UNIVERSITY OF SCIENCE AND TECHNOLOGY OF SOUTHERN PHILIPPINES

COLLEGE OF ENGINEERING AND ARCHITECTURE

CE 426|PROJECT PROPOSAL
THREE - STOREY RESIDENTIAL BUILDING
AT CAGAYAN DE ORO CITY

Submitted by:

Kenneth Acuman
Jaymar Cahoy
Bonna Mae Dominguez
Cherrylen Jalandoni
Brylle Jamen
Mylene Madelo
Gielo Nino Mendez
Jemelyn Mae B. Moniza

BSCE_4F

Submitted to:

ENGR. CHRISTIAN KENNETH PANTONIAL


INSTRUCTOR

DECEMBER 2024
CONSTRUCTION
NOTES AND
SPECIFICATIONS

CONSTRUCTION NOTES
GENERAL NOTES:

1. THE STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION


WITH THE SPECIFICATIONS, ARCHITECTURAL, MECHANICAL,
ELECTRICAL AND SANITARY DRAWINGS.

2. IN THE INTERPRETATIONS OF THE DRAWINGS, INDICATED


DIMENSIONS SHALL GOVERN AND DISTANCES OR SIZES SHALL NOT
BE SCALED FOR CONSTRUCTION PURPOSES.

3. BARS OR REINFORECED CONCRETE MEMBER EXPOSED TO THE


WEATHER SHALL BE PROTECTED WITH A T LEAST 3.81 CM (1-1/2”)
AND IN NO CASE LESS THAN 2.54 CM (1”) CONCRETE. THESE
CONDITIONS MAY BE WAIVED WHEN ADEQUATE WATERPROOFING IS
PROVIDED.

4. REINFORMENTS BARS SHALL BE DEFORMED CONFIRMING TO ASTM-


315 AS FOLLOWS:

a. 20 mm dia. BARS and LARGER SHALL BE HIGH GRADED


WITH MINIMUM Fy-276 MPa (40,000 psi)

b. 16mm dia. BARS, SHALL BE INTERMEDIATE GRADED WITH


MINIMUM Fy-228 MPa (33,000psi)

c. 8mm, 10mm, AND 12mm dia. SHALL BE AT MINIMUM OF Fy


-228 MPa (33,000psi).

5. ALL CONCRETE WORKS SHALL BE DONE IN ACCORDANCE WITH THE


ACI318-87 BUILDING CODE FOR REINFORCED CONCRETE AND ALL
STRUCTURAL WORKS SHALL BE DONE IN ACCORDANCE WITH AISC
SPECIFICATIONS FOR AS DO NOT CONFLICT WITH LOCAL BUILDING
CODE REQUIREMENTS.

6. CONTRACTOR SHALL COORDINATE WITH THE AR, EE, & SE PLANS AT


TO THE EXACT SIZES AND LOCATION OF HOLES THRU FLOOR SLABS
AND WALLS.

7. THE CONTRACT STRUCTURAL SPECIFICATIONS AND DRAWINGS


SHOWS THE FINISH STRUCTURE. THEY DO NOT INDICATE METHOD
OF CONSTRUCTIONS UNLESS STATED. THE CONTRACTOR SHALL
PROVIDE NECESSARY MEASURES TO PROTECT THE STRUCTURES,
PROPERTIES, WORKMEN AND OTHER PERSONS DURING
CONSTRUCTIONS. THE CONTRACTOR SHALL IMMEDIATELY NOTIFY
THE OWNER AND THE STRUCTURAL ENGINEER FOR CAUSE IN THE
STRUCTURE.

8. CONSTRUCTION MATERIALS SHALL NOT BE INCLUDED ON POURED


FLOORS. IT IS THE CONTRACTOR’S GENERAL RESPONSIBILITY TO
ENSURE THAT THE SUB-CONTRACTORS ARE INFORMED. DO NOT
VIOLATE THIS IMPORTANT REQUIREMENT.

9. THE CONTRACTOR SHALL TAKE NECESSARY STEPS TO ENSURE


PROPER ALIGNMENT OF THE STRUCTURE AFTER INSTALLATION OF
ALL STRUCTURAL AND FINISH MATERIALS.
10. THE CONTRACTOR SHALL PROVIDE TEMPORARY ERECTION,
BRACING AND SHARING AT ALL STRUCTURAL MEMBERS AS
REQUIRED FOR STRUCTURES STABILITY DURING CONSTRUCTION.

11. THE TYPICAL DESIGN AND GENERAL NOTES SHALL APPLY TO ALL
PARTS OF THE JOBS SHOWN ON THE DRAWINGS.

CONCRETE MIX AND PLACING:

1. UNLESS OTHERWISE INDICATED IN THE PLAN OR NOTES IN THE


STRUCTURAL SPECIFICATIONS, THE MINIMUM 28-DAYS COMPRESSIVE
CYLIINDER STRENGTH OF CONCRETE SHALL BE AS MINIMUM AS
FOLLOWS:

a. LEAN CONCRETE 2,500PSI

b. SLAB ON GRADE 3,000PSI

c. FOOTINGS 3,000PSI

d. PEDESTAL 3,000PSI e. COLOUMS AND BEAMS 3,000PSI

e. CONCRETE SLABS AND SHEAR WALLS 3,000PSI

2. CONCRETE SHALL BE DISPOSITED IN ITS FINAL POSITION WITHOUT


SEGREGATION, REHANDLING OR FLOWING. PLACING SHALL BE DONE
PREFERABLY WITH BUGGIES, BUCKETS OR WHEEL-BORROWS. NO
CHUTES SHALL EXCEED SIX(6) METERS AGGREGATE LENGTH.

3. NO DEPOSITING OF CONCRETE SHALL BE ALLOWED WITHOUT THE


USE OF VIBRATORS UNLESS AUTHORIZED BY THE DESIGNER IN
WRITING.

4. REINFORCING BARS SHALL HAVE 2.54 CM(1”) CLEAR DISTANCE


FROM WALL FACE. FOR WALL DEPOSITED AGAINST THE GROUND,
REINFORCING BARS SHALL HAVE 7.62 CM (3”) MIN. CLEAR DISTANCE
FROM WALL FACE. FOR EXPOSED FACES OR FORMED WALLS,
REINFORCING BARS SHALL HAVE 5.08 CM (2”) MIN. CLEAR DISTANCE
FROM WALL FACE OR BARS LARGER THAN 16mm dia. BARS AND
SMALLER.

5. CARRY VERTICAL BARS AT LEAST 0.60M ABOVE FLOOR LEVELS TO


PROVIDE SPACES. WHEN NECCESARY STOP 0.05M BELOW TOP OF
SLAB OR SOLID BOND WHERE THE WALLS END.

6. HORIZONTAL AND VERTICAL BARS SHALL BE SPLICED BY LAPPING


DISTANCE EQUAL TO 40d AND WIRED SECURELY WITH NO. 16 GI
TIEWIRE PROVIDED THAT THE SPLICES IN ADJACENT IS
STAGGEREDBY AT LEAST 1.52M ON CENTERS.

FOOTINGS:

1. CONTRACTOR SHALL REPORT TO THE ENGINEER THE ACTUAL


UNUSUAL SOIL CONDITIONS UNCOVERED AND CONFIRM ACTUAL
BEARING CAPACITY OF SOIL IN WRITING BEFORE DEPOSITING
CONCRETE. THE ASSUMED BEARING CAPACITY IS 125 MPa.
2. FOOTING SHALL REST AT LEAST 1.00M TO 1.50M BELOW FINISED
GRADE LINE UNLESS OTHERWISE INDICATED.

3. UNLESS OTHERWISE SPECIFIED, ALL FOOTING SHALL REST ON


DENSE SAND OR VERY HARD CLAY. THIS MAY SOMETIMES REQUIRE
OVEREXCAVATION OF ABOUT 1.00M FROM PRESCRIBED BOUNDARY
LEVEL. SUCH EXCAVATION SHALL BE REPLACED WITH WELL
COMPACTED CRUSHED ROCK BACKFILL. COMPACTION SHALL BE 80%
OF MAXIMUM DRY DENSITY.

4. MINIMUM CONCRETE PROTECTION FOR REINFORCEMENT SHALL BE


0.075M CLEAR FOR CONCRETE DEPOSITED AGAINST THE GROUND
AND 0.05M FOR CONCRETE DEPOSITED AGAINST FORMWORK.

FOUNDATION:

1. CONTRACTOR SHAL ENSURE THAT ALL EXISTING STRUCTURES ARE


PROPERLY AND ADEQUATELY SUPPORTED AGAINST SETTLEMENT OR
MOVEMENT DURING EXCVATION.

2. REINFORCED CONCRETE SPREAD FOOTING SHALL BE PLACED AS PER


DETAIL.

3. THE MINIMUM CONCRETE STRENGTH OF THE FOUNDATION SHALL BE


20 MPA AFTER 28 DAYS.

CHIPPING:

1. CHIP-OFF TO EXPOSED SLAB/BEAM REBARS AND WELL NEW REBARS.

2. CLEAN THOROUGHLY CHIPPED-OFF SURFACES OF ALL LOOSE


MATERIALS.

3. APPLY EPOXY PRIOR TO RE-CASTING OF NEW CONCRETE/TYPICAL TO


ALL CHIPPED-OFF SURFACES.

4. PROVIDE ADEQUATE SHORING PRIOR TO DEMOLITION OF EXISTING


ELEMENTS. CONTRACTOR SO SUBMIT SHOP DRAWINGS SHOWING
DETAILS/LOCATIONS FOR APPROVAL.
5. CARE SHALL BE TAKEN SO AS NOT TO IMPAIR THE VALUE OF
RETAINED STRUCTURE.

6. VERIFY RELVANT BUILDING DIMENSIONS AND REPORT TO


STRUCTURAL ENGINEER ALL DIMENSIONS AND ACTUAL CONDITIONS
THAT COULD AGGREVATE WORKMANSHIP AND/OR CONSTRUCTTION
IMPOSSIBLE.

EQUIPMENT AND MACHINERY LAYOUT:

1. CONTRACTOR SHALL ALSO REFER TO OWNER FURNISHED


EQUIPMENT DIAGRAMS AND LAYOUT TO VERIFY WHETHER ANY
DISCREPANCY IS PRESENT.

2. IN CASE OF DISCREPANCIES, THE OWNER AND THE ENGINEER SHALL


BE NOTIFIED IN WRITING BEFORE PROCEEDING WITH ANY AFFECRED
WORK.
EMBEDDED PIPES IN CONCRETE:

1. ALL EMBEDDED PIPES FOR UTILITIES, ETC., SHALL BE MAXIMUM


100mm DIAMETER SINGLE RIGID GALVANIZED IRON PIPE UNLESS
OTHERWISE SPECIFIED OR APPROVED IN WRITING BY THE
STRUCTURAL ENGINEER.

2. SUCH PIPES WHEN SO EMBEDDED SHALL NOT TAKE UP MORE THAN


FOUR(4) PERCENT OF THE GROSS AREA OF THE CONCRETE MEMBER.

COMPACTED FILL:

1. FILL AND SUBRADES UNDER SLABS AND FOOTINGS SHALL BE


COMPACTED TO A MINIMUM OF 80% OF MAXIIMUM DRY DENSITY
BASED OS ASTMD-698.

2. MAXIMUM LIFT THICKNESS FOR COMPACTION SHALL BE 450MM.

SLAB ON GRADE:

1. ALL SLABS ON GRADE SHALL BE DESIGNED WITH A MAXIMUM


WATER CEMENT RATIO 0.40. ANY DECREASE IN WORKABILITY SHALL
BE COMPENSATED USING A PLASTICIZER.

2. ALL SLOPES SHALL BE POURED INTEGRAL WITH SLAB. OVERLAYS OR


BOUNDERING SHALL NOT BE ALLOWED.
STRUCTURAL
ANALYSIS AND
DESIGN
PARAMETERS

DESIGN PARAMETERS

A. STANDARD REGULATIONS AND REFERENCES:


The following shall govern the design, fabrication, and construction of the project.
Below are the structural codes and specification to be used in the structural analysis and
design of reinforced concrete special moment resisting a three (3)-storey residential
building.

1.1. NATIONAL STRUCTURAL CODE OF THE PHILIPPINES (NSCP 2015)

Volume 1 - Generally, for the entire analysis and design requirements.

B. SYSTEM OF UNITS

The system units to be used will be in International Standards Units (SI), wherein all
dimensions are in meter (m) unless specified.

C. MATERIAL PROPERTIES

❖ CONCRETE COMPRESSIVE STRENGTH (fc’)

Columns fc’ = 20.7 MPa (3000 psi)

Beams fc’ = 20.7 MPa (3000 psi)

Slabs fc’ = 20.7 MPa (3000 psi)

Footings fc’ = 20.7 MPa (3000 psi)

❖ MASSONRY COMPRESSIVE STRENGTH

Concrete Hollow Blocks 3.5 MPa (500 psi)

Concrete Mortar 17.20 MPa (2500 psi)

D. MATERIAL PROPERTIES

❖ REINFORCING STEEL BARS according to ASTM 615

o COLUMN AND FOOTING:

Main Reinforcement Grade 40 Fy = 276 MPa

Secondary Reinforcement Grade 33 Fy = 228 MPa

o BEAM SLAB AND STAIRS:

Main Reinforcement Grade 40 Fy = 276 MPa

Secondary Reinforcement Grade 33 Fy = 228 MPa

E. SOIL BEARING CAPACITY

The allowable soil bearing capacity of the site can be as high as 125KPa. Contractor
shall conduct the necessary soil exploration to determine the configuration of the soil to
design appropriate foundation of the building.
F. LOAD CASES

Loads are forces or other actions that results from the weight of all building materials,
occupants and their possessions, environmental effects, differential movement, and
restrained dimensional changes. Permanent loads are those loads in which variations over
time are rare of small magnitude. All other loads are variable loads. Below are case in which
loads will be used and classified.

❖ MINIMUM MATERIAL DENSITIES (NSCP 2015, TABLE 204.1)

Reinforce Concrete Unit Weight 23.6


Masonry Unit Weight 21.2
Mortar Unit Weight 20.4

❖ MINIMUM DESIGN DEAD LOADS (NSCP2015, TABLE 204.2)

Concrete Unit Weight 23.544 kN/cu.m.


Unit weight of wall (Masonry) 21.2 kN/cu.m.
Unit weight of glass 25.1 kN/cu.m.
Floor Finishes 1.10 kPa
Full Grout 2.84 kPa

❖ MINIMUM DESIGN LIVE LOADS (NSCP2015, TABLE 205.1)

Typical Floors 1.9 kPa


Roof Deck 1.9 kPa
Exterior Balconies 2.9 kPa

❖ EARTHQUAKE LOADS

The vibratory ground motion caused by earthquake can have damaging effects
on structures and can even lead to collapse. That’s why earthquake provision is
primarily to

design seismic resistant structures to safeguard against major structural damage that
may lead to loss of life and property. Below are the seismic analysis parameters
calculation that has been quoted from
NSCP 2015, Section 208:
EARTHQUAKE LOADS.

o IMPORTANCE FACTOR

Standard Occupancy (I) 1.0


o SEISMIC ZONING

Seismic Zone Factor (Z) 0.4

Source Type Type A


o Nearest Source Factors: 16.5 km Nearest to Tagoloan River Fault

Near Factors 1.0


Na 1.0
Nv 1.0

o SEISMIC MAP AND DISTRIBUTION OF ACTIVE FAULTS

Near Source Factor 1


Source: https://faultfinder.phivolcs.dost.gov.ph/

o SEISMIC NEAR SOURCE FACTOR AND RESPONSE COEFFICIENT

Soil Type SD

o SEISMIC COEFFICIENTS

Ca 0.44 Na
Cv 0.64 Nv
o SEISMIC COEFFICIENTS

Special RC Moment Frames (R) 8.5

o STATIC FORCE PROCEDURE

Design Base Shear


*Section 208.5.2.1 of NSCP 2015

Cv I 2.5 Ca I
V= ; V not exceed V = W
RT R

Where:

Ca Acceleration-controlled coefficient
Cv Velocity
I Importance factor
R Numerical representative of the
inherent overstrength
T Elastic fundamental period of the
structure in the direction under
consideration
Lower limits for V:

V =0.11Ca W (For structures )

0.8 Z N v I
¿ W (Additional limits for zone 4)
R

o STRUCTURAL FRAMING SYSTEM

RC Structures (CT) 0.0731

G. LOAD COMBINATIONS

Considering that earthquake load E, is as specified under NSCP 2015 section 208.6.1
which is equal to:

Where:

the earthquake load on an element of the structure resulting from the


combination of the horizontal component, and vertical component
the earthquake loads due to the base shear as set forth in Section 208.5.2 or the
design lateral force, as set forth in Section 208.9
the load effect resulting from the vertical component of the earthquake ground
motion and is equal to an addition of to the deadload effect D, for Strength
Design, and may take as zero for Allowable Stress Design
Reliability/ Redundancy Factor as given by the following equation:

Assuming:
E v =0.5 CaID

Say SD Soil Type=0.44 Na ; Na=1.0

So , Ev=0.5(0.44)(1.0) D=0.22 D

Therefore:

1.4 DL
1.2 DL + 1.6 LLa
1.2 DL + 1.6 LLb
1.42 DL + 0.5 LLa + 1.0 EL
1.42 DL + 0.5 LLb + 1.0 EL
1.42 DL + 0.5 LLa + 1.0 ER
1.42 DL + 0.5 LLb + 1.0 ER
ARCHITECTURAL
PLANS
`
INITIAL SIZING OF
STRUCTURAL
ELEMENTS

INITIAL SIZING - BEAM


INITIAL SIZING – SLAB 1
LOAD
CALCULATIONS

DEAD LOAD CALCULATION - BEAM


DEAD LOAD CALCULATION -
COLUMN
LIVE LOAD CALCULATION – CASE A
LIVE LOAD CALCULATION – CASE B
STRUCTURAL
PLANS
DESIGN
CALCULATIONS

FLOOR BEAM 1 DESIGN


FLOOR BEAM 2 DESIGN
FLOOR BEAM 3 DESIGN
FLOOR BEAM 4 DESIGN
FLOOR BEAM 5 DESIGN
ROOF BEAM 1 DESIGN
ROOF BEAM 2 DESIGN
ROOF BEAM 3 DESIGN
ROOF BEAM 4 DESIGN
ROOF BEAM 5 DESIGN
FOOTING DESIGN
STAIR DESIGN – 1ST FLR TO 2ND FLR
STAIR
STAIR DESIGN – 2ND FLR TO ROOF
DECK STAIR