IS 1646 : 1997
(Reaffirmed 2002)
Indian Standard
CODE OF PRACTICE FOR FIRE SAFETY OF
BUILDINGS (GENERAL): ELECTRICAL
INSTALLATIONS
(Second Revision)
ICS 91.120;13.220.50
© BIS 1997
BUREAU OF INDIAN STANDARDS
MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG
NEW DELHI 110002
June 1997
Price Group 8
FOREWORD
This Indian Standard (Second Revision) was adopted by the Bureau of Indian
Standards, after the draft finalized by the Fire Safety Sectional Committee had been
approved by the Civil Engineering Division Council.
This standard was first published in 1961, revised subsequently in 1982. The present
revision is based on the subsequent development and modifications in other regulations
such as electrical rules of the Tariff Advisory Committee, Indian Electricity Rules, etc, and
other Indian Standards. Special precautionary measures for use of aluminium conductors
and for use of fluorescent fittings in electrical installations are included in the revision. The
other changes relate to the developments in wiring methods and other general aspects.
The requirements of this code are to be treated as supplementary to the requirements
of the Indian Electricity Act, 1910 and the Rules of 1956 thereunder and in no case as
substitutes. In the preparation of this code, it has been presumed that the electrical
installation work is carried out by qualified contractors and electricians under the
supervision of competent engineers as required by the Indian Electricity Rules.
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 1/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
ii Indian Standard
CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL):
ELECTRICAL INSTALLATIONS
(Second Revision)
1 SCOPE
2 REFERENCES
2.1
The Indian Standards listed in Annex A contain provisions which, through reference
in this text, constitute provisions of this standard. At the time of publication, the editions
indicated were valid. All standards are subject to revision, and parties to agreements based
on this standard are encouraged to investigate the possibility of applying the most recent
editions of the standards given in Annex A.
3 GENERAL REQUIREMENTS
3.1
Besides conforming to this Code all equipment shall comply with relevant Indian
Standard Specifications (wherever available) as regards construction, temperature rise,
current rating, overloads and performance, etc, where an Indian Standard does not exist the
various items of electrical equipments should be those approved by the competent
authority.
3.2
Execution of work unless otherwise exempted under the appropriate rule of the
Indian Electricity Rules, the work of electrical installations shall be carried out by an
electrical contractor licensed and under the direct supervision of a person holding a
certificate of competency and by persons holding a valid permit issued and recognized by
any Indian Government.
3.3
All equipment shall be capable of developing and/or consuming the rated power
safely and continuously (unless specifically meant for intermitent use), without undue
heating, sparking, noise and vibration.
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 2/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
3.4
All electrical equipment shall be securely mounted on the surface on which they are
installed.
3.5
All electrical equipment, fittings, accessories and wiring systems in locations which
are exposed to the following shall be of types approved for particular situations and subject
to special conditions as laid down in the appropriate clauses of this code:
a. Fumes;
b. Flammable or other gases, vapours or liquids having deleterious effect on equipment
and conductors or creating dangerous situations;
c. Dust and fibrous accumulations;
d. Damp or wet locations; and
e. Excessive temperature.
3.6
3.7
The type of wiring installed in a particular occupancy shall be as permitted under the
relevant provisions of this standard.
3.8
4 POWER EQUIPMENT
4.1
4.2
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 3/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
4.3
Equipment which depends on natural air for cooling shall be so located and installed
that air flow over the exposed cooling surface shall not be prevented by adjacent equipment
or walls. For floor mounted equipment, clearance between top surface of the equipment and
the adjacent surface shall be provided to dissipate rising hot air.
4.4
4.5
All equipment of more than 1/4 kW shall be separated from unprotected woodwork
by a distance of at least 300 mm horizontally and 1 200 mm vertically. Equipment of 1/4
kW or less, except those of totally enclosed type, shall be suitably guarded to avoid heat
being transmitted to readily combustible material in the vicinity.
4.6
4.7
4.8
Equipment terminals shall be rigidly designed and planned according to size and
type of machine. Industrial motors shall have a robust metal clad terminal box of adequate
dimensions arranged to receive armoured or vulcanized rubber insulated/PVC cables in
conduits without unnecessary bends in the cables. All terminal boxes shall be entirely
reptile, rodent and insect proof.
5 SWITCHBOARDS
5.1
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 4/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
5.2
The space around the switchboards shall not be used for storing of clothing or other
materials, even for temporary period.
5.3
5.4
All switches and circuit breakers shall be operated from the front of the switchboard.
5.5
All fuses shall be mounted on the front of the switchboard as far as practicable.
5.6
All screws, bolts and nuts, which secure current carrying parts to the board shall be
of brass, copper or similar rustproof material.
5.7
All wires and cables shall be provided with soldered or approved lugs or crimped
joints or any other approved means of connection.
5.8
5.9
Where the switchboard is erected in a room of a building isolated from the source of
supply or at a distance from it, adequate means of control and isolation shall be provided
both near the boards and at the origin of supply.
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 5/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
5.10
All switchboard shall be of metal clad totally enclosed type or any insulated enclosed
pattern which should be fixed at close proximity to the point of entry of supply.
5.11
In case of outgoing circuits from the switchboard, where the current rating exceeds
63A, connection between the busbar chamber and the automatic circuit breaker or switch
fuse or any other control gear shall be made only by solid connections.
5.12
5.13
All circuits shall be clearly and indelibly labelled for identification in English and
vernacular.
5.14
Moulded case circuit breakers shall not be permitted except inside a metal enclosure.
5.15
The neutral of each main and branch main circuit shall be provided with a removable
link placed in an easily accessible position, for purpose of testing. The neutral shall not be
punched at the back of the board.
2
6 POWER DISTRIBUTION AND MOTOR CONTROL GEAR
6.1
All equipment shall be of metal clad construction throughout, dust tight, suitably
proportioned and of adequate capacity and shall conform to the relevant Indian Standards.
6.2
Equipment shall be accessible at all times, stacks of goods and the like shall not
impede access to any part of the equipment.
6.3
Wiring to and from the gear shall be of the armoured, mineral insulated or screwed
steel conduit type and provision shall be made to secure the same by approved and efficient
mechanical methods. Flexible tubing shall not be accepted for general wiring. It may,
however, be used for connections between the terminal boxes of motors and starters,
switches and motors but the length shall be restricted to a maximum of 1 200 mm.
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 6/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
a. The conduits should be supported not more than 800 mm distance and
should have suitable joints.
b. Separate earthing conductor shall be run inside the conduit for earthing
the equipment to which the conductor is connected.
c. Expansion joints shall be provided where required to compensate for
thermal expansion and contraction.
a. In locations less than 2.5 m above walking floor level unless protected
against mechanical damage.
b. Where ambient temperature is likely to be above 55°C at some time or
other during year.
c. In concealed places of combustible construction.
d. In locations where the atmosphere is likely to contain flammable gases or
vapours.
e. In locations where the surrounding atmosphere is likely to affect the
non-metallic conduits.
6.4
6.5
6.6
All current carrying parts, namely terminals, washers and clips shall be of copper,
brass or of any other equally non-rusting material, properly tinned at joints.
6.7
All cables shall be provided with soldered lugs or other approved means for
connection.
6.8
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 7/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
is/are located inside the same compartment but separated from each other by more than 15
m.
6.9
Outgoing circuits shall be clearly marked in English and vernacular, indicating the
department or place or item controlled, by each.
6.10
6.11
Each circuit from a main distribution board shall be provided with a circuit breaker,
linked switches or cut-outs.
6.12
Looping of conductors and tee joints in power wiring shall be provided with a circuit
breaker, linked switches or cut-outs.
6.13
6.14
6.15
6.16
Suitable guard enclosures shall be provided to protect exposed current carrying parts
of motors and insulations of motor leads where installed directly under equipment or in
other locations where dripping or spraying of oil, water or other injurious liquids may
occur, unless the motor is designed for such conditions.
6.17
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 8/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
NOTES
7.2
NOTES
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 9/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
7.3
7.4
7.5
Substations and switchgear rooms shall only be used to house the intended
equipment. Storage of any kind/or any repair work shall not be permitted therein.
7.6
Suitable apparatus shall be provided in approved positions for the control and
protection of windings of transformers.
7.7
All transformers shall have suitable isolating equipment on both high and
low/medium tension side.
7.8
Cable trenches inside substations shall be filled with sand, pebbles or similar non-
flammable materials or covered with incombustible slabs. If a number of cables are taken in
a trench, it is desirable that cables are taken on racks.
7.9
All control gears shall be protected against rodents, reptiles and insects.
7.10
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 10/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
7.11
NOTES
5 000-20 000 8
Over 20 000 15
5. The provisions of 7.1, 7.2, 7.3 and 7.11 are not applicable if the
transformer is filled with non-combustible insulant liquid.
8 EARTH CONNECTIONS
8.1
8.2
In no case shall gas, steam, sprinkler or humidifier pipes be used for an earth
connection.
9 WIRING METHODS
9.1.1
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 11/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
Only such wiring methods as are permissible for a particular situation or location as
laid down in rules under this clause, shall be allowed.
4
9.1.2
Wherever aluminium conductors are used, the special precautionary measures laid
down in IS 732 shall be followed.
9.1.3
9.1.4
9.1.5
9.1.6
Where cables, conduits, cable ducts or trunkings pass through floors, walls,
partitions or ceilings, the surrounding holes shall be made good with cement or similar
incombustible material to the full thickness of floor, wall, etc. In addition where conductors
are installed in channels, ducts, trunkings or shafts passing through floors, walls, partitions
or ceilings, suitable internal fire resisting barriers shall be provided to prevent spread of fire
from one side to the other.
9.1.7
Cables of ac circuits installed in steel conduits, shall always be so bunched that the
cables of all phases and the neutral (if any) are contained in the same conduit.
9.1.8
Ducts of metal or insulating material and trunking shall be securely fixed and where
they are liable to suffer mechanical damage, shall be adequately protected.
9.1.9
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 12/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
9.1.10
Metallic ductings or 450 mm (with concrete envelope of not less than 50 mm around the
trunkings ducting of trunking)
9.1.11
No wiring system of any kind shall be permitted inside ducts needed for transporting
dust, loose materials or flammable vapours.
9.1.12
Electrical services shall not be installed in the same conduit or trunking as pipes or
tubes or non electrical services like air, gas, oil, water, etc.
9.1.13
Only PVC sheathed armoured cables or rigid metallic conduits shall be allowed in
ducts or plenums used for movement of environmental air.
10.1 General
10.1.1
Wiring shall be on distribution board system with main, branch main and final sub-
circuit boards fixed at convenient positions and shall conform to IS 732.
10.1.2
Conductors which are not arranged for connection to the same system and circuit or
which supply different phases of the same supply, shall be kept apart throughout their
entire run. This shall particularly apply to installations in which there are pilot lights in
addition to the main lighting and the like.
10.1.3
Conductors for final sub-circuits shall not be enclosed in the same conduit or casing
as sub main and branch of main conductors.
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 13/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
10.1.4
Conductors which pass through windows or door frames, wood beams walls, ceilings
and floors shall be protected by porcelain tubes or conduits according to the conditions. The
tube or conduit shall extend at least 13 mm on both sides of the wall and 25 mm above the
floor and below the ceiling.
10.1.5
10.1.6
10.1.7
10.1.8
Incoming mains shall be used for control of circuit in conjunction with suitable
circuit breakers.
10.1.9
The system of wiring and all other details shall be suitable to the conditions
prevailing.
10.1.10
10.1.11
Flexible leads shall hang vertically downwards from the ceiling rose without any
obstructions, shall not be in contact with shafting structural member, pipe work, etc, and
shall not be coiled or tied up but cut to correct length.
5
10.1.12
Flexible leads shall be renewed when they show signs of deterioration. Joints in
flexible conductors of pendants shall not be permitted.
10.1.13
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 14/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
Flexible leads shall not be used where they are likely to swing due to ventilation or
humidifier apparatus or any other cause; fixed rod or conduit protection shall be used in
such cases.
10.1.14
10.1.15
Ceiling roses shall be securely fixed and shall be complete with caps.
10.1.16
Straight or slanting wall batten holder shall not be fitted at switchboard height or on
the switchboard.
10.1.17
Shades or reflectors of light points shall not be in contact with structural members,
pipe work, etc.
10.1.18
10.1.19
10.1.20
Only rod pendants shall be used in industrial buildings like textile mills, flour mills,
saw mills, etc.
10.1.21
In ducts and tunnels only bulk head fittings with wires in conduits or armoured
cables shall be used for lighting.
10.1.22
NOTES
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 15/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
10.1.23
10.1.24
Fittings for lamps in places where considerable dust or fluff is present (such as
willowing, lap breaking, waste opening, mixing, blowing, and raising rooms in textile mills,
flour mills, saw mills and other wood working factories, etc) shall be of dust tight type
conforming to IS 4013.
10.1.25
10.1.26
The run or course of wiring shall be arranged to avoid crossing of belt drives; where
such crossing is unavoidable mechanical protection shall be provided against damage by
belt breakages.
10.1.27
The paper insulated lead covered cables shall not be brought right through the
sealing box without a break. The conductors of paper insulated cables shall be terminated in
the trifurcating box and tails of India Rubber (VIR) Conductors sweated by ferrules to the
conductors of paper insulated cables shall be brought through the trifurcating box.
10.1.28
10.1.29
Wiring of lighting circuits shall be on distribution board system and circuit diagrams
shall be attached to it.
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 16/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
10.1.30
Conductors shall be run as far as possible along the walls and ceilings, so as to be
accessible for inspection.
10.1.31
Where two or more points are mounted, with a voltage differences exceeding 230 V
between them, a minimum distance of 2 m between the points shall be maintained to avoid
possibility of shocks.
10.1.32
Cord grips shall be provided for pendant lamp holders of bayonet contact type, and
chain suspended reflector fittings shall have the cable entries made bell-shaped or bushed
to avoid damaging the flexible cables.
10.1.33
Chain suspended fittings, fans, etc, shall be fixed at a distance not exceeding 250 mm
away from ceiling rose.
10.1.34
Where long spans occur between beams and supports, battens shall be provided for
attachment of conduits, casing, or other wiring or fittings. The runners shall be of well
seasoned teak wood, free from shakes, splits, etc, and shall not be less than following
dimensions:
1.2 to 1.8 75 × 38
1.8 to 2.4 75 × 50
2.4 to 3.4 75 × 63
10.1.35
The wiring for hot air chambers shall be mounted on the walls outside the chamber,
as far as possible. The light fittings inside the chambers shall be of oyster type or shall be
waterproof fittings.
6
10.1.36
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 17/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
Where wiring is to be carried along the face of rolled steel joists or stanchions, a
wooden or non-conducting backing, preferably of the full width of joists or stanchions shall
first be laid on the joist or stanchions and secured rigidly thereto. Wooden pieces for the
support of casing or conduit to steel joists or stanchions shall be secured by metal clips with
at least two screws.
10.1.37
Scaffolding ropes shall not be tied round conduits, casings or other forms of wiring.
10.1.38
All strands of cables shall be fitted into terminals of switches, fuses, etc; strands of
cables shall not be cut. In damp locations, the strands shall be soldered together.
10.2
The wiring methods specified in 10.3 to 10.7 shall only be permitted subject to
conditions stipulated therewith.
10.3 Conduits
10.3.1
Conduits and fittings shall be of solid drawn and welded steel of heavy gauge screwed
type, conforming to IS 2667.
a. Conduits should be supported not more than 800 mm and should have
suitable joints;
b. For earthing, separate earthing conductors shall be run inside the
conduit from end to end; and
c. Expansion joints shall be provided, where required, to compensate for
thermal expansion and contraction.
10.3.2
Solid drawn welded steel conduit shall be permitted under all atmospheric conditions
and in all occupancies subject to stipulations laid down in 10.3.3 and 10.3.4.
10.3.3
In damp situations, such as textile sheds, the conduits shall be hot galvanized or zinc
impregnated or treated with special rust-proof paint.
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 18/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
10.3.4
In occupancies like chemical factories, bleach and dye houses, where strong corrosive
vapours are present special conduits or conduits with additional coatings of bitumen paint
or with a glass wool lagging provided with a protective covering shall be used.
10.3.5
a. Where wiring height is less than 2.5 m above working floor level, unless protected
against mechanical damage;
b. Where exposed to ambient temperatures likely to be above 55°C at sometime or other
during the year;
c. In concealed places of combustible construction;
d. Where the atmosphere is likely to contain flammable gases or vapour;
e. Where conductor operates at voltage above 650 V; and
f. In locations where surrounding atmosphere is likely to affect the non-metallic
conduits.
10.3.6
Flexible conduits shall not be used for general wiring. It may be, however used for
connections between terminal boxes of motors and starters, switches and motors but the
length shall be restricted to a maximum of 1 200 mm.
10.4.1
Mineral insulated metal sheathed cables and other types of metal sheathed cables are
permitted under all atmospheric conditions and in all occupancies except as mentioned
hereunder:
10.4.2
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 19/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
In case of wet locations like in parts of laundries, tanneries, etc, and in locations
where walls are frequently washed, a minimum clearance of 6 mm shall be maintained
between mineral insulated cable and the wall to which it is affixed.
10.5.1
Armoured cables shall be permitted under all atmospheric conditions and in all
occupancies except in commercial garages, storage battery rooms and in locations where
they would be exposed to corrosive fumes or gases.
10.6.1
Tough rubber or plastic sheathed cables shall not be permitted in the following
locations:
a. Where considerable dust and/or fly in generally present (for example cotton and jute
mills and other vegetable, fibre processing factories, flour mills, saw mills and other
wood working factories, plastic and rubber goods factories, pulverising works, etc);
7
b. Where atmosphere is likely to contain flammable/explosive gases or vapours;
c. Where the hazardous trades or processes are carried out (for example, oil mills, paint
and varnish factories);
d. Where they would be exposed to mechanical damage (godowns, engine rooms, rope
and motor alleys, etc); and
e. Where wet processes are carried out.
10.6.2
10.7.1
This system shall be permitted for use in industrial buildings for low tension circuits
only, with prior approval of appropriate authority.
10.7.2
When installed in bleaching or dyeing sections of a textile mills, the wiring shall be
held by porcelain bobbins secured to teak wood battens by brass screws and the whole run
inverted.
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 20/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
10.7.3
This system shall not be used for any type of building of permanent nature other than
of the kind mentioned in 10.7.2.
10.8.1
All cable trays or wire or bus ducts shall be constructed from earthed sheet metal,
enclosed or open troughs with hinged or removable covers housing and protecting either
electric wires and cables, installed at site, or factory mounted bare conductors of aluminium
or copper and shall be capable of withstanding electro-mechanical stresses.
10.8.2
Such systems shall be permitted under all atmospheric conditions and all
occupancies except in following locations:
10.8.3
10.8.4
10.8.5
10.8.6
Extensions and branches of such systems shall also be of the same type.
10.9.1
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 21/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
Such systems may be permitted under all atmospheric conditions and in all
occupancies except where exposed to corrosive vapours and locations where
flammable/explosive vapours or gases may be present, unless the cables or conductors are
specially approved for such use or the trenches are completely filled with sand.
10.9.2
10.9.3
The top of the trenches shall be covered with removable concrete slabs or chequered
plates.
10.9.4
In case of long trenches, it is recommended that trenches of more than 1 000 cm2
cross-sectional area be divided by incombustible barrier walls at intervals not exceeding 45
m. Such barrier wails shall be of at least 50 mm thickness and of the same height as of the
cable trench. The cables shall be carried through holes in these barrier walls, which shall be
made good thereafter to prevent passage of fire beyond the barriers (see also IS 12459).
10.9.5
The combined cross-sectional area of all conductors or cables shall not exceed 40
percent of the internal cross-sectional area of the trench.
10.9.6
The trench shall be kept free of accumulation of water, dust and waste materials.
10.11.1
a. Pendants;
b. Wiring of fixtures;
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 22/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
10.11.2
Where a lighting fitting is supported by one or more flexible cords, the maximum
mass to which twin flexible cords may be subjected shall be as follows:
10.11.3
Where flexible cables or cords are exposed to risks of contact with oil or petrol or
where cable which will not support combustion is required, use shall be made of cables or
cords having a PVC or oil resisting and fire retardant sheath.
10.11.4
Flexible cables and cords shall not be used as fixed wiring unless contained in
earthed metal or any other non-combustible and mechanically strong enclosure. This
requirement need not, however, apply to short lengths of sheathed flexible cable or flexible
cord used as final connections to fixed apparatus or for connections of control gear of
fluorescent lamps or discharge lamps. Non-sheathed flexible cables and flexible cords shall
not be drawn into conduits or ducts.
10.11.5
Flexible cables or cords shall also not be run through holes in walls, ceiling or floors
or through doors, windows or other similar openings. Nor shall they be permitted to be
concealed behind walls, ceilings or floors.
10.12.1
Bare conductors are permitted for low tension side, of drawing frame transformer
circuits where the potential difference does not exceed 12 volts. Bare or lightly insulated
conductors of extra low voltage systems shall have adequate insulation and further
protection, where necessary, to ensure that they do not cause risk of fire.
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 23/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
Bare conductors are also permitted for cranes and hoists subject to special conditions
laid down in this code for such equipment.
10.13.1
The lightning protection system for buildings shall generally conform to IS 2309.
10.13.2
All overhead transmission lines, including compound lines shall not be run above any
process or storage blocks or open storage site.
10.13.3
Lightning arresters shall be provided for lines at both ends and at supports where
exposed to and liable to damage or injury from lightning. The arresters shall preferably be
of the non-horn type for low and medium tension because of likely damage by buds and
distortion.
10.14.1
All wall plugs and sockets in industrial buildings shall be of metal clad 3 pin pattern
separately controlled by a switch, adjacent to the wall socket.
NOTE—This shall not apply in case of wall plug and socket with current
ratings of 5 amp and less.
10.14.2
Where it is necessary to earth the metal case of wall plug and/or portable appliances,
the connection shall be done with soldered or approved lugs or crimped joints or any other
approved means of connection.
11.1.1
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 24/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
c. Flame proof explosion type—For use in places where flammable/explosive gases and
vapours are present.
NOTES
11.2.1
Main switches and fuses shall be metal clad and branch main board shall be metal
clad when used on medium tension circuits.
11.2.2
11.2.3
Each circuit from main distribution centre except fuse distribution board shall be
provided
11.2.4
11.2.5
Each final sub-circuit from a distribution board shall be controlled by a single pole
switch connected to the live, outer or phase conductor.
11.2.6
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 25/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
Wood work shall not be used for mounting of or construction of the frame work for
iron clad switch, distribution boards and control gear.
11.2.7
All equipment shall be numbered in English and vernacular for ready identification
and to indicate the department, place or circuit controlled.
11.2.8
12.1.1
The antenna of radio and television sets shall be connected through a double pole
change over switch so connected that the antenna and the set completely earthed when not
in use of during, thunderstorms.
12.1.2
The antenna shall be provided with a suitable lightning arresters if situated in an area
subject to heavy thunderstorms.
12.1.3
All circuits (aerial and all internal wiring) shall be so constructed that contact with
any other electric light and power circuits is impossible.
12.1.4
The lead-in conductor shall be of copper and shall be not less than 2 mm in diameter.
12.1.5
The lead-in conductor shall enter the building through a non-combustible and non-
absorptive insulating bushing.
12.2.1
The installation and precautionary measures shall comply strictly with Rule 73 of
Indian Electricity Rules.
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 26/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
12.2.2
12.3.1
Motor generator sets and/or separate generators and/or rectifiers together with
necessary switch and control gear shall be separated by blank walls or located sufficiently
away from the electrolyser.
12.3.2
12.3.3
Windings and insulation generally shall be specially treated to resist the corrosive
effects of the electrolytic fumes.
12.4.1
Electrostatic charge eliminating devices shall be provided for all high speed machines
and equipment of similar type where static electricity may be developed, specially during
dry seasons of the year.
12.5.1
The lighting inside cold storages shall be in heavy gauged screwed steel conduit and
water tight fittings shall be used throughout.
12.5.2
12.6.1
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 27/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
In industry sufficient spare power shall always be available to drive the fire pump
set(s) at all times throughout the year.
12.6.2
The power station and/or substation(s) supplying power for fire pump circuit shall
be so placed that any falling masonry and the like from other buildings occasioned by a fire
or other cause cannot damage the station and cut off power to the fire pump circuits.
12.6.3
A direct feeder, without any tappings shall be laid from the substation to the pump
house to ensure that the supply to the pumping set(s) is entirely independent of all other
electrical equipment in the premises viz, even when power throughout the rest of the
premises is switched off the supply to the fire pumps remains available uninterrupted.
Overhead feeders to sub-stations
10 supplying power to the fire pumps are not permitted within a horizontal distance of:
In case the feed to such sub-station is by means of under-ground cables, the cables
shall not pass under any building or permanent structure.
12.6.4
Where there is more than one sources of power for the operation of pumping set(s),
the electrical circuits shall be so designed as to ensure that when necessary the set(s) shall
continue to operate without manual operation of any emergency switch, when the supply is
interrupted.
12.6.5
Indicator lamps shall be fitted in prominent position(s) both in the sub-station and
pump house, which would continuously glow as long as power is available to the fire
pump(s). A sound alarm shall also be provided in the event of power failure to the fire
pumps.
12.6.6
The pump set(s) shall be of direct coupled type, securely mounted on robust bed-
plate(s), if or horizontal type and should be free from vibrations at all variations of load.
12.6.7
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 28/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
The motors of fire pumps shall be either of totally enclosed or drip-proof type, the
latter having air-inlets and outlets protected with meshed wire panels to exclude rodents,
reptiles and insects.
12.6.8
The motors shall be wound for Class-E insulation and the windings shall be vacuum
impregnated with heat and moisture-resisting varnish preferably glass-fibre insulated, to
withstand tropical conditions.
12.6.9
Motors wound for high-tension supplies shall have a suitable fixed warming
resistance to maintain the motor windings in a dry condition at all times and particularly
under monsoon conditions. The resistance shall be fed from medium voltage circuits.
12.6.10
Heating apparatus shall also be provided, when necessary, for medium tension
motors where they are located below ground level, in order to maintain the motor winding
in a dry conditions. Adequate drainage shall also be provided in the pump house in such
cases.
12.6.11
The pumping set shall preferably be housed in a separate building located at least 6
m away from all other buildings and at least 15 m away from units and/or storage tanks of
plant handling flammable liquids/gases.
12.6.12
The motor rating should be adequate to drive the pump when operating on 150
percent of rated flow.
12.6.13
The fire pump circuit shall be protected at its origin by an automatic circuit breaker,
from which either the no volt coil is removed or which is fitted with automatic re-setting
type of no-volt coil, and the overload setting shall be so adjusted as to permit the motor to
carry on overload of 50 percent of its rated capacity.
12.6.14
Cables for motors of fire pumps and their switchgear shall be armourd or shall be
enclosed in heavy gauge screwed steel conduit. Overhead lines shall not be permitted within
6 m of window, door or other opening in any of the protected building or any other building
within 15 m of a protected building.
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 29/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
12.6.15
12.6.16
Pumping sets shall be worked for at least 15 min each week and records of the same
shall be maintained.
12.6.17
The incoming cable to the fire pump room shall terminate in an isolating switch fuse
unit incorporating HRC fuses and where necessary provided with distribution system.
12.6.18
The starting switchgear for the fire pumps should be suitable direct on line starting
but other alternative arrangements are acceptable with the approval of competent
authority.
For the purpose of this code a location shall be regarded as hazardous where any one
or more of the following conditions exist:
13.1.1
In locations where the atmosphere may contain flammable gases or vapours the
classification of areas and selection of Electrical
13.1.2
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 30/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
if such liquid is (a) sprayed or (b) present in the form of mist or (c) heat to or above its flash
point.
13.1.3
13.1.4
Except the wiring of rigid metal conduits and armoured cable wiring, no electrical
equipment or fittings shall be permitted where it may be subjected to hazardous
accumulation of readily ignitable deposits or residue, as within a spray painting booth or
drying oven.
13.1.5
a. lighting fittings are of fixed type and installed behind glass panels;
b. glass panel(s) is so sealed, that, it effectively isolates the lighting equipment from the
hazardous area;
c. panels are so located that deposits of hazardous residues on them are avoided as far
as possible; and
d. glass used for panel is either of the wired or specially toughened type.
13.1.6
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 31/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
special provisions:
13.2 Lifts
13.2.1
The installation of lifts and care of electrical installation shall fully comply with
relevant provisions of IS 1860 and IS 4666.
13.3.1
Electrically operated valves shall be so designed that they can also be manually
operated.
13.3.2
The valve or valves shall close automatically when the electric supply ceases.
13.3.3
All fusible links in the circuit supplying the valve or valves shall be in series and on
the live lead.
13.3.4
The circuit in which the possible links form a path for the current to the fire valve
shall be a
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 32/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
13.3.5
Equipment shall be of certified ‘flame proof type unless it is separately mounted and
is away from any possible source of fumes.
13.4.1
Where general lighting of the auditorium and exits can be controlled from within the
enclosure, separate and independent means of control shall also be provided outside the
enclosure and well away from it.
13.4.2
All switches, fuses and connections thereof shall by totally enclosed and iron-clad
and all electric lamps and resistances so protected as to avoid their possibility of coming
into contact with or in close proximity of films or other combustible materials. Resistance
connected with auditorium or stage lighting shall not be located in the projection or
rewinding rooms.
13.4.3
The insulating material of all electric cables including leads to lamps shall be covered
with fire resisting material.
13.4.4
There shall be no unnecessary and loose electric cable. The ‘leads’ to the projector
lamps shall be taken as separate circuits from the source of supply and from the supply side
of main fuses in general lighting circuit. Efficient switches and fuses shall be inserted at the
point where the supply is taken, and, in addition, an efficient double pole switch shall be
fitted in the cinematograph lamp circuit inside the enclosure. When the cinematograph
lamp is working the voltage across the terminals of the double pole switch inside the
enclosure shall not exceed 110 volts.
13.4.5
Cables from projector lamps should be taken as separate circuits from the source of
supply and from the supply side of main fuses in general lighting circuit. Efficient switches
and fuses should be inserted at the point where the supply is taken, and in addition, an
efficient double pole switch should be fitted in the cinematrograph lamp circuit inside the
enclosure when the cinematograph lamp is working the voltage across the terminals of the
double pole switch inside the enclosure should exceed 110 volts.
13.4.6
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 33/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
13.4.7
The operator shall satisfy himself before the commencement of each performance
that all cables, lead connections and resistances are in proper working order. The resistance
shall be inspected at least once during each performance. If any fault is detected, current
shall be immediately switched off and shall remain switched off until the fault has been
remedied.
13.5.1
Charging shall be carried out in well ventilated situations and no smoking or naked
lights shall be allowed.
13.5.2
13.5.3
13.5.4
13.5.5
The charging circuit shall be provided with double pole switches and fuses, and,
where a motor generator is employed the motor shall be provided with double pole switches
and fuses and an automatic battery cut-out shall be placed in the generator circuit. Any sub-
circuit shall be provided with a fuse rated at not more than 7 A in each live conductor.
13.5.6
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 34/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
13.5.7
If accumulators are charged through resistance coils or lamps, such resistance coils
or lamps shall be at least at distance of 60 cm from the nearest accumulator.
13
13.5.8
All wiring shall be securely mounted and protected against mechanical injury and
efficient terminal or connections shall be provided from which the connections to the
accumulators can be made. Rubber or P.V.C. insulated wiring, if on insulators shall not be
run in such a position that a fire arising at any accumulator could reach it. All conductors
connecting supply terminals to the accumulators shall have either rubber or tough
compound insulation without a tape or braid.
13.5.9
If the supply is taken from mains having one conductor earthed, the lamps or other
resistances shall be connected on non-earthed lead and the accumulators connected direct
to earthed conductor. Precaution shall be adopted to prevent the attendant receiving
shocks.
13.5.10
13.5.11
13.5.12
13.6.1
All electric distribution cables/wiring shall be laid in a separate fire resistant duct.
The duct shall be sealed at every floor with non-combustible materials having the same fire
resistance as that of the duct. Low and medium voltage wiring running in shafts and in false
ceiling shall run in separate conduits.
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 35/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
13.6.2
Separate circuits for water pumps, lifts and staircase and corridor lighting and
blowers in pressurising system shall be provided directly from the main switchgear panel
and these circuits shall be laid in separate conduits so that fire in one circuit will not affect
the others. Master switches controlling essential service circuits shall be clearly labelled.
13.6.3
Staircase and corridor lights shall be on separate circuits and shall be independently
connected so that it could be operated by on switch installation on the ground floor easily
accessible to fire fighting staff at any time.
13.6.4
13.6.5
If more than 200 litres of oil are contained in any oil immersed electric gear a
retaining sill threshold shall be provided around the gear or at the door.
14 GODOWNS
14.1 General
Wiring shall either be in rigid steel conduits or armoured cable. Wall brackets shall
be eliminated and rod pendants and batten holder fittings shall be erected for the lamps
which shall be of a type protected against mechanical damage. Industrial type fluorescent
light fittings shall, however, be permitted. The fittings for lamps shall be fixed at sufficient
height above the highest level of bulk or other goods which are stored in the godown. The
circuit shall be controlled by a linked switch and cut-outs which shall be placed outside the
godown in a convenient portion.
14.2.1
The supply of electricity shall be at low voltage, that is, not exceeding 250 volts.
14.2.2
All wiring shall be encased in screwed steel conduits, the horizontal portions of which
shall be sloped to allow condensed moisture to collect at set places where drainage outlets
shall be provided. Such outlets shall be properly secured, against entry of insects, etc.
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 36/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
14.2.3
The cable used shall not be of less than 3/.029 size of 250-V grade and shall be of
single core, rubber or PVC insulated, taped and branded.
14.2.4
14.2.5
The conduit shall be affixed to (not recessed into) walls or roofs of godowns by means
of saddles grouped on walls or roofs, the distance between saddles not exceeding 750 mm.
All conduits must be laid externally on the outside walls or roofs of the godown except those
lengths which are required to carry the cables to light fittings. In the latter case, the conduit
should be run above the level of highest stacking.
14.2.6
Only bulkhead light fittings of approved design with C.I. frames of robust
construction and bulkhead glasses protected with thick steel lined guards shall be used.
14.2.7
Each lighting fittings shall be affixed to the wall or at not more than 450 mm below
the roof of the godown. In case of a sprinklered godown each lighting fitting shall either be
above the level of the sprinkler heads or not less than 300 mm below that level, it being
understood that in no case shall a light fitting be installed low than 750 mm above the
maximum stacking height.
14.2.8
All lights in the godown shall be controlled by one or more double pole metal-clad
switches and
14 fuses situated outside the godown in a convenient place and effectively protected
from weather.
14.2.9
An indicator light controlled by the switch(es) shall be provided on the switch panel
to show whether the lights inside the godown are on or off when the godown is closed and
locked.
14.3.1
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 37/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
14.4.1
Lamps in nitrocellulose storage rooms shall be rigid fixtures of glass enclosed and
gasketted type or flameproof fluorescent fittings. Lamps shall be controlled by a switch
having a pole in each unearthed conductor. This switch shall be located outside the room
and provided with a pilot light to indicate whether the switch is ‘on’ or ‘off’. This switch
shall disconnect from all sources of supply all unearthed conductors terminating in any
outlet in the room.
14.4.2
No socket outlets, electric motors, heaters, portable lights or other portable electric
equipment shall not be located in nitrocellulose storage rooms.
15 TESTING
15.1
15.2
The following tests shall be carried out as required by the appropriate authority:
1. All switches ‘on’ and consuming devices in circuit, both poles connected
together to obtain resistance to earth;
2. Between poles with lamps and other consuming devices removed and switches
‘on’; and
3. With lamps and other consuming devices in position but switches ‘off’.
d. Earth continuity tests.
e. Power circuits to be tested between phases or outer and middle or neutral wires and
to earth.
15.3
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 38/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
The appropriate authority shall have the right to vary the foregoing tests or carry out
further tests as may be considered necessary.
16 INSPECTION
16.1
All electrical inspections shall be inspected, periodically and proper vigilance shall be
kept. Any faults or defects that are notice shall be attended to and the defects rectified
immediately.
15
ANNEX A
LIST OF REFERRED INDIAN STANDARDS
(Clause 2)
IS No. Title
732 : 1989 Code of practice for electrical wiring installations (third revision)
1860 : 1980 Code of practice for installation, operation and maintenance of electric passenger
and goods lifts (first revision)
2309 : 1989 Code of practice for the protection of buildings and allied structures against
lightning (second revision)
2667 : 1988 Fittings for rigid steel conduits for electrical wiring (first revision)
5571 : 1979 Guide for selection of electrical equipment for hazardous areas (first revision)
5572 : 1994 Classification of hazardous areas (other than mines) having flammable gases and
vapours for electrical installations (second revision)
9537 (Part 3): Conduits for electrical installations: Part 3 Rigid plain conduits of insulating
1983 materials
16 ANNEX B
FLUORESCENT LAMP FITTINGS
(Clause 11.1.1)
B-1.1
The general design of reflectors shall be of suitable type and material. The material
shall be any suitable metal or plastic. If plastic of a combustible nature is used, it shall not
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 39/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
be in contact with any electrical conducting part and shall not ignite by the radiation from
the lamp.
B-1.2
The auxiliary equipment, that is, choke coil, power-factor condenser and stating unit
(comprising thermal switch, radio-suppresser condenser) shall comply with relevant Indian
Standards Specifications and shall preferably be mounted on the lamp fitting itself in a
dust-tight enclosure, but if any item is mounted separately it shall be mounted on parts
made of non-combustible material.
B-1.3
The wiring connections between the equipment, that is, chockes and condensers,
shall be in PVC insulated wiring, properly clamped as necessary.
B-1.4
The suspension shall be made by two conduits or rods or robust chains, spaced to
share equally the weight of the fitting.
B-1.5
The lamp or tube holders may be of plastic material provided these are of efficient
and approved design, and that each tube is securely held by suitable metal spring clips at
each end.
B-1.6
Earthing of the fixture shall be made with an unbroken conductor, the suspension
chains (where employed) shall not be regarded as an approved means of earthing.
B-1.7
Florescent fixtures may be suspended from conduit wiring junction boxes as a means
to prevent exposure of conductors from the fitting to the wiring in the conduit. The
connection inside the junction box shall be made to a porcelain junction base. Plain
procelain connectors shall not be permitted in the box.
B-2.1
Mild steel trough suitably enamelled or painted or any other robust reflectors shall be
used which may, if necessary, have upward lighting slots.
B-2.2
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 40/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
The auxiliary equipment, that is, choke coil, power-factor condenser and starting unit
(comprising thermal switch and radio-suppresser condenser) shall conform to relevant
Indian Standards and shall be mounted on suitable framework in a separate detachable
dust-proof non-ventilated box, with tight fitting covers securely fixed by machine screws
and bolts to the main trough.
B-2.3
The wiring connections between the equipment housed in the choke and condenser
box shall be vulcanised rubber insulated flexible cabling or approved PVC insulated
conductors in heavy gauge, welded or solid-drawn steel conduit, or run internally and
properly clamped.
B-2.4
Suspension shall be made by two conduits spaced to share equally the weight of the
fitting. Each conduit rod shall be provided with a spring loaded ball-and-socket joint ceiling
plate at the top, and the other end shall be bolted to the trough.
B-2.5
Lamp or tube holders shall be made of plastic, provided an efficient and approved
design is employed and each tube is held with suitable metal spring clips at each end.
B-2.6
B-2.7
B-2.8
B-2.9
Incoming twin twisted flexible conductor shall enter the side of the box through a
dust-tight bushed hole.
B-2.10
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 41/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
The lighting tubes and reflectors shall be kept clean to obtain maximum efficient
light. Cleaning shall be carried out by competent personnel.
17
ANNEX C
FIRE SAFETY SECTIONAL COMMITTEE, CED 36
(Foreword)
Chairman Representing
Members
Dr K. S. Uppal (Alternate)
Shri S. M. Desai In personal capacity (B-4/5 A.G. Khan Road Municipal officers
Society, Worli, Mumbai)
Shri P. N. Ghosh In personal capacity (J-1916, Chittaranjan Park, New Delhi 19)
Lt-Col A. T. Parnaik
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 42/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
Shri P. N. Panchal In personal capacity (46, Block E-1, Pocket-11, Sector 15, Rohini,
Delhi)
Member Secretary
S. Chaturvedi
Dy Director (Civil Engg), BIS
18
Bureau of Indian Standards
BIS is a statutory institution established under the Bureau of Indian Standards Act,
1986 to promote harmonious development of the activities of standardization, marking and
quality certification of goods and attending to connected matters in the country.
Copyright
BIS has the copyright of all its publications. No part of these publications may be
reproduced in any form without the prior permission in writing of BIS. This does not
preclude the free use, in the course of implementing the standard, of necessary details, such
as symbols and sizes, type or grade designations. Enquiries relating to copyright be
addressed to the Director (Publication), BIS.
https://law.resource.org/pub/in/bis/S03/is.1646.1997.html 43/44
02/09/2024, 13:12 Indian Standard: CODE OF PRACTICE FOR FIRE SAFETY OF BUILDINGS (GENERAL): ELECTRICAL INSTALLATIONS (S…
Amendments are issued to standards as the need arises on the basis of comments.
Standards are also reviewed periodically; a standard along with amendments is reaffirmed
when such review indicates that no changes are needed; if the review indicates that changes
are needed, it is taken up for revision. Users of Indian Standards should ascertain that they
are in possession of the latest amendments or edition by referring to the latest issue of ‘BIS
Handbook’ and ‘Standards Monthly Additions’.
This Indian Standard has been developed from Doc: No. CED 36 (5418).
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
Headquarters:
Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002 Telegrams: Manaksanstha
Central : Manak Bhavan, 9 Bahadur Shah Zafar Marg NEW DELHI 323 76 17, 323 38 41
110002
Eastern : 1/14 C.I.T. Scheme VII M, V.I.P. Road, Maniktola 337 84 99, 337 85 61
CALCUTTA 700054 337 86 26, 337 91 20
Southern C.I.T. Campus, IV Cross Road, CHENNAI 600113 235 02 16, 235 04 42
: 235 15 19, 235 23 15
Western : Manakalaya, E9 MIDC, Marol, Andheri (East) MUMBAI 832 92 95, 832 78 58
400093 832 78 91, 832 78 92