Eaton 9PHD Industrial UPS 30 - 200 kW

Technical Specification

GENERAL
Output power rating (PF 1.0) 30, 40, 50, 60, 80, 100, 120, 150, 160, 200 kW
External paralleling Up to 8 units with HotSync technology

Efficiency in double-conversion mode Up to 97%

Efficiency in Energy Saver System (ESS) Up to 99%


mode
UPS topology IGBT with PWM, double conversion
Degree of ingress protection IP23, IP33 or IP54
Ambient temperature 0°C to 40°C up to 1000m altitude, higher ratings as optional
RoHS/WEEE compliancy Yes

INPUT
Nominal voltage rating 380 V, 400 V, 415 V, 440 V or 480 V, conficurable
Input voltage with internal transformers 208 V - 690 V
Input frequency range 40 - 72 Hz
Input wiring 3ph+N+PE / 3ph+PE

Input power factor 0.99


Input THDi 100% linear load < 4,5%
Soft start for generators Yes
Internal back feed protection Yes, for rectifier and bypass lines

OUTPUT
Output wiring 3ph+N+PE / 3ph+PE
Rated output voltage 380 V, 400 V, 415 V, 440 V or 480 V, configurable
Output voltage with internal transformers 208 V - 690 V
Output frequency 50 Hz / 60Hz configurable
Output UTHD < 1% (100% linear load), < 5% (reference non-linear load)
Default overload capacity 10 min 102 – 110% load
on inverter 60 s 111 – 125% load
10 s 126 – 150% load
300 ms > 150% load
Max overload capability 60 min 102 - 110% load
on inverter 10 min 111 – 125% load
60s 126 – 150% load
300ms > 150% load
Overload capability on bypass Continuous < 125% load, 50 ms 2000% load
Rated output power factor 1.0
Load power factor range 0.8 lagging to 0.8 leading
Eaton 9PHD Industrial UPS 30 - 200 kW

BATTERY
Battery technology VRLA, Li-Ion, NiCd, Eaton Super Capacitors
Nominal battery voltage 432 V - 480 V
Maximum charging current 29.3 A, 58.6 A, 87.9 A, 117.2 A depending on model
Charging method Voltage regulated current limited with Eaton ABM technology
Boost charge function Yes
Temperature compensation Yes
Battery start option Yes

Communications
MiniSlots 4 communication bays for Web/SNMP, ModBus/Jbus & Industrial realy

Standard connectivity ports Device USB and Host USB, RS-232 service port, relay output, 5 building
alarm inputs, 1 relay output and a dedicated EPO

Accessories
Accessories for UPS Internal transformers; Vibration dampers with mounting brackets; Seismic
kit; Internal automatic transfer switch; Single feed kit; Earth fault
monitoring; 24V Emergency Power Off (EPO); Custom system and
battery voltages; Custom colors; Exhaust air management options

Accessory cabinets Industrial battery cabinets with long-life batteries; Matching transformer
cabinet for one or two transformers; External maintenance bypass switch.

COMPLIANCE WITH STANDARDS


Safety (CB certified) IEC 62040-1

EMC IEC 62040-2

Performance IEC 62040-3

RoHS EU directive 2011/65/EU

WEEE EU directive 2012/19/EU

Seismic testing NEBS GR-63-CORE, Zone 4

Due to continuous product imrovement programmes, specifications are subject to change without notice.
For product specific specifications, contact Eaton sales representatives.