Homework 9 Example Solution
Homework 9 Example Solution
Given Information:
• Moment frame locations given in the plan below. Use dimensions between gridlines and story
heights from the structural drawings posted on Canvas for Homework 4.
• Lateral forces from ELF for the E-W direction are: F2=74.2 kips, F3=163 kips, F4=259 kips, F5=303
kips, FPHroof=101 kips. This includes consideration of the redundancy factor.
• From a rigid diaphragm analysis, the force in the most heavily loaded moment frame is 0.36Fi
for the typical floor. At the penthouse roof, the lateral force to this moment frame is 0.50Fi.
• The vertical loading for the moment frame beams is D=3.0 k/ft (includes self-weight) and L=1.7
k/ft. Assume this is the same for the beams at every level including the roof.
1 3 4 5 6 7 8 9 10 12 13
B
C
D
E
W24x76
W14x176 W24x76
W14x176
W14x176
W14x176
W14x176
W14x176
W14x90
W14x90
W30x116
Beam to be
W36x150 checked
Column to
W14x176
W36x150
W14x176
be checked
W14x370
W14x370
W14x370
W14x370
W14x370
W14x370
Connection
to be
designed
1. Verify that the beam and column satisfy highly ductile section criteria. Assume the axial force in
the beam is Pu=50 kips, and column is Pu=442 kips.
2. Check that the beam and column satisfy prequalification limits for a WUF-W given in AISC 358.
3. Do Steps 1 through 6 in the Design Procedure in AISC 358 Section 8.7. A few notes for you:
a. Step 3 says to calculate required shear force (demand). As part of this step, it is also
necessary to verify that the beam’s design shear strength (capacity) is sufficiently large
using AISC 360 Chapter G.
b. Step 4 includes the panel zone check. If doubler plates are required, determine the
doubler plate thickness and verify that it satisfy the requirements in AISC 341 E3.6e.
c. Step 4 also includes the strong column weak beam check. Use 442 kips as the column
axial force.
d. Step 6 involves checking for continuity plates. If continuity plates are required, make
sure they satisfy AISC 341 Section E3.6f.
4. Draw a detail of the identified moment connection
a. Identify all demand critical welds
b. Identify the protected zone and show dimensions
c. Give specific weld information including what to do with back up bars
d. Specify the weld access hole geometry and shear plate geometry either by providing all
the relevant dimensions or by including (and citing from your drawing) the typical
details in your submittal.
CEE5470 Abdullah Al Rufaydah HW#9
ORIGIN ≔ 1
QUESTION (1): Verify that the beam and column satisfy highly ductile section criteria. Assume
the axial force in the beam is Pu.b ≔ 50 kip , and column is Pu.c ≔ 442 kip .
From AISC Manual, Table 2-4 (assume A992 fy ≔ 50 ksi fu ≔ 65 ksi E ≔ 29000 ksi
for columns and beams)
From AISC 341 Seismic Provisions, Table A3.1 Ry ≔ 1.10
Beam Check:
‾‾‾‾‾‾
E
For Flange: λhd.f.b ≔ 0.30 ⋅ ―― = 6.889 > λf.b = 6.37
Ry ⋅ fy
Pu.b
For Web: Ca.b ≔ ―――― = 0.021
Ry ⋅ fy ⋅ Ag.b
‾‾‾‾‾‾
E
λhd.w.b ≔ 2.5 ⋅ ⎛⎝1 - Ca.b⎞⎠ 2.3 ⋅ ―― = 54.733 > λw.b = 51.9
Ry ⋅ fy
Beam Section is Highly Ductile OK
Column Check:
‾‾‾‾‾‾
E
For Flange: λhd.f.c ≔ 0.30 ⋅ ―― = 6.889 > λf.c = 3.1
Ry ⋅ fy
Pu.c
For Web: Ca.c ≔ ―――― = 0.074
Ry ⋅ fy ⋅ Ag.c
‾‾‾‾‾‾
E
λhd.w.c ≔ 2.5 ⋅ ⎛⎝1 - Ca.c⎞⎠ 2.3 ⋅ ―― = 48.134 > λw.c = 6.89
Ry ⋅ fy
PageQUESTION
1 of 7 (2): Check that the beam and column satisfy prequalification limits for a WUF-W
given in AISC 358. Non-Commercial Use Only
CEE5470 Abdullah Al Rufaydah HW#9
QUESTION (2): Check that the beam and column satisfy prequalification limits for a WUF-W
given in AISC 358.
(6) Width-to-thickness ratios for flanges and web of the beam conform to AISC 341 requirements (this
was done in problem 1). OK
(7) Beam is laterally braced at plastic hinges by floor beams just outside the protected zone. OK
(8) No attachments/defects in the protected zone 3ft from the face of the column. OK
PageQUESTION
2 of 7 (3): Do Steps 1 through 6 in the Design Procedure in AISC 358 Section 8.7.
Non-Commercial Use Only
CEE5470 Abdullah Al Rufaydah HW#9
QUESTION (3): Do Steps 1 through 6 in the Design Procedure in AISC 358 Section 8.7.
Sh ≔ 0 in for WUF-W
2 Mpr
Vu.b.eq ≔ ―― = 388.842 kip beam shear due to earthquake
Lh
Page 3 of 7
Non-Commercial Use Only
CEE5470 Abdullah Al Rufaydah HW#9
check strong-column-weak-beam
⎛ dc ⎞
Beam Mpr = 3728.083 kip ⋅ ft Mpb_star ≔ Mpr + Vu.b ⋅ ⎜―+ Sh⎟ = 4055.994 kip ⋅ ft
⎝2 ⎠
⎛ Pu.c ⎞
Column Mpc ≔ Zx.c ⋅ ⎜fy - ―― ⎟ = 2817.957 kip ⋅ ft Mpc_star ≔ Mpc = 2817.957 kip ⋅ ft
⎝ Ag.c ⎠
ΣMpc_star
―――― = 0.695 < 1.0 NG Note: Strong-Column-Weak-Beam check
ΣMpb_star fails. However, we will move forward for the
check panel zone shear purpose of this assignment.
Pu.c = 442 kip < 0.75 ⋅ fy ⋅ Ag.c = 4087.5 kip use AISC J10.6 (Eq.10-11)
⎛ 3 ⋅ bf.c ⋅ tf.c 2 ⎞
ϕRn ≔ 1.0 ⋅ ⎛⎝0.6 ⋅ fy⎞⎠ ⋅ dc ⋅ tw.c ⋅ ⎜1 + ―――― ⎟ = 1184.102 kip < Vpz = 2093.315 kip NG, we need
⎜⎝ db ⋅ dc ⋅ tw.c ⎟⎠ doubler plates
Use a 1-in thick doubler plate on each side of the column (two plates total)
zplates
I
Page 4 of 7
Non-Commercial Use Only
CEE5470 Abdullah Al Rufaydah HW#9
Other requirements for doubler plates in AISC 341 E3.6e.3 (Doubler plates without
continuity plates):
(1) Thickness is 1in > 1/4in. OK
(2) Use PJP weld to column web.Ok
(3) Extend 6 in above and below the beam flanges. ok
dz + wz
tdp = 1 in > ――― = 0.518 in OK, no doubler plate buckling
90
Page 5 of 7
Non-Commercial Use Only
CEE5470 Abdullah Al Rufaydah HW#9
ϕRn_J10.min ≔ min ⎛⎝ϕRn_J10.1 , ϕRn_J10.2 , ϕRn_J10.3⎞⎠ = 1430.92 kip WLY controls J10.2
PageQUESTION
6 of 7 (4): Draw a detail of the identified moment connection
Non-Commercial Use Only
CEE5470 Abdullah Al Rufaydah HW#9
3A
an
JP Beam
BackupBar W36 150
5116 to Column
was
Column erectionbolts
PJPShearplate
W 4 370 toColumn
CJPBeamweb
toColumn
shearplate
1in doubler tp34in end of
plate on each seeFig bi
protected
side zone
tpy.at
ffmmEEEes3
Inoue
mix Bar
Backup
Backgouge
516 Reinf Fillet
FigCall Fig bi
Page 7 of 7
Non-Commercial Use Only