
pawl (4). At the same time, piston (5) shuts
off drain channel IV, so auxiliary trip fluid III
can build up pressure. Once this has been
done, the auxiliary start-up fluid can be
Test sequence
depressurized.
After energizing of test signal transmitter
(solenoid valve) MAG01AA201, fitted in the
signal line to the condenser, this signal line
Low Vacuum Trip is blocked off and simultaneously the space
MAGO1 AAO11 above diaphragm (4) is connected to
Function atmosphere. The air flow via orifice causes a
slow increase of pressure by which the
The function of the low vacuum trip is to pistons (6) and (7) move to their trip position
operate the main trip valve if, during normal
connecting the auxiliary trip fluid circuit to
the drain.
5.1-0661-00/6
The low vacuum trip is monitored for Dispersion of the auxiliary start-up fluid
operation within the specified vacuum range pressure is monitored by pressure switch
by observing pressure switches MAG01 MAX48CP201. The second reset solenoid
CP202 and MAG01CP204. MAX48 AA202 is then de-energized to
disperse the pressure between the two-
solenoid valves. This is monitored by
Latching-in pressure switch MAX48 CP202. The use of
When test signal transmitter (solenoid valve) two reset solenoids ensures that main trip
MAG01AA201 has been de-energized and valve MAX51AA005 and MAX51AA006 and
the connection between low vacuum trip and over speed trip will always be sure to be
the condenser re-established, condenser actuated if either one of the two reset
pressure builds up again above diaphragm solenoids is de-energized.
(4). Piston (6) moves into its upper end
position thereby opening the passage for the
control fluid flow to piston (7). When piston
(7) is in its upper end position, the auxiliary
trip fluid circuit is closed again. Restoration
of normal operating configuration is
annunciated by the limit switch of the low
vacuum trip and by pressure switches
MAG01CP201
Reset Solenoids
MAX48 AA201 and MAX48 AA202
Function
The function of the reset solenoids is to
restore the tripped protective devices to their
normal operating positions during the ATT
reset program.
Operation
The reset solenoids are two 2/3-way 1 Compression I Aux. start-up fluid
solenoid valves, fitted in the auxiliary start- spring II Aux. start-up fluid
2 Coil to protective devices
up fluid line. Both solenoid valves are
3 Valve disc III Control fluid
energized in the course of the reset program
conducted after each subtest, so that Fig. 7 –Reset Solenoid
auxiliary start-up fluid II is supplied with
control fluid III. The control fluid pressure
forces all protective devices back into their
normal operating positions and the trip fluid
and auxiliary trip fluid pressure can build up
again.
When the protective devices have latched-in
again, reset solenoid MAX48AA021 is de-
energized first to shut oft the control fluid
supply through this value.
5.1-0661-00/7
Steam Turbine Automatic Turbine Tester
Description Stop and Control Valves
Selection 3:
Closure of Control Valve
Reheat stop and control valve (LHS)
If all the test requirements have been
Selection 4: fulfilled and the selection and operation
Reheat stop and control valve (RHS) push buttons pressed, the control valve
(MAA10 and 20AA002) is closed by
means of the associated actuator (test
Test Procedure
motor –AA002M). Operation of the
Start of Test actuator (KA01) is continued until limit
The test starts with the selection of switch (-CG002C) and limit switch (-
subgroups by pressing the On/Off push- AA002M S72, S73) on the actuator is
button. tripped to annunciate that the control valve
being tested is in closed position.
The subgroup remains on until it is
switched off after the programme is
5.1-0662-01/2
During this time, the turbine output pressure switch MAX51CP222, 227. If all
controller compensates for the effects of conditions are fulfilled within this relatively
closure of the valve being tested on the long monitoring period, solenoid valve
turbine output by opening the remaining MAX61AA211 and 212 is de-energized
control valves. (operating position), so that trip medium is
once again able to flow to test valve
The running time for closure of the control
MAX47AA011 and 012 and the drain is
valve is monitored. If the control valve is
blocked off again. The buildup of trip
functioning properly, it will close within the
medium pressure is monitored by pressure
preset running time.
switch MAX51CP221, 226.
When the pressure is sufficiently high, the
Closure of Stop Valve
stop valve is opened by de-energizing
Then the solenoid valve (MAX61AA211 solenoid valve MAX47AA211 and 212
and 212) energized. This allows trip fluid (operating position). Test valve MAX47
to flow to the space below changeover AA011 and 012 switches over, admitting
slide valve (MAX61AA011 and 012), which trip medium to the underside of the piston
moves into its upper end position and disc KA02 and after a certain amount of
connects the space below piston disc further travel, slowly connects the space
(KA02) with the drain. The pressure in this above piston KA01 with the drain. The
space drops rapidly and is monitored by resultant pressure difference causes the
pressure switch (MAX51CP223,228). tensioned piston relay to open the stop
When the pressure at this pressure switch valve. As soon as the open position is
has dropped slightly below the breakaway reached, the full trip medium pressure
pressure of piston disc (KA02), monitoring builds up. This is monitored by pressure
of the stop valve closure time starts. The switch MAX51CP221, 228 and by limit
associated limit switch (-CG001E) switch –CG001D. Testing of the stop valve
annunciates entry of the valve into its is now completed.
closed position, thus making it possible to
monitor the valve closing action for
completion within the maximum Re-Opening of Control Valve
permissible running time. If the conditions are fulfilled within the
specified monitoring period, the control
valve is reopened. The motor of positioner
Opening of Stop Valve
–AA002M is operated in the opening
Next, solenoid valve MAX47AA211 and direction. Positioner –AA002M moves the
212 is energized (test position) and trip control valve into its original position in the
medium is admitted to the control surface reverse sequence to the closing action.
of the piston in the test valve MAX47 Again the initial pressure and output are
AA011 and 012. The pilot moves into its kept constant by the appropriate controller.
lower end position against the spring Operation of positioned -AA002M is
force, thus permitting trip medium to flow continued until, after a certain amount of
to the space above piston KA01 of the over travel, it has positively ceased to
stop valve. This piston is forced influence the controller. This position is
downwards by pressure of the medium, detected by limit switch –AA002 MS61 or
thereby tensioning the spring between –AA002 MS62. If the control valve is
piston KA01 and piston disc KA02 and functioning properly, it will open within the
finally pressing against piston disc KA02. preset running time.
Up to this point the medium pressure
above piston KA01 is relatively low, being
equal to the spring force acting against it. Cancellation of Selection
The spontaneous pressure rise when On conclusion of testing of each
piston KA01 has made contact with piston combination of valve assembly, the
disc KA02, and thus on completion of the selection is automatically cancelled and
spring tensioning action, is detected by the programme is shut down.
5.1-0662-01/3
Interruption due to Running Time Interruption due to Turbine Trip
Exceeded If electrical turbine trip is initiated during
The reset program is automatically testing, all solenoid valves are de-
initiated if the running time for any step in energized and positioner –AA002M is
the test program is exceeded. If any returned to its extreme position and the
running time is exceeded during the reset programme cancelled. All equipments
program, the program halts. In either case, associated with the automatic turbine
the alarms Fails signal and Time overrun tester are automatically returned to their
generated. If the Faults in ATT alarm is normal position.
displayed, the fault lies in the automatic
tester itself.
5.1-0662-01/4
Steam Turbine HP Actuator
Description
The actuator is of the two-stage the signal fluid pressure changes, pilot valve
amplification type, i.e. it incorporates pilot KA05 is displaced which results in
and main control mechanisms. The movement of auxiliary pilot piston KA06. The
actuating forces for movement of the HP movement of piston KA06 is transmitted via
control valve are generated, in the opening the resetting linkage of the pilot mechanism
direction, by main actuator piston KA02 to the resetting spring, causing spool valve
under the force of the control fluid and, in KA05 to return to the central position which
the closing direction, by the disc spring establishes proportionality between the
column. During actuation main pilot valve signal fluid pressure and the travel of
KA07 acts as a 3-way valve to allow the auxiliary pilot piston KA06.
control fluid to flow to the space behind main
At the same time, main pilot valve KA07
actuator piston KA02. Main pilot valve KA07
displaced via the resetting linkage system by
is actuated via the resetting linkage by
auxiliary pilot piston KA06, effects
means of auxiliary pilot piston KA06 which is
displacement of main actuator piston KA02
subject to control fluid pressure on both
whose movement returns main pilot valve
sides.
KA07 to the central position via the resetting
The actuating signal given by the signal fluid mechanism. Consequently the position of
pressure acts on the face of pilot valve KA05 the pilot and main actuator pistons are
pressing it against the resetting spring on proportional to the secondary fluid pressure
the opposite side. Acting as a 4-way valve, in the steady state (on completion of the
the pilot valve allows fluid to flow to both control action).
sides of auxiliary pilot piston KA06. When
5.1-0670-01/2
(39), until the tension of the springs and Electric manual control
magnetic forces reach a state of The controller can be switched off by the
equilibrium. The armature returns to its push button “Controller on/off”. Then the
mid position, the pressures on the faces of valves can be controlled directly by hand
the slide gates (1a) are of equal by means of the push-button
magnitude. The slide gate moves to its “Higher/Lower” below the valve position
mid position, the oil flow to the cylinder is display with the aid of the remote-control
initially reduced and, when the slide gate manual control setter of the electrical
(1a) reaches its middle setting it is equipment. The inscription “Higher/Lower”
completely shut off, and the main piston of refers to the change in pressure when the
the hydraulic cylinder is in its set position. push-button is operated, e.g. “Higher”
The position of the main piston or rather means increasing the pressure (the leak-
the actuator is directly proportional to the off steam control valve closes or the seal
input signal on the servo valve. steam control valve opens). Manual
control is disconnected during automatic
control; the manual control setter is then
Double Blocking Valve
automatically tracked to the controller
A double blocking valve is connected to output voltage by the equalizing controller
the outlet side of the servo-valve. The so that when changing over from
pump pressure opens the hydraulically automatic control to manual control the
operated check valve (8). the connections manual control setter is already in the
to the hydraulic cylinder (5.1) are free. If correct position. Under manual control the
the oil supply fails, both hydraulically equalizing controller automatically tracks
operated check valve close. The hydraulic the output voltage of the disconnected
cylinder’s piston will be retained in its last controller 1.9 to the manual control
position. voltage. If the control deviation has been
reduced to zero by positioning the valves
Display of control deviation /Adjusting before the controller is switched on, the
the set value change-over from manual control to
automatic control will be bump less;
The control deviation is displayed on each otherwise the controller regulates the
of the two desk tiles for the valves. The pressure to the preset value after it has
two instruments are connected in parallel.
been switched on. Thus, it is quite easy to
The set value for steam pressure in the switch the controller on and off during
header can be adjusted between 0 and 22 operation.
mbar at the controller by means of the set
value push-button.
5.1-0670-01/3
5.1-0670-01/4
5.1-0680-02
Steam Turbine Control System
Description Diagram Legend
Power Plant iden- Title Coor- Power Plant iden- Title Coor-
tification System dinete tification System dinete
LBS42 AA001 Extraction Check Valve A4 AB11 MAB10+ 20 Main Control Valve BC9,10
KA01 Servomotor A 11 AA002
LBS42 CG001A Remote Position Indicator B 11
KA01 Servomotor C10
LBS42 AA002 Extraction Check Valve A4 AB1 1,12 KA02 Piston C10
KA01 Servomotor A12 KA05 Pre Control Pilot Valve C10
LBS41 CG002A Remote Position Indicator B12 KA06 Relay Piston for Precontrol Pilot ValveC10
KA07 Main Pilot Valve C10
LBQ50AA001 Extraction Check Valve A5 E9 KA09 Hand wheel for Testing Device B10
KA01 Servomotor E9 M Electrical Motor for Testing Device B10
LBQ50CG001 A Remote Position Indicator E9 MS61 Torque Limit Switch,
Testing Device 100% ATT B10
LBQ5OAA002 Extraction Check Valve A5 E9 MS62 Travel Limit Switch,
LBQ50 CG002A Remote Position Indicator E9 Testing Device 100% ATT B10
MS72 Torque Limit Switch,
MAA10 + 20 Testing Device 0% ATT B10
AA001 Main Stop Valve ABC7 MS73 Travel Limit Switch, B10
KA01 Piston AB7 Testing Device 0% ATT
KA02 Piston Disc B7
MAB10 + 20
MAA10 + 20 CG002 A Remote Position Indicator C10
CG001 B,F,H Limit Switch, Open Valve Position B7 C Limit Switch, Closed Valve Position C10
C,G,J Limit Switch, Closed Valve Position B7 ATT
D Limit Switch, Open Valve PositionATT B7 MAD12
E Limit Switch, Closed Valve PositionATTB7 CY011,012,013 Electrical Thrust Bearing Trip D8
MAX31
MAX41 CP50l Pressure Gauge. Control Fluid
BB011, 016 Accumulator for HP Servomotor,
Main Control Valves B7 (Hydraulic Control Equipment Rack) C2
MAX31 Accumulator for HP Servomotor, MAX42AA001 Slide Valve for Swing Check Valve
BB21, 26 Reheat Control Valves B9 Cold Reheat D7
MAX31 BB021 Accumulator for HP Servomotor, MAX42AA002 Slide Valve for Swing Check Valve
BB041,049 Bypass Control Valves C11 Cold Reheat D8
MAX32
MAX42AA011 Non-Return Valve B1
BT011 +012 Fluid Filter for Pre Control.
Main Control Valves A7
MAX42BT001 Fluid Filter
(Hydraulic Control Equipment Rack) C1
5.1-0681-02/2
Power Plant iden- Title Coor- Power Plant iden- Title Coor-
tification System dinete tification System dinete
MAX45 MAX47CG001F Limit Switch, 56% G1
CG001 A Remote Position Indicator F4 MAX47CP501 Pressure Gauge, Start-up Fluid G1
K Remote Position Indicator F4 MAX48 CP501 Pressure Gauge,
T Solenoid F4 Auxiliary start-up fluid E3
B Limit Switch Operating Without Bypass
Valves and Adjusting Device Blocked F5
C Limit Switch, Displacement of MAX51
Control Valves F5 AA005 +006 Main Trip Valve B2
MAX46CP501 Pressure Gauge. MAX51 CP542 Pressure Gauge, Trip Fluid above Piston
Auxiliary Secondary Fluid F2 547 Reheat Stop Valve A9
MAX47BY001 Starting and Load Limit Device F1 MAX 52 CP501 Pressure Gauge, Aux, Trip Fluid D3
KA01 Hand wheel F1
KA02 Valve F1
M Electrical Motor F1
5.1-0681-02/3
Power Plant Iden- Title Coor- Power Plant Iden- Title Coor-
tification System dinate tification System dinate
MYA01
CS011-013 Electrical Speed Transmitter E1
MAG01 AA201 Solenoid Valve for Testing
Low Vacuum Trip B4
MAX42AA001 Solenoid Valve, Adjustment of
Control Valves F5
MAX47
AA211 +212 Solenoid Valve for start -up Fluid,
Main Stop Valve B5
MAX 47
AA221 +222 Solenoid Valve for Start-up Fluid,
Reheat Stop Valves B8
MAX48
AA201 +202 Solenoid Valve for Auxiliary
Start-Up Fluid B1,2
MAX62CP501 Pressure Gauge, Test Oil Overspeed D1 MAX53AA051 Solenoid Valve for Sequential
Trip Water Injection C13
MAY10
AA001 +002 Overspeed Trip E2 MAX61AA201 Solenoid Valve for Changeover from
KA01 Releasing Device E2 Trip Fluid to Control Fluid C3
MAY10
CG001 +002 C Limit Switch, Alarm E3
E Limit Switch Alarm ATT E3
5.1-0681-02/4
Power Plant iden- Title Coor-
Power Plant iden- Title Coor-
tification System dinete
tification System dinete
MAX48 CP202 Pressure Switch for Auxiliary
MAX61
Start-up Fluid Between Solenoid
AA211 +212 Solenoid Valve for Testing of Valves MAX48AA201 and202 B1
Main Stop Valves C5,6
MAX51
MAX61 CP001 +002 Pressure transmitter for Trip fluid A1
AA221 +222 Solenoid Valve for Testing of
Reheat Stop Valves C8
MAX51
CP205 +206 Pressure Switch for Trip Fluid Between
Solenoid Valves MAX51 AA201
and 202 B3
LBS42 CP002 Differential Pressure Monitor for
Extraction Check Valve-A4 MAX51
(Batron -Cell) B11
CP207 +208 Pressure Switch for Trip Fluid Ahead of
Changeover Valve MAX51 A211 B3
MAX51
CP209 +210 Pressure Switch for Trip Fluid Ahead of
MAG01CP201 Pressure Switch, low-Vacuum Trip, Changeover Valve MAX51 AA211 B2,3
Vacuum min. B4
MAX51CP 221 Pressure Switch for Trip Fluid ahead of
MAG01CP202 Pressure Switch, low-Vacuum Trip, +226 Main Stop Valve, Test Valve B6
Vacuum max. B4
MAX51CP222 Pressure Switch for Pressure above
MAG01CP203 Pressure Switch, low-Vacuum Trip, +227 Piston of Main Stop Vale B7
Vacuum min. B5
MAX51 CP223 Pressure Switch for Pressure below
MAG01CP204 Pressure Switch, low-Vacuum Trip
+228 Piston Disc of Main Stop Vale A7
Vacuum max. B5
MAX51CP242 Pressure Switch for Trip Fluid above
MAG10CP011 Pressure Switch, Electrical Low
+247 Piston of Reheat Stop Valve A9
Vacuum Trip.
Signal Pressure to high E13 MAX51 CP243 Pressure Switch for Trip Fluid Below
+248 Piston Disc of Reheat Stop Valve B9
MAG 10CP012 Pressure Switch, Electrical low
Vacuum Trip, Alarm E13 MAX52CP211 Pressure Switch for Auxiliary
Trip Fluid B3
MAG10CP013 Pressure Switch Electrical low Vacuum
Trip Interlocking MAG10CPO12 E14 MAX62 CP 211 Pressure Switch for Test oil of
overspeed Trip max D1
MAG10CP016 Pressure Switch for Energizing of
Vacuum Breaker E13 MAX62 CP 212 Pressure Switch for Test oil of
overspeed Trip max. D1
MAX45 CP211 Pressure Switch For Reheat Control
Valves Secondary Fluid E2 MAX62 CP 213 Pressure Switch for Test oil of
overspeed Trip Pressure Collapsed D2
MAX48 CP201 Pressure Switch For Auxiliary C2
Start-up Fluid MAX45 AA031 Pressure Converter for IP secondary
Oil E4
5.1-0681-02/5
Steam Turbine Lubrication Chart
Description
5.1-0690-02/2
5.1-0690-05/3
Steam Turbine Hydraulic Speed Governor
Description with Starting and Load
Limiting Device
Function
The function of the hydraulic speed governor Mode of Operation
is to operate the control valves to give the If the primary oil pressure falls (as a result of
appropriate turbine steam throughput for the increasing load and the resulting drop in
particular load condition. The arrangement speed), the link (11) and the sleeve (5)
and functioning of the governor within the sliding on the follow-up piston (4) are moved
overall governing system is described in the downwards by the speed setting spring (13)
section on governing. so that the overlap of the ports in the sleeve
and the follow-up piston is reduced. This
Construction causes the pressure in the auxiliary
secondary fluid circuit to rise and the follow-
The principal components of the speed
up piston follows the movement of the
governor are the bellows (8), the link (11),
sleeve against the increasing force of the
the speed setting spring (13), the sleeve (5)
tension spring (3) until normal overlap of the
and the follow-up piston (4). The primary oil
ports and equilibrium are restored. The lift of
supply from the hydraulic speed transmitter
the control valves is increased in this
is available at connection ‘a1‘. A fire
manner by the increased secondary fluid
resistant fluid is used as the hydraulic fluid in
pressure.
the governing system. An additional bellows
(9) prevents primary oil getting into the Conversely, a rise in primary oil pressure
control fluid circuit if there be a leakage in causes the lift of the control valves to be
the governor bellows (8). In this case, the reduced.
leakage oil can be drained off via connection
When the pre-compression of the speed
‘c1 ‘. In case a leak in the bellows (9) occur,
setting spring (13) is varied with the
the control fluid that has leaked in will also
reference speed setter it changes the
be drained off via connection ‘c1’.
relationship between the primary oil
The primary oil pressure (connection ‘a1‘) is pressure and the secondary fluid pressure
dependent on the speed and determines the and hence the relationship between speed
position of the link (11) via the bellows (8) and power output.
and the push rod (10). The speed setting
Lever (12) allows the link (11) to be
spring (13) opposes the primary oil
depressed by hand to give a lift signal to the
pressure. Its pre-compression can be varied
governor, e.g. to provide a second means of
either by hand or remotely by the motor (16).
overspeeding the machine for testing the
The sleeve (5) which can slide on the
overspeed trips in addition to the overspeed
bottom end of the follow-up piston (4) is
trip tester.
attached to the link (11). The follow-up
piston is held against the auxiliary
secondary fluid pressure (connection ‘b’) by Starting and load limiting device
the tension spring (3). The follow-up piston Before start-up, the pilot valve (21) is
and the sleeve have ports, which at normal brought to its bottom limit position either by
overlap allow sufficient fluid to escape to hand or remotely by the motor (20). This
produce equilibrium between the auxiliary causes the bellows to be compressed via
secondary fluid pressure and the force of the the lever (6) and the pin (7) until the
tension spring (3). governor assumes the position “Control
Each steady-state position of the link (11) valves closed”. With the pilot valve (21) in
and hence of the sleeve (5) corresponds to the bottom limit position, control fluid from
a specific force from the tension spring (3) connection ‘a’ can flow simultaneously to the
and hence to a specific secondary fluid auxiliary start-up fluid circuit (connection
pressure which in turn determines the ‘u1‘) and as start-up fluid via connection ‘u’
position of the control valves.
5.1-0710-00/2
Steam Turbine Adjusting Gear
Description
Function
spindle to slide axially in the bushing (4),
The adjusting gear is used for manual or which can rotate in cover (19). Spring (6)
motor operation of the reference speed forces the thrust rings (18) against bushing
setter and the starting and load limiting (4) which prevents bushing (4) and spindle
device. (16) from turning. Spindle (16) however, can
be moved axially by turning the worm wheel
Mode of Operation (15).
The speed/load adjusting gear is operated Spindle (16) can be moved up or down
either manually or by means of motor (28). depending on which direction worm- wheel
The rotary movement of the motor shaft is (15) turns. The limit of travel is set by limit
transmitted to worm wheel (15) via worm rings (14 and 17). If either stop has been
wheel (9) and the worm attached to it. reached the thrust rings operates as a slip
Wormwheel (15) is located axially on the coupling. The thrust rings also protect the
threaded portion of the hand wheel spindle motor (28) from overload in the event of
(16) by insert (5) and the gear casing (11). restrictive movement within the adjusting
The spindle (16) is connected with bushing gear.
(4) by a feather key so as to permit the
Function
The electro-hydraulic converter is the The secondary fluid circuits, which are fed
connecting element between the electrical from the trip fluid circuit via throttles and
and hydraulic parts of the turbine control supply the various actuating devices, are
system. It converts the signals from the connected at point ‘b’. The secondary fluid
electric controller into the hydraulic signals pressures are determined by the tension of
and amplifies them before transmitting them springs (22) which counter balance the fluid
to the actuating devices. pressure acting on the follow-up pistons
(21). Each follow-up piston and sleeve (20)
Construction has ports, which control the secondary fluid
The principal components of the converter flow according to their overlap. When the
are proportional valve (1), Manifold plate throttling area is changed by the movement
(12), EHC Piston (7), Casing (4), position of the sleeve (20), it also changes the
transmitter (2), follow-up pistons (21) and pressure in the follow-up piston causing it to
actuator (17). Bushings and follow-up follow the movement of the sleeve. This
pistons ‘A’ are connected to each other via varies the tension of springs (22) until
the adjusting screws (24), spring end pieces equilibrium is regained between the spring
and the springs (22). The control signals force and the new secondary fluid pressure.
from the electro-hydraulic controller Each position of the EHC piston (7) thus
operates on proportional valve(1) through a corresponds to a specific position of the
matching amplifier module. The control fluid sleeves (20) and, therefore, the follow-up
from connection ‘a’ is admitted to the space pistons (21). The position of the follow-up
above or below the piston (7)with the piston is the determining factor for the
opposite side of the piston opened to the secondary fluid pressure at point ‘b’.
fluid drain. The resulting motion of the piston The initial tension of the follow-up piston
(7) is transmitted via lever (13) to the springs can be varied by means of the
sleeves (20) which in turn can slide on the setscrews (24).
follow-up pistons (21).
5.1-0730-03/2
Adjusting Device for Valves Setting Device for start-up without
Bypass Valves
The follow-up pistons ‘B’ and the lever (14)
of the rotary shaft (15) situated above it are If the plant is started up without bypass
connected by the springs (22) of follow-up system, the IP/reheat stop and control
pistons ‘B’, the guide pin (16) and the valves must open before the main steam
setscrews (30). During normal operation an stop and control valves. For this purpose,
energized solenoid valve allows control fluid the hand wheel (32) is set in the upper end
‘a1’ to flow under the piston (25) of the position. Signal from limit switch (33):
actuator (17). The piston (25) is moved Setting device in operation without
upwards against the forces of the spring bypass system position.
(26). Stop (34) locked in normal position by
pin and the initial tension of the tension
springs (22) of the follow-up pistons ‘B’ is
adjusted by means of the lever (28, 14)
which results in the IP control valves
opening in relation to the HP control valves
as intended for this operation.
If the condition turbine load less than a set
minimum load and the ratio of HP
exhaust steam pressure to main steam
pressure greater than the set pressure
ratio is fulfilled, for example after load
shedding, the solenoid valve will be de-
energized. This blocks the flow of control
fluid to the actuator (17) and allows control
fluid under the piston (25) to flow into the
return pipe. The force of the spring (26)
moves the piston into the lower end position
and the tension springs (22) of the follow-up
pistons ‘B’ are adjusted so that the IP control
valves do not begin to open until the HP
control valves are wider open. The lever (28)
then rests on the precisely set stop (34).
Limit switch (29) indicates: Setting device
engaged.
5.1-0730-03/3
Steam Turbine Hydraulic Amplifier
Description for Turbine Control System
Function
auxiliary secondary circuit and the force of
The function of the hydraulic amplifier is to
spring (8) are in equilibrium. The pilot valve
amplify the signals from the hydraulic speed
is kept in rotation by control fluid flowing
governor (connection ‘b1’) so that they are
from tangential holes in an integral collar to
sufficient for the actuating devices.
give greater freedom of reciprocal motion
and high response sensitivity.
Construction When the pilot valve is deflected from its
The principal components of the amplifier center position control fluid from connection
are amplifier piston (1), pilot valve (7), ‘a’ is, admitted to the space above or below
follow-up piston (2) with sleeves (3), the amplifier piston (1) with the opposite side
mechanical feedback system (6) and of the piston opened to the fluid drain. The
actuator (21). Bushings and follow-up resulting motion of the amplifier piston is
pistons ‘A’ are connected to each other via transmitted via lever (5) to the sleeves (3)
the setscrews (10), spring end pieces and which in turn, slide on the follow-up piston
springs (11). Auxiliary secondary fluid flows (2). The secondary fluid circuits, which are
over the pilot valve (7) via connection ‘b1’. In fed from the trip fluid circuit via throttles and
the steady-state condition, the pilot valve is supply the various actuating devices, are
in its center position and the pressure in the
5.1-0740-02/2
reduction in the secondary fluid pressure If the condition Turbine load less than a
causes the actuating device to close. The set minimum load and the ratio of HP
motion of the amplifier piston produces a exhaust steam pressure to main steam
simultaneous feedback via lever (6) and pressure greater than the set pressure
causes the pilot valve to assume its center ratio is fulfilled, for example after load
position when the new position of the shedding, the solenoid valve will be de de-
amplifier piston is reached. Each auxiliary energized. This blocks the flow of control
secondary fluid pressure corresponds to a fluid to the actuator (21) and allows control
certain position of the piston (1) which, in fluid under the piston (20) to flow into the
turn, results in a certain secondary fluid return pipe. The force of the spring (19)
pressure at connection ‘b’ with each moves the piston into the lower end position
auxiliary fluid pressure. The degree of and the tension springs (11) of the follow-up
proportionality of the hydraulic governor can pistons ‘B’ are adjusted so that the IP control
be adjusted by varying the position of lever valves do not begin to open until the HP
pivot (6) with the setscrew (9). control valves are wider open.
The follow-up piston ‘B’ and the lever (15) of The lever (16) then rests on the precisely set
the rotary shaft (12) situated above it are stop (25). Limit switch (17) indicates:
connected by the springs (11) of follow-up Setting device engaged.
pistons ‘B’, the guide bolts (13) and the
setscrews (14).
Setting Device for Start-up without
During normal operation, an energized bypass valves
solenoid valve allows control fluid ‘a1’ to flow If the plant is started up without bypass
under the piston (20) of the actuator (21). system, the IP/reheat control valves must
The piston (20) is moved upwards against open before the main steam control valves.
the force of the spring (19). Stop (25) locked For this purpose, the hand wheel (24) is set
in normal position by pin and the initial in the upper end position.
tension of the tension spring (11) of the Signal from limit switch (23): Setting device
follow-up piston ‘B’ is adjusted by means of in operation without bypass system
the lever (15, 16) which result in the IP position.
control valves opening in relation to the HP
control valves as intended for this operation.
5.1-0740-02/3
Steam Turbine Electrical Speed Pick-Up
Description
Construction and Mode of Operation toothed wheel, which rotates, with the
The electrical speed pick-up located in the rotation of the turbine shaft. On rotation of
front bearing pedestal indicates the exact the toothed wheel (1), electrical impulses
speed through all speed ranges of the are generated as a result of alternating
turbine. The measuring procedure effect between the speed probe (3) and
functions as follows: - the toothed wheel (1). The output
frequency is conducted to the speed-
A toothed wheel (1) is mounted on shaft measuring unit.
(2) of main oil pump. The speed probes
are installed around the periphery of the
Function
The pressure converter is installed in the IP
secondary oil circuit. It does not permit to
raise the IP secondary oil pressure beyond
certain value.
Construction
The pressure converter is provided with a
follow up piston (3), which slides in the
bushing (6) at the top, and in the sleeve (2)
at the bottom. The bushing and follow up
piston are connected to each other via the
set screw (9, 10) and the spring (4). There
are drainage slots in the follow up piston (3)
and sleeve (2), through which a larger or
smaller amount of fluid can flow into the fluid
return line ‘c’ depending on how much they
overlap. The fluid pressure prevailing in the
follow up piston (3) is connected to the
reheat control valves for speed control via
connection ‘x’.
Mode of Operation
When the setscrew (9) of the pressure
converter has been appropriately set, IP
secondary fluid pressure is permitted to
increase to certain value.
1 Ring 8 Cap
2 Sleeve 9 Set Screw
3 Follow up piston 10 Set Screw
4 Spring
5 Casing
6 Bushing c Return flow
7Cover x IP secondary fluid
5.1-0810-01/2
Steam Turbine Servomotor for Main
Description and Reheat Stop Valves
The operative part of the servomotor the piston and the piston disc connected to
consists of a two-part piston, the lower disc- the valve stem moves to close the valve.
shaped part of which is connected via piston Just before the valve disc seats, the piston
rod to the valve stem. The other part of the disc enters a part of the cylinder where the
piston is bell-shaped and moves within the diametral clearance is reduced. This
housing, which is in the form of a cylinder. arrangement restricts the flow of fluid past
Two spiral springs are placed between the the piston disc and so produces a braking
two halves of the piston at the lower end a action, which causes the valve disc to seat
spring plate is interposed between the gently.
springs and the piston disc. When trip fluid
All fluid connections are routed through a
is admitted to the space above the bell-
test valve. All operations can be controlled
shaped part of the piston, it moves this half
by means of the test valve and the starting &
of the piston downwards, compressing the
load limiting device and main trip valve.
springs, until it seats against the piston disc.
After the main stop valves have been
opened, the turbine is started by the control
valves. Before the main stop valves can be
opened, however, they must be
“pressurized”, i.e. prepared for opening, by
admitting trip fluid from the trip fluid circuit to
the space above the piston to press it down
against the piston disc after overcoming the
resistance of the springs. The edge of the
bell-shaped half of the piston is designed to
produce an fluid tight seal with the piston
disc.
To open the valve, fluid from the trip fluid
circuit is admitted to the space below the
piston disc and, simultaneously, the space
above the bell-shaped half of the piston is
opened to drain. This causes both halves of
the piston to move together in the direction,
which opens the valve. In order to reduce
fluid leakage past the bell-shaped part of the
piston when the valve is open, a back seat is
provided in the housing against which the
collar of the piston can seat.
When the valve is tripped, the pressure in
the trip fluid circuit, and hence in the space
below the piston disc, falls, with the result
that the springs separate the two halves of
The flow of steam to the turbine is regulated order to ensure that the valve moves freely
by varying the lift of the control vale by at all times.
means of its servomotor. Main Control System
The control valve is actually moved by the The movement of the pilot piston (4) deflects
piston (9), which is loaded, on one side by the main pilot valve (3) from its center
the disc springs (10) and on the other side position by means of lever (5) so that either,
by hydraulic pressure. The position of the control fluid from connection ‘a’ is directed to
valve is determined by the secondary fluid the underside of piston (9) and the control
pressure, which is controlled by the valve opens, or the underside of piston is
governor. Since large operating forces are opened to drain so that the disc springs can
required, the servomotor is of the high- close the control vale. Shortly before the
pressure type (approx. 32 bar) and has a main valve disc actually comes into contact
pilot control system. The supply of with the seat, the servomotor piston (9)
secondary fluid (connection ‘b’) controls the enters a recess turned in the body and
auxiliary pilot valve (14) which directs control throttles the flow of fluid draining from the
fluid from connection ‘a1’ to the appropriate underside of the piston. This slows down the
side of the pilot piston (4). The pilot piston valve closing motion and the disc seats
operates the main pilot valve (3) through gently. The spring (1) pre-loads the linkage
lever (5) so that when the valve is being and prevents any slackness or lost motion at
opened, control fluid from connection ‘a’ is the pivots. The straight feedback cam (7)
directed to the underside of piston (9). When mounted on the end of the servomotor
the valve is being closed, fluid drains piston rod (8) returns the main pilot vale (3)
through the main pilot valve. to its center position by means of a lever
system. The slope of the feedback cam is in
Pilot Control System
two stages to give two degrees of
When the turbine is running and the valve is proportionality, which produce good linearity
steady at any particular value of lift, the of the steam flow characteristics.
auxiliary pilot valve (14) will be in the center
position shown in the drawing. In this Testing Device
position the force exerted by the spring (13) The control valve can be operated either by
and the secondary fluid pressure acting on hand or under power independently of the
the auxiliary pilot valve are in equilibrium. governor by means of the testing device (11)
When the governor varies the secondary in order to check the free movement of the
fluid pressure to open or close the control valve. The testing device acts on the lever
valve, the auxiliary pilot valve is deflected (5) in the same manner as the pilot piston
from this center position. This allows control (4); the system demanding the smaller valve
fluid (connection’ a1 ‘) to flow to one side of lift being in control,
the pilot piston (4) while the other side of the
Damping Device
piston is opened to drain. The movement of
the pilot piston returns the auxiliary pilot Fig.2 illustrates the auxiliary pilot valve (14)
valve to its center position by means of the and the damping device in the secondary
feedback linkage (12) thus giving fluid circuit. Any signals in the secondary
proportionality between secondary fluid fluid circuit are damped out by passing the
pressure and pilot piston travel. The degree secondary fluid through capillary tube (16)
of proportionality of the pilot control system before it enters the auxiliary pilot vale (14).
can be adjusted by varying the position of Any air carried by the secondary fluid is
the feedback lever pivot (12). The auxiliary conducted to the free space in the actuator
pilot valve is continuously rotated by the via the screw plug (18) and holes in the
action of fluid issuing from tangential casing of the damping device and pilot
drillings in a disc mounted on its spindle in valve.
Opening of the Emergency Stop Valve Closing the Emergency Stop Valve by
In order to open the emergency stop valve, Automatic Testing Device
the valve (6) must first be forced downwards When trip fluid is admitted under the
against the force of the spring (7). This can auxiliary valve (5) via connection v, this will
either be done by start-up fluid (connection be forced upwards against the force of the
‘u’) or manually with the hand wheel (3). Trip spring (4). This links connection x2 with
fluid (connection ‘x’) can then flow to drain ‘c’ via valve (5). Fluid thus drains
connection ‘x1’ and on over the piston in the under the piston disc in the emergency stop
emergency stop valve. The valve must then valve and the valve closes suddenly.
be returned to the upper position, either by
Function and Construction inlet of the valve body (2) and remains
One stop and one control valve are above the valve disc (7) when the stop
combined in a common body with their valve is closed. A pilot valve, integral with
stems arranged at right angles to each the valve stem (6) is provided for relieving,
other. The stop valve can interrupt the thereby reducing the force necessary for
supply of steam from the reheater to the opening. The valve disc (7) slides in the
IP and LP turbines extremely quickly. The bushing of the valve cover (4) and has a
control valve controls the steam flow to bead on the back which lies against the
the IP and LP turbines on load rejection, base bushing (5) and provides additional
start-up & shutdown and remains fully sealing at this point. Metal packing rings (3)
open in the upper load range to eliminate seal the valve stem. The stop valve is
any throttling losses. Further details of the opened hydraulically and closed by spring
arrangement of the valve combination in force.
the control system can be seen under
section “Governing system”.
Testing Stop Valves
Each stop valve must be checked for
Reheat Stop Valve correct operation at regular intervals. A test
The stop valve is a single seat valve with valve is provided for this purpose. The
integral pilot valve. Steam enters via the checking procedure is described in section
“Test valve”.
5.1-0814-00/2
Steam Turbine Hangers for Reheat Stop
Description and Control Valves
The reheat stop and control valves arranged directions. Tensile forces are taken up via
beneath the turbine operating floor in front of the disk spring (8) and tie rod (6) by girders
the turbine-generator unit are suspended at (1) that rest horizontally on shims in a
three points from girders in the upper recess in the foundation and are connected
foundation plate in such a way that they can to the foundation via clamping plates.
follow thermal expansion of the steam lines.
Tie rod (6) is screwed into rod cap (5) and
The ball-and-socket design of the tie caps when the correct elevation of the reheat stop
(5) and spring body (9) and the disk spring and control valve (3) has been established,
stack (8) arrangement permit free movement is secured to prevent turning.
of the reheat stop and control valve (3) in all
Function
The function of the changeover valve is to
manually operate the actuator of the
bleeder check valve.
Mode of Operation
The trip fluid (connection x) holds the valve
(10) in the upper end position (illustrated)
against the force of the spring (8). The trip
fluid flows via the holes in the valve to
connection x 1 and then on to the actuator
of the bleeder check valve. The valve can
be moved downwards by means of hand
wheel (1). In this way connection x1 is
connected to the fluid drain ‘c’ and the fluid
drains away from the actuator of the bleeder
check valve. The spring of the actuator can
then initiate the closing of the check valve. If
the pressure drops at the trip fluid
connection x, the spring (8) pushes the
valve (10) downwards. In this way the fluid
drain of the actuator is also freed.
Function
The auxiliary valve controls the fluid supply With this position of the valve, the trip oil
to the extraction check valve actuators and ‘x’ can flow to the other valves and as
its function is to give the check valves a soon as these valves have been
signal to close in the case of a drop in load switched to the upper position by
or trip-out so that steam can not flow out of secondary fluid from follow-up piston of
bleeder lines back to the turbine. The reheat control valves-on to the change-
auxiliary valve serves several check valves. over valves of the extraction check
valves (connection ‘x1‘). The check
valves are then free to open. On a
Mode of Operation reduction in load, as mentioned above,
Trip fluid is admitted through connection ‘x’ the pressure above the valve (11) is
on the body (10) (section A-B). Secondary reduced accordingly while the Pressure
fluid from follow-up pistons of main control below the valve is retained for a while.
valves is admitted to the spaces above and This is made possible by the fact that the
below the valve (11) through connection ‘b2’ pressure reduction below the valve is
As the pressure above and below the valve retarded by the ball (15) and the
(11) are equal under normal conditions, the pressure in the accumulator (connection
valve is held in the lowest position by the ‘b’) until the equilibrium is re-established
force of the spring (7).
5.1-0841-00/2
Steam Turbine Rotary Vane Actuator
Description for Reheat Swing-Check Valve
Function
The function of the rotary vane actuator segments (1). This rotary movement,
flanged to the swing-check valve is to transmitted by actuator shaft (8) to shaft (3)
open or close the swing-check valve fitted of the swing-check valve via coupling (5;6)
in the cold reheat line. closes the swing-check valve. Conversely,
the swing-check valve is opened when
control fluid is admitted through
Operation connections ‘d1’
When the pilot valve operated by the
transformer of the speed controller
Seals, Fixing
passes control fluid via connections ‘d’ to
the interior of the actuator, the adjacent Actuator shaft (8) is guided in bushings
connection ‘d1’ is depressurized. The (11) at both ends of the segments (1) and
control fluid then flows through bores in is sealed off by seal ring (10). The
the body into the two diametrically segments (1) are fixed in body (12) and in
opposite chambers turning rotary vane (2) cover (13) by means of fitted pins. Leaking
on actuator shaft (8) into contact with the fluid ‘c’ is drained to the header.
Function
The function of the pilot valve is to control
the admission of control fluid to the moving
vane actuator in such a way that the swing-
check valve is operated in accordance with
the pressure in the secondary fluid circuit.
Mode of operation
The swing-check valve is kept open as long
as the pressure in the secondary fluid circuit
does not drop below a definite limit value. If
signal fluid enters the body via connection
‘b’, the valve (10) is lifted against the action
of the spring (5). The initial tension of this
spring and thus the point at which the swing-
check valve opens can be adjusted. If the
valve (10) is lifted beyond the center position
illustrated, the control fluid entering at
connection ‘a’ flows on to a chamber of the
actuator via connection ‘a2’ to open the
swing-check valve. Connection ‘a1’ then
communicates with the fluid return ‘c’ via
passages in the body, permitting the fluid to
drain away from the actuator chambers not
supplied with control fluid. If the valve (10)
drops below the center position illustrated,
the control fluid will then be conversely
admitted to the actuator chambers in such a
way that the swing-check valve closes.
To prevent the valve (10) from seizing in its
sleeve (9) during operation control fluid is
passed through the center bore and out
through the tangential bores at the wheel
disc (8) to impart rotary movement to the
valve (10). For this reason, a thrust ball
bearing (7) and a ball (13) is fitted for this
purpose.
1 Throttle capillary tube 12 Slotted nut
2 Cap nut 13 Ball
3 Setscrew
4 Hood
5 Compression spring
6 Spring disc
7 Thrust ball bearing
8 Wheel disc
9 Valve bush
10 Valve
11 Bush c Return
a Control fluid b Signal fluid
a1 Control fluid(closes swing check valve)
a2 Control fluid(opens swing check valve)
Function
The function of the auxiliary pilot valve for
the pilot valve for the reheat check valve
actuator is to control the admission of
control fluid to the pilot valve in such a way
that the swing-check valve is actuated in
accordance with the pressure in the
secondary fluid circuit.
Operation
The swing-check valve is kept open as long
as the pressure in the secondary fluid circuit
does not drop below a definite limit value.
Secondary fluid entering body (9) via
connection ‘b’ lifts spool (7) against the
action of the spring (3). The initial tension of
this spring and thus the point at which the
swing-check valve opens can be adjusted. If
spool (7) is lifted beyond its central position
as illustrated, the control fluid entering at
connection ‘a’ flows on via connection ‘a1” to
connection ‘b’ of the pilot valve to open the
swing- check valve via the rotary actuator. If
spool (7) drops below its central position as
illustrated, control fluid is admitted to the
opposite chambers of the rotary actuator, so
that the swing-check valve closes.
To prevent spool (7) from seizing in its
sleeve (6) control fluid is passed through the
center bore in the spool during turbine
operation and out through tangential bores
in the upper part of spool (7) to impart rotary
motion to the spool. A deep-groove ball
bearing (5) between spool (7) and spring
retainer (4) reduces friction from the rotary
motion.
Function
One function of the gland steam control
valve, which is situated in the grand steam
pipe of the seal steam system, is to supply
the shaft seals with seal steam during start-
up and in the lower load range. A further
function is to keep the set pressure in the
header constant in order to prevent air
penetrating the vacuum of the shaft seals.
Function
The function of the leakage steam control
valve, which is situated in the leakage steam
pipe of the seal steam system, is to drain
excessive steam from the header in order to
keep the set pressure in the seal steam
header.
1-Body
2-Seat
3-Plug
4-Bush
5-Packing
6-Plug stem
7-Lock Nut
8-Threaded bush
9-Retainer Ring
10-Body Gasket
11-Adaptor
12-Ext. Bonnet
13-Yoke
14-Travel Indicator
15-Coupling (Clamp)
16-Diaphragm plate
17-Diaphragm Supplier’s catalogue may be referred for
18-Actuator casing complete details. Valve alongwith actuator is
19-Spring supplied by M/S Samson Controls Pvt. Ltd.
20-Actuator nut B-43, Wagle Industrial Estate, Road No. 27,
21-1 ½ “ – 6UNC-2B Nut Thane (Maharashtra)
22-1 ½ “ – 6UNC-2A Stud
Function
(12) are designed as differential pistons
The Function of the main trip valve is to being forced tightly against the body
open the trip fluid circuit in the event of assemblies (10) by the rising pressure of the
abnormal conditions, thereby closing the fluid. Control fluid flows into the casing (11)
valves and thus shutting off admission of via connection ‘a’ and with a tripping device
steam to the turbine. latched in (in the position shown), into the
trip fluid circuit via connection ‘x’. The trip
Construction fluid circuit leads to the stop valves and the
secondary fluid circuits. Via passage drilled
The main trip valve consists of mainly two
in the body (11) (Section A-A) fluid flows to
valves (12) that slide in the casing (11) and
the auxiliary trip fluid circuit, which leads to
are loaded by the springs (5,6). The valves
the hydraulic protection devices.
5.1-0910-00/2
Steam Turbine Emergency Trip Valve
Description for Manual trip out
Function
The solenoid valve is installed in the
auxiliary trip fluid line to the automatic trip
gear and, when operated, causes the
auxiliary trip fluid circuit to be opened and
the turbine stopped, The solenoid valve is
remote-controlled electrically, e.g. from the
control room or from a protective device.
Construction
The directions of flow are indicated by
arrows on the body. The solenoid sleeve (4)
is bolted to the casing (6) and is inserted in
the magnet casing (1) with the armature (3).
The complete valve element is placed in the
body (6) and held by the plug (11). The two
valve discs (8) seal the valve seats (9). The
solenoid valve and the line to the automatic
trip gear are ventilated by means of the
screw (12).
Mode of Operation
When the solenoid (1) is not energized, the
armature (3) is moved downwards by the
spring (2) so that the valve disc (8) is
pressed against the valves seats (9) to
provide sealing. The solenoid valve is
operated by energizing the solenoid (1). The
armature and the valve discs are drawn
upwards against the force of the spring (2)
so that the auxiliary trip fluid ‘a’ is linked with
the drain ‘c’ and the pressure in the line to
the automatic trip gear collapses.
1 Magnet casing
2 Spring
3 Armature
4 Solenoid sleeve
5 Hexagonal nut
6 Casing
7 Ring
8 Stem with two valve discs
9 Valve seat
10 O-ring
11 Plug
12 Ventilation screw
a Auxiliary trip fluid to automatic trip gear
c Drain
Mode of Operation
The overspeed trip mechanism is set by the
adjusting screw (6). By appropriate
adjustment of the screw, the center of
gravity of bolt/striker (4) is positioned
eccentrically to the turbine shaft so that
below the tripping speed the bolt is held in
the position shown by the spring (5) against
the centrifugal force. In this position, the bolt
bears against the screw plug (1). If the
turbine rotational speed exceeds the
overspeed setting, the centrifugal force
overcomes the force of the spring (5) and
forces the bolt/striker (4) out of the turbine
rotor (7). This activates the turbine 1 Screw plug 5 Spring
2 Guide bushing 6 Adjusting screw
automatic stop mechanism.
3 Guiding foil 7 Turbine rotor
4 Bolt/striker 8 Guide ring
5.1-0921-00/2
Steam Turbine Overspeed Trip Test Device
Description
Pilot valve (10) performs the function of Pilot valve (4) is used for resetting the
admitting test oil to the eccentric overspeed trip release device after the test
bolts/strikers of the overspeed trips, causing operation. When pilot valve (4) is pushed
them to protrude from the turbine shaft inwards against the force of spring (3),
during the overspeed trip test operation. control fluid can flow from connection ‘a’ to
Pilot valve (10) is guided in guide bushings ‘u1, thus latching in the overspeed trip
(13,14). A center bore with radial openings device. During start-up, connections ‘u’ and
is provided in the pilot valve. An annular ‘u1’ provide a passage for auxiliary start-up
chamber in the bushing (13) is connected to fluid for latching in the overspeed trip release
test oil connection ‘a1’. In the position device. After the test operation, the pilot
shown oil is prevented from entering the valves (4,11) are blocked.
5.1-0922-00/2
Steam Turbine Low Vacuum Trip
Description
Function
The function of the condenser safety device
situated in the control fluid circuit of the
bypass control system is to protect the
condenser, when there is an excessive
increase in pressure in the condenser, by
opening the control fluid lines so that the
resulting drop in pressure causes the
bypass valves to close.
Mode of Operation
The steam space in the condenser is
connected with the spring space above the
diaphragm (5) via connection ‘I’. The space
below the diaphragm is at atmospheric
pressure. If the pressure in the condenser
increases excessively, the diaphragm (5),
and thus the valve (6), is forced downwards
out of the upper end position by the
increasing pressure and the force of the
spring (4). This shuts off the connection ‘a1”
to the bypass valve from connection. ‘a’
which is from the converter and connects it
to drain ’c’.
The pressure range in which the vacuum
safety device operates can be varied by
adjusting the initial tension of the spring (4)
by means of the adjusting screw (2).
During commissioning the valve (6) is
automatically moved into the upper end
position, where it keeps the control fluid
circuit closed, as soon as the negative
pressure in the condenser falls below the
preset value. In order to be able to close the
control fluid circuit when there is still
insufficient vacuum in the condenser, the
valve is lifted via the lever (10) and cam (9)
but is not yet brought into its upper end
position. As already mentioned, this end
position is not reached until there is
sufficient vacuum.
After this, the lever (10) and cam (9) drop
down and do not impair the functioning of
the vacuum safety device. Any leakage fluid
can drain off through passages in the valve
sleeve (7) and the casing (8).
Function
When there is an unallowable rise in
condenser temperature due to lack of
injection water a temperature sensor
situated in the condenser dome sends
electric signals to the solenoid valve which
open the signal fluid circuit of the bypass
valve actuators, thereby closing the bypass
valves so that the steam flow to the
condenser is interrupted.
Mode of Operation
During normal operation, the control fluid ‘a’
holds the main control valve (7) against the
force of the compression spring (8) in the
center position as shown here, This provides
the connection between the signal fluid from
pressure switch for injection water ‘b’ and
the stop and control valve operator of the
bypass stop valve ‘b1 “, If the temperature in
the condenser rises to an unallowable value,
the solenoid valve (3) is moved downwards
against the force of the compression spring
(4) so that the control fluid ‘a’ arising before
the main control valve (7) is connected with
the drain ‘c’.
Simultaneously, the control fluid ‘a’ can flow
behind the main valve (7) so that the main
valve moves forwards against the force of
the compression spring (6) and the signal
fluid circuit ‘b1’ is opened and connected to
the drain ‘c’ and the bypass stop and control
valve closed’.
Function
With normal shut down or tripping of the
machine, the function of the vacuum breaker
is to cause an increase in condenser
pressure by conducting atmospheric air into
the condenser together with bypass steam
flowing into the condenser from the bypass
station. When the pressure in the condenser
increases, the ventilation of the turbine
blading is increased, which causes the turbo
set to slow down so that the running down
time of the turbo set and the time needed for
passing through critical speeds are
shortened.
Partial and Total Vacuum Breakers
The partial vacuum breaker is used when
the running down time is to be shortened
with normal shut down and plant conditions
are free of disturbance. Taking blade stress
into consideration, the permissible
operational condenser pressure of 0.3 bar
should not be exceeded. For this reason the
limiting value for the condenser pressure
has been set at 0.2 bar.
In special cases requiring a rapid shut down 1- LP Turbine
of the turbo set, the total vacuum breaking is 2- Pressure Transmitter
employed. 3- Solenoid Valve
4- Vacuum Breaker Valve with actuator
5- Condenser
Electrical Control of Partial Vacuum Breaker
6- Condensate Pump
The vacuum breaker valve is actuated to 7- Water Injection Valve
open once by a manual key. It closes
automatically when the pressure in the d Steam from IP Turbine
condenser rises. This control achieves a d1 Bypass Steam
rapid passing through the speed range up to k Condensate
hydraulic shaft turning operation. The I Atmospheric air
pressure transmitters installed in the c Drain
condenser for registering the pressure
increase is set at 0.18 bar so that the
condenser pressure will not exceed 0.2 bar
after the valve has closed.
This control enables a complete equalization
Electrical Control of Total Vacuum of condenser and ambient pressure.
Breaker
Automatic Control
So that the vacuum can also be broken
The vacuum breaker is also actuated
without limitation due to condenser
automatically by the turbine fire protection
pressure, a manual key is provided. This key
system to shut the turbo set down more
opens the vacuum breaker valve. However,
quickly. It is switched back manually using
it can not go into the closing position until
the close key in this case.
the close key provided for closing is used.
Working Arrangement:-
Opening Process:-
When the magnet of solenoid valve is
excited/energized then the signal air is
supplied to volume booster for its operation.
Pressurized air from volume booster through
quick exhauster valve is supplied to the
actuator to open the vacuum breaker valve.
Closing Process:-
When the magnet of solenoid valve is not
excited/de-energized then the vacuum
breaker valve is closed as air gets
exhausted from the actuator through quick
exhauster valve as well as volume booster
and at the same time further signal air
supply from solenoid valve is also cut-off.
5.1-0960-02/2
Steam Turbine Changeover Valve
Description for Testing Device
Function
The function of the changeover valve is to
shut off the flow of trip fluid into the trip
fluid circuit while the protective devices
are being tested for proper operation by
means of the Automatic Turbine Tester
(ATT) and to allow control fluid ‘a’ to flow
in so that the stop valves do not close
when the safety devices respond.
Mode of Operation
During normal operation, the control fluid
‘a1’ in the space under the lower piston
(8) of the changeover valve keeps the
valve in the upper end position shown
here. In this way, connection ‘x’ is
connected with connection ‘x1’ and trip
fluid can flow into the trip fluid circuit. The
space above the piston (6) (connection
‘a’) remains depressurized during normal
operation.
When safety devices are checked for
proper operation, the space below the
lower piston (8) is depressurized by
means of a solenoid valve and control
fluid ‘a’ enters the space above the upper
piston, which moves the valve into the
lower position. Due to the connection now
made between connections ‘a’ and ‘x1’,
control fluid ‘a’ can flow freely into the trip
fluid circuit, which keeps the stop valves
open for the duration of the test. Two limit
switches (1) transmit the position of the
valve to the control room.
BHEL,HARDWAR 5.1-1000-77/1
• Motive oil valve of the MAV51 AA001 The bearing-specific oil flow rates are set with
turning gear the throttle valves in the lubricating oil lines
The motive oil valve of the turning gear is actuated upstream of the turbine and generator bearings.
by the associated motor.
Piping and valves
• Oil coolers
oil cooler 1 MAV41 BC001 The turbine oil is supplied to where it is needed
oil cooler 2 MAV41 BC002 through piping. The dimensions of the oil lines are a
function of oil velocity and the oil pressure during
One oil cooler is always in operation to remove operation.
the heat generated by the turbine and generator
bearings from the turbine oil. The second oil Piping, oil coolers, and oil filters are equipped with
cooler is on standby. Changeover to the standby drain valves. Oil coolers and oil filters can be filled
oil cooler must be made when the oil cooler in and vented.
operation clogs or leaks., Air and oil vapour is extracted from the return lines.
Sampling valves are provided for taking oil samples.
The maximum flow rate of the cooling water
.through the oil cooler in operation must be Passive turbine fire protection
maintained for good heat transfer and preventing
deposits in the cooler tubes. The main oil tanks, oil pumps, oil coolers, oil
filters, and important oil system valves are
Double multiport butterfly MAV41 AA521 installed in separate compartment of the turbine
valve building. This compartment is designed with a
The double multiport butterfly valve is the sump for catching leak oil. The sump volume is
changeover valve for the oil coolers. the same as that of the main oil tank.
The oil lines are laid in ducts, which can collect
Oil temperature control MAV41 AA001 leak oil and prevent it from contacting machine
valve parts on which it can ignite.
The lubricating oil temperature upstream of the
turbine and generator bearings is maintained by Information for operation and maintenance
the oil temperature control valve.
Technical Data
The oil temperature control valve is a multiport
valve in which hot and cold turbine oil is mixed to The Technical Data contain the following
obtain the desired lubricating oil temperature of
information:
approx. 45-degree C downstream of the control
valve. - nominal capacity of the main oil tank
Duplex lubricating oil filters - reference values for the capacity of the
lubricating oil filter MAV42 BT001
lubricating oil system including the oil-side
volume of the system tanks, coolers, filters, and
One element of the switchable duplex lubricating piping, which are filled during operation
oil filter is always in operation to protect the - highest and lowest oil level in the main oil tank
turbine and generator bearings against solid during turbine generator operation at rated ,s-
contaminants. .peed
- reference values for the amount of oil which
The differential pressure across the lubricating oil must be filled into the main oil tank for operation
filter in operation is a measure of filter clogging. of the hydraulic and lubricating oil system and
for the amount of oil necessary for flushing the
Double multiport butterfly valve oil system during commissioning or inspection
and overhaul
The double multiport butterfly valve is the - manufacturer, type designation, and design data
changeover valve for the lubricating oil filters. of oil pump motors
- setpoint and limit values of the lubricating oil
Lubricating oil throttle valves upstream of temperature for operation and shutdown of
turbine and generator bearings the turbine generator unit
5.1-1000-77/2
-
- manufacturer, type designation , and fineness auxiliary oil pump must be switched off.
of the lubricating oil system filter
Extended parallel operation of the main and auxiliary
- reference values for oil heatup in the bearings oil pumps shall be avoided.
and bearing-specific oil requirement
Sub-loop controls of the hydraulic and
Dimensioning of the main oil tank lubricating oil system.
The main oil tank is dimensioned so that the total oil - Sub-loop controls for the oil Pumps
in the tank is not recirculated more than 8-10 times
per hour. The turbine oil in the system takes up air All oil pumps of the hydraulic and lubricating oil
during every recirculation. This air is released from system driven by electric motors are controlled
by the switching commands of the associated
the turbine oil in the course of the dwell time in the
sub-loop controls. The oil pumps should always
main oil tank. Large amounts of air in the turbine oil be switched on in a certain sequence to ensure
are either due to an excessive turbine oil recirculation the lubricating oil supply to the turbine and
rate or due to an inadequate air release property of generator bearings in the event of a drop in oil
the turbine oil. pressure in the hydraulic or lubricating oil
system. The sub-loop controls of the oil pumps
Setting of the throttle valves of the hydraulic must be in AUTO mode as long as the line of
and lubricating oil system shafting is driven by steam or the turning gear.
The throttle valve settings for the hydraulic and Changeover of oil coolers and filters
lubricating system are optimised during initial start- Standby oil coolers and standby lubricating oil
up when the turbine generator unit is running at filters must be filled and vented before
rated speed: changeover.
- The INJECTOR (MAV21BN001 / Venting of the oil coolers
MAV21BN002) ensure a positive pressure of
approx. 0.2 bar in the suction line immediately The oil-side vent of the oil cooler in operation
upstream of the main oil pump.
must be open.
- Lubricating oil throttle valves upstream of the
turbine and generator bearings, e.g.,
lubricating oil throttle valve upstream of the
first turbine bearing MAV42 AA501.
5.1-1000-77/3
5.1-1000-77-4
Steam Steam Turbine Oil System MAY
Description Oil Vapour Extraction System
System Description
BHEL,HARDWAR 5.1-1002-77-1
Steam Turbine Oil System MAV
Description Oil Discharge and Vent System
System Description
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
oil pumps which draw the turbine oil from the transportation effort involved, turbine oil should only be
main oil tank must be deactivated to prevent the discharged into drums if neither stationary nor mobile oil
oil pumps from running dry. tanks are available.
Discharging the turbine oil into drums
To allow rouse of the turbine oil, drums into Oil level in the main oil tank
which the oil is discharged must be free of The oil level in the main oil tank must be topped
contaminants of any kind. up while the turbine generator unit is operating
at rated speed, since this operating condition is
Drums must not overflow when being filled with
used as the basis for defining the reference
the discharged oil, nor must they be damaged operating level for the oil.
during transportation.
Due to the amount of time and the large Care should be taken that the reference
operating level is not exceeded.
5.1-1002-77/2
Steam Turbine Oil System MAY
Oil Conditioning (Purification)
Description System Description
The main oil pumps draws the oil through a The basket type oil strainers (13) are mounted in the
suction pipe (1) situated at the flow end of the tank tank. They are of brass wire mesh of 0.25 mm
(1). This suction pipe is constructed as an injector to filtration particle size and can be exchanged by
aid the suction of the main oil pump which has to opening the tank cover.
overcome a certain suction head. Power oil is
conducted to the injector via an injection pipe. This Oil Vapour Exhaust
injection pipe also fills the suction pipe of the main
oil pump when the plant is being started up. The whole tank is made as airtight as possible.
Oil vapour exhausters (11) produce a slight negative
The auxiliary oil pumps (2,3) arranged on the pressure in the tank, in the return drain lines and in
tank are electrically driven rotary oil pumps(2). The the spaces in the bearing pedestals so that oil
jacking oil pumps(4) also situated on the tank, are vapour arising is drawn off.
electrically driven jack-screw immersion pumps (3).
All pumps immerse in the oil contained in the tank Oil Level Indicator
and draw oil from the deepest point in order to
obtain oil as free of air as possible. The driving The main oil tank has a direct reading oil level
elements of the pumps are fixed to the base plates indicator and a fluid limitswitch. This permits signals
of the tank covet. to be transmitted when maximum and minimum
levels have been reached. Extra tank volume is
provided between the normal operating level and the
tank cover to accept oil from the entire oil supply
system when the turbine is shut down, The tank is
constructed with a sloping bottom with drain
connections at the lowest point (6,7).
5.1-1010-01/2
Steam Turbine Main Oil Pump with
Description Hydraulic Speed Transmitter
Function pump shaft (5) runs in the journal bearing (1) and the
The main oil pump is situated in the font bearing combined journal and thrust bearing (7). Both
pedestal and supplies the entire turbine with oil that is bearings are lubricated with filtered 011. If the
used for bearing lubrication, cooling the shaft journals overspeed trip test device, which is described
and as primary and test oil. The main oil pump is separately [2] is actuated, overspeed trip test oil ‘a’
driven direct from the turbine shaft via the coupling flows to the overspeed trip devices via the oil tube
(11). If the turbo-set is out of operation or the main oil (16) built into the pump shaft (5).
pump fails, auxiliary oil pumps take over the Hydraulic Speed Transmitter
necessary oil supply. These pumps also convey oil The pump shaft (5) also carries the hydraulic
into the suction branch of the main oil pump until the speed transmitter (14) which runs in the bearing (7)
main oil pump has started to draw from the main oil and in rings (13). The hydraulic speed transmitter
tank which is situated at a lower level [1]. operates on the same principle as a centrifugal pump
Construction impeller. Any change in speed gives rise to a
the double flow impeller (5) is an integral part of pressure change in primary oil circuit ‘a1’ which
the pump shaft. The pressure and suction chambers serves as a control impulse for the hydraulic speed
are sealed off from each other by seal rings (4) which controller. The hydraulic speed transmitter (14) is
are split and secured against turning at the joint. The supplied with control oil from the hydraulic control
5.1-1020-01/2
Steam Turbine Auxiliary Oil Pump
Description
Description removed from the tank as a complete unit. After the
The auxiliary oil pump is a vertical one-stage suction casing (14) has been removed and the shaft
rotary pump with a radial impeller and spiral casing. It nut (16) loosened. The impeller can be extracted. It is
is fixed to the cover of the oil tank and submerges advisable to renew the split rings (17) when
into the oil with the pump body. It is driven by an exchanging the impeller. The now clearance between
electric motor that is bolted to the cover plate (1). The split ring and impeller neck is 0.3 mm in diameter.
oil enters the suction connection from underneath and
is supplied to the oil system via the pressure pipe Exchanging the Bearings
(18). The pump shaft has: a sleeve bearing (12) in the When dismantling the pump must be removed as
pump casing and a grooved ball bearing (7) in the above. Loosen the pump casing from the pressure
bearing yoke. The bearings are lubricated from the line and suspension pipe from cover plate. Remove
pressure chamber of the pump; the sleeve bearing coupling halves from the shaft by means of an
via a bore in the casing; the grooved ball bearing ‘,ia appropriate device. Remove retaining ring (6), loosen
a lube line. bearing nut (6) and detach grooved ball bearing.
Extract pump shaft after the unscrewing of impeller.
Assembly The pump is reassembled in reverse order.
The pump is assembled before dispatch and can
be mounted on and bolted to the oil tank as a Adjusting Pump Rotor
complete unit. When connecting, care must be taken During assembly, the rotor rests on the sealing
the piping is not stressed when bolted. ring of the suction casing. Lift the rotor by means of
the bearing nut (5) until the rotor sits firmly with the
Dismounting shoulder of the shaft and the distance ring (8) at the
Exchanging the Impeller inner ring of the grooved ball bearing. Secure the
After the motor has been disassembled and the bearing nut with threaded pin.
pressure pipe disconnected. the pump must be
5.1-1050-00/2
Steam Turbine Oil Throttle
Description
Arrangement
The oil throttles arranged immediately before
the bearing in the lubricating lines serve for
adjusting the necessary amount of oil for the
bearings. While the left half of the sectional view
represents the oil throttle during oil flushing, the
right half shows the oil throttle in normal operation.
Construction
The main parts of the oil throttle are the body
(8), in which either the oil strainer (7) which is held
in place by the screw plug (6), for the flushing
process or the adjustable throttle piece (5) with
parts (1, 2, 3) for normal operation are inserted.
Operation
The flushing process is carried out before the
turbine is taken into service. After the flushing, the
oil strainer (7) as well as the screw plug (6) are to
be exchanged with the throttle piece (5) and the
screw plug (3) with the capped nut (11. By means
of the adjustable throttle piece, the cross section
of the passage is then adjusted for normal
operation, according to the necessary amount of
the lubricating oil and consequently the lubricating
oil flow adapted to the required oil exit temperature
of the bearing.
Description
Valve Type
Description
The extraction or dual pressure pump is a
vertical rotary pump in multiple stages. It is attached
to the cover of the fluid tank and submerges in the
control fluid. Drive is provided by an electric motor
located on the cover plate (1). Control fluid enters
the suction casing (10) from below and is conducted
into the LP control fluid circuit via the pressure pipe
(19) and into the HP control fluid circuit via pressure
pipe (23). The pump shaft is guided by a sleeve
bearing (11) in the suction casing and by ball
bearings (25) in the bearing support (4). The ball
bearings and the bevel gear coupling are lubricated
by oil from the 1st stage pressure chamber via
lubricating pipe (22).The sleeve bearing is lubricated
via a passage in the casing.
Assembly
The pump is delivered in assembled state and
can be placed as a unit on the tank and bolted to it.
When connecting the pressure pipe care must be
taken that the piping is not stressed when bolted.
Construction
The plate type filters are installed in
Governing and LP Bypass racks. Single stage
plate type filters are used in LP Bypass racks
while in Governing rack the filter has three
stages. The filtering elements are arranged in
parallel inside the casing. The main components
of the filter are: handwheel (1), filter top (2), filter
element (3), body (4) and sludge drain plug (5).
Mode of Operation
The control fluid enters the body at the right
hand arrow and passes through the filter
element (3). The sludge gets arrested on the
surface ot the cartridges. The clean fluid flows
out to the machine.
Installation of Duplex Filters to the indicating disc and the two contacts
When the filter is being bolted to the foundation, the outside the pressurized area. At certain red portion
casing must not be subjected to any external of the two viewing windows of the indicating disc
stresses. This also applies when the piping is being which occures for example when filter contamination
connected .Care must be taken that the fluid flows increases and at specified switching points a
through in the correct direction. The directin of flow particular contact, thus correspond to the prevailing
is normally marked on the flanges of the filter bodies. differential pressure.
BHEL Hardwar
5.1-1130-00/1
Operating the Changeover Valve
The large arrow on the switching gauge (1) gives
the direction of flow and the small arrow the
switching direction. Before operating the changeover
device, the pressure equalizing coak (2) must be
open.
The duplex filter is switched to the other filter
chamber by turning the star-wheel (3) in the given
direction. By means of a turning lever, the valve
discs can be easily loosened. The star-wheel (3) is
also tightened to the end position by means of this
turning lever. The valve discs (4) open in the
appropriate direction of flow and the change-over
process is then completed. The cock of the pressure
equalizing pipe must then be closed so that one filter
chamber is hermetically sealed.
Start-up and Cleaning
5.1-1130-00/3
Regenerating Plant
Steam Turbine
Description
General The Fuller’s earth needed for regenerating
Of the various types of fire resistant fluid, the the fire resistant fluid must be dry with a residual
only ones suitable for use with our turbines are water content of not more than 1% of the weight.
phosphoric esters of the group HS-D which have If required Fuller’s earth must be dried at a
a low water and chlorine content. temperature not exceeding 105 C.
Their chemical composition and structure The US strainer number 30/60 mesh is the
necessitate certain measures and alterations granular size to be used (or this must
compared with an oil system. correspond to the details from the fluid
Fire resistant fluid systems for our turbines manufacturer). The dust proportion of the
are provided with a bypass regenerating plant. granulate must not be used. The amount of
The design of this plant is made to the earth must not be too little and must be stamped
specifications of the fluid manufacturer. Any or shaken to avoid the formation of gaps and
acids and ageing products are removed during channels which would reduce the effectiveness
operation by continuous filtering through of the Fuller’s earth.
Fuller’s-earth and mechanical filters. The efficiency of the regenerating plant is to
The mode of operation of this natural earth be controlled by an exact record of the
treatment is based on a ion-exchange reaction. neutralization value and the degree of purity.
In addition to the precautions against acidifying
of the fluid, continuous care is taken that any Construction of Regenerating Plant
solid particles are separated by the fine filter so The filter group consists of one dry filter (10),
that they can not speed up the reaction. The fine 2 Fuller’s earth filters (6) and a mechanical Filter
filter of this plant retains particles of Fuller’s (7). The cleaning and deacidifying takes place in
earth as well as providing the essential a separate circuit. A pump (4) conducts a
cleanliness of the whole system and increasing constant amount of fluid through the filter group
the life of the filters. and back into the tank (1). When the filter is
contaminated there is an increase
5.1-1140-00/1
BHEL Haridwar
in the fluid pressure. A spring safety valve (3) is
installed to protect the system against an
excessively high increase in pressure.
Dry Filter
Fluid first enters the dry filter . The cartridges
inside the filter remove dirt and water from the
fluid.The outer media layer filters out silt, rust
and other particular contaminants. The inner
layers absorb water and will chemically bond it
so that no water will release downstream.When
the cartridge reaches its water holding limit, the
media swells and the differential pressure
rapidly increases. The differential pressure
indicator reaches the all-red range.This signals
the operator that the cartrdge must be changed.
5.1-1140-01/2
Instructions for Installation of Filter
Cartridges
of Fine Filter (Fig.3)
The filter cartridges (8) are to be immersed in
the control fluid before the first commissioning
and installed in the filter. The cartridges must be
placed above the standpipes such that the large
opening of the filter cartridge faces downwards.
By inserting the rubber and metal discs and the
clamping springs in this sequence, the filter
cartridges are stressed by means of the
clamping screws to equalize an alteration in the
length of the filter cartridge column.
Means of Cleaning
The following are to be used for cleaning:
Textile and paper cloths without threads,
benzine, white spirit, trichloroethylene,
perchloroethylene and compressed air.
When using these, the respective accident
prevention rules are to be observed.
Remains of cleaning materials are to be
Carefully removed (when chlorinated
hydrocarbon is used there must be no increase
in the chlorine content of the FRF).
Each newly cleaned surface is susceptible to
corrosion. In order to protect the surfaces,
therefore, they must be moistened with FRF or a
corrosion protection medium compatible with
FRF immediately after cleaning.
5.1-1140-01/3
Steam Turbine Drain System MAL
Description System Diagram
Index
System Diagram
MAL Turbine Drains System Drawing No. 1-13100-91131 on sheet No. 5.1-1210-77/2
MAG Turbine Drains System Drawing No. 1-13100-91131 on sheet No. 5.1-1210-77/2
System Diagram
Component Diagram
MAA HP Stop & Control Valves Drawing no. 4-18000-51021 on sheet 5.1-1230-77/3
MAB IP Stop & Control Valves Drawing no. 4-18000-51021 on sheet 5.1-1230-77/4
MAN LP Bypass Valve (ETA Type) Drawing no. 4-18000-51021 on sheet 5.1-1230-77/5
MAW Seal Steam /Leak off Steam Valve Drawing no. 4-18000-51021 on sheet 5.1-1230-77/6
MAD Measuring Points on Turbine – Generator Drawing no. 4-18000-51022 on sheet 5.1-1230-77/7
Bearings
BHEL,HARDWAR 5.1-1240-77/1
5.1-1240-77/2
Keeping the seal steam line upstream of the
seal steam control valve warm
5.1-1240-77/3
5.1-1240-77/4
5.1-1240-77/5
Steam Turbine Operation of the Turbine
Description Introduction
The efficiency of turbine and functioning of its maintenance instruction on Oil Care [4] should be
components depend, among other things, on followed. Regular sampling and laboratory checks
whether the steam quality and the properties of the will indicate that the turbine oil complies with the
operating fluids fulfil the requirements listed in the specifications.
Description section of this manual. Particular care
should always be taken during startup that the The purity (freedom from liquid and solid
purity and the physical & chemical properties impurities), air-release properties and foaming
comply with the turbine manufacturer’s guidelines. characteristics of the oil are important to the
functioning of the turbine generator unit’s
Steam Purity components.
The steam purity must comply with the guideline
on ‘Steam Purity’ (1) before startup and power Control Fluid
operation is begun. The guideline ‘Control Fluid’ [5] has the
requirements for this operating fluid. The
Blade deposits reduce the efficiency. Deposits maintenance instruction ‘Care of Control Fluid’ [6]
can only be removed by time-consuming processes should also be followed. Regular sampling and
[2] and occur during power operation when normal laboratory checks will indicate that the control fluid
values are exceeded. complies with the specifications.
Immediate corrective action must be taken to The purity (freedom from liquid and solid
restore the required steam Quality specified in the impurities), neutralization coefficient as a
guideline [1]. characteristic for aging, air-release properties and
foaming characteristics of the fluid are important to
Turbine Oil the functioning of the turbine generator unit’s
Oil Specifications guideline [3] lists the components.
requirements for the operating fluid. Also
Introduction
Countermeasures for Abnormal Conditions
The operational reliability and availability of a
turbine is assured only if all the vital components and It is recommended that all abnormal conditions
monitoring equipment for operation are in the specified detected in the course of testing be eliminated by the
condition at all times. countermeasures specified in the remedial action and
maintenance instructions in the turbine manual.
This applies particularly to :
In some cases the desired condition may be
controllers restored sooner or prevented from deteriorating if the
protective devices testing intervals are shortened. Use of this opportunity
safety devices is recommended. Shorter testing intervals also make it
stop and control valves and other important turbine easier to detect and monitor any progressive
valves deterioration in the condition of component.
monitoring equipment
On this basis, the optimum timing for the
The unit’s operating parameters can provide necessary remedial actions may be determined in the
important information on the condition and reliability of light of other factors, requiring consideration.
the turbine unit and its systems,
Performance of Tests
Testing Intervals Tests are generally performed by the operator’s
The following recommendations, for time Intervals properly qualified plant personnel.
between tests have been compiled, on the basis of As a rule the performance testing should be
experience gained by the turbine manufacturer and the executed immediately after maintenance or overhaul
operators. activities, such as major inspection, in the presence of
concerned qualified personnel form BHEL.
shutdown
Running
monthly
weekly
yearly
Turbine Governor
- function 1 X X X
- setting X X
Bypass Controller
- function 3 X X X
- setting X X
Fluid Temperature
Controller
- function
X X
Oil Temperature
Controller
- function X X
shutdown
Running
monthly
weekly
yearly
Automatic Turbine
Tester for Protective
Devices
- functioning of remote 2 X X X
trip solenoid
- functioning & setting of
overspeed trips
- functioning & setting of
hydraulic low
vacuum trip
shutdown
Running
monthly
weekly
yearly
Automatic Turbine
Tester for Stop & Control 2 X X X
valves
- free movement of stop
valves
- free movement of
control valves
shutdown
Monthly
running
Weekly
month
Yearly
Main Trip Valves
- functioning and breakaway pressure x x x
Overspeed Trips
- functioning and setting during testing with x x x
hydraulic test signal transmitter
- functioning and setting during testing by Overspeed 1 x x
Shutdown
Running
Monthly
Weekly
Yearly
Safety Valves
- functioning and set pressure x
After shutdown>1month
Shutdown
Running
Monthly
Weekly
Yearly
Stop Valve
- free movement x x x
using starting and load limiting device.
test valve or trip actuation
- breakaway pressure x x
- leak tightness at each startup x x x
Control Valve
- free movement x x
using starting and load limiting device.
test gear or trip actuation
- leak tightness 1 x x
(in conjunction with test of reverse power protection at
each shutdown)
- free movement x x
(observe control valves lift at each load change) 1 x
Extraction Valves
- free movement 2-4 x x x
by observation of position indicators
Vacuum Breaker
- functioning at each shutdown 1 x x x
CRH NRV
- free movement 2 x x x
by operating pushbutton on desk
shutdown
Running
monthly
weekly
yearly
Alarms
- functioning X X
Binary Signal
Transmitters X X
- functioning and setting
Speed Indicators
Temperature Gauges
Expansion Measuring
Devices
Vibration Measuring
Devices
liquid Level Measuring
Devices
Valve lift Transducers
- accuracy of indication 3 X X X
Shutdown
Running
Monthly
Weekly
Yearly
Steam Pressures
Steam Temperatures
Steam Mass Flow Rates
Casing Temperatures
Bearing Metal Temperatures
Expansion
Vibration
liquid Levels
Oil Pressures
Oil Temperatures
Control Fluid Pressures
Control Fluid Temperatures
- recording of operating values for long term monitoring 3 x x
purposes
5.2-0112-00/2
Steam Turbine Preparation for Startup
Operation Startup Diagram
5.2-0130-02/2
+ SEAL OIL SYSTEM NO ALARM
+ LIQUID IN GENERATOR NO ALARM -----------------
AND MKA22 CLOO1
AND MKA23 CLOO1
AND MKA23 CL 011
5.2-0130-02/3
(06/S) + SUBLOOP CONTROL TURNING GEAR ON MAV51 EEO01
SUBLOOP CONTROL OPENS AND CLOSES THE
TURNING GEAR OIL VALVE DEPENDING ON
TURBINE/GENERATOR SPEED.
TURNING GEAR OIL VALVE (OPEN) < 210 RPM
TURNING GEAR OIL VALVE (CLOSED) > 240 RPM
TURNING GEAR OIL VALVE CLOSES DURING
STARTUP AND OPENS WHEN THE TURBINE
IS COASTING DOWN AFTER SHUTDOWN.
DO NOT SWITCH OFF SUBLOOP CONTROL
AS LONG AS TURBINE IS IN OPERATION TO
MAKE SURE TURNING GEAR CUTS IN IF
TURBINE WILL BE SHUTDOWN.
5.2-0130-02/4
+ SUBLOOP CONTROL OF JACK1NG OIL PUMP SWITCH ON MA V30 EEOO1
AND MAV33 EEOO1
+ SUBLOOP CONTROL OF JACKING OIL PUMP ON MAV30 EEOO1
AND MAV33 EEOO1
OR WITH FGA(OIL SUPPLY)
(09/S)*+ SUBLOOP CO~TROL OF JACKING OIL PUMP ON MAV30 EEO01
AND MAV33EEOO1
+ JACKING OIL PUMP ON MAV31 APOO1
OR JACKING OIL PUMP FAULTED MAV31 APO01
+ JACKING OIL PUMP MANUAL OPERATION ON MAV32 APO01
OR MAV33 APO01
SUBLOOP CONTROL STARTS AND STOPS THE
JACKING Oil PUMP 1 DEPENDING ON
TURBINE/GENERATOR SPEED CRITERIA.
JACKING OIL PUMP 1 ON < 510 RPM
JACKING OIL PUMP 1 OFF > 540 RPM
AND
SUBLOOP CONTROL STARTS THE JACKING OIL
PUMP 2 DEPENDING ON JACKING OIL PRESSURE
5.2-0130-02/5
Steam Turbine Control Fluid System
Description Startup Diagram
5.2-0135-02/2
-START RECONDITIONING PUMP
-VENT FILTERS
-SHUT-DOWN RECONDITIONING PP
- DEAERATION OF CF- TANK READY F OPE RAT
AIR-FILTER: NO CHANGE IN
COLOUR.
EXHAUSTER FAN <ON>
- CONTROL FLUID PROPERTIES NORMAL
REFER TO 5.3-0082
- CONTROL FLUID HEATER READY F OPERA T
5.2-0135-02/3
(06/S)*+ ONE CONTROL FLUID PUMP ON MAX16APOO1
OR MAX16APO02
5.2-0135-02/4
Steam Turbine Condensing Plant
Operation Startup Diagram
5.2-0140-02/2
(04) + DRAIN OF SEAL STEAM HEADER OPEN MALe-1AA011
+ DRAIN OF SEAL STEAM HEADER OPEN MAL81AA011
OR WITH SUBLOOP CONTROL
+ SUBLOOP CONTROL DRAINS SWITCH ON MALOOEEO01
+ DRAIN OF SEAL STEAM HEADER OPEN MAL81AA011
POSITION OF DRAIN VALVE(S)
DEPENDING ON TEMPERATURE
CRITERIA IN HEADER
VALVE(S) <OPEN> STEAM-TEMP. < 120 CEL
VALVE(S) <CLOSEQ> STEAM-TEMP. >150 CEL
5.2-0140-02/3
(07) + VACUUM-PUMPS SWITCH ON
THE VACUUM PUMPS DO NOT BELONG
TO THE SCOPE OF SUPPLY OF THE
<TURBINE/GENERA TOR>.
OPERATION OF PUMPS AND VALVES ‘.
FOR AIR REMOVAL PRIOR TO AND
DURING OPERATION ,\CCORDING
TO SPECIAL INSTRUCTIONS. .
IOPERATION OF PUMPS AND VALVES
FOR AIR REMOVAL PRIOR TO AND
DURING OPERATION REFER
TO PLANT-MANUAL
+ VACUUM-PUMPS ON MAJ60ANO01
AND MAJ70ANO01
GENERAL OUTLINE:
5.2-0140-02/4
Steam Turbine Bypass-System
Description Start of Operation
+ FIXPRESSUREREFERENCEVALUE KG/CM2
THE SETTING OF THE FIX
PRESSURE REFERENCE VALUE
DEPENDS ON THE REQUIREMENTS
OF THE STEAM-GENERATOR
F.E. THE SYSTEM FLOW THROUGH
THEREHEATER.
THE SETPOINT HAS TO BE
RAISED DURING STARTUP TO
MEETTHE DESIGN-VALUE FOR
MINIMUM LOAD OF THE STEAM-
GENERATOR.
FIX PRESSURE REFERENCE
VALUE AS DESIGNED. ...KG/CM2
+ VACUUM-PUMPS IN OPERATION
+ VACUUM-PUMPS IN OPERATION
+ STEAM-GENERATOR IN OPERATION
+ REHEATPRESSURE/FIXPRESS. RELATION = 1
REF. VALUE
5.2-0150-00/2
+ LIMIT VALUE OF STEAM FLOW NOT INITIATED
5.2-0150-00/3
Steam Turbine Warm up and Startup of Turbine
Operation Startup Diagram
5.2-0160-02/2
OPERATION OF PUSH BUTTONS
REFER TO MANUAL FOR THE FGA
(12) + STARTING AND LOAD LIMIT DEVICE SET HIGHER MAX47 BYO01
OR WITH OF FGA (TURBINE CONTROL)
(12/S) + STARTING AND LOAD LIMIT DEVICE SET HIGHER MAX47 BYO01
STARTING AND LOAD LIMIT DEVICE > 42% MAX47 BYO01
+ MAIN STEAM STOP VALVES OPEN MAA10 AAO01
MAA20 AAO01
(16) + WAIT
WARM UP PROCEDURE WILL BE GUlDED BY THE
WARM.UP CONTROL. LEADING PARAMETER IS THE
TEMPERATURE ALLOWANCE OF THE TSE/TSC CHANNEL
(ADMISSION). THE DRAINS OF THE CONTROL
VAL VES WILL BE OPENED AND CLOSED DEPENDING
ON THE MAGNITUDE OF TSC ALLOWANCE. IF THE
WARM.UP CONTROL IS DISTURBED OR NOT IN
5.2-0160-02/3
OPERATION OPERATE DRAIN VALVES OF THE HP
CONTROL VALVES MANUALLY. CLOSE ON DECREASING
TSE/TSC ALLOWANCE. OPEN ON INCREASING TSE/TSC
ALLOWANCE. IF THE TSE/TSC IS FAULTY OPERATE
DRAIN V ALVES ACCORDING TO WALL TEMP
AT THE TSE/TSC RECORDER. REFER TO TECHNICAL
DATA FOR LIMITS OF DIFFERENTIAL
TEMPERATURES OF THE TSE/TSC.
5.2-0160-02/4
OR WITH SUBLOOP CONTROL
AND
+ OPERATIONAL VALUES OF TURBINE CHECK
+ STEAM TEMPERATURE CRITERIA FULFILLED REF. 5.2-0170 FIG,6
+ TURBINE STRESS MARGIN > 30 OK
+ BEARING VIBRATION NORMAL
+ SHAFT VIBRATION NORMAL
DEFINITION OF NORMAL VALUES OF VIBRATION:
VIBRATION PREVIOUSLY OBSERVED WHEN OPERATING
WITH SAME SPEED AND OTHER PARAMETERS
(26) + WAIT
THE LIMITED SPEED REFERENCE VALUE FOLLOWS
THE SPEED REFERENCE VALUE WITH THE PRESET
GRADIENT. DO NOT HOLD THE TURBINE IN THE
CRITICAL SPEED ZONE. THE SPEED GRADIENT
WILL BE REDUCED IF REDUCTION OF THE TSE/TSC
ALLOWANCE OCCUR. THE TSE/TSC INFLUENCE WILL
BE EFFECTIVE VIA THE REFERENCE LIMITER.
IF A SIGNIFICANT REDUCTION OF THE TSE/TSC .
ALLOWANCE OCCURS, THE TURBINE SPEED WILL BE
REDUCED TO WARM UP SPEED. IF THE TSE/TSC IS
FAULTED THE DIFFERENTIAL TEMPERATURES AT
THE MEASURING POINTS WHICH REPRESENT THE
THERMAL STRESSES OF CASING AND ROTOR MUST
BE EVALUATED REFER TO 5.1-011..
REDUCE SPEED REFERENCE VALUE TO WARMUP
SPEED WHEN OPERATING WITHOUT TSE/TSC
INFLUENCE AND THE TSE/TSC ALLOWANCE
REDUCED TO ZERO.
5.2-0160-02/5
AND MAL 12 AA011
5.2-0160-02/6
Steam Turbine Warming-up and Starting the Turbine
Description Temperature Criteria
θms>θs Fig.1
θs = Temperature of saturated
steam (depending on main
steam pressure)
and
θms>f(θmcv50%) Fig.2
θs>f(θmcv50%) Fig.3
Starting Cretaria
θs = Temperature of saturated
steam (depending on main
steam pressure)
and
θms>f(θHT50%) Fig.4
5.2-0170-01/2
Minimum reheat temperature
Speeding up criteria
5.2-0170-01/3
Loading criteria
5.2-0170-01/4
Steam Turbine Warming up and Starting the Turbine
Operation Controller
5.2-0180-00/2
+ Turbine generator unit speed = Turning gear speed
+ Stop valve position = 0%
+ Control Valve position = 0%
+ Main trip valves = depressurized
+ Starting and load limit device = 40% open
+ Reference speed setter = 0%
+ Electrical speed reference = 0%
(6) + Using Starting and load limit device maintain constant speed
Operating logic sequence 1: Starting up the turbine generator unit with the
starting and load limit device and the hydraulic
speed governor
A see Warming up the Main Steam Line
B see Warming up Starting up the Turbine
5.2-0180-00/3
+ Turbine generator unit speed > turning gear speed and
< 75% rated speed
+ Electrical speed reference = turbine generator unit speed
+ Reference speed setter = 100%
(4) + Using starting and load limit device maintain constant speed
Operating logic sequence 2: Transition from operating with electrical speed controller to
operating with starting and load limit device
(Speed approx, 80% rated speed)
Operating logic sequence 3 : Transition from operating with starting and load limit
device to operation with electrical speed controller
(Speed approx ,80% rated speed)
5.2-0180-00/4
Steam Turbine Load Operation
Operation Introduction
SYNCHRONIZED
+ SYNCHRONOSCOPE SWITCHED ON
+ GENERATOR/LINE-VOLTAGE MET
OR WITH (AUTOMATIC SYNCHRONIZER)
+ GENERATOR/LINE-FREQUENCY MET
5.2-0210-00/2
(11) + STARTING AND LOAD LIMIT DEVICE SET HIGHER MAX47BYO01
(13) + WAIT
REFER TO 5.2-0430 IF
TSE-ALLOWANCE IS
REDUCED.
5.2-0210-00/3
(14) + DRAIN DOWNSTREAM RCV CLOSE
CRETERIUM:
TEMP.HP-CASING TOP >320 CEL
CRITERIUM: LBC10AAO01
NON RET.CHECK VLV COLD REH. OPEN
5.2-0210-00/4
+ DRAINS OF EXTRACTIONS CLOSED MAL47AAO11
AND MAL51AAO11
AND MAL54AAO15
AND MAL 55AAO11
5.2-0210-00/5
Steam Turbine Power Operation
Operation Controllers
Reference limiter
- Target reference value/actual The actual reference value tracks the target
reference value reference along a preset gradient.
- Limitation of reference limiter by TSE The present gradient Is reduced in accordance with
(turbine stress evaluator) component a predetermined characteristic to conform to the
load margin generated by the TSE.
- Application of TSE signal The TSE signal must always be present unless the
TSE is faulted. .
- Operation with TSE faulted The actual reference value no longer tracks the
target reference value if the TSE is faulted;
Actual and target reference value must be matched
up before the TSE signal can be switched off.
The thermal stresses In the turbine components
must be assessed by comparison of the actual tem-
peratures and their differences with the curves for
permissible temperature margins given in
TechnicaI Date 5.1-011.
limitation by priority or alternative
controllers or other equipment
- Minimum value selection Controller in effect = controller with lowest
setpoint;
(also applicable to other equipment that affects
the controller output signal.
- Hydraulic governor < 100% limits reference value by means of hydraulic minimum
value selection.
- Starting and load limit device < 100% limits reference value by means of hydraulic minimum
value selection.
Control valve lift overshot can be prevented by
means of starting and load limit device
Operation
- Control and monitoring devices See desk allocation diagram in controller manual.
Note instructions on use of release pushbuttons I
-Control logic for changing operating See appendix
mode
Instructions for control and operational
monitoring
- speed reference value after changeover After changeover to load control the speed
to load control reference value is to be set such that speed will
revert to approx. 0.6% above rated speed in the
event of load shedding.
3 Hydraulic Governor
Control range
- Speed 80-107%
- Valve travel at rated speed 100%
- load at design pressure 100%
Reference limiter
- Target reference value/actual Actual reference value tracks target reference
reference value value directly (no TSE component).
During operation with the hydraulic governor in
control, the thermal stresses in the turbine com-
ponents must be assessed by referring to the TSE
display or, if the TSE is faulted, by comparing
the actual temperatures and their differences with
the curves for permissible temperature margins as
give in Technical Data 5.1-011.
Limitation by priority or alternative
5.2-0220-00/2
controllers or other equipment
- Minimum value selection Controller in effect == controller with lowest
reference value;
(also applicable to other equipment that affects
the controller output signal).
- Electrohydraulic controller < 100% Limits reference value by means of hydraulic
minimum value selection.
- Starting and load limit device < 100% Limits reference value by means of hydraulic
minimum value selection.
Operation
- Control and monitoring devices See desk allocation diagram in controller manual.
- Control logic for changing operating See appendix
mode
Instructions for control and operational
monitoring
- Actual speed after load shedding As dictated by setting of speed reference value
before load shedding with allowance for droop,
After shedding, the actual speed must revert to
rated speed.
- Starting and load limit device During operation with the hydraulic governor in
control, the turbine generator assists in grid
frequency stabilization as governed by the droop
of the controller;
The influence of the frequency component on the
load reference value tending to raise power can
be eliminated by switching in starting and load
limit device
4 Load Control by the Electrical Controller
Control range
- Valve travel 100%
- Load at design pressure 100%
Reference limiter
- Target reference value/actual The actual reference value tracks the target
reference value reference value along a preset gradient.
- Limitation of reference limiter by TSE The present gradient is reduced in accordance with
a predetermined characteristic to conform to the
load margin generated by the TSE.
- Application of TSE signal The TSE signal must always be present unless the
TSE is faulted.
- Operation with TSE faulted The actual reference value no longer tracks the
target reference value if the TSE if faulted;
Actual and target reference value must be matched
before the TSE signal can be switched off.
The thermal stresses in the turbine components
must than be assessed by comparison of the actual
temperatures and their differences with the curves
for permissible temperature margins given in
Technical Data 5.1-011.
Limitation by priority or alternative
controllers or other equipment
- Minimum value selection Controller in effect = controller with lowest
reference value;
(also applicable to other equipment that affects
the controller output signal).
Absolute limit load reference value Limit reference values by means of electric minimum
selection;
Active in the event of unit malfunctions.
5.2-0220-00/3
- Hydraulic speed governor < 100% Limits reference value by means of hydraulic
minimum value selection
- Starting and load limit device < 100% See above
Operation
- Control and monitoring devices See desk allocation diagram in controller manual.
Note instructions on use of release pushbuttons
-Control logics for changing operating See appendix
mode
Instructions for control and operational
monitoring
- Changeover from speed to load and from Valve lift reference value must be matched up prior
load to speed control To changeover..
- Switching off load controller in the Changeover from load to speed control is effected
event of load shedding When the load falls below a preset value;
Changeover back to load control is effected if the
actual load rises above the lower limit within
approx. 2s.
- Cut in of initial pressure controller The pressure control deviation must be 0 before
the initial pressure can cut in.
5.2-0220-00/4
APPENDIX
Control logics 1: Changeover from electrical to hydraulic speed control in idling mode, e.g. for exercising overspeed trips.
Contrl logics 2: Changeover from hydraulic speed control in idling mode e.g. after exercising overspeed trips.
5.2-0220-00/5
+ Turbine generator load >0MW
+ Individual valve controller in operation
+ Plunger coil on
+ Electrical speed controller in operation
+ Electrical load controller in operation
+ Electrical speed reference value = rated speed + load component
+ Speed Changer = 100%
+ Starting and load limit device = 100%
Control logic 3: Changeover from electrical to hydraulic speed control during speed controlled Power operation
(procedure (5) onwards: Switching off hydraulic frequency influence)
5.2-0220-00/6
+ Turbine generator load > OMW
+ Plunger coil off
+ Electrical speed controller not in operation
+ Electrical load controller not in operation
+ Electrical speed reference value = max. speed
+ Speed changer = 100%
+ Starting and load limit device = in effect
(4) + Electrical speed reference value < speed changer reference value
Control logics 4: Changeover from hydraulic to electrical speed control in power operation
(up to procedure (2): switching on hydraulic frequency component)
5.2-0220-00/7
+ Turbine generator load > a MW
+ Plunger coil on
+ Electrical speed controller in operation
+ Pressure component on
+ Pressure controller in operation
+ Electrical load reference value = actual # pressure component
+ Electrical speed reference value = approx 1.005 x rated speed
+ Speed changer = 100%
+ Starting and load limit device = 100%
Control logics 5: Changeover from electrical load control to hydraulic speed control
procedure (5) + (6) switch off hydraulic frequency influence
5.2-0220-00/8
+ Turbine generator load > 0 MW
+ Plunger coil A off
+ Electrical load controller not in operation
+ Electrical load reference value = max. load
+ Electrical speed reference value = max. speed
+ Speed Changer = 100%
+ Starting and load limit device in effect
Control logics 6: Changeover from hydraulic to electrical load control in power operation
Procedure (1) + (2) Switch off hydraulic frequency cornball
Procedure (9) + (10) Switching on pressure condoner
5.2-0220-00/9
Steam Turbine Actions to Prevent Unallowable Heat up
Operation Through Blade Wind age
Procedural Instruction
Introduction
During startup and shut-downs, there can be iong Owing to the proportional relationship between steam
period during which Steam turbines are operated at very density and steam pressure, the steam pressures in
low volumetic flows. This operating mode can result in
blade windage in individual stages of multi-stage expansion sections undergoing windage can be used to
turbines. determine the degree of heatup due to windage.
The direction of the energy conversion cycle at the
affected blade stages is reversed. The mechanical General actions to prevent unallowable heatup of the
energy transmitted by the turbine shaft is converted to steam turbine due to windage
thermal energy, which in turn result in an increase in the
temperature of both the steam and the turbine Limitation of the period of ‘motoring’ operation Blade
components. windage can occur in expansion sections of a steam
Unallowably high temperatures can occur as a result turbine if volumetric flow drops to zero, resulting in
of blade windage, leading to loosening of the blade the turbine being driven by the generator which acts
assembly of drum stages through plastic deformation. as a motor driven by the public power system.
Turbine casings can undergo deformation due to the - Activation of short-time reverse power protection
effects of high temperatures. following turbine trips
During steam turbine operation, the operating mode After turbine trip, which can be initiated during any
and limiters and protective devices must be used to keep operating mode of the turbine generator unit. the
heatup due to blade windage within the prescribed Imits. generator must be isolated from the public power
system after no more than four seconds through
Thermodynamic and operating factors affecting activation of the short-time reverse power
blade windage protection.
The following factors can lead to blade windage: in order to prevent motoring of the generator at
Volumetric flow Blade windage can occur as a result high speed beyond this time period owing to the
of insufficient volumetric flow through a multistage interruption in volumetric flow and high steam
expansion section of the steam turbine. pressure in one expansion section.
The lower the volumetric flow through a blade stage, Activation of long-time reverse power protection
the lower the turbine efficiency will be in the case of during a (schedule) turbine generator shut-down,
very low volumetric flows, steam flow through the the control valves of the turbine generator unit are
stage is not directed and the steam has to be closed, to allow the generator to be isolated from
accelerated up to the average speed of the rotating the public power system through activation of the
blades, which creates a deceleration effect. long-time reverse power protection.
As the volumetric flow decreases, and the turbine The maximum time delay for activation of the
starts to operates at zero load, blade windage result long-time reverse power protection specified in the
in transition from power transfer from the blades to Technical Data must not be exceeded. The long-
power transfer to the blades. time reverse power protection must be functionally
Blade windage starts in the final blade stages of an tested in conjunction with leak testing of the
expansion section, and extends towards the first control valves each time the turbine generator unit
stages as flow decreases. is shut down.
Steam density, steam pressure and turbine generator Turbine trip after limit values have been reached
speed. Blade windage causes temperature increases at
The degree of windage-induced heatup Which occurs certain exhaust-steam or casing -temperature
as a result of low volumetric flow through an measuring points. The limit values of the
expansion section of the steam turbine depends on temperature at which turbine trip is to be initiated are
the windage power. specified in the Technical Data. if, under particularly
The higher the steam density and the turbine speed unfavorable conditions, these temperatures are
to the third power, the greater will be windage power, reached, turbine trip must be initiated, either
and therefore the heatup, in one blade stage. manually from the control room, or automatically by
tripping of a protective device.
5.2-0230-00/2
prevent adverse effects in terms of blade windage. After the alarm “LP casing temperature high” has been
Actions to the taken in the event of a high steam initiated the spray valve of the LP condensate injection
temperature downstream of the HP turbine system must be opened, either automatically or
If blade windage occurs in the HP turbine, there will manually, in order to prevent unallowable heatup due to
be an increase in steam temperature at1he windage.
measuring point down steam of the HP turbine.
The limit value of maximum allowable exhaust steam Settings and Tests
temperature specified In the Technical Data must not Settings of the staggered operating sequences for
be exceeded. main steam & reheat steam control valves in
After the alarm “HP exhaust temperature high” has accordance with the relevant setting diagram.
been issued the following actions must be Settings of the settings for the staggered operation
implemented immediately to prevent unallowable of main steam & reheat steam control valves
heatup due to windage: following inspections and overhauls.
Actions to be taken to prevent unallowable heatup The turbine controller is used to reduce the steam
of LP turbine due to windage turbine load so far that the turbine control valve
close and the generator then acts as motor, driving
the turbine. This reverse power operation causes the
The following actions can be implemented to prevent reverse power protection to be activated, which
the unallowable heatup due to windage: isolates the generator from the public power system
Increase the turbine load. after a certain time delay has elapsed.
Cooling by means of condensate injection.
5.2-0230-00/3
Testing of activation of short time reverse power
protection during each shut down of the turbine Isolation of the generator from the public power
generator unit. system after 4 seconds must be monitored and
recorded.
Testing and maintenance of protective device in the
event that a fault has resulted in a stricter
changeover in the protection circuit (annunciation:
“protective device faulted”).
5.2-0230-00/4
Steam Turbine Startup and Shutdown Diagrams
Operation Introduction
(10) + OIL SYSTEM WITH FGA (OIL SUPPLY) SHUT -DOWN REF. TO 5.2-0340
OR
MANUAL OPERATION AT OPER. CONSOLE
+ SHAFT STANDSTILL
+ OIL SYSTEM NOT IN SERVICE
(03) + WAIT
*+ LIMITED LOAD REFERENCE VALUE LOWER
THE LIMITED LOAD REFERENCE VALUE FOLLOWS
THE TARGET LOAD REFERENCE VALUE WITH THE
ADJUSTED LOAD GRADIENT. THE LOAD GRADIENT
WILL BE REDUCED IF REDUCTION OF TSC
ALLOWANCE OCCUR. THE TSC INFLUENCE WILL
BE EFFECTIVE VIA THE REFERENCE LIMITER.
5.2-0320-02/2
(10) + DE-EXCITATION BREAKER OPEN
+ DE-EXCIT A TION BREAKER OPEN
(14) + DRAIN UPSTREAM OF MAIN STEAM CONTROL VALVES OPEN MAL11 AA011
OR WITH FGA AND MAL12 AAO 11
+ DRAIN UPSTREAM OF MAIN STEAM CONTROL VALVES OPEN MAL 11 AA011
AND MAL12 AA011
5.2-0320-02/3
+ SPEED OF TURBINE/GENERATOR < 210 RPM
(17) + TURNING GEAR OIL VALVE OPEN MAV51 AAOO1
+ TURNING GEAR OIL VALVE OPEN MAV51 AAOO1
OR BY SUBLOOP CONTROL TURNING GEAR
*+ TURNING GEAR OIL VALVE OPEN MAV51 AAO01
5.2-0320-02/4
+ TEST PROGRAM (STANDSTILL) COMPLETED
+ CONTROL FLUID SUPPLIED DEVICES NOT IN SERVICE
(20) + CONTROL FLUID SYSTEM MANUAL OPERATION SHUTDOWN
OR WITH FGA (CONTROL FLUID SYSTEM)
+ FGA (CONTROL FLUID SYSTEM STANDSTILD START
OPERATION OF PUSH BUTTONS
REFER TO THE MANUAL FOR FGA.
5.2-0320-02/5
Steam Turbine Condensing Plant
Operation Shutdown Diagram
5.2-0330-01/2
Steam Turbine Oil System
Operation Shutdown Diagram
(05) + WAIT
THE WAITING TIME IS EXPIRED WHEN THE
SHAFT COMES TO A COMPLETE STOP.
+ SHAFT STAND STILL
(07) + WAIT
WAIT FOR SHUTDOWN OF JACKING OIL PUMP UNTIL
THE RELATIVE EXPANSIONS ARE REDUCED AND NO
FURTHER MAJOR AXIAL SHIFTING OF THE JOURNALS
IN THE BEARINGS IS EXPECTED.
5.2-0340-01/2
Steam Turbine Fast Cooling Down of the Turbine
Operation
Introduction
If service activities or repairs have to be carried out
very soon or immediately after shut down of the Fast cooling down during stand still
turbine, it is advisable to reduce the cooling down time.
Fast cooling down is necessary especially if activities During stand still air will be sucked through the
are to be executed at turbine parts, which are exposed turbine by the vacuum pumps resulting in fast cooling
to high operational temperatures. of casing and rotor.
Cooling down of the turbine during operation Arrangement of the air Inlet sockets
The cooling down of the turbine is to be started HP turbine: Between main steam stop valves and
during load operation as follows: control valves.
Reduce unit power output to the boiler minimum IP turbine: At the admission pipes between control
load. valves and IP turbine,
Slowly reduce admission temperatures to values,
which can be maintained steady by boiler control. During normal operation the air inlet sockets are
closed by blank flanges.
The HP exhaust temperature may not be reduced to
the saturation point corresponding to the HP exhaust Procedure
pressure.
Open air inlet sockets
Observe the TSE/TSC lower margin.
Set test valve of all stop valves in the position stop
NOTE: Do not reduce load and temperature at valve closed.
the same time because of the danger to exceed the
Operate vacuum pumps
permissible relative expansion and the lower
margin of the TSE/TSC
Observe TSE/TSC lower margin and stop vacuum
pumps if limit values are exceeded.
Load or temperature reduction have to be stopped
or the rate of ‘change to be reduced depending upon
the limiting values of relative expansion and the lower
The fast cooling down of turbine has to be
margins of the TSE/TSC.
limited to those cases where this measure is
Operate the turbine with reduced load and steam unavoidable with respect to the availability of the
temperatures until the lower margin of TSE/TSC do turbine.
not change significantly any more.
Seizure of sliding components due to increased Preventing Corrosion During Idle Periods
volume of the products of corrosion,
If complete effectiveness of the following method of
Heavier wear of corrosion-damaged surfaces,
The turbine itself and its connecting pipe work must The high relative humidity air inside the turbine can
be well drained through out the idle period. It is also be exchanged for dry air.
advisable to drain the condensate from the condenser.
There are basically two possible methods of For large turbines, therefore, a method of
preventing corrosion attack caused by condensation prevention is recommended employing an Air dryer to
from the air inside the turbine: exchange the high relative humidity air in the turbine
for dry air.
The turbine components can be heated by means of
a hot air blower to a temperature above that of the
outside air.
5.2-0360-00/2
Steam Turbine Fault Tracing
Operation Introduction
The scope and content of the trouble In the instruction Serious Faults [1], the
shooting instructions are limited to criteria or remedial measures are indicated against the
measures that can be performed by the faults that could have severe consequences.
control panel operator or the turbine
The operating staff must be trained to take
operator without specialized help and avert
proper action should such fault occur.
events detrimental to the operation and
availability of the turbine generator unit.
5.2-0410-00/2
Fault Cause Remedy
Other symptoms
Reverse power protection
relay fails to open generator
breaker
Turbine control valves Suspected that steam is still Attention: do not open
closed by control as load entering the turbine. generator breaker manually
removed (danger of impermissible
overspeed).
Check position of control and
extraction valves (Desired
position: 0%).
Trip turbine.
Observe closing of stop
valves, check steam pressure
in turbine, check output
display, reduce condenser
vacuum:
− Open vacuum breaker
− Stop air extraction from
condenser plant
− Allow air to enter
condenser plant
Open turbine drains
Open drains between stop and
control valves
Shut down steam generator;
reduce steam pressure in
steam supply lines.
Fault in reverse power If reverse power protection
protection relay relay is not actuated by all or
some of the above mentioned
measures, it is very probable
that there is a fault in the
reverse power protection relay.
In this case, disconnect the
generator from the supply
system by opening the
breaker.
The following parameters Use load limiting device to
exceed the permissible reduce load on turbine
limits even though remedial generator unit from any
measures have been taken operating mode to no-load
as prescribed in the relevant and/or shut-down unit by
fault tracing instructions actuating main trip valve.
Vibration high See 5.2-0420 Reduce condenser vacuum to
shorten coast down.
5.2-0410-00/3
Fault Cause Remedy
Other symptoms
Casing differential See 5.2-0423 Note: The decision whether
temperatures high the load limiting device should
be used to further reduce load
Bearing metal See 5.2-0421
before the main trip valve is
temperatures high
actuated will depend both on
Temperature differences the seriousness of the danger
between parallel steam and on the amount by which
supply lines high the limits are exceeded.
Rapid, large drop in inlet
stream temperature
Condensate level in
condenser very high
5.2-0410-00/4
Fault Cause Remedy
Other symptoms
Control valve or stop valve
fails to open again after
testing with automatic
turbine tester
All measures as Fault in valve or turbine tester. The turbine plant may be
prescribed in 5.2-0455 fail. operated with defective valve
for max.1 week.
If necessary, the output must
be reduced so that the limits
as prescribed in 5.1-0100 are
not exceeded.
Drain steam line upstream and
downstream of defective valve
thoroughly.
Observe limits for temperature
difference between parallel
steam supply lines.
Shaft assembly runs down
without lubricating oil
Fault in auxiliary and Check bearing metal
emergency oil pumps. temperatures, if impermissibly
Jacking oil pumps in high, inspect bearings.
operation
Fault in jacking oil Danger of bearing whipping.
pump(s). Check bearing metal
temperatures. Check bearings.
Fire or fire hazard during Set off fire alarm. Follow fire
operation protection rules. if
necessary, initiate fire
fighting measures.
At the same time:
Escape of control fluid Leakage in piping or other Press fire protection
turbine components pushbutton 1
or
Switch off sub-loop control for
the control fluid pumps
immediately and shut-down
(operating) pump (result:
turbine generator unit trips).
Escape of oil from the Leakage in piping or other Press fire protection
lubricating oil system turbine components pushbutton 2 (pressing fire
protection pushbutton 2
automatically initiate fire
protection 1 measures), result:
turbine generator unit trips.
5.2-0410-00/5
Fault Cause Remedy
Other symptoms
or
Shut down turbine generator
unit. Depressurize control fluid
system (measures as above).
Switch off sub loop control for
jacking oil pumps.
Start up jacking oil pumps.
Switch off subloop control for
auxiliary oil pump. If
necessary, shut down auxiliary
oil pump(s). Check to ensure
that subloop control cuts-in
emergency oil pump as oil
pressure drops. Close turning
gear oil valve. Reduce
condenser vacuum to shorten
coast down.
− Open vacuum breaker
− Stop air extraction from
condenser plant
− Allow air to enter
condenser plant
Shaft comes to a standstill Shut down DC lubricating oil
when fire protection pump. Keep jacking oil pump
measures are initiated in operation if no leakage from
the jacking oil system.
Turn shaft through 180 degree
at intervals of approx. 10
minutes. For treatment of
turbine after complete
standstill shaft see 5.2-0460.
Eliminate leak and perform
hydrostatic pressure test.
Acknowledge initiation of fire
protection measures.
Restart lubricating and control
fluid system.
Commence turning gear
operation.
Replace insulating materials
soaked with escaped fluid.
Start up turbine generator unit.
5.2-0410-00/6
Fault Cause Remedy
Other symptoms
Fire or fire hazard during Set off fire alarm.
turning gear operation
Follow fire protection rules.
If necessary, initiate fire
fighting measures.
Escape of control fluid Leakage in piping or other Measures as for fire or fire
turbine components hazard during operation.
Escape of oil from the Leakage in piping or other Jacking oil pump stays in
lubricating oil system turbine components operation.
Close turning gear oil valve.
Switch off sub-loop control for
auxiliary oil pumps.
Shut down auxiliary oil pumps.
Check to ensure that, sub-loop
control cuts in the lubricating
oil pumps as oil pressure
drops. For further measures
see: Fire or fire hazard during
operation.
Escape of oil from the Leakage in piping or other Shut down jacking oil pump
jacking oil system turbine components (risk of bearing damage is
minor if turning gear stays in
operation).
Isolate and eliminate leak.
Start up jacking oil pump.
Lubricating or control fluid
loss annunciated by level
monitoring circuit
Separate control fluid The system must be checked
system immediately for leakage if this
Alarm: fluid level low or very alarm is generated in rapid
low (2-out-of-3) succession. A leak must be
assumed and appropriate fire
protection measures taken.
Oil system The system must be checked
Alarm: oil level low immediately for leakage if this
alarm is generated.
Oil system
Turbine trip due to oil level Fire protection measures
very low (2-out-of-3) initiated automatically.
Note: The trip system is
inoperative during turning gear
operation.
5.2-0410-00/7
Fault Cause Remedy
Other symptoms
Escape of steam Leakage in piping or other Isolate steam leakage area
turbine components immediately and depressurize
system concerned, if possible.
If there is a rupture hazard
(pre-rupture leak), shut down
turbine generator unit
immediately.
Carefully consider risk of
erosion at sealing surfaces
and decide on time of shut
down.
5.2-0410-00/8
Steam Turbine Vibration
Operation Fault Tracing
Despite all design, manufacturing and manufacturer to determine its cause and
erection measures to prevent it, excessive effective measures to be taken to combat it.
vibration can occur and because the various So, it is difficult to give a complete list of
kinds of vibrations are intermingled, the possible causes and proper corrective action
reasons for it are difficult to isolate. to be taken, in this instruction.
If excessive vibration occurs, it is necessary The following data refers to the
to carryout extensive tests together with the characteristics, causes and remedial actions
pertaining to some typical type of vibration.
5.2-0420-00/2
Fault Cause Remedy
Other symptoms
Final corrective action: Stress
relieving, thermal stabilisation
and balancing at
manufacture’s works, if runout
is more.
Temporary increase in Temporary shaft distortion due Reduce speed, load and/or
vibration during non steady to temporary non-uniform rate of change of temperature.
state operating conditions temperature distribution during
Wait until vibration improves
(startup, loading and temperature changes.
when steady state conditions
unloading, main steam
are reached.
temperature changes etc.)
5.2-0420-00/3
Fault Cause Remedy
Other symptoms
After, each variation there
must be a delay for steady
state conditions.
Check the following operating
parameters and conditions:
- Speed
- Active load
- Reactive load
- Valve lift
- Steam temperatures
- Casing temperatures
- Steam pressure
- Oil temperatures
- Bearing metal temperatures
- Casing expansion
- Thrust bearing position
- Shaft eccentricity
Check turbine casing and
bearing housing for:
- Freedom of spacing
washers
- Seating and freedom of
expansion of casing palms
- Freedom of movement for
bearing housings
- Freedom of movement for
piping
Note: Changes in vibration
characteristics due to changes
in temperature usually occur
slowly and at a constant rate.
Increased vibration during Warm-up speed near a critical. Change the warm-up speed
warm-up. within permissible ranges.
Increased vibration during Increased vibration while Pass through critical speed
turbine acceleration. passing critical speeds. ranges rapidly.
Vibration is normal at rated
speed.
Increased vibration during Distortion remaining from an Reduce turbine speed to less
turbine acceleration. No interruption of turning gear than 400 rpm. and eliminate
improvement in vibration at operation before start-up. shaft distortion before
rated speed. increasing speed.
5.2-0420-00/4
Fault Cause Remedy
Other symptoms
Vibration is related to load Bearing loading too low. Increase bearing loading by
and valve lift. changing the alignment.
Vibration related to Bearing clearance excessive Change oil temperature
lubricating oil temperature
Changes in damping
changes.
properties due changes in
viscosity.
5.2-0420-00/5
Steam Turbine Bearing Temperature
Operation Fault Tracing
After load reductions, ∆θ + Steam backflow or entry of Open drain valves in extraction
water into turbine through lines; test functioning and leak-
extraction lines tightness of extraction valves.
Take measures at the feed
water heaters to prevent back
flow.
During power operation, Casing temperatures affected Check condition and measure
∆θ + / - by leaks in sealing elements clearances at sealing elements
inside the turbine during overhaul and refit or
replace leaky elements as
necessary.
notify manufacturer and ask to
calculate if turbine can be
operated at higher temperature
differentials for the time being
During start-up, ∆θ - Casing or steam lines not Check position of drain valves,
properly drained open any close drain valves.
During start-up, ∆θ + Drain valves still open too Close drain valves further or
wide, causing uneven steam completely.
flow through turbine
During standstill or turning Uneven cooling due to air Start turbine very carefully;
gear operation, ∆θ + currents within the foundation wait until the steam admitted
or inside the turbine begins to reduce temperature
differentials before running up
to rated speed.
Casing temperature
differentials excessive
In any operating mode Coast down turbine
(additional turbine immediately by tripping;
protection not operative) observe coast down; record
coast down time.
Turbine generator comes Carefully try to turn shaft
to standstill after coast system using manual shaft
down ( in turning gear turning device.
operation)
Warning: Do not rotate the
shaft system forcibly.
Wait until temperature
differential has fallen to
permissible level; set turning
device in operation.
5.2-0423-02/2
Steam Turbine Turbine Stress Controller
Operation Measures to Avoid Impermissible
Operation
Limitation by TSC Stop valves opened at too high Check whether warm-up
admission monitoring a pressure. valves (drains) between stop
channel by TSC detector in and control valves are closed;
control valve during warm- if not, close-warm up valves;
up of the main steam line wait for sufficient margin
and the main steam valves before re-opening warm-up
immediately after opening valves. If margin is negative,
of the stop valves. repeatedly open and close the
main steam stop valves.
General rule: If main stem
temperature can be reduced
when margins narrow, this
should be done in order to
avoid prolonging warm-up.
Limitation by TSC turbine Steam already entering the Both the admission channel
monitoring channel during turbine, causing reduction of and the turbine channel must
warm-up of the main the margin. be observed and step must be
steam line. taken to avoid reduction of
margin; retard temperature
increase up-stream of turbine
by throttling the warm-up
valves (drains) between stop
and control valves.
Limitation by TSC turbine Turbine is being warmed up Reduce supply steam flow by
monitoring channel during too quickly. closing the control valves by
warm-up in wait step below means of the speed set point
critical speed range. controller or the starting and
load limit device.
Limitation by TSC turbine Increase in steam flow during The influence of the TSC on
monitoring channel during acceleration of turbine the set-point controller reduces
turbine run-up to rated diminishes margin. the speed gradient or, at a
speed. certain margin, caused the
speed gradient to tend
towards 0.
A certain TSC margin
(determined empirically) must
be available before the turbine
generator until is run up to
rated speed.
Operation of the turbine
generator unit at constant
speed within the critical speed
range is inadmissible.
The control valves must
therefore be closed and the
turbine generator must be
warmed up at a speed below
the lower boundary of the
critical speed range specified
in the Technical Data 5.1-011..
until an appropriate TSC
margin is available.
The turbine generator unit is
automatically run down to the
set warm up speed by means
of the gradient monitor as soon
as a certain permanently set
minimum speed gradient is not
attained.
5.2-0430-01/2
Fault Cause Remedy
Other symptoms
Margin for IP turbine Warm up operation does not Automatic and/or manual
reduced; temperature of IP warm up the IP turbine measures as above.
turbine low; reheat sufficiently to prevent reduction
temperature high. of the margin. Proper adjustment of the
reheat temperature within the
limits permitted by the steam
generator is recommended.
If the turbine generator unit
can be run up to rated speed,
wait for IP turbine to warm up
sufficiently at rated speed
before synchronizing the
generator, since further margin
reductions are to be expected
when the unit goes on load if
the IP turbine has not been
warmed up sufficiently.
Limitation by TSC turbine Steam flow too high in relation The influence of the TSC on
monitoring channel during to turbine temperature the setpoint controller reduces
power operation. conditions. the speed gradient and/or the
turbine load is reduced and the
generator is possibly
disconnected from the grid by
the reverse power protection
relay.
5.2-0430-01/3
Fault Cause Remedy
Other symptoms
5.2-0430-01/4
Fault Cause Remedy
Other symptoms
5.2-0430-01/5
Steam Turbine Stop and Control Valves
Operation Fault Tracing
Change in mutual
relationship of control valve
travels
Steady-state operation Many causes possible As above
Restriction in movement of Less clearance between valve Maintain required clearance
valve stem cone & bush between valve cone & bush by
machining ID of bush
Slightly reduce the tightening
Excessive tightening of glands of the glands of the valves
of the valve
5.2-0440-01/2
Steam Turbine Protective Devices
Operation Fault Tracing
5.2-0450-01/2
Fault Cause Remedy
Other symptoms
Check temperature in
extraction lines.
Rapid temperature drops after
load rejection are probably due
to extraction check valves
leaking.
Electrical low vacuum trip Loss of condenser vacuum Identify the cause of
responded condenser vacuum loss.
Fault in circulating water Check circulating water
supply pumps. Check flow of
circulating water through
condenser.
5.2-0450-01/3
Fault Cause Remedy
Other symptoms
Turbine trip started via Trip by fire protection system See 5.2-0410
electrical signal from the
fire protection system
Both overspeed trips fail to Overspeed trip jammed or Repeat testing by test oil
operate during over speed fouled pressure several times until
testing turbine trip starts at normal test
oil pressure values.
Attention : Normal trip speed
must not be exceeded by more If the defective overspeed trip
than 2% still does not operate
satisfactorily, operation of
turbine generator unit must not
been continued.
Trip devices jammed. Locate and repair fault
Incorrect speed reading immediately.
5.2-0450-01/4
Fault Cause Remedy
Other symptoms
One over speed trip fails to Jammed or fouled Perform testing by test oil
operate during over speed pressure.
testing
Staggering of overspeed trip If testing by test oil pressure
settings reveals that the two overspeed
trips respond at slightly
staggered settings, no further
action is necessary.
Over speed trip operates Turbine generator unit speed Check speed indicator.
at too high a test oil too low when generator not (Compare frequency of excited
pressure when tested by synchronized generator system frequency by
test oil pressure means of synchronizing
device).
Correct speed
Adjust speed indicator.
Movement of over speed trip Repeat testing by test oil
mechanism impaired pressure several times until
turbine trip operates at the test
oil pressure values previously
measured.
Leak in test-oil line inside the Check test oil line at next
bearing pedestal opportunity.
Over speed trip fails to Cause of maloperation may be Adjust test oil pressure.
operate when tested by too high a test oil pressure
test oil pressure
Movement of overspeed trip Increase speed with generator
mechanism impaired unsynchronized and perform
test. If the defective over
speed trip still does not
operate satisfactorily,
operation of the turbine
generator device must not be
continued until fault has been
corrected.
Overspeed trip operates at Turbine generator unit speed Check speed indicator (for too
too low a test oil pressure too high when generator not high a trip speed)
synchronized
5.2-0450-01/5
Fault Cause Remedy
Other symptoms
5.2-0450-01/6
Fault Cause Remedy
Other symptoms
In the fire protection system Fault in signal path Check signal path and
test, one or more fire control devices.
or
protective devices do not
Correct fault or inform and
operate automatically. Device malfunction
instruct shift personnel that fire
protective device must be
manually operated if a fire
occurs.
5.2-0450-01/7
Steam Turbine Automatic Turbine Tester
Operation Fault Tracing
5.2-0455-00/2
Fault Cause Remedy
Other symptoms
the criteria for turbine trip are Check criteria that caused trip
fulfilled. to make trip conforms to
protection concept.
Locate and remove fault in
Automatic Turbine Tester if trip
was caused by wrong test
procedures.
Running of protective
devices test program
interrupted, program
stopped in faulted program
step
Several annunciation show Fault in electronic circuitry of Test circuit remains in force.
fault in electronic circuitry Automatic Turbine Tester.
Protection of the turbine is
of Automatic Turbine
ensured for the duration of this
Tester
fault by the protective
equipment operative during
testing.
Call in maintenance personnel
for the electronic equipment of
the Automatic Turbine Tester
to repair faults as described in
the ATT manual.
5.2-0455-00/3
Fault Cause Remedy
Other symptoms
Circuit breaker of test motor, If a circuit breaker has tripped,
solenoid valve, or other actuate test equipment or
electrical equipment tripped. valves locally to restore normal
operating condition.
Identify and remove cause of
fault in power supply as
described in the Automatic
Turbine Tester manual.
Fault during reset program
after testing of protective
devices
Program stopped, Position of protective and test Check position of test or
changeover valve in test devices incorrect due to protective devices locally and
position electrical or mechanical faults. return to operating position by
hand, if necessary.
− Test signal transmitter for Move test signal transmitter for
overspeed trip not in overspeed trip into normal
operating position, e.g. operating position by hand.
because miniature circuit
breaker tripped.
− Main trip valve or trip Actuate contactor for
device not in operating approximately 10s to return
position. main trip valve or trip device
to normal operating position.
If normal operating position
cannot be restored, there is a
mechanical or hydraulic fault
(e.g. jamming of solenoid
valves, worn latching edges,
oil pressure too low for
latch-in) that must be
corrected.
False electrical signals due to Check monitoring equipment
faults in monitoring elements and signal paths.
(pressure switches, position
Check valves of pressure
transmitters, etc.). This type of
switches (desired status:
fault is present if devices are in
open).
operating position but no
checkback signal is generated. Check circuitry of position
transmitter; correct setting if
Incorrect operation of necessary.
protective device during
testing
Trip solenoid valves for Fault in electrical operation or Testing of protective devices is
protecting the turbine mechanical fault in solenoid not permissible if this fault
testing are not actuated. valves. occurs, the test will be
5.2-0455-00/4
Fault Cause Remedy
Other symptoms
Incorrect operation of prevented by the electronic
monitoring equipment circuitry.
− Operating fault Check trip signal.
− Fault in solenoid valves Check operation.
Check power supply.
Check solenoid.
Check freedom of valve
movement.
− Fault in monitoring Check valves of pressure
equipment switches (desired status:
open).
Vent pressure switch.
Check signal path of
checkback signal.
Check functioning of faulted
pressure switch.
Replace pressure switch.
Failure of remote trip Fault in electrical operation or The protection of the turbine
solenoids mechanical fault in solenoid generator unit is not fully
valves. guaranteed.
Incorrect operation of The turbine must be shut down
monitoring equipment unless the fault can be cleared
during operation (e.g. by
switching on the power
supply).
- Fault in operation Check signal path for
formation of trip signal.
Check operation.
- Fault in solenoid valves
Check power supply.
Check freedom of movement
of valve.
- Fault in monitoring Check valves of pressure
equipment switches (desired status:
open).
Vent pressure switch.
Check signal path of
checkback signal.
Check functioning of faulted
pressure switch. If necessary
replace pressure switch.
5.2-0455-00/5
Fault Cause Remedy
Other symptoms
Main trip valves fails to Fault in protective device See trouble shooting
operate instructions for protective
devices.
Main trip valve jammed Turbine generator unit must
not remain in operation.
Fault may be corrected
immediately.
Fault in monitoring equipment Check valves of pressure
switches (desired status:
open).
Check position transmitter,
reset if necessary.
Overspeed trips fail to Actuation fault in test device or Take action if incorrect
operate (running time incorrect operation of operation of the overspeed
exceeded) overspeed trip. trips occur.
See instruction: Protective
Devices. Troubleshooting:
5.2-0450.
Actuation fault in test signal Check if the test signal
transmitter transmitter operates during
test.
Fault in power supply If the test signal transmitter
does not operate, check power
supply and motor.
Check actuation.
Overspeed trips operate at Limit switch of test signal Correct setting of limit switch.
normal test oil pressure, transmitter incorrectly set.
but after test signal
transmitter has reached its
limit position.
5.2-0455-00/6
Fault Cause Remedy
Other symptoms
Check overspeed trip setting
by precise oil pressure testing
or actual overspeed test.
Check setting.
Low vacuum trip operates Incorrect operation of low For consequences and steps
too late (at too low a vacuum trip device to be taken, see instruction
vacuum) 5.2-0450.
Check condenser vacuum
where trip device operates.
Repair mechanical fault or
correct setting.
Low vacuum trip operates Incorrect operation of low Availability of turbine generator
too early (at too high a vacuum trip device unit may be reduced due to
vacuum) annunciation premature tripping.
only, no interruption
Check condenser vacuum
where trip device operates.
Repair mechanical fault or
correct setting.
5.2-0455-00/7
Fault Cause Remedy
Other symptoms
Incorrect operation of
valves during testing
Stop valve fails to close Control valve not closed
- Fault in valve test Check power supply and motor
positioner or its actuation of valve test positioner.
Check actuation circuitry.
Stop valve fails to open Fault in operation of solenoid Check operation solenoid
valves.
Open stop valve with test
valve.
Locate fault in operation.
Check power supply and
solenoid as soon as
downstream valves are closed.
5.2-0455-00/8
Fault Cause Remedy
Other symptoms
Stop valve opens abruptly Jamming of valve positioner Locate fault immediately and
repair valve.
Control valve or other valve Close valve downstream of
downstream of stop valve stop valve.
open
Identify why control valve was
open (step sequence, step
criteria).
Locate fault and repair.
5.2-0455-00/9
Steam Turbine Oil System
Operation Fault Tracing
Foaming on oil surface of Foaming during startup due to Introduce waiting period
oil tank simultaneous release of air between closure of turning
trapped in the oil and air gear oil valve and run-up of the
entrained in the system as a turbine.
result of temperature increase
Check oil level and correct by
in the oil tank.
topping up or draining.
Water content Entry of steam vapour into oil Remove water from oil system
system by separation or draining.
Check vapour pressure in
bearing pedestals.
Locate cause of excessive
leak-off steam from shaft seals
and repair.
Oil level in oil tank low
During rated speed Normal oil loss (oil level drops Top up with oil of the same
operation slowly) make and type.
High oil loss Examine system for leaks. If a
large leak occurs, unload
turbine generator immediately
and/or initiate fire protection
measures. Examine oil coolers
for punctured tubes.
Plug leaky tubes.
During rated speed or Oil builds up in return Open oil tank cover
turning gear operation compartment due to choked
Check strainer and if heavily
strainer.
choked, change strainer and
clean.
Examine residues in strainer.
Oil pressure low
In pressure oil system Normal procedure Observes start up of auxiliary
during shut-down of oil pump.
turbine generator unit
If subloop control fails, start
auxiliary oil pump manually
from control desk.
In pressure oil system Main oil pump is not taking See incorrect operation of
immediately after rated over oil delivery. main oil pump.
speed has been reached
Check for leakage through Check pressure downstream
valve downstream of auxiliary of auxiliary oil pumps and
oil pump. pumps for reverse rotation.
Start up and shut down
auxiliary oil pumps with
defective valve once more.
Shut down turbine generator
and ensure freedom of check
valve movement by alternating
auxiliary oil pumps.
Overhaul check valve.
Turning gear oil valve still open Close turning gear oil valve
from control desk or locally by
hand.
5.2-0460-00/2
Fault Cause Remedy
Other symptoms
In pressure oil system Oil level too low Check oil level in oil tank.
during rated speed
Top up if necessary.
operation
Main oil pump faulty Check main oil pump.
Air content of oil too high Examine air release capability
(ARC) (joint investigation by
operator, oil supplier and
turbine manufacturer).
In lubricating oil system on Filter not filled and vented Check bearing metal
filter changeover before changeover temperatures.
Check bearings after
temperature increase.
In lubricating oil system on Standby oil cooler not filled Measures as for pressure loss
oil cooler changeover and vented before changeover on filter changeover.
Warning: Danger of bearing
damage is considerably
greater than with improper
filter changeover.
Main oil pump does not take Oil level in tank low See faults: Oil level low
over oil supply on startup
Air content of oil too high See faults: Oil properties
inadequate
Main oil pump faulty Check main oil pump.
Turbine sped may be
temporarily raised to force
main oil pump to take over.
Oil temperature high
During rated speed No flow of cooling water Check positions of cooling
operation after startup through oil cooler in service water isolating valves for oil
(malfunction can also occur on cooler in service. Open if
oil cooler changeovers) closed or throttled.
5.2-0460-00/3
Fault Cause Remedy
Other symptoms
During startup and power Oil cooler not vented on oil Check vents.
operation side or cooling water side.
Cooling water inlet Look for cause of cooling
temperature too high. water temperature increase
and correct.
Oil cooler choked on cooling Changeover oil cooler.
water side.
Note: Follow changeover
instructions
Clean choked oil cooler.
Oil temperature low
During shut-down of Oil temperature control valve Close oil temperature control
turbine generator unit not closed. valve.
During rated speed Oil temperature controller Close oil temperature control
operation after startup faulty. valve manually.
Turning gear oil valve Radial clearance bridged by Let turbine cool down.
open, Jacking oil pump on. casing or rotor distortion.
Jacking oil pump must be
Differential temperature on
operating.
one casing > limit
temperature. Warning: Do not rotate the
shaft system forcibly.
or
Turbine generator unit shut Rubbing of rotor due to Check bearing and replace.
down due to high bearing damage of bearing or shaft
metal temperature. journal in bearing not jacked.
5.2-0460-00/4
Fault Cause Remedy
Other symptoms
5.2-0460-00/5
Fault Cause Remedy
Other symptoms
Seal steam pressure high, Seal steam pressure set point Lower set point
no fault in valve or too high
controller functions
5.2-0460-00/6
Steam Turbine Control Fluid System
Operation Fault Tracing
High water content Water entering via cooler Change over to other control
fluid cooler; determine cause
of water entry.
Air release property Take measures as for rise in
diminished neutralization number.
Control fluid pressure low Pump faulty Check control fluid pumps.
Change over to standby pump
or observe start up of standby
pump.
Temperature at heater Control fluid heater overheated Switch off control fluid heater
protective tube high
5.2-0470-00/2
Fault Cause Remedy
Other symptoms
Leakage of oil or oil and Diaphragm damaged on the Repair leak
control fluid at the trip control fluid side, danger of
mechanisms of the over turbine trip. If both oils are
speed governor or the leaking, danger of control fluid
shaft position monitor. mixing with oil.
5.2-0470-00/3
Steam Turbine Gland Steam System
Operation Fault Tracing
Electrical fault
Valves Many causes possible Determine problem on the
basis of valve description
and correct.
Control system Many causes possible Determine cause on the
basis of instrumentation and
control manual and correct.
Reheat pressure < Constant pressure setpoint too Lower constant pressure
constant pressure setpoint high. setpoint.
but > variable pressure
setpoint.
Reheat pressure > Fault in control
Check fault annunciation in
constant or variable
control cabinet.
pressure setpoint.
Interlocks ineffective Attend fault as described in
bypass control manual.
Shut down control until fault is
attended, and control the
reheat pressure manually.
Bypass stop and control
valves close during bypass
operation
Reheat pressure > Injection water interlock
constant pressure setpoint effective.
5.2-0490-00/2
Fault Cause Remedy
Other symptoms
Limit pressure control gear Locate and attend fault in
opens: fault in pressure pressure switch.
switch.
If only one of the hydraulic
condensate pressure
monitoring channels is faulty,
the faulty channel may be
blocked and bypass operation
continued.
Attention: No redundant
pressure monitoring effective:
use other criteria, e.g. bypass
steam temperature, to asses
injection water flow rate.
Attend fault as soon as
possible.
Reheat pressure > Fault in interlock elements for
constant pressure setpoint. loss of condenser vacuum.
Condensate pressure
Diaphragm of limit Replace diaphragm;
normal.
pressure control gear
damaged.
Diaphragm of bypass Replace diaphragm.
condenser safety device
damaged. Close cutoff valve upstream of
measuring element.
Insert lever and lock.
Replace diaphragm.
In this case bypass operation
may be continued for the
duration of the repair.
Reheat pressure > Fault in interlock elements for Check temperature measuring
constant pressure setpoint. high bypass steam instrument circuit, actuators of
Bypass steam temperature temperature. solenoid valves and attend
normal. fault.
5.2-0490-00/3
Steam Turbine In-Service Maintenance
Maintenance Introduction
Frequency
h = hourly
Parameter
d = daily
Activity Work to be performed measured Remarks
w = weekly
No. or tested
m = monthly
y = yearly
1.0 Testing of Tests according to:
1.1 Controllers Functioning Ref. 5.2-0021 5.3-0030
& setting 5.3-0035
1.2 Automatic Turbine Tester Functioning Ref. 5.2-0022 5.3-0060
& 5.2-0023 5.3-0061
1.3 Protective devices Functioning Ref. 5.2-0024 during start up,
& setting power operation,
1.4 Safety devices Functioning Ref. 5.2-0025 shut down & stand
& setting still
1.5 Valves Functioning Ref. 5.2-0026
free movement
leak tightness
1.6 Monitoring devices Functioning Ref. 5.2-0027
setting and
accuracy
5.3-0010-04/2
Frequency
Parameter h = hourly
Activity Work to be performed measured d = daily Remarks
No. or tested w = weekly
m = monthly
y = yearly
10.0 Inspection of hydraulic
accumulator
10.1 Check charge pressure 2w
5.3-0010-04/3
Steam Turbine Maintenance Schedule
Maintenance Turbine
Frequency
h = hourly
Parameter
d = daily
Activity Work to be performed measured Remarks
w = weekly
No. or tested
m = monthly
y = yearly
1. Cleaning of sliding Visual 1m
surfaces inspection
casing supports
spacer bolts and discs
for bearing pedestals and
turbine casings
2. Cleaning of turbine blading measurement as indicated by The criteria
by flushing through with of ηi criteria indicating stage
saturated steam as pressure when
prescribed in 5.3-0070 saturated steam
flushing is
necessary are the
internal efficiency
ηi and the stage
pressures
3. Preservation of turbine relative continuous During shutdowns
using air drying equipment humidity in lasting longer than
as prescribed in 5.2-0360 turbine < 50% 1 week
4. Lubrication of components as prescribed in
of the turbine control and 5.1-0690
turbine protection systems
5. Tightening of turbine 1m
control valve packings
6. Tightening of valve stem 3m or in the
seals event of
leakages
7. Lubrication of valve stems as prescribed
5.1-0690
Oil System
Frequency
h = hourly
Parameter
d = daily
Activity Work to be performed measured Remarks
w = weekly
No. or tested
m = monthly
y = yearly
1. Cleaning of filters and
strainers
Switch over duplex filters ∆ p across as indicated by
and clean fouled filter filter criteria, max 6m
cartridges as prescribed
in 5.1-1130
Turn plate-type filters d
through two three
revolutions as
prescribed in 5.1-1 120
Clean plate-type filters 6m -1y during
appropriate
shut-downs and
overhauls
Replace filter papers in ∆ p across as indicated by
fine mesh filter filter criteria, max 6 m
Change oil tank oil level in as indicated by during
strainers, clean chocked bucket criteria, appropriate
strainers as prescribed strainers max. 6m - 1y shut-downs and
in 5. 1-1 010 overhauls
Clean wire mesh of oil 6m
stripper
2. Cleaning of oil using solid or liquid continuous, as
centrifuge foreign matter indicated by
in oil criteria
3. Cleaning of centrifuge as deposits in 1m as
specified by the centrifuge indicated by
manufacturer criteria
4. Cleaning of oil tank after deposits in oil 3 -4 y during overhauls
draining oil tank
5. Maintain oil tank level at level in oil tank 1 d (check),
service level; top up with topping up as
oil of same make and indicated by
properties criteria
6. Draining of water from the water collecting as indicated by establish cause
oil tank on oil tank criteria of water
bottom accumulation
5.3-0022-01/2
Seal steam system
Frequency
Parameter h = hourly
Activity Work to be performed measured d = daily Remarks
No. or tested w = weekly
m = monthly
y = yearly
1. Change of control fluid for 1y
seal steam control valve
actuators as prescribed in
5.1-0690
2. Filter change for seat 1y
steam control valve
actuators as prescribed in
its manual
3. Lubrication of vapour as specified by
exhaust fan motors motor
manufacturer
4. Lubrication of vapour as prescribed by
exhaust fan bearings fan manufacturer
5. Lubrication of valve stems 3m
at the lubrication points as
prescribed in 5.3-0081
6. Tightening of valve stem 3m or in the
seals event of leakages
Drains
Frequency
Parameter h = hourly
Activity Work to be performed measured d = daily Remarks
No. or tested w = weekly
m = monthly
y = yearly
1. Oil or grease change in as specified by
drain valve actuators actuator
manufacturer
2. Lubrication of drain valve 3m
stems at the lubrication
points provided as
prescribed in 5.3-0081
3. Tightening of drain valve 3m or in the
stem seals event of leakages
4. Check on drain line sludge 1 -2y
traps
5.3-0022-01/3
Steam Turbine Maintenance Schedule
Maintenance FRF system
Frequency
h = hourly
Parameter
d = daily
Activity Work to be performed measured Remarks
w = weekly
No. or tested
m = monthly
y = yearly
1. Cleaning of filters ∆ p across filter
and strainers
Switch over duplex
filters; and clean fouled
filter cartridges as
prescribed in 5.1-1130
Turn plate-type filters d
through two three
revolutions
Clean plate-type filters 6m -1y during appropriate
shut-downs and
overhauls
5.3-0023-01/2
Steam Turbine Testing during Start-up
Maintenance
Main trip valves in o Starting and load limit devices not in 0% position
operating Position
o Test valve of stop valve in left-hand end position
o Stop valves open
(1) Bring starting and load limit device into 0%
position
• Main trip valve in operation position
(2) Bring starting and load limit device into 40%
position
• Main trip valve in operating position and ready to
trip
• Stop valves open
5.3-0030-02/2
Equipment tested o Preconditions Date
o Type of test () Test Step Result
• Result Tested by
(3) Switch auxiliary oil pump 1 subloop 1control to
Manual
(4) Switch auxiliary oil pump 1 off
• Auxiliary oil pump 2 on
• System oil pressure present
5.3-0030-02/3
Equipment tested o Preconditions Date
o Type of test () Test Step Result
• Result Tested by
Auxiliary Oil pumps
o Speed-dependent o Turbine generator unit speed = rated speed
cutout when rated
(1) Verify cut out of auxiliary oil pump
speed is reached
Jacking oil pumps
o Speed-dependent on o Shaft at standstill
command of AC
o Jacking oil pumps off
jacking oil pump from
subloop control before o Subloop controls on Manual
starting turning
(1) Switch AC jacking oil pump subloop control to
gear operation
Auto
• AC jacking oil pump on
• Jacking oil pressure present
(2) Switch AC jacking oil pump subloop control to
Manual
(3) Switch AC jacking oil pump off
• AC jacking oil pump off
• Jacking oil system depressurised
5.3-0030-02/4
Equipment tested o Preconditions Date
o Type of test () Test Step Result
• Result Tested by
(2) Switch DC jacking oil pump subloop control to
Manual
(3) Switch DC jacking oil pump off
• DC jacking oil pump off
• Jacking oil system depressurised
Jacking oil pumps
o Operational readiness o Shaft at stand still
of Jacking oil
o Jacking oil pumps off
pumps
o Subloop controls on Manual
(1) Switch jacking oil pumps in turn to Manual on
• Jacking oil pressure present
Control fluid pumps
o Pressure-dependent o Control fluid system depressurised
on command from
o Control fluid pumps off
subloop control
o Subloop control on Manual
(1) Select one control fluid pump (e.g. pump 1)
(2) Switch subloop control to Auto
• Control fluid pump 1 on
• Control fluid system pressure present
(3) Select control fluid pump 2
(4) Switch control fluid pump 1 off
• Control fluid pump 2 on
• Control fluid system pressure present
(5) Switch subloop control to Manual
(6) Switch control fluid pump 2 off
• Control fluid system depressurised
• Control fluid pumps off
Control fluid pumps
o Operational readiness o Control fluid system depressurised
(Testing not required
o Control fluid pumps off
if subloop controls
have already been o Subloop control on Manual
successfully tested)
(1) Switch control fluid pumps in turn to Manual on
• Control fluid system pressure present
5.3-0030-02/5
Equipment tested o Preconditions Date
() Test Step Result
o Type of test
• Result Tested by
Stop valves
o Leak test o Main steam pressure present upstream of stop
valves
o Stop valves closed using test valves
(1) Open control valves
• No speed increase
(2) Bring back test valves to operating position
Control valves
o Leak test o Control valves closed using motorised actuator
o Main steam pressure present upstream of turbine
(1) Open stop valves
• No abnormal speed increase
(2) Bring back motorised actuator to open position
Overspeed trip
o Oil injection test o Turbine speed < 2970rpm or
o Unit in low-load operation
(1) Release testing device for operation
(2) Press and hold down test valve for inhibiting trip
(left-hand valve)
(3) Turn handwheel of hydraulic test signal
transmitter to right until test oil circuit is
pressurised
(4) Observe oil pressures where overspeed trip
device operates
• Auxiliary trip circuit depressurised
5.3-0030-02/6
Equipment tested o Preconditions Date
() Test Step Result
o Type of test
• Result Tested by
5.3-0030-02/7
Steam Turbine Testing during Power Operation
Maintenance
Bypass control
o Functional test o Load approx. 50%
(1) Open HP bypass station slowly by operating
pushbutton on control panel
• Reheat pressure increases
• Injection water pressure present
• Bypass stop valves open
• Bypass control valves begin to open
(2) Close HP bypass station
• Reheat pressure drops
• Bypass control valves close
• Bypass stop valves close
• Injection water pressure reduced
Auxiliary and
emergency oil pumps
o Operational readiness o Auxiliary and emergency oil pumps off
test
(1) Auxiliary pumps subloop control off
(2) Auxiliary oil pump 1 Manual on
• Pressure buildup downstream of pump
(3) Auxiliary oil pump 1 Manual off
(4) Auxiliary oil pump 2 Manual on
• Pressure buildup downstream of pump
(5) Auxiliary oil pumps 2 Manual off
(6) Auxiliary oil pumps subloop control on
(7) Emergency oil pump Manual on
• Pressure buildup downstream of pump
(8) Emergency oil pump Manual off
Control fluid pumps
o Operational readiness o Service control fluid pump on
test
(1) Stand-by control fluid pump Manual on
• Pressure buildup downstream of tested pump
(2) One control fluid Manual off
5.3-0035-02/2
Equipment tested o Preconditions Date
o Type of test () Test Step Result
• Result Tested by
Main trip valves
o Ease of movement o Automatic turbine tester available
test
(1) Select and start test program for one protective
device
• Main trip valves respond
• No fault annunciations on automatic turbine tester
Remote trip solenoids
o Functional test o Automatic turbine tester available
(1) Select and start Remote trip solenoids test
program
• Main trip solenoid respond
• No fault annunciations on automatic turbine tester
Overspeed trips
o Functional test and o Automatic turbine tester available
testing of setting
(1) Select and start Remote trip test program
• Overspeed trips respond
(2) If ATT annunciates fault repeat overspeed trip
test
Overspeed trips (1) Release hydraulic test signal transmitter
o Manual functional test (2) Depress left-hand piston of hydraulic test signal
and testing of setting transmitter to limit and hold down
(3) Increase test pressure using handwheel of
hydraulic test signal transmitter
o Overspeed trip(s) respond(s)
(4) Ascertain pressure at which trip(s) respond(s)
and record
(5) Reduce test pressure using handwheel of
hydraulic test signal transmitter
(6) Depress right-hand piston of hydraulic test signal
transmitter to limit
• Auxiliary trip pressure builds up
(7) Release right-hand piston of hydraulic test signal
transmitter
(8) Release left-hand piston of hydraulic test signal
transmitter
5.3-0035-02/3
Equipment tested o Preconditions Date
o Type of test () Test Step Result
• Result Tested by
5.3-0035-02/4
Equipment tested o Preconditions Date
o Type of test () Test Step Result
• Result Tested by
Alarms
o Functional test o Alarms generated
(1) Record alarms generated
Speed indicator (1) Compare with grid frequency
Important operating
values
o Recording (1) Record important operating values in accordance
with 5.3-0036 & 5.3-0037
Drains
o Leak test (1) Test temperature condition of drain values
5.3-0035-02/5
Steam Turbine Acquisition and Archiving
Maintenance of operating data
Procedural Instruction
5.3-0037-03/2
Table – 1
5.3-0037-03/3
Steam Turbine Remedial Actions for
Maintenance off-normal operating conditions
Turbine
Main steam pressure > Pmax Increase turbine load or reduce In-service correction
(Long-term) steam generator output
Main/reheat steam Reduce main / reheat steam In-service correction
temperature > θmax (long- temperature
term)
Main / reheat steam Raise main / reheat steam In-service correction
temperature < θdesign temperature
Steam pressure ahead of Reduce turbine load until pressure In-service correction
turbine blading > Pmax (long- ahead of turbine blading < Pmax
term) (long-term)
5.3-0040-01/2
Oil system
Oil system pressures < pnormal Perform examinations and checks Check and remedial
as prescribed in 5.2-0460 and take actions may in many
appropriate action cases be performed
during operation;
otherwise shut down
plant and perform repairs
Lubricating oil pressure Change over filter and clean In-service maintenance
downstream of filter < Pnormal
Control fluid pressure Change over filter and clean or In-service maintenance
< Pnormal replace, or clean filter by rotating
filter plates
Oil temperature downstream Perform examinations and checks In-service checks and
of oil cooler > θnormal as prescribed in 5.2-0460 check maintenance
control system, if necessary
correct setpoint or repair
Check oil cooler vents;
check that no water is
being admitted to standby oil
cooler; check oil cooler for
chocking, where necessary
change over and clean
Oil level in oil tank < normal
- Slow change Top up with oil of same make and In-service check and
type maintenance
Locate leak and take appropriate In-service check and
- Rapid change
actions, e.g. initiate fire protection remedial action
measures
Oil level in tank strainer high Change and clean strainer Maintenance during
service or shut-down
Water collecting on oil tank Drain off water; separate water In-service maintenance
bottom from oil
Establish causes and eliminate Check and repair during
overhaul
Oil escaping at oil guard Check if oil vapour exhauster In-service check and
rings of bearing pedestals fan is in operation correction
Adjust throttle valves on bearing
pedestals
Check leak-tightness of oil tank
covers and if necessary reseal
Oil properties, e.g. air Perform additional oil In-service maintenance
separation capability and examinations; consult on
antifoaming, changed appropriate actions with oil
supplier and turbine manufacturer
5.3-0040-01/3
Control Fluid System
5.3-0040-01/4
Control System, Protective Devices
Control valve leaking Replace valve stem; rework seat Repair during overhaul
(internal steam leak)
Load shedding relay Repair load shedding relay In-service repair
defective
Faults in valves detected by
automatic turbine tester
- Running time exceeded Adjust limit switch In-service repair
during testing of stop and
control valves
Extraction swing check valve Repair position indicators In-service repair
position indicators defective
5.3-0040-01/5
Pumps and Piping
5.3-0040-01/6
Steam Turbine Measurement of
Maintenance internal Efficiency
Test Instructions
∆h
S1
∆hs P2
h2
T2
hs
Figure-1 : Steam conditions and enthalpies for calculating the internal efficiency of a
turbine cylinder
Notations:
∆h h1 - h2
Internal Efficiency in % = -------- x 100 = ----------- x 100
∆hs h1 - hs
Where,
Note: Values of h1, S1, h2 and hs are to be worked out from steam table.
5.3-0050-02/2
Determining the enthalpy Install precision thermocouples or use the
The enthalpies for the steam conditions operational instruments for temperature
measured in the reference plane at the measurement
turbine inlet and outlet are taken from steam Adjust the inlet steam conditions and the
table. control valve lift to the same values used
Calculating the internal efficiency for previous measurements
The internal efficiency of a turbine cylinder is Wait until turbine temperatures have
calculated with the ratio of the actual stabilized under steady-state operating
decrease in enthalpy to the isentropic conditions
decrease in enthalpy.
Measure and record the steam pressures
Trend of change in internal efficiency and temperatures
Trend of changes in internal efficiency can Use steam tables to determine the
be seen when the measurements are plotted enthalpies of the steam condition at the
versus time in a graph. turbine inlet and outlet
Calculate the efficiency
Measuring points and instruments
Compare the measured internal
When taking measurements for calculating
efficiencies with the values recorded
the internal efficiency of a turbine, the
previously or when the unit was new, and
measuring points should be in the same
evaluate
reference plane at the turbine inlet and
outlet as for the acceptance tests.
Duration of testing
The turbine is also provided with test
measuring points for installing precision For reliable measurement, arithmetic
instruments to measure pressures and averages of pressure & temperature
temperatures. measurements should be taken for at least
half an hour duration at stable load condition
Appropriate instruments can be installed in and rated steam parameters.
addition to the operational instrumentation
and used for taking necessary
Reasons for actual conditions deviating
measurements.
from reference condition
If the measurements are to be taken by Changes in internal efficiency can be due to
means of operational instrumentation one or more of the following reasons:
installed in the reference planes, the
instruments must be tested and calibrated Increased roughness of the blade
regularly in order to eliminate any surfaces due to a build-up of deposits,
inaccuracies due to problems such as drift. corrosion, or solid particle erosion
Increase in clearances in the blading flow
Measuring procedure path
The procedure for measuring the steam Increased tip clearance losses due to
pressures and temperatures and calculating seal strip wear
the internal efficiency of a turbine is as
follows: Bypass flow due to internal leaks
5.3-0050-02/3
Steam Turbine Testing during Shut-down
Maintenance
5.3-0060-01/2
Equipment tested o Preconditions Date
o Type of test () Test Step Result
• Result Tested by
5.3-0060-01/3
Equipment tested o Preconditions Date
o Type of test () Test Step Result
• Result Tested by
5.3-0060-01/4
Equipment tested o Preconditions Date
o Type of test () Test Step Result
• Result Tested by
5.3-0060-01/5
Steam Turbine Testing during Standstill
Maintenance
Introduction
Tests that demonstrate the proper Test performance
functioning of important components, must Take care to avoid any risks to people or
be performed during stand still of the turbine machines while performing tests.
generator unit.
Any simulated conditions necessary for the
The time intervals between tests are given in tests must be cancelled after completion of
a separate instruction [1]. tests.
Steam inlet valves may only be opened for
Test Procedures test purposes if the piping systems upstream
Test prerequisites, test activities and criteria of those valves are not under pressure and
in tabular form are intended to simplify the system concerned have been cleared for
testing. testing.
The tables are also suited to use as Test performance must be recorded.
checklists. Wherever no specific instructions If incorrect operation of the equipment being
are prescribed for a test, the test sequences tested occurs, take action establishing full
shown in the table are to be followed. operational reliability of the turbine generator
A number of tests require certain unit immediately. Pay attention to fault
components be in a definite position (e.g. tracing instructions.
main trip valves in operating position, stop
valves closed, etc.)
The operating sequence establishing certain
operating conditions is given in the form of Also refer to the following sections:
general instructions to avoid constant [1] 3-001x : Testing of turbine components
repetition in the tables of test sequences.
Turbine control
o Testing of setting o Main trip valves in operating position
Hydraulic amplifier
o Control medium temperature approx. 50 ºC
(1) Read and record setting data of control
system as a function of travel of starting
and load limit device (use starting and load
limit device to change auxiliary secondary
oil pressure by 0.1 – 0.2 bar per reading).
• Travel of starting and load limit device
• Travel of governor bellows
• Auxiliary secondary pressure
• Travel of converter (mm or %)
• Secondary pressures
• Travel of control valves
(2) Prepare curves from readings and compare
with curves of last adjustment by
manufacturer
(3) If comparison reveals major changes, have
them inspected and corrected by
manufacturer
5.3-0061-02/2
Equipment tested o Preconditions Date
o Type of test () Test Step Result
• Result Tested by
5.3-0061-02/3
Equipment tested o Preconditions Date
o Type of test () Test Step Result
• Result Tested by
Remote trip solenoids
o Functional test o Main trip valves in operating position
o Test valves of stop valves in closed
position
(1) Press pushbutton to start remote turbine
trip
• Trip initiated
Low vacuum trip
o Functional test and testing of o Condenser vacuum > response level
setting
or
o Test pump operating and simulated
condenser vacuum > response level
(1) Reduce condenser vacuum or increase
pump pressure
• Low vacuum trip responds
(2) Determine vacuum where trip started
Fire protection system
o Functional test o Shaft at standstill
o Normal operating conditions of oil system
established (exception : jacking oil pump
subloop control off)
o Main trip valves in operating position
(1) Operate fire protection switches 1 and 2 in
succession in the control room and at the
local control stations in the power plant
• Start of fire protection measures in
accordance with functional diagram
• No annunciation “Fire protection measures
not performed”
(2) Acknowledge fire protection measures and
re-establish normal operating conditions for
further testing
5.3-0061-02/4
Equipment tested o Preconditions Date
o Type of test () Test Step Result
• Result Tested by
Low lub oil pressure trip
o Functional test o Oil system operating
o Main trip valves in operating position
o Stop valves closed
(1) Simulate pressure Transmitters (2 out of 3)
for lubricating oil trip
• Trip started
Stop valve
o Exercising o Oil system operating
o Main trip valves in operating position
o Stop valves open
(1) Actuate main trip valves (manual trip-out
from control system rack or remote trip
• Stop valves closed
5.3-0061-02/5
Equipment tested o Preconditions Date
o Type of test () Test Step Result
• Result Tested by
Vacuum breakers
o Functional test (1) Operate vacuum breakers
Alarms
o Functional test 4-1190
General measuring
instrumentation
o Functional and annunciation (1) Test and calibrate in accordance with
test manufacturer’s instructions
5.3-0061-02/6
Steam Turbine Testing of Safety Valves
Maintenance
These instructions deal with the Testing during operation by varying the
fundamentals of testing and maintenance of operating condition. When shutting down
signaling devices. and starting up the turbine and its
auxiliaries. and when testing control and
protection equipment, all alarms and
Types of signaling devices condition signals must be carefully
observed and a record made of their
Alarm signaling devices give a visual and
response. It is also important to check
audible indication of operating values
that the signaling actually reflects the
reaching predetermined limits. If this results operating condition accurately.
in automatic intervention in the plant
process. e.g. triggering of the turbine trip, Examples: When shutting down the turbine
then this is also signaled. the “low oil pressure” alarm must come
before the auxiliary oil pump starts
Condition signaling indicates the state of automatically. When testing the overspeed
control devices, e.g. whether a stop valve is trips, the “Overspeed trip operated” alarm
open or closed. must come.
Finally, signaling can provide a reminder
Triggering of the sensor. In this method
that certain action needs to be taken.
the sensor is operated without there
being any change in operating value or
condition.
Basis of signaling device testing
Whenever possible, testing of the signaling Examples: The travel-controlled limit switch
devices should be carried out under a close which signals response of the thrust bearing
approximation to operating conditions. The trip is operated by hand. The pressure
test should also enclose all components of switch for the “condenser vacuum low”
the device. alarm is isolated and then vented to
atmosphere.
In addition to functional testing, the device
settings should also be checked at longer The response limit value is adjusted so
intervals, especially after inspections. that signaling response occurs. (With this
method it is possible for mistakes to be
made when returning the settings to their
Test procedures original values. Therefore the method
should only be used in exceptional
There are various ways to test the cases.)
functioning of signaling devices.
Signaling response is produced by an
Testing during operation by varying the electrical pulse. If, for some reason, none
operating values. This type of testing is of the previous methods can be used, a
most appropriate when operating values partial test of the signaling device must
can be varied by intervention in the plant be performed by means of an electrical
process. pulse.
5.3-0063-00/2
Steam Turbine Testing of
Maintenance Turbine Stress Controller (TSC)
5.3-0064-01/2
Long-term monitoring through recording the turbine stress monitoring equipment.
of all measured and calculated values These must be adapted to plant-specific
requirements.
By registering and recording all measured
and calculated values at the intervals
specified in Table-1 during steady-state Actions to be taken when actual
turbine operation, the thermal behavior of conditions deviate from reference
the turbine and the function of the turbine conditions
stress monitoring equipment can be
monitored on a long-term basis. If actual conditions deviate from reference
conditions, the measured value acquisition
Long-term monitoring can be used to detect function must be carefully checked and any
and rectify any gradually developing faults corrected.
changes.
If the deviations in measured and calculated
If the check on the measured values reveals values are particularly large, it must be
that the margins have changed due to the assumed that the behavior of the turbine
measured absolute temperatures and the plant will be adversely affected. In this case,
differences arising between them, this can action of the TS monitoring equipment on
probably be traced to a fault in the the setpoint control for the turbine controller
calculation circuitry. The cause of the fault must be temporarily deactivated.
must be determined, e.g. by checking the
specified limit curves in accordance with the As long as action of the TS monitoring
procedure described in the manual for the equipment on the set point control for the
TS monitoring equipment. turbine controller is deactivated, the TS limit
curves must be used for evaluation of the
Table-2 contains all measured and thermal stresses imposed on the turbine
calculated values which may be required for components.
5.3-0064-01/3
Table-2 : Measured and calculated values for long-term monitoring
5.3-0064-01/4
Steam Turbine Steam Washing of Turbine
Maintenance
Steam Washing of IP Turbine After the saturated steam line (Fig.1, item 2)
has been joined up at the connection points
All stop and control valves and all valves in
(3), the washing steam can be routed into
the extraction lines remain closed during
the IP turbine, from there via the cross-
steam washing of the IP turbine. Any
around lines to the IP turbine and then to the
isolating valves present upstream of the
condenser.
feedwater heaters must also be closed.
There are two possible ways of discharging
The drains from the IP turbine between the
the condensate condensing in the
reheat control valves and the IP outlet, the
condenser to the atmosphere. These are:
extraction valves or the swing check valves
in the extraction lines must be vented during By opening the blind flanges (4) on the
steam washing only to the extent required to condenser. The condenser must be
allow the condensate arising to drain off under atmospheric pressure. With this
whilst preventing excessive loss of steam. method of steam washing samples for
All other drains from the turbine generator finding out the saIt content may also be
must be full open. taken at this point.
5.3-0070-02/2
With the vacuum pump \ ejector Steam Washing of HP Turbine
switched on and the blind flange (4) The main control valves must be open
closed, i.e. with the condenser at sub during steam washing of the HP turbine.
atmospheric pressure, via the
All drains (7, 8) from the HP turbine situated
condensate discharge line of an
between the main stop valves and the HP
operation condensate pump. In this
outlet may be vented during steam washing
case, make sure that the condensate is
only to the extent required to allow the
discharged to the atmosphere
condensate arising to drain off while
downstream of the pump. Samples for
preventing excessive loss of steam.
finding out the salt content are also
taken at this point. All other drains particularly those in the cold
reheat line, must be fully open. Local
The first method of steam washing with the
drainage may also be provided so that no
condenser under atmospheric pressure
steam can enter the Reheater of the Boiler,
guarantees a slight overpressure at the
if at all possible.
drains so that it is possible to perform
additional sampling at these points. For this After the steam line (6) has been joined up
purpose, the appropriate drains may be cut at the connection points (3), the stream can
off at the sludge traps, or the steam inserts be routed into the HP turbine. The steam
of the drain valves may be removed. leaving the HP turbine is exhausted to the
condenser via the drains (9).
It is suggested to record the salt content at
the sampling point continuously throughout The condensate is discharged and samples
the washing Process. Also, water samples are taken to determine the salt content as
should be taken every half an hour for described in steam washing of IP turbine,
deposit analysis. the completion criteria remaining same.
Steam washing may be stopped when the
purity of steam entering the turbine (as Restoring the Turbine to Operating
determined by sampling) is approximately Condition
the same as that of the condensate or steam On completion of steam washing, all
extracted at the discharge sampling point. temporary fittings must be dismantled and
The steam washing may be stopped when the flanges closed off. Any drain lines cut off
the salt content in condensate remains must be rewelded. Controllers and control
constant at a very low level. valves must be returned to normal position.
The temporary lines are to be preserved for
future use.
5.3-0070-02/3
Steam Turbine Turbine Oil Care
Maintenance Maintenance Instructions
In this case, the turbine manufacturer and Solid-contaminant quantities and purity
the turbine oil supplier should be consulted of turbine oil
in order that measures for restoring the Whereas the material property value for
turbine oil can be implemented. solid-contaminant quantity defines the
overall content by weight of solid-
The turbine oil cannot be used if the function
contaminant quantities in a turbine oil
of sensitive turbine generator components is
sample, when defining turbine oil purity only
impaired through corrosion and/or aging
the proportion of solid-contaminants of a
products and if the aging process, i.e., the
specified size is determined. Turbine oil
change in the total-acid number, cannot be
purity is the more reliable criterion.
reversed by treating the turbine oil.
Solid-contaminants can ingress into the
From this highly simplified description of the
turbine oil from outside, or as a result of the
turbine oil aging process, it can be seen that
aging process or corrosion. They contribute,
aging is affected not only by physical loading
along with other factors, to the turbine-oil
of the turbine oil but also by catalysts and
aging process and impair the condition and
aging products, e.g., oleic acids. Treatment
function of the turbine components.
of the turbine oil in the oil conditioning
station removes products of aging and Among the principal areas which can be
corrosion which are not soluble in oil, affected are turbine and generator bearings.
thereby slowing down the aging process. Their load capacity can be reduced due to
scoring caused by solid-contaminants in the
turbine oil. In addition, changes of state and
Water content and water separability of
impaired functioning in control and
the turbine oil
protection equipment can be expected.
With healthy gland sealing & oil vapor
extraction system during normal operation The oil system is thoroughly cleaned during
the moisture content in turbine oil is not initial startup of the turbine generator set.
expected to be more then 100 ppm as in the Flushing of the entire system is included in
turbine oil specification (1). In case the the cleaning process.
moisture content found more then 300 ppm The filters and strainers of the operating oil
during sample testing, the reason is to be systems are used to retain contaminants
investigated. With moisture content value with a particle size larger than the filter mesh
more then 1000 ppm machine should be size, before the turbine oil reaches the oil
tripped and source of water entry is to be consumers. The dwell time of the oil in the
eliminated. filters and strainers will depend on the purity
Water which ingresses into the oil system of the turbine oil.
from an oil cooler, in the form of shaft seal Purity in accordance with the Turbine Oil
steam or leakage water, results in the Specification [1] is achieved through
corrosion in ferrous materials and can continuous filtration or separation of turbine
adversely affect the aging process and oil in the oil centrifuge.
foaming characteristics of the turbine oil.
During inspections and overhauls the turbine
Corrosion causes changes in the surfaces must be drained and the main oil tank, the
and shape of the sensitive turbine generator oil coolers and the bearing pedestals must
components. The corrosion products behave be thoroughly cleaned. It is recommended
in the same as solid contaminants, and lead that the turbine oil be either filtered or
to impaired component functioning. treated in a separator during drainage an
The cause of any increase in turbine-oil refilling.
water contents must be determined and The ingress of solid contaminants into the
remedied. turbine oil must be prevented.
5.3-0080-03/2
Air release properties of the turbine oil with the foam, resulting in a drop in the oil
level in the main oil tank. This change in the
The air release property represents the time
level can cause activation of the level
taken for a specific volume of air to be
monitoring equipment for the main oil tank.
released from the turbine oil sample under
the boundary conditions stipulated in the Increased turbine oil foaming tendency
testing standard of the Turbine Oil occasionally occurs due to high water
Specification [1]. content or increased dust contamination of
the turbine oil.
The turbine oil circulates inside the oil
system and becomes aerated. This air is Silicone-based foam inhibiting additives
-1
released during the dwell time tv = 60n (in have an adverse effect on air release
min) of the turbine oil in the main oil tank, n properties. There is no generally binding
corresponds to the number of passes per evidence regarding any further correlation
hour made by the turbine oil. between foaming tendency and air release
properties, although such a correlation may
If the time required for air release by the exist in individual cases and should be
turbine oil is longer than the dwell time in the investigated.
main oil tank, an oil-and-air mixture will
develop, which will not have as favourable a
density and compressibility as non aerated
Turbine oil care program
turbine oil. This can lead to faults in the
operating oil pumps, fluctuations in oil Owing to correlation between the turbine oil
pressure and impaired functioning of any properties and the factors influencing turbine
control and protection equipment which is oil during operation, the following care
supplied with turbine oil. program for turbine oil must be implemented
during and after initial startup of the turbine
Only in rare cases it is possible to improve
generator set:
the Air release properties of turbine oil with
economically viable treatment methods. For Regular inspection of turbine oil samples
this reason, any factors which might lead to
Continuous treatment of the turbine oil
deterioration of the air release properties of
the turbine oil, must be avoided. Protection of the turbine oil system from
the effects of contaminants
It has been proven that the air release
properties of turbine oil are adversely Drainage of the turbine oil and cleaning
affected by materials containing silicone, of the oil system and the turbine oil
e.g., seal materials or foam inhibiting during inspections and overhauls.
additives.
5.3-0080-03/3
If the turbine oil inspections reveal that or wear to parts such as oil pump seal
alarm levels for certain properties have been ring, etc.
reached or exceeded, it is advisable to
request inspection and evaluation of the Treatment of the turbine oil in the oil
turbine oil by the turbine oil supplier. All data centrifuge
relevant to turbine oil inspection should be
The oil centrifuge can be continuously
sent in together with the turbine oil sample
operated independent of the operating oil
When taking turbine oil samples, care must systems. A small volume of turbine oil is fed
be taken to ensure that sampling bottles are through oil centrifuge with a high separation
clean. efficiency. This achieves a high degree of
purity for the treated turbine oil.
In case of deviation in properties, actions to
be taken as per table 1. As regards the treatment of turbine oil in the
centrifuge, oil filter, dynamic or static
separators, and multipurpose oil purification
Treatment of the turbine oil in the oil
units can be used either independently or in
filters or strainers of the operating oil
combination. In addition, many power plants
systems
have centralised oil purification equipment,
Switchable oil filters either permanently installed or mobile.
The switchable oil filters of the operating The function of the most commonly used oil
oil systems are used to protect purification equipment is described below:
downstream consumers. Contaminants
which, because of their size or
consistency, can cause damage and/or Fine-mesh filter
impair functioning are retained in the oil The turbine oil can be conditioned in an
filters. Because of their relatively large oil filter with filter elements made of fine-
mesh size, the operating oil filters are pored cloth or filter paper. Since the fine-
not suitable for complete removal of mesh filter has a high separation
contaminants from the turbine oil. The efficiency, a high degree of turbine oil
differential pressure across the oil filters purity can be achieved. Contaminants
is monitored. insoluble in oil which ingress into the oil
system from outside, as well as products
If the differential pressure across an oil
of system-internal aging and corrosion
filter increases, this filter should be
mechanisms are almost completely
isolated from the system and cleaned.
removed from turbine oil.
Fine-mesh filters with cloth or paper
Oil Strainers of the main oil tank
elements can also retain small amounts
The oil strainers of the main oil tank of water. If the turbine oil has a high
have a relatively large mesh size and water content, a dynamic or static
are used to retain contaminants in the separator must be used to reduce the
returning turbine oil and to protect the oil water content in the turbine oil to the
pumps from contaminant damage. value stipulated in the Turbine Oil
If the strainer mesh becomes clogged Specification [1].
during the course of operation, this can
lead to a drop in the level in the suction Dynamic separator
space of the main oil tank as a result of
The dynamic separator uses centrifugal
an increase in the level in the riser
force to remove either solid or liquid
space.
contaminants as required from the
For this reason, the oil strainers of the turbine oil. The dynamic separator must
main oil tank must be regularly cleaned, be set to operate in either solid
if possible while the oil pumps are shut contaminant or water separation mode
down. Metal particles in the oil strainers in accordance with the manufacturer’s
can be an indication of bearing damage instructions.
5.3-0080-03/4
Static separator different additive packages. For this
reason, when topping up, turbine oil
A static separator is used to remove
which has the same product designation
water from the turbine oil. Since the
and which is supplied by the same
efficiency of the filter elements
manufacturer as was originally filled,
deteriorates due to deposits of solid
should be used.
contaminants, and in view of the
expense of filter elements, it is
recommended that the static separator Hydraulic oil
be used in conjunction with an upstream Hydraulic oil or control fluid containing
fine mesh filter. phosphoric esters, if in use, must not be
allowed to ingress into the oil system.
Multipurpose oil purification unit
The multipurpose oil purification unit is Main oil tank
used to remove solid and liquid Openings in the main oil tank must
contaminants from the turbine oil. always be closed and sealed in such a
Operation and maintenance instructions of way that there can be no ingress of
the oil purification unit manufacturer must be contaminants into the main oil tank. The
complied with. cover plates of the main oil tank must be
tightly bolted. There must be no bolts
The maintenance interval for oil filters missing from the plates.
depends on the differential pressure across
the oil filters. For this reason, the differential
pressure instrumentation must be regularly Oil coolers
checked and corresponding annunciations If the water content of the turbine oil
noted. increases, the leak tightness of the
operating oil cooler must be checked.
Cleaning of the oil system during
inspections and overhauls Oil return lines
Over the course of time, solid contaminants Inspection holes in oil return lines must
settle in areas of the oil system not be sealed to prevent the ingress of
subjected to high flow velocities, e.g. the contaminants into the oil system.
main oil tank. For this reason, the turbine oil
must be drained via filters during inspections
Oil vapor extraction system
and overhauls, and the main oil tank, the oil
coolers and the bearing pedestals must be The throttle check valves in the oil vapor
thoroughly cleaned. The drained turbine oil extraction system must be set so that
must either be refilled into the main oil tank the pressure in the bearing pedestals
via fine-mesh filters or treated in a and the main oil tank is slightly sub
centralised oil purification unit before atmospheric. This ensures that no
refilling. leakage steam, or airborne water and/or
dust is drawn into the oil system in the
event of turbine oil or oil vapor being
Measures to protect the oil system from released to the atmosphere.
contaminant ingress
Just as important as turbine oil care are
Dirty fluid
measures designed to protect the oil system
from contaminant ingress: Fluid from the dirty-fluid tank must not
be refilled into the main oil tank without
thorough inspection and treatment.
Turbine oil Small amounts of turbine oil which
Problems can arise as a result of the accumulate in the dirty-fluid tank are to
incompatibility of turbine oils from be disposed properly.
different manufacturers and containing
5.3-0080-03/5
Material
The compatibility of materials with the
turbine oil has been taken into account
by the turbine manufacturer during
materials selection. During inspections
and overhauls, care must be taken to
ensure that no incompatible materials
are used. This applies particularly to
gaskets and silicone-based seal
materials.
5.3-0080-03/6
Table1 : Actions to be taken when actual conditions deviate from reference conditions
5.3-0080-03/7
Fault Cause Actions
Boundary conditions
- Reduce intervals for turbine
oil inspections and monitor
evaluation of total-acid
number
Investigate the origin of
contaminants and prevent
contaminant ingress into oil
system.
The solid contaminant The oil centrifuge is not in Put oil centrifuge into operation.
content or the purity of the operation
turbine oil does not comply
The contaminant separation Take turbine oil samples
with the Specification
efficiency of the oil centrifuge upstream and downstream of
does not comply with the the oil centrifuge and determine
requirements the separation efficiency.
Implement measures in
accordance with the operating
unit manufacturer, in order to
improve contaminant separation
efficiency.
Check oil filter cartridges or
elements, replace damaged oil
filter cartridges or elements.
If necessary, vent the oil filters.
5.3-0080-03/8
Fault Cause Actions
Boundary conditions
The water content of the There is no permanently Install a dynamic or static
turbine oil does not comply installed dynamic or static separator for removing water
with the specification separator for removing water form the turbine oil. Take turbine
from the turbine oil oil samples upstream and
downstream of the separator
and check water separation
efficiency.
If necessary, implement
measures in accordance with
the operating instructions of the
separator manufacturer, in order
to improve water separation
efficiency.
5.3-0080-03/9
Fault Cause Actions
Boundary conditions
The air release properties In many cases, there is no Check whether the deterioration
of the oil do not comply specific cause for a in air release properties has an
with the Specification deterioration in air release adverse affect on the operating
properties performance of the systems of
components supplied with
turbine oil.
Involve oil supplier and turbine
manufacturer in inspection
program. If effects are
particularly unfavorable,
consider replacing the turbine
oil.
As a precautionary measure,
care should always be taken to
prevent the ingress into the
turbine oil of materials which
could adversely affect the air
release properties (e.g. silicone-
based materials)
Turbine oil foaming The foam inhibiting additives in Consult oil supplier and top up
characteristics do not the turbine oil have been turbine oil with foam inhibiting
comply with the depleted over time additives.
Specification
As a rule, foam inhibiting
additives have an adverse effect
on the air release properties and
for this reason, the air release
properties must be closely
monitored when topping up with
such additives.
5.3-0080-03/10
Fault Cause Actions
Boundary conditions
The oil centrifuge is
defective or the operating
conditions for the oil do not
comply with the
requirements
Oil filters
The differential pressure Isolate duplex oil filter and clean
across one oil filter is high filter cartridge
Take oil centrifuge filters out of
operation and replace filter
elements
One oil filter is not sufficiently Open valve in oil filter venting
vented line and adjust
Unit-specific or additional The mode of operation of the Adapt the mode of operation of
dynamic separator dynamic separator does not the separator (solid-contaminant
correspond to the content of separation or water separation)
solid or liquid contaminants in according to the content of solid
the turbine oil contaminants or water in the
turbine oil
5.3-0080-03/11
Steam Turbine Grease and Oil Lubrication
Maintenance
Procedures to preserve the control fluid The system must be refilled from lead-
properties. sealed barrels; precautions must be taken to
prevent filling with a control fluid that is not
Data on sampling points in the cycle. identical to the one specified for use or with
Sampling and analysis programs. mineral oil from similar casks.
5.3-0082-02/2
Do not eat, smoke or drink when working copper does not apply since the surface
with control fluid or parts in contact with area exposed to control fluid is small.
control fluid. Only austenitic steel may be used for filter
Keep control fluid away from foodstuffs. meshes; brass is unsuitable.
If control fluid gets into eyes, sponge Bearing and shaft seals and the nonmetallic
carefully and rinse with water. Obtain parts of couplings on pumps and their drive
medical attention if irritation persists. motors most be compatible with control fluid.
Since aerosols of the fluid may reach the
After handing control fluid, wash hands motors windings through the motor
immediately. ventilation system, the windings must be
Wear protective clothes, gloves and designed to be compatible with control fluid.
goggles.
Change any article of clothing that comes Materials for tools
into contact with control fluid. If skin Nonmetallic parts of tools (handles) must be
contact occurs, flush areas with water. made of material compatible with control
Obtain medical attention if irritation fluid or covered with suitable surface
persists. protection (See plastics). Remember this
when ordering new tools.
If control fluid is swallowed, give large
amounts of warm salty water to cause Plastics
vomiting; if unsuccessful tickle inside the
patients throat with a finger. Obtain Plastic materials are susceptible to swelling,
medical attention if stomach discomfort shrinking and surface deterioration.
persists. Plastic incompatible with control fluid may
Avoid inhaling spray clouds (aerosols) or impair the control fluid properties. Following
decomposition products (e.g. use clothes plastics are compatible with control fluid:
to protect respiratory tract). Fluorcarbon elastomers FKM Viton
Wear gas mask if thick clouds of control Butyl rubber IIR Butyl IIR-40
fluid are present. Polytetrafluorethylene PTFE Teflon
Polyethylene PE Hostalene
Polyamide PA Nylon
Compatibility with other materials
Following Plastics are incompatible with
Control fluid’s foaming, air release capability control fluid: PVC plastic, Polycarbonate-
and its resistance to aging are impaired by Makrolon, normal plexiglass.
contact with materials incompatible with
control fluid. Also materials, which are Only glass or Plexidur T may be used for
incompatible with control fluid, can be sight glasses. Protective caps on switches,
attacked. plungers and valves must be of metal or
plastic material compatible with control fluid.
Metallic materials
Sealing material, hose, cable insulation
Phosphoric esters have a negligible effect
and accumulator bladders
on steel, copper alloys, zinc, tin and
aluminum alloys provided the neutralisation Following sealing materials are compatible
number is within the admissible limits. The with phosphoric esters:
solid outer oxide layer of aluminum alloys For o-rings, packing rings, collars and
must not be destroyed due to friction. diaphragms: viton, teflon, butyl rubber
Pure copper cannot be used due to its and composite material such as cotton-
catalytic effect on the decomposition of the viton, teflon-white asbestos, viton
phosphoric ester. Sealing material made of asbestos.
5.3-0082-02/3
For flat gaskets: viton, teflon, butyl - Stability
rubber and compressed asbestos. Acid and aging products may cause a loss
For hoses and cable insulation: viton, of stability; the speed of aging increase in
teflon and nylon coatings. the manner of a chain reaction, drastically
reducing the service life of the control fluid
For accumulator bladders: butyl IIR-40 (resulting from chemical reactions of the
(up to 80 ºC), viton control fluid with water, air and other
Liquid sealing materials: Hylomar impurities).
SQ32L, Loctite 270, ciba-geigy CY246.
+ Removal of acids and aging products
Caution: Butyl rubber IIR is not compatible The presence of acids and aging products
with oil. Silicon rubber must not be used raises the neutralisation number; the
since it severely impairs the properties of the permissible limit is 0.5 mg KOH/g.
control fluid (reduces its air release
capability). Acid and aging product must be eliminated
from the control fluid by continuous bypass
filtration through a Fuller’s earth filter.
Paints
Only two-component, desmodur / Regeneration through a Fuller’s earth filter is
desmophene (DD) base and epoxy resin based on an ion exchange reaction.
base lacquers may be used. When painting The Fuller’s earth used must be dry (1 % by
the inner surface of containers, make sure weight expellable water at 105 ºC). We
the coating is applied properly. If the paint recommended drying the Fuller’s earth
flakes off, it may cause considerable before filling. The design of the Fuller’s earth
damage. and filter regenerating equipment conforms
to the control fluid manufacturer’s
Caution: Paints compatible with control fluid requirements.
(epoxy resin and desmodur /desmophene
base) give off toxic vapour when exposed to Design and functioning of the filters are
heat. (e.g. during welding or grinding). explained in the Description Section. The
Repair procedures must specify the flow diagram of the regenerating plant is
presence of such paints. Signs on parts, also given in the relevant chapter.
containers with these paints must not be The grain size of the fuller’s earth should be
removed. US screen number 16/30 to 30/60 mesh.
The dust portion must not be used.
Control Fluid properties
When filling the filter, ram down and/or
Requirements shake the earth into the filter elements to
Requirements for control fluid are listed in prevent formation of gaps or channels that
the specifications for control fluid (1). would reduce the efficiency of the Fuller’s
earth.
Special care must be taken during
commissioning and operation to preserve Unnoticed exhaustion of the Fuller’s earth is
control fluid properties. prevented by changing the earth filling at
six- month periods, unless this interval does
Keeping a daily service log is not have to be reduced for other reasons.
recommended; all values from analysis and
details of important events (filter changes Since the control edges of electrohydraulic
and exchange of filter mass, refilling) must servo valves are subjected to erosion-
be entered. All changes and their cause corrosion if the control fluid is not suitably
should be readily detectable on the basis of treated, regular regeneration of the Fuller’s
these records. earth is always necessary, even if there is
no increase in neutralisation number.
Preservation of Properties
5.3-0082-02/4
Regeneration should be started about 48 element being cut out as soon as the limit is
hours before commissioning of the servo reached.
valves. Temperatures above 75°C are admissible
The control element of control circuits for a short period only during flushing
actuated by servo valves must be filled with procedures.
new control fluid through the regeneration
equipment even when the fluid supplied by
the manufacturer has the specified Note: If the temperature rises from 60°C to
neutralisation number. This applied both for 70°C, the speed of oxidation doubles.
initial and refills.
A fine-mesh mechanical filter (polishing + Prevention of influence due to foreign
filter) downstream of the Fuller’s earth filter matter
traps Fuller’s earth particles and other
foreign matter that would act as a catalyst in Measures must be taken to stop the entry of
the control fluid. The fine-mesh filter has the solid or liquid foreign matter or other
added function of establishing the required impurities with a view to maintaining the
purity of the control fluid in the overall stability of the system. All possible
system. measures must be taken to protect the
system from rust.
The fine-mesh filter must be cleaned in the
same way as other fitters in the system. The system is vented and deaerated via a
When changing the filter elements, do not defined opening to stop degeneration of the
remove the protective covers from the new control fluid due to moisture and
elements until just before they are installed. contamination. The opening is sealed by
absorbers or filters to prevent the entry of
Strainers must be cleaned using the moisture and contamination when venting
cleaning agents recommended by the filter and to ensure adequate deaeration.
and control fluid manufacturer; make sure
that dirt does not get onto the clean side. Silica gel absorbers are used to indicate the
buildup of absorbed moisture by changing
Immerse filters in the cleansing fluid only up colour. Evaporating moisture is necessary in
to their upper edge. Filters must always be the absorbers during deaeration. Refill Silica
blown-out from the clean side towards the gel if a permanent change in colour is
dirty side. Use only dry air for blowing-out noticed.
(relative humidity 60% at 20 ºC).
A large absorber or filter is used when the
Confirm absence of oil and dust by using system is vented or deaerated via exhaust
filter paper test. fans to ensure that the control fluid is
Use a magnifying glass to check the separated from the air downstream of the
completeness of the cleansing process. fan.
When deaerating using fans, the system
+ Prevention of thermal influences must not be under a substantial vacuum.
If deaerating valves are used that open
The control system requires a service
when a slight internal over pressure has built
medium viscosity that complies with the
specification at a control fluid service up, make sure the moist air is unable to
temperature of 55±5 ºC. enter into the system.
Accumulated water is annunciated by using
No adverse effects on the stability of the
electrodes. The cause of water
control fluid due to thermal influences are to
accumulation must be located immediately
be expected at this service temperature.
and corrected. Water accumulating on the
A maximum temperature of 90°C is surface of the control fluid tank due to its low
admissible locally, for example, at heating density, must be removed by siphoning or
element / protective pipes with heat pumped off. Condensate occurring in small
conducting oil fillings. Compliance with this amounts evaporates at service temperature.
limit temperature is monitored the heating Increase monitoring the neutralisation
5.3-0082-02/5
number if and after the accumulation of the About 3-4 % mineral oil will dissolve in,
water is detected. control fluid between room temperature and
50°C. If oil enters the control fluid circuit, the
control fluid manufacturer must examine the
- Fire resistance effect this has on the fluid’s fire resistance
Following are the causes of impairing the properties. It is impossible to separate oil
fire resistance properties of the control fluid: from the control fluid since the mixture is a
Mixing of mineral oil by mistake; this can genuine solution. Only when the oil content
be prevented if filling guidelines are exceeds 3-4% does a two-phase liquid
followed. result.
Penetration of mineral oil from the
lubricating oil circuit. - Air release capability
Design measures have been taken to The air release capability of the fluid
prevent oil and control fluid from intermixing. depends on the presence of foreign matter.
Contact points between the lubrication oil The chapters on the subject of stability and
control systems are separated by interface prevention of the influences of foreign matter
made of metal bellows between which there must be observed to ensure the air release
is a drain line to the leakage tanks; the tank capability complies with the requirements.
has a device to annunciate the accumulation
of control fluid due to leaks.
- Purity
The bellows are arranged if one ruptures,
the second takes over its shielding function. SAE guidelines (Table-1) govern the purity
Penetration of one media into the other is requirements for media used in hydraulic
only possible if both dividing elements have systems.
leak.
SAE Class classification applicable for Samples must be taken at sampling points
maintaining the service reliability for from the flowing liquid into clean laboratory
protection and control systems are as bottles. Take care to avoid any secondary
follows: contamination. The sampling bottles must
be permanently marked with these data:
Class-6: Protection and Control systems
facility, sampling point, fluid manufacturer
without servo valves
and type, date, sampler.
Class-3: Protection and Control systems
They must then be sent to a laboratory
with servo valves
(turbine manufacturer, control fluid supplier
or operator) for examination.
Sampling and analysis It is possible to filter the samples at the site
by using the field monitoring method so only
Samples must be taken and examined to be
the diaphragm filter has to be sent for
able to ensure the control fluid meets the
analysis to a laboratory outside the power
purity requirements.
plant.
5.3-0082-02/6
Performing routine analysis of the same fluid mesh filter, before it enters control system
filling involves relating the degree of colour sections susceptible to contamination, and
change of the test filter (relative measuring at the same time to check the function of the
method) to the quantitative degree of fine-mesh filters.
contamination as determined by counting
the contamination particles. Sampling point - Return (PNR)
The precondition for application of the field The PNR is provided in the return line.
monitoring method using diaphragm filters or Analysis of the samples from this point
of the relative measuring method is the makes it possible to determine the degree of
availability of reliable sampling and analysis purity of the fluid in the overall system
equipment at the plant site. without the direct influence of the service
filters.
Sampling and analysis programme
The sampling and analysis program Sampling point - Fluid Tank (PNB)
according to Table-2 makes it possible to The PNB is provided at the tank.
perform the essential assessment of the
control fluid properties and purity at all Sampling points downstream of the
stages of commissioning and during circulation pump (PNU), downstream of
continuous service. Fuller’s earth filter (PNFB) and downstream
of the fine-mesh mechanical filter (PNMF)
Besides, it allows assessing the flushing are provided.
procedures and the condition, efficiency and
regeneration of the filter equipment. Samples from the sampling points (PNU,
PNBF and PNMF are used to determine the
When required, it is possible to compare the efficiency of the regeneration and filtration
results of the routine analysis with the processes.
analysis of the baseline reference samples
taken before filling and completion of The sampling program applies both to the
commissioning. initial filling and to all fillings thereafter.
Sampling points are marked as follows: If any deposits are found, they must be
analysed in consultation with the control fluid
manufacturer.
Sampling point - Supply (PNV)
Then checks must be carried out to find out
The PNV is provided within the supply unit. if rust or other forms of corrosion have
Analysis of the samples from this point developed within the system.
makes it possible to ensure the degree of
purity of the fluid downstream of the fine
5.3-0082-02/7
Time of Sampling Degree of purity NZ ASC Water Density Kinem. Anti-
3
Discol Particle KOH min content g/cm Visco corro.
mg/g % by 2 Props.
oration count V mm /s
test vol. (2)
Before filling FRF
Lab sample x x x
x x x
Control sample
Two weeks after filling
FRF, if flushing not yet x x x
started
Before commencing PNB
flushing for record of
as-delivered condition
Continuous sampling PNR
during flushing
Towards end of refilling x x x x
via superfine filter
(3)
Continuous monitoring PNB
during superfine PNU
filtering
PNBF
PNMF
Before commencing
hot operation (Last x x x
sample taken more
than 2 weeks earlier)
24h after
commencing hot x x x x x
operation
One month after
commencing of x x x
operation: weekly
One month after
x x x x x
commencing hot
(1)
operation : monthly
Before handing over PNR x x x x x
with final log
Table-2: Sampling program for SAE purity grade class 6
5.3-0082-02/8
Parameter and Inspection Permissible Inspection Measures to be taken if
dimensions method limit interval limits exceeded
Water content No free water weekly Evaporate, suction-extract,
% by vol. visible to ladle-off, centrifuge using
naked eye special device
Neutralisation DIN 51 558-1 0.5 Monthly, Check regeneration plant,
number ASTM D974 weekly if Replace fuller’s earth, Check
NZ (mg KOH/g) negative effects by frequent
trend measurement of NZ
Kinematic DIN 51562-1 26-50 monthly Replace filling
viscosity at ASTM D445
2
40°C (mm /s)
Solid impurities Particle count SAE purity monthly Check filters for proper
and grade class 6 functioning. If necessary,
discolouration replace filter elements.
test Examine deposits on filter
elements
th
Air separation DIN 51381 Proper every 4 Check fluid for contamination
capability functioning of month (chemical and mechanical,
(min. at 50°C) system must entrained oil)
be assured
th
Density at 15°C DIN 51757 every 4 Check points in system
3
(g/cm ) ASTM D1298 month where oil can enter FRF
system. Examine fluid for
entrained oil, air or water
Fire resistance DIN/ISO 14935 ≤ 5 sec after Replace FRF filling
test determining
oil content
th
Anti-corrosion DIN 51585 no corrosion every 4 Have anti-corrosion additive
properties ASTM D665-60 permissible month analysed by fluid
manufacturer. Replace FRF
filling if necessary.
Oil content nuclear 3% max. see note Replace FRF filling. Perform
% by vol. resonance test, fire resistance test.
density
Table-3: Maintenance Measures
Note : If examination of the points in the system where the oil and FRF loops are structurally
separated reveal that oil has entered the FRF system as a result of structural failure, the
oil content in the FRF must be determined.
5.3-0082-02/9
Steam Turbine Fire Resistant Fluid
Maintenance Determination of Fluid Purity
5.3-0083-01/2
Steam Turbine Vibration Dampers
Maintenance
5.3-0100-00/2
Steam Turbine Instructions for Overhaul
Maintenance
In this chapter scope and schedule of Detailed knowledge of the next major
overhaul has been described. overhaul can be gained from the medium
overhaul.
Types of Overhaul The following criteria form the basis for
deciding whether or not to open a casing:
Minor Overhaul (inspection, servicing)
conclusions drawn from long-term
A minor overhaul should be carried out as observation, operating experience and
required simultaneously with shutdowns of manufacturer’s recommendations.
other plant components or during standstill
of the turbine-generator unit due to faults.
Major Overhaul (inspection, servicing,
The purpose of the minor inspection is to repair)
avoid reduction in availability due to forced
A “major overhaul” is a planned shutdown. It
outages by inspection and servicing and, if
permits detailed inspection and the
necessary, by preventive maintenance,
determination of the condition of all
The casings are not opened. components. All casings are opened.
Detailed knowledge of importance for Schedule inspection interval: after 50,000
intermediate overhaul or major overhaul is equivalent operating hours.
gained during minor overhaul.
The term equivalent operation hours is
Scheduled interval: after about 17,000 defined by the following equation:
equivalent hours of operation.
Te = To + ns x 25
Turbine bearings
Turbine bearings
Turbine bearings
Operating years
Coupling check
Coupling check
Coupling check
Turbine valves
Turbine valves
Turbine valves
HP turbine
HP turbine
LP turbine
LP turbine
IP turbine
IP turbine
8600 01
02
* *
25800 03
04
43000 05
06
60200 07
08
77400 09
10
94600 11
12
111800 13
14
129000 15
16
146200 17
18
-Mandatory, -Optional, *Mandatory for turbines with spring mounted TG deck
5.3-0200-05/2
Medium Overhaul
Minor Overhaul
Major Overhaul
List of’ Activities to be performed during Minor, Medium and Major Overhaul
For units with spring mounted TG deck, check reference readings of deck * *
spring units, carryout alignment and catenary check and readjust spring
units after first year of operation.
Check guides of inner casing for freedom of movement and wear. Overhaul.
Measure permanent elongation of bolts in high temperature zone and check
them for embrittlement, check all bolts for cracks.
Check shaft seals and labyrinth glands for abrasion and scaling. Check
springs of spring-mounted ring segments. Replace springs of high
temperature zone.
Check shaft for cracks. Perform run out check, eliminate score-marks in
shaft journals. Inspect coupling.
Visually examine last stage blades of LP turbine (check for cracks if
necessary).
Clean rotors and casings and examine for damage. Pay particular attention
to blades and seal strips.
After every 50,000 equivalent hours of operation, remove LP free standing
blades from fir-tree grooves, clean root & groove, check complete blade
with specific attention to blade root for crack by MPI and carry out NFT.
Check earthling brush contact surface of shaft.
Open main oil pump, check bearings, seal rings, shaft, impeller etc.
Open auxiliary, emergency and jacking oil pumps.
Check control and protective devices. Pay particular attention to parts
subject to wear or deposits, replace these if necessary.
Perform mechanical, electrical and/or hydraulic functional tests on
monitoring instrumentation; if necessary, overhaul and re-calibrate.
Disconnect couplings, measure elongation of coupling bolts, check axial *
and radial alignment, perform run out check, clearance check.
Disassemble bearings, check babbitt surface, measure clearances, check
seating of bearing in bearing pedestal.
Check, overhaul and, if necessary, replace seal rings of bearing pedestals.
Check casing guides for deposit, if guides are jammed, remove, clean and
overhaul keys. Ensure design key clearances.
Check stop valves, control valves, bypass valves; if necessary, replace
worn parts on the hydraulic and steam sides.
5.3-0200-05/3
Medium Overhaul
Minor Overhaul
Major Overhaul
List of’ Activities to be performed during Minor, Medium and Major Overhaul
Remove and check steam strainers for deposits and damage, clean/replace
if necessary.
Check drains for foreign material, open and clean sludge traps.
Measure casing distortion, check casing joints for erosion, check for cracks.
Replace springs of sealing segments in high temperature zone
Drain main oil / control fluid tank, separate impurities, change oil / control
fluid if necessary. Inspect tank. Clean strainers.
Check oil / control fluid filters for leaks, remove and clean the inserts, pay
attention to damage.
Examine oil / control fluid lines for damage, eliminate leaks. Retighten
flange joints. Change gaskets, if applicable.
Examine steam turbine integral piping for cracks, deformation and
ballooning. Special attention is to be given to balance piston leak-off line of
HPT.
Check pipe supports and hangers and readjust if necessary. Check casing
horn drop and eliminate pipe pull by adjusting hangers & supports
Replace TSE/TSC thermocouples fitted in IP inner casing whenever IP
turbine is overhauled.
5.3-0200-05/4
MINOR OVERHAUL If couplings are disengaged it is advisable to
perform a roll check, especially if the
Casings are not opened. Bearing check,
couplings need to be realigned. At the same
coupling check if necessary, mandatory for
time measure the axial displacement of the
spring mounted TG deck after first year of
rotors relative to the casing. If
operation, checks of controls, safety and
disengagement of the couplings is not
protective equipment on steam and oil sides.
performed, coupled run out checks are to be
performed in the vicinity of the bearing as a
Components to be inspected minimum requirement. For accurate runout
− TG deck springs (if applicable) after 1
st
measurement, rotor system temperature
year of operation, alignment & catenary should be close to ambient.
− Casing roll check (if rotors realigned)
− Bearings Bearings
− Oil guard rings of bearing pedestals Dismantle bearings. It is necessary to check
the babbitt metal lining for damage and
− Sliding pieces in casing guides and looseness by UT. Check seating of bearing
supports in bearing pedestal. Measure clearances of
− Control valves, bypass valves bearings.
− Emergency stop valves and extraction
− non-return valves Oil guard rings of bearing pedestals
− Control and safety equipment Remove contaminants and abraded
particles on the seal edges to prevent oil
− Piping supports and hangers
leakage. Replace oil guard ring in case of
− Steam strainers excessive clearance.
− Drains
− Oil lines Sliding pieces in casing guides and
supports
− Pumps (main oil pump, jacking-oil pump,
auxiliary oil pumps and emergency oil Inspect keys and sliding pieces for any
pumps, if necessary) abnormality. If there are indications of
− Oil / control fluid tanks jamming, dismantle and overhaul. Check
and ensure thermal clearances as per
− Oil / control fluid filters design.
− Last stage of LP Turbine
− Monitoring equipment Control valves, bypass valves
Activities should generally be concerned
Scope of activities with checking of parts subject to wear.
TG deck springs (where applicable) Decisions on further activities and valves to
be covered are to be taken according to the
For units with spring mounted TG deck, the
circumstances on the basis of performance
deck springs are to be inspected and
in the preceding period of operation. Spindle
reference dimensions compared and
seals consisting of packing material are to
adjusted after first year of operation. This
be replaced in all cases. Clearances
will also call for alignment, catenary and roll
between moving and stationary parts should
check.
be checked and corrected.
Couplings Emergency stop valves
If couplings are to be opened, carry out Emergency stop valves should always be
swing check & coupled runout measurement inspected completely (steam and oil side).
before loosening the coupling bolts, This includes spindle, cone, seat, bush,
measure the pretension of the coupling bolts actuator. With mechanical drives (lever
while loosing and tightening. Check the linkage) in particular, attention is to be give
alignment radially and axially. If deviations to compliance with plays and travel
exceed the permissible tolerance, reserves.
realignment is required.
5.3-0200-05/5
Piping supports and hangers − Inlet and outlet connections
Check and measure alignment dimensions − Casings
in the cold conditions and adjust, if − Inner casing guides
necessary. Verify adjustment by casing horn − Blading
drop test. Check pipes for visible changes. − Glands
− Rotors
Steam strainers − Fasteners
Dismantle and check for foreign bodies and
damage. Replace gasket. Scope of activities
Inlet and outlet connections
Drains Inspect for scale and freedom of movement
The scope of activities depends on at I-and L-seal rings. Inspect U-seal rings
performance during the preceding period of and measure precompression.
operation and susceptibility to malfunctions.
The sludge traps should be opened in all Casing
cases. Measure for deformation, crack examination.
Rework according to findings. Inspect casing
Oil lines joint plane for erosion
Remove leaked oil, inspect pipes and
mounting for fretting point and strengthen Inner casing guides
accordingly. Check for freedom of movement and wear.
Pumps Blading
The main oil pump is to be opened in order Clean entire blading with casing open and
to inspect bearings, sealing rings, shaft, inspect for damage and incipient cracks,
impeller and coupling. Check other pumps in Check shrouds for scale according to
redundancy configuration only as necessary. temperature. Check for blade looseness and
lock blade lift.
Oil / Control fluid tanks
The fir-tree root free standing blades of LP
Clean strainers rotor need special attention. After every
50,000 hours of operation, take out the
Oil / Control fluid filters blades from groove, clean root and groove,
Remove elements and clean. Check for carry out crack detection of the entire blade
damage. including root, check natural frequency in
position with technological pieces.
Last stages of LP turbine
Visual inspection of condition. Crack Glands and labyrinths
examination where necessary. Check for abrasion and scale (dependent on
temperature). Check condition of springs.
Monitoring equipment
Check that mechanical, electrical and Rotor
hydraulic monitoring equipment function Check for cracks in fillets. Perform run out
properly and repair or recalibrate as check. Eliminate scoring on the journals.
necessary. Check coupling.
5.3-0200-05/6
5.3-0200-05/7
Fasteners in high temperature zone Depending on the results of the inspection
Replace all fasteners of size upto M64 in the examined components are to be:
high temperature zone after 100,000 Left in the as-inspected condition,
equivalent hours of operation. Carry out because no faults have been found.
destructive test on sample fastener of higher
sizes to determine usability of the lot. Left in the as-inspected conditions
although damage (e.g. crack formation)
has been found. Continued operation,
MAJOR OVERHAUL either in an unaltered or altered mode, is
All casings are to be opened and the rotors to be justified. The propagation of the
lifted out. Otherwise as for medium damage is to be kept under observation;
overhaul, but instruction if necessary is spare parts, often requiring lengthy
inapplicable. delivery periods, are to be ordered.
Replaced with spare parts (in general
Components to be inspected
small parts subject to wear are normally
As for medium overhaul but instruction “if kept in stock e.g. spindles, fasteners)
necessary” is inapplicable, and augmented
by the following: Repaired by reworking at site or in the
− Oil / Control fluid tanks works of the supplier
− Steam lines It is necessary to increase the scope of the
− Casing center guides inspection as soon as the units have clocked
more than 100,000 equivalent hours of
Scope of Activities operation. Component integrity assessment
and/or residual life assessment studies are
Oil / Control fluid tanks to be initiated at this stage. Inspection
Drain and clean tank. Purify oil / Control planning must allow for the additional time
fluid, change if necessary. and costs consumed by the inspections.
Apart from this, the intervals between major
Steam lines overhauls necessitate the coverage of
considerably more components by the
Check steam lines exposed to main or
inspection as has been customary hitherto.
reheat steam for expansion, deformation
and crack. When stipulating the scope of the
inspection, the experience gained from
Casing centre guide comparable units should be taken into
account in the plans and/or the
Disassemble and overhaul. Ensure design
manufacturer is to state at which highly
clearances
stressed points the various components are
to be inspected. It is advisable to get the
SUGGESTED INSPECTION & TESTING special checks and tests conducted by the
PROCEDURES specialists from turbine plant.
During inspection of steam turbine generator
units, certain components are required to be
INTEGRITY ASSESSMENT
inspected in-depth to achieve more accurate
evaluation of their condition. The findings During integrity assessment, following
are to be documented (descriptions, check examination / inspection / testing of steam
calculations, drawings and photographs). turbine parts may be done.
Visual Inspection
− With the naked eye and good Surface crack examination
illumination e.g. 500 Watt − Dye penetration test (DPT)
photographic lamp, mirror
− Magnifying glass − Magnetic particle inspection (cannot
be used on austenitic materials)
− Borescope
5.3-0200-05/7
− Eddy-current examination − Contact print (Replica) procedure
after etching material surface
− Crack depth determination as far as
possible with capacitance probe or
ultrasound Hardness test
5.3-0200-05/8
Steam Turbine Turbine Restart
Maintenance After Boiler Repairs
5.3-0220-00/2
Pre-service inspection and testing of Report on the findings and checks made
major C&I hardware Report on repairs and other actions
- Controllers and protective devices Report on the replacement and spare
- Turbine stress controller parts used or required
Full documentation of the history of a turbine The scope and nature of in-service
unit includes, among other elements, testing
reporting on turbine restart following major Evaluation of turbine performance
inspections or repairs.
Findings from in-service testing
The report on restart should make reference
to certain preceding reports, namely: Matters remaining open (actions,
replacement parts, implementation
Report on the performance of the turbine deadline, etc.)
unit prior to the major inspection
Report on the scope of the inspection
5.3-0220-00/3
Steam Turbine Environmental protection
Maintenance
It is the social and moral obligation of all Oil leakage does not only pollute the
concerned to ensure adequate protection of environment but is also a potential fire
the environment in every wake of operation. hazard. Oil leakage from any source is to be
quickly attended. In the viscinity of high
During maintenance inspection and capital temperature equipment & pipes, any oil
overhauls, it is of paramount importance to leakage has to be immediately attended,
ensure safety of work force by adhering to even if it calls for unit shutdown.
the applicable safety codes. In addition,
while handling and disposing hazardous Steam leakage from any source is
materials, necessary precautions, as associated with thermal & noise pollution of
published from time to time, are to be the environment. Depending on the source
adhered. & parameters of the leakage steam, it can
be injurious to the associated equipment
Some material, through harmless in normal and also to any individual coming in contact.
regime, may become quite hazardous under Any such leakage is to be quickly attended.
different circumstances. Gaskets made of
Fluorelastomers (viz. Viton), when exposed Proper upkeep & periodic lubrication of all
0
to temperatures in the region of 400 C or rotating equipment as per the
higher due to fire or any other reason, get manufacturer’s instructions goes a long way
decomposed. One of the products of such in ensuring their smooth and noise-free
decomposition is Hydrofluoric acid, which is operation.
highly corrosive and any skin contact with it
must be prevented. To promote environment friendly aesthetic
appearance, the external surface of all the
To protect the natural environment and to equipment should be painted once in two
control pollution from disposed hazardous or years. General upkeep and cleanliness
non-bio-degradable material, a proper standard should be maintained all around,
system of disposal is to be evolved and especially around the turbine floor to
compliance ensured. promote a pleasing look.
Oil of viscosity class ISO VG 46, commonly procedure for safe disposal of used turbine
known as turbine oil, is used for lubrication oil is as follows:
of turbine bearings as well as for hydraulic
turning gear. To send the discarded oil to
registered refiners who have facilities to
The oil should comply with the requirements reclaim the oil by physico-chemical
given in Operation and Maintenance Manual treatment for further use in non-critical
[1]. It is recommended that the condition of applications.
oil in use, be periodically monitored to
ascertain the quality and properties of To send the used oil to the parties
turbine oil [2]. All major oil manufacturers who are licensed to handle and dispose
have facility for complete checking of oil used lubricating oil.
properties.
To burn-off the discarded oil in
Turbine oil has to be changed if its boiler furnace by mixing with fuel oil.
properties have crossed discard limits. The
While ordering for spares, complete the functioning. For ordering spares, only the
identification details of the required project specific drawings supplied separately
component should be furnished. The details should be referred and following details may
of components described in various chapters be furnished:
of this manual are given only to understand